WattMaster WCC III User Manual part 15

14. SAT III Controller Installation Guide
WCC III
14. SAT III Controller Installation Guide
14. SAT III Controller Installation Guide
Table of Contents
SECTION 14: SA T III CONTROLLER INST ALLA TION GUIDE
SAT III Introduction ...................................14-1
SAT III - SAT II Comparison .......................14-2
SAT III I/O Terminology ..............................14-3
SAT III I/O Layout Sheet ............................14-4
WCCIII System Overview ...........................14-6
SAT III Analog Input Wiring .......................14-8
SAT III Control Output Wiring ..................14-16
SAT III Analog Output Wiring ...................14-17
SAT III Binary Input Wiring ......................14-22
Input/Output Terminology ........................14-26
SAT III General Installation Information .14-27
WCC III Technical Guide
+V SENSORS
12
3456
R1
R2
R3R4R5
123456
1 23456
V16 V15 V14 V13
K16
R6
K15
K14
78
R7
R8
7 8
78
K13
THE USA
14. SAT III Controller Installation Guide
SAT III Introduction
AT
ON OFF
BATTON/ OFF PULSE INPUT OPTION 3
ON OFF
ON OFF
ON OFF
OPTION 2 OPTION 1 LOCAL SET DISABLE LOCAL SET TEST
L16 L15 L14
BINARY
L13 L12
INPUTS
L11 L10 L9
L8 L7 L6
BINARY
L5 L4
INPUTS
L3 L2 L1
128 64 32 16 8 4 2
SATADDRESS
1
R
GND
VOUT
H
C
C
MADE IN
STATUS
SATREC
SATXMIT
HSS REC
HSS XMIT
LOCAL SET
STATUS 1
STATUS 2
STATUS 3
1 2 3 4 5 6 7 8
CH
SAT III
PROGRAMMABLE CONTROLLER
ANALOG INPUT
JUMPER SELECTION
THERM
0 TO 1V
0 - 10V 0 - 5V
INPUT
0 - 1V
THERM
0 TO 5V
0 - 10V 0 - 5V
INPUT
0 - 1V
THERM
0 TO 10V
0 - 10V
INPUT
0 - 5V 0 - 1V
THERM 0 - 10V
THERMISTOR
0 - 5V
INPUT
0 - 1V
THERM 0 - 10V
CURRENT
0 - 5V
INPUT
0 - 1V
A4 TO 20 mA SENSOR WILL REQUIREA 50 OHM LOAD RESISTORWHEN SET FOR A1 VOLT INPUT, ORA 250 OHM LOAD RESISTORWHEN SET FOR A 5 VOLTINPUT.
A2 WIRE ROOM SENSOR WILL REQUIRE A300 OHM LOAD RESISTOR WHEN SET FORA 1 VOLTINPUT.
A3 WIRE ROOM SENSOR WILL NOT REQUIREA LOAD RESISTOR WHEN SET FORA 1 VOLTINPUT.
WattMaster Controls Inc.
SAT III CONTROLLER - OE421-01
INSTALLATION GUIDE (SS5003)
SAT III General Specifications:
The SAT III controller is a drop-in replacement for the older SAT II line of controllers that WattMaster Controls manufactured from 1983 to 2006. The SAT III is an advanced product improvement over the SAT II controller.
The SAT III features the following:
8 Analog Inputs with 12 bit resolution (The SAT II originally had an 8 Bit A to D converter later upgraded to 10 Bit.) 8 Analog Outputs with 8 bit resolution (The SAT II also had an 8 Bit D to A converter.) 16 Relay Outputs that are Normally Open Relays with varistors for electrical noise suppression. (The SAT II used
expensive "chipswitches" that were low current output, and would only pass AC voltage and they did not have varistors on the output for electrical noise suppression.)
16 Binary Inputs that are isolated from the microprocessor bus . These Binary Inputs are for use with an external
Binary input board (The older SAT II required an Isolation board. The new SAT III does not require a separate isolation board.)
For further details on the SAT III inputs and outputs - See the "SAT III - I/O Specifications" on page 3.
The SAT III communications: It is a proprietary RS-485 based protocol, and it is based on packetized data in pre-defined parameter blocks. Troubleshooting of the SAT III RS-485 communications loop is possible with a Digital Volt Meter. (The SAT II was based on Manchester encoded data and was very reliable but was hard to troubleshoot.)
.
For the WCC III system, WattMaster Controls has developed a new isolated 485 communication bus that can support 239 SAT III's on four separate communications channels. A single channel can support up to 60 SAT IIIs on one communications loop. This is for redundant operation. If for some unknown reason a WCC III communications channel loop goes down, it does not cause other SAT III controllers on the other loops to lose communications.
