or replaced.
8. If the device fails either step 5 or 6 or both, it must be repaired
functional.
7. If the device passes steps 5 and 6, it should be reported as
leakage of water at the vents, this indicates a faulty device.
and hold for five (5) minutes (Fig. 3). If there is a continuous
6. Raise the hose and the nozzle to a height of 10 feet (3 meters)
faulty device. (Retighten device by turning clockwise.)
the vents of the device. If no water is observed, this indicates a
the same time (Fig. 2). A spurt of water should be observed at
5. Turn the device counterclockwise while applying a gentle pull at
at the device, hose or the nozzle.
4. Turn off nozzle and then the supply. There must be no leakage
sufficient amounts of water through the nozzle to purge the air.
3. Turn on supply and pressurize the device and the hose. Run
2. Attach a hose and nozzle to the outlet of the device (Fig. 1).
1. Install the device per the installation instructions.
Field Test Instructions for Model N9-CD
Maximum Temperature: 180°F
Maximum Pressure: 125psi
sures maximum life and proper product function.
since cleaning and checking of all water system safety valves asMAINTENANCE: Annual inspection and testing is recommended
as chemical dispensers and hose bibbs.
sure, backsiphonage protection and health hazard applications such
APPLICATIONS: The N9-CD is designed for noncontinuous pres-
observed draining from the inlet connection of the device.
clockwise while applying a gentle pull at the same time. Water will be
TO DRAIN: Shutoff supply to N9-CD and turn the device counter-
devices must not be installed inside a wall or any concealed location.
conditions. For this reason and for maintenance accessibility, these
age because they are not designed to be spill free under all service
emergency or temporary water discharge can cause water damIMPORTANT: These devices are not intended for installation where
removal.
thread outlet, the built-in non-removable locking feature prevents
should not be used. To install, thread the N9-CD onto the hose
N9-CD is furnished with an inlet gasket, pipe dope or teflon tape
with the arrow on valve body pointing in the direction of flow. No.
and debris. The valve can be installed horizontally or vertically. Install
INSTALLATION: Before installing, flush pipe line to remove scale
more full American National Hose (NH) threads.
Use only with approved hose bibbs or hose fittings having four or
Installation Instructions
Backflow Preventer
Model N9-CD
IS-N9-CD
Fig. 1
Tested and approved in conformance with Standard 1052 of the American
Society of Sanitary Engineers and by all principal cities, states, and areas
having these requirements.
NOTE: Product information is subject to change without notice and
supersedes all previous publications.
Limited Warranty: Watts Regulator Co. (the “Company”) warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of
original shipment. In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge.
THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER
WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental, special
or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resulting
from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has no
control. This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product.
Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the above
limitations may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to
determine your rights. SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.
Fig. 2
Fig. 3
10 feet
(3 meters)
Repair Kit consists of diaphragm assembly,
disc assembly and gasket.
Model N9-CD Total Repair Kit:
ORDER NO. KIT NO. SIzE
0886009 RKN9-CD-T
3
⁄4"
Backflow Prevention Products
Canada: 5435 North Service Rd., Burlington, ONT. L7L 5H7; www.wattscanada.ca
USA: 815 Chestnut St., No. Andover, MA 01845-6098; www.watts.com
IS-N9-CD 0829 EDP#1915163 © Watts, 2008
IS-N9-CD 0829 EDP#1915163 © Watts, 2008
Canada: 5435 North Service Rd., Burlington, ONT. L7L 5H7; www.wattscanada.ca
USA: 815 Chestnut St., No. Andover, MA 01845-6098; www.watts.com
having these requirements.
Society of Sanitary Engineers and by all principal cities, states, and areas
Tested and approved in conformance with Standard 1052 of the American
Backflow Prevention Products
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.
determine your rights. SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF
limitations may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to
Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the above
control. This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product.
from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has no
or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resulting
The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental, special
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED
THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER
original shipment. In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge.
Limited Warranty: Watts Regulator Co. (the “Company”) warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of
supersedes all previous publications.
NOTE: Product information is subject to change without notice and
⁄4"
3
0886009 RKN9-CD-T
ORDER NO. KIT NO. SIzE
Model N9-CD Total Repair Kit:
disc assembly and gasket.
Repair Kit consists of diaphragm assembly,
10 feet
(3 meters)
Model N9-CD
Backflow Preventer
Installation Instructions
Use only with approved hose bibbs or hose fittings having four or
more full American National Hose (NH) threads.
INSTALLATION: Before installing, flush pipe line to remove scale
and debris. The valve can be installed horizontally or vertically. Install
with the arrow on valve body pointing in the direction of flow. No.
N9-CD is furnished with an inlet gasket, pipe dope or teflon tape
should not be used. To install, thread the N9-CD onto the hose
thread outlet, the built-in non-removable locking feature prevents
removal.
IMPORTANT: These devices are not intended for installation where
emergency or temporary water discharge can cause water damage because they are not designed to be spill free under all service
conditions. For this reason and for maintenance accessibility, these
devices must not be installed inside a wall or any concealed location.
TO DRAIN: Shutoff supply to N9-CD and turn the device counterclockwise while applying a gentle pull at the same time. Water will be
observed draining from the inlet connection of the device.
APPLICATIONS: The N9-CD is designed for noncontinuous pressure, backsiphonage protection and health hazard applications such
as chemical dispensers and hose bibbs.
MAINTENANCE: Annual inspection and testing is recommended
since cleaning and checking of all water system safety valves assures maximum life and proper product function.
Maximum Pressure: 125psi
Maximum Temperature: 180°F
Fig. 3
Fig. 2
Fig. 1
IS-N9-CD
Field Test Instructions for Model N9-CD
1. Install the device per the installation instructions.
2. Attach a hose and nozzle to the outlet of the device (Fig. 1).
3. Turn on supply and pressurize the device and the hose. Run
sufficient amounts of water through the nozzle to purge the air.
4. Turn off nozzle and then the supply. There must be no leakage
at the device, hose or the nozzle.
5. Turn the device counterclockwise while applying a gentle pull at
the same time (Fig. 2). A spurt of water should be observed at
the vents of the device. If no water is observed, this indicates a
faulty device. (Retighten device by turning clockwise.)
6. Raise the hose and the nozzle to a height of 10 feet (3 meters)
and hold for five (5) minutes (Fig. 3). If there is a continuous
leakage of water at the vents, this indicates a faulty device.
7. If the device passes steps 5 and 6, it should be reported as
functional.
8. If the device fails either step 5 or 6 or both, it must be repaired
or replaced.