Watts LF210-5 User Manual

For Gas Water Heater Applications
ES-LF210-5
Job Name
Job Location
Engineer
Approval
LEAD FREE
–––––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––––––
*
Series LF210-5
Automatic Gas Shutoff Valves
Series LF210-5 automatic gas shutoff valves are positive-acting energy shutoff for the emergency temperature protection of gas water heaters. They are self-contained devices independent of all other operating con­trols. They provide protection against overheating water in the domestic hot water supply heating systems by automatically shutting off the gas supply to the heater in the event that the water temperature reaches 210°F (99°C). Series LF210-5 must be manually reset in order to resume heater service. This feature serves as a warning of malfunctioning of the normal operating controls. Manual resetting is easily done and does not require dismantling or replacing of any part of the valve. See “Reset Button” feature. The LF210-5 features Lead Free* construction to comply with Lead Free* installation requirements.
This gas shutoff differs from other contemporary design in that Watts engineers have embodied the time tested Watts auto-thermatic thermal actuator principle along with a snap-acting trip latch which closes the valve at a definite controlled temperature.
Models LFL210-5 M2, LFLL210-5 M2 and LFLLL210-5 M2 feature extended shanks for use with the new generation of water heaters con­taining extra thick insulation.
Contractor
Approval
Contractor’s P.O. No.
Representative
LF210-5 M2
––––––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––––––
––––––––––––––––––––––––––––––––––––––––
––––––––––––––––––––––––––––––––––
Reset Button
Thermostat
LFL210-5 M2
Features
• Seating - Buna N disc to metal seating assures positive seal for
shutting off the gas to burner in the event of high water tempera­ture conditions.
•Reset Button - After operating from high temperature, the gas
shutoff must be manually reset (opened). Pressing the reset button in as far as it will go and then releasing, opens the valve and allows gas to again flow to the burner.
•Trip Latch Assembly - Snap acting latch releases the valve to
closed at a definite controlled temperature. Stainless steel spring seats valve when trip latch releases valve to closed position
•Thermostat - Operates trip latch in response to water temperature.
Thermobulb, temperature sensitive portion, is at end of extension tube for accurate response to tank temperature.
LFLL210-5 M2
Models
LF210-5 M2 Suitable for water heaters with up to 3⁄4" of insulation LFL210-5 M2 Suitable for water heaters with up to 2" of insulation LFLL210-5 M2 Suitable for water heaters with up to 2 LFLLL210-5 M2 Suitable for water heaters with up to 3" of insulation
1
2" of insulation
Specifications
Standard setting: 210°F (99°C) Extension: Furnished with 5" thermostat extension only.
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with­out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
NOTICE
Inquire with Governing Authorities for Local Installation Requirements
*The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight.
LFLLL210-5 M2
Typical Installations
!
WARNING
Installation: The gas shutoff valve must be installed so that the thermostat is immersed in the water within the upper 6" of the tank
DO NOT INSTALL IN COLD WATER LINE.
!
WARNING
The installation of a separate pressure relief valve is required for installations without T&P. Removal of the factory installed T&P valve may void water heater manufacturer’s warranty.
Fig. 1
Water Heaters equipped with T&P valve
Gas From
Supply
Series
Cold
LF210-5
Gas To Burner
Hot
T&P Relief Valve
Gas Capacity
C.S.A. listed ratings of this valve are:
For use with natural gas 150,000 BTU/hr.
For use with liquified petroleum gas 243,000 BTU/hr.
NOTICE
See C.S.A. directory for adjustment factors when used with manufactured, mixed and L.P. gas-air mixtures.
Dimensions — Weights
A
B
D
C
Water Heaters without factory installed T&P *
Pressure Relief Valve
Pressure Relief Valve Alternate Installation
Cold
Drain Tube
Fig. 2
Water Heaters without factory installed T&P alternate *
Hot
Fig. 3
Drain Tube
Drain Tube
To Bottom Supply
Pressure Relief Valve
Cold
Pressure Relief Valve Alternate
Installation
Gas From
Supply
Hot
Drain Tube
Series LF210-5
Gas To Burner
Gas From
Supply
Series
LF210-5
Gas To Burner
MODEL DIMENSIONS WEIGHT
A B C D
in. mm in. mm in. mm in mm lbs kgs.
LF210-5 M2 21⁄2 64 11⁄8 29 8 203 7/8 22 1.0 0.45 LFL210-5 M2 2 LFLL210-5 M2 2 LFLLL210-5 M2 2
MODELS
LF210-5 M2, LFL210-5 M2, LFLL210-5 M2, LFLLL210-5 M2
A Watts Water Technologies Company
ES-LF210-5 1240 © 2012 Watts
1
2 64 11⁄8 29 713/16 198 17/8 48 1.0 0.45
1
2 64 11⁄8 29 85/16 211 23/8 60 1.0 0.45
1
2 64 11⁄8 29 813/16 224 27/8 73 1.0 0.45
CONNECTIONS
TANK GAS NATURAL GAS L.P. GAS
3
4" male
1
2" female 150,000 243,000 77,400 125,750
USA: Tel: (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com
Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • www.watts.ca
BTU/HR RATINGS M.F.G. AND
L.P. GAS AIR MIXTURES MIXED GASES
Loading...