14-1
WCC III Technical Guide
14. SAT III Controller Installation Guide
SAT III - SAT II Comparison
14-2
WCC III Technical Guide
14. SAT III Controller Installation Guide
SAT III I/O Terminology
WCC III Technical Guide
14-3
14. SAT III Controller Installation Guide
SAT III I/O Layout Sheet
14-4
WCC III Technical Guide
14. SAT III Controller Installation Guide
Notes
WCC III Technical Guide
14-5
14. SAT III Controller Installation Guide
WCCIII System Overview
Optional B-OUT Board
( 8 RELAYOUTS)
(2 PER SATIII)
HSS PORT
OE210 TYPICAL SPACE SENSOR (X8 MAX)
ON/OFF RELAY PUMPS, LIGHTS, ETC.
16 OUTPUTS PER SATIII
CONNECTION TO OLD WCC II MANCHESTER COMM LOOP
WCC II TO WCC III GLOBAL BRIDGE
WATTMASTER CONTROLS INC
SATII
UP TO 60 TOTAL SATIII OR SAT3C/D/F/P PER LOOP. THERE ARE 4 POSSIBLE SATIII RS485 COMMUNICATIONS LOOPS (UP TO 239 SAT III MAXIMUM)
BUILDING # 2
BB
PL102335 RS-485 TO FIBER OPTIC ADAPTOR
USUALLYONE OR TWO PER FLOOR
SATCOMM LOOP
Optional B-INPUT Board
( 8 BINARY INPUTS)
(2 PER SATIII)
HSS PORT
+V
ATI
ON OFF
BATTON/ OFF
STATUS
PULSE INPUT
L
OPTION 3
SATREC
OPTION 2
O
OPTION 1
A
SATXMIT
LOCALSETDISABLE
D
LOCALSET TEST
HSS REC
GND
HSS XMIT
ON OFF
LOCALSET
L16
V
L15 L14
STATUS 1
OUT
BINARY
L13 L12
INPUTS
STATUS 2
L11 L10
2134
5678
L9
STATUS 3
CHANNEL
ON OFF
L8 L7
2134
567
8
L6
BINARY
L5 L4
INPUTS
L3 L2
H
L1
ON OFF
COM
128 64 32 16 8
C
4 2
SATADDRESS
1
PROGRAM SOCKET
ADDRESS
PCF8583
24C128
LT1785
SATIII
FIBER OPTIC LINES MAXIMUM OF 2.5 MILES (USES "ST" CONNECTORS)
SATCOMM LOOP
PL102224 POWER AND SWITCHABLE COMM
CH 1 2 3 4 5 6 7 8 WattMaster Controls Inc.
SATIII
PROGRAMMABLE CONTROLLER
ANALOG INPUT JUMPER SELECTION
0TO 1V INPUT
0TO 5V INPUT
0TO 10V INPUT
THERMISTOR INPUT
CURRENT INPUT
SINGLE PULSE INPUT FROM POWER METER
MULTIPLE PULSE INPUTS FROM POWER METERS
2134
5678
CHANNEL
2134
567
SATCOMM LOOP
SATCOMM LOOP
OE421- SATIII CONTROLLER
+V
ATI
L O
A
D
GND
V OUT
2134
5678
CHANNEL
2134
5678
H
COM
C
OE455-P SAT3P CONTROLLER
PULSE INPUTS
TOTALWIRING FOR EACH INPUTNOT TO EXCEED 100 FEET. USE 18 GAUGETWISTED PAIR WITH SHIELD FOR EACH PULSE METER CONNECTION. CONNECTTHE SHIELD WIRETO GND.
“P”MODEADDRESSING NOTES
SATIIIADDRESSING STARTSAT ADDRESS NUMBER 8. EACH "P" MODE SATIIITAKES UP (8) SATIII LOGICALADDRESSES. THEREARE ONLY(8) USEDACTIVE INPUTS PER SAT3P.
OPTIONS
ANALOG INPUT#1 (PULSE INPUT#1) ON EACH SATIIIADDRESS ISACTIVE.
TEST
ALLOTHER INPUTSAND OUTPUTS ON
LOCAL
THE SAT3PARE NOTFUNCTIONAL.
