Potable Hot Water Expansion Tank
Installation Instructions Model PLT-35
IS-PLT-35
Figure 1
Water Heater
Water
Supply
Watts
Shutoff Valve
Watts
Backfl ow
Preventer
Watts Pressure
Reducing Valve
Expansion
Tank
Water Pressure Gauge
Pressure — Temperature
PLT-35 Order No. 0067373
Max. Pressure: 50psi (10.3 bar)
Max. Temp: 200 °F (93ºC)
Tank Volume: 14.0 gal. (53 liters)
Tank Acceptance: 5.6 gal. (21.2 liters)
Air Pre-charge: 20psi (138 kPa)
Connections Size: 1" (25mm)
Diameter: 16.0" (406mm)
Length: 21.7" (551mm)
Weight: 32 lbs. (15 kgs.)
Acceptance Volume
AIR SIDE
PRE-PRESSURE
psi kPa/bar PLT -35
20 138 kPa 10.7
40 276 kPa 9.2
60 413 kPa 7.6
80 551 kPa 6.1
WATER SIDE VOLUME
AT 150 psi (gallons)
To System
Watts
T&P Safety
Relief Valve
Discharge Line
Certifed to
ANSI/NSF 61
(73°F/23°C)
PLT-35
WARNING!
!
Improper installation, adjustment, alteration, service or maintenance
may cause property damage, serious bodily injury or death. Read
instructions completely before proceeding with installation. Only
qualified personnel should install or service this equipment in
accordance with local codes and ordinances.
This Expansion Tank is designed and intended for water storage at
a maximum pressure of 150psi (10.3 bar) and a maximum temperature of 200°F. (93ºC) Any use other than for potable water or at a
sustained or instantaneous pressure in excess of 150psi or 200°F
is UNSAFE and may cause property damage, serious bodily injury
or result in death.
Do not exceed 80psi (5.5 bar) air charge. Air charge pressures
exceeding 80psi (5.5 bar) could become hazardous and will void
any and all warranties, either written or implied. Failure to follow
these instructions may cause property damage, serious bodily
injury or death.
Disclaimer: The manufacturer of this tank does not accept any liability
or other responsibility for personal injury or property damage resulting
from improper use, installation or operation of this tank or the system
of which it is a part.
Notice: This Expansion Tank, like all Expansion Tanks, may eventually
leak. Do not install without adequate drainage provisions where water
flow will cause damage.
Installation
1. Before beginning installation determine the
system pressure.
a. Open a faucet to allow the system pressure to equalize.
b. Read the system pressure at the Pressure Gauge
(Figure 1).
c. Close faucet.
2. The Expansion Tank Pre-Charge must be set to the system
pressure as determined in Step 1.
Note: The normal pre-charge is 20psi. Do not exceed 80
psi. If system pressure exceeds 80psi, it will be necessary
to either: A. Add a pressure Reducing Valve to the system
or, B. Locate the
pressure is below 80psi.
a. Unscrew the protective cap from the air inlet valve.
b. Using a tire pressure gauge check the tank pre-charge
pressure.
c. If necessary, pressurize the tank to the proper setting us-
ing a manual bicycle tire pump. Caution do not
exceed 80psi.
d. Replace the protective air cap.
3. Shut off the water supply valve.
4. Shut off power source to the hot water heater, (electricity,
gas, oil burner switch), and drain system following water
heater manufacturer recommendations.
5. Install the Expansion Tank in the System (refer to Figure 1).
a. This Expansion Tank, as all Expansion Tanks, may even-
tually leak. Do not install without adequate
drainage provisions.
expansion tank in a riser where the static
Important!
• A Pressure Relief Valve sized and installed in accordance
with Local Codes must be incorporated in the system.
In those systems requiring a combined Temperature and
Pressure Safety Relief Valve, the Temperature and Pressure
Safety Relief Valve should be sized and installed in accordance with Local Codes.
• Never plug a Safety Relief Valve.
6. Turn on the water supply valve.
7. Open a hot water fi xture and allow water fl ow until
all air is removed from the system.
8. Reapply power to the hot water heater.
9. Open a hot water fi xture to allow a slight fl ow until
the hot water has reached operating temperature.
10. Re-check system pressure following Step 1.a through c.
Caution: Do not adjust the air pre-charge of the Expansion
Tank with the system under pressure. The air pre-charge
should only be adjusted under zero system pressure.
If necessary adjust the Pressure Reducing Valve to the
Expansion Tank Pre-charge as determined in Step 2.
Air Inlet
Valve Cap
Figure 1
Expansion
Tank
Watts
Water
Supply
Watts
Shutoff Valve
Limited Warranty: Watts Regulator Co. (the “Company”) warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of
original shipment. In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge.
THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER
WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental, special
or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resulting
from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has no
control. This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product.
Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the above
limitations may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to
determine your rights. SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.
Backfl ow
Preventer
Watts Pressure
Reducing Valve
Water Pressure Gauge
To System
Water Heater
Watts
T&P Safety
Relief Valve
Discharge Line
Note: Product information is subject to change without notice and
supersedes all previous publications.
A Watts Water Technologies Company