For Residential Fire Sprinkler Applications
ES-LF07S
Job Name
Job Location
Engineer
Approval
LEAD FREE
–––––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––––––
*
Series LF07S
Residential Fire Sprinkler
Dual Check Backflow Preventer
Sizes: 1" – 2" (25 – 50mm)
The Watts Model LF07S Residential Fire Sprinkler Dual Check
Backflow Preventer is designed for non-health hazard [i.e., pollutant]
application on potable fire sprinkler service connections to protect
against possible backsiphonage conditions that could inadvertently
drain the fire sprinkler system.
Approvals - Standards
Please consult Local Governing Code for proper installation and
agency code requirements,
Sizes Applicable: 1" Only
B64.6
Contractor
Approval
Contractor’s P.O. No.
Representative
––––––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––––––
––––––––––––––––––––––––––––––––––––––––
––––––––––––––––––––––––––––––––––
1" LF07SU2-2
2" LF07SU2-2
Sizes Applicable: 1", 11⁄2" & 2" Only
All Sizes Applicable
1024
ANSI/NFPA 13, 14, 15, 20, 22, and 24 Compliant All Sizes Applicable
End Connections – National Pipe Thread Taper ANSI B1.20.1
Pressure - Temperature
Max. Working Pressure: 175psi (12.1 bar) 11⁄2" & 2"
Min. Working Pressure: 10psi (0.69 bar)
Hydrostatic Test Press: 700psi (48.3 bar)
Temperature Range: 33°F to 140°F (0.5°C to 60°C)
160psi (11.03 bar) 1" & 1
1
1" & 1
⁄4"
33°F to 180°F (0.5°C to 82°C)
1
1
⁄2" & 2"
1
⁄4"
Specifications
The Lead Free* Dual Check Valve Backflow Preventer shall be
®
Listed 1024 and be UL Classified. The main body shall
ASSE
be Lead Free* brass featuring replaceable seats and silicone seat
discs. The check assemblies shall have captured springs to prevent injury. The Dual Check Valve shall be a Watts Model LF07S.
Material Specifications
• Body: Lead Free* Brass
• Elastomers: Silicone
• O-Rings: EPDM or Buna N
• Check Modules: Engineered Plastics
• Springs: Stainless Steel
Typical Installation
The Model LF07S is typically installed for service on residential fire
sprinkler systems. It is recommended this device is installed after
a water meter and/or isolation shutoff valve with installation techniques that comply with the latest edition of the Uniform Plumbing
Code. Please consult Local Governing Code for proper installation
and agency code requirement.
*The wetted surface of this product contacted by consumable
water contains less than 0.25% of lead by weight.
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
Configurable Options
The Model LF07S is standardly supplied with National Pipe Thread
Female [NPT] union inlet & Female [NPT] outlet connection.
Refer to the table below for optional inlet/outlet configurations.
Available Inlet Connections
CONNECTION TYPE LOCATION MODEL
SUFFIX
CODE
Meter Thread Female Inlet 4
Meter Thread Male Inlet 5
National Pipe Thread Male Inlet/Outlet 3
National Pipe Thread Female Inlet/Outlet 2
APPLICABLE
MODEL SIZES
1
⁄4"
1" & 1
(25 & 32mm)
1
1" & 1
⁄4"
(25 & 32mm)
1
1" & 1
⁄4"
(25 & 32mm)
1
1", 1
⁄4", 11⁄2" & 2"
(25, 32, 40 & 50mm)
Ordering Matrix Examples
VALVE
SIZE
MODEL UNION
INLET
INLET
THREAD
CODE
OUTLET
THREAD
CODE
MODEL ORDERING
DESCRIPTION
1" x 1" LF07S U 2 - 2 1" x 1" LF07SU2-2
1" x 1" LF07S U 4 - 2 1" x 1" LF07SU4-2
2" x 2" LF07S U 2 - 2 2" x 2" LF07SU2-2
Dimensions – Weights
Capacity
16.0
14.0
12.0
10.0
PSI
8.0
Drop
*Friction
6.0
Loss
4.0
2.0
0.0
24.0
22.0
20.0
18.0
16.0
14.0
PSI
Drop
12.0
*Friction
10.0
Loss
8.0
6.0
4.0
2.0
0.0
1" (25mm) LF07S
Rated Flow *UL Rated Flow [1" Only]
0.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0
0.0 37 75 114 151 190 227 265
10.2 20.4
11⁄2" (40mm) LF07S
Rated Flow *UL Rated Flow
0.0 20.0 40.0 60.0 80.0 100.0 120.0 140.0
0.0 75 151 227 303 379 454 530
9.0 818.1
GPM
LPM
fps
GPM
LPM
fps
B
C
A
LF07S
SIZE (DN) DIMENSIONS WEIGHT
A B C
in. mm in. mm in. mm in. mm lbs. kgs.
1 25
11⁄4 32
11⁄2 40
2 50
NOTE: This information is not intended to replace the product
installation and safety information available or the experience of a
trained product installer. Please refer to the product installation and
safety instructions for further information.
63⁄4 171 213⁄16 71 2 50 3.0 1.36
63⁄4 171 213⁄16 71 2 50 3.0 1.36
63⁄4 171 311⁄16 93 213⁄16 71 3.9 1.77
615⁄16
176
311⁄16
93
213⁄16
71 4.4 2.0
PSI
Drop
*Friction
Loss
2" (50mm) LF07S
35.0
30.0
25.0
20.0
15.0
10.0
5.0
0.0
0.0 20.0 40.0 60.0 80.0 100.0 120.0 140.0 160.0 180.0
0.0 151 303 454 606
8.2 16.3
Rated Flow *UL Rated Flow
GPM
LPM
fps
A Watts Water Technologies Company
USA: Tel. (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com
Canada: Tel. (905) 332-4090 • Fax: (905) 332-7068 • www.watts.ca
ES-LF07S 1315 © 2013 Watts