LDIS OPT1 OPT2 OPT3
24 VAC
GND
OE421- SATIII CONTROLLER
+V
ATI
ON OFF
BATTON/ OFF
STATUS
PULSE INPUT
L
OPTION 3
SATREC
SATIII
OPTION 2
O
PROGRAMMABLE CONTROLLER
OPTION 1
A
SATXMIT
LOCALSETDISABLE
D
LOCALSET TEST
HSS REC
ANALOG INPUT
GND
JUMPER SELECTION
HSS XMIT
ON OFF
0TO 1V
LOCALSET
L16
INPUT
V
L15 L14
STATUS 1
OUT
BINARY
L13 L12
0TO 5V
INPUTS
STATUS 2
L11
INPUT L10 L9
STATUS 3
0TO 10V
INPUT
ON OFF
L8
CH
L7
8
L6
THERMISTOR
1
BINARY
L5
INPUT L4
INPUTS
L3
2
L2
H
CURRENT
L1
3
INPUT
4
ON OFF
COM
128
5
64 32
6
16 8
C
4
7
2
SATADDRESS
1
8 WattMaster Controls Inc.
USUALLYONE OR TWO PER FLOOR
TO THE ISP (INTERNET SERVICE PROVIDER) CONNECTION TO THE INTERNET (BY OTHERS)
PL102335 RS-485 TO FIBER OPTIC ADAPTOR
USED IN MULTIPLES OF TWO
ON OFF
BATTON/ OFF
STATUS
PULSE INPUT OPTION 3
SATREC
SATIII
OPTION 2
PROGRAMMABLE CONTROLLER
OPTION 1
SATXMIT
LOCALSETDISABLE LOCALSET TEST
HSS REC
ANALOG INPUT JUMPER SELECTION
HSS XMIT
ON OFF
0TO 1V
LOCALSET
L16
INPUT L15 L14
STATUS 1
BINARY
L13 L12
0TO 5V
INPUTS
STATUS 2
L11
INPUT L10 L9
STATUS 3
0TO 10V
INPUT
ON OFF
L8
CH
L7
THERMISTOR
L6
1
BINARY
L5
INPUT L4
INPUTS
L3
2
L2 L1
CURRENT
3
INPUT
4
ON OFF
128
5
64 32
6
16 8 4
7
2
SATADDRESS
1
8 WattMaster Controls Inc.
SATIII-P
ADDRESS
1 2 4 8 16 32 64 128
R
T
OE454/O 455/OE456E
SAT3C/D/F
CONTROLLER
OE421- SATIII CONTROLLER
2134
5678
CHANNEL
2134
5678
OE213 TYPICAL SPACE SENSOR
SATREC
SATIIICD
SATXMIT
Communications Interface
TUC REC
TUC XMIT
ON OFF
BATTON/ OFF OPTION 4 OPTION 3 OPTION 2 OPTION 1 LOCALSETDISABLE LOCALSET TEST
ON OFF
128
"C" MODEADDRESSING NOTES
64
"C" MODE SATIIIADDRESSING STARTS
32
ATADDRESS 8.
16
EACH "C" MODE SATIIITAKES UP
8
8 SATIII LOGICALADDRESSES.
4
A"C" MODE SATIII CAN COMMUNICATE
2
WITH 8 DEVICESTOTAL.
SATADDRESS
1
"D" MODEADDRESSING NOTES
"D" MODE SATIIIADDRESSING STARTS
ATADDRESS 4. EACH "D" MODE SATIIITAKES UP4
LOCALSET
SATIII LOGICALADDRESSES. A"D" MODE SATIII CAN COMMUNICATE
STATUS
WITH 32 DEVICESTOTAL.
"C" MODE
"D" MODE
+V
ATI
ON OFF
BATTON/ OFF PULSE INPUT
L
OPTION 3
O
OPTION 2 OPTION 1
A
LOCALSETDISABLE
D
LOCALSET TEST
GND
ON OFF
L16
V
L15 L14
OUT
BINARY
L13 L12
INPUTS
L11 L10 L9
ON OFF
L8 L7 L6
BINARY
L5 L4
INPUTS
L3 L2
H
L1
ON OFF
COM
128 64 32 16 8
C
4 2
SATADDRESS
1
OE320
TUC-2R
W A R M E R
C O O L
OVR
E R
VAV B O X
PL102224 POWER AND SWITCHABLE COMM
HIGH SPEED CABLE MODEM / ROUTER
SATCOMM LOOP
STATUS
SATREC
SATIII
PROGRAMMABLE CONTROLLER
SATXMIT
HSS REC
ANALOG INPUT
JUMPER SELECTION
HSS XMIT
0TO 1V
LOCALSET
INPUT
STATUS 1
0TO 5V
STATUS 2
INPUT
STATUS 3
0TO 10V INPUT
CH
THERMISTOR
1
INPUT
2
CURRENT
3
INPUT
4 5 6 7 8 WattMaster Controls Inc.
OE213 TYPICAL SPACE SENSOR
TUC COMM LOOP
SATCOMM LOOP
ETHERNET CABLE
OE213 TYPICAL SPACE SENSOR
OE455
SAT3D
CONTROLLER
SATREC
SATIIICD
SATXMIT
Communications Interface
TUC REC
TUC XMIT
ON OFF
BATTON/ OFF OPTION 4 OPTION 3 OPTION 2 OPTION 1 LOCALSETDISABLE LOCALSET TEST
ON OFF
128
"C" MODEADDRESSING NOTES
64
"C" MODE SATIIIADDRESSING STARTS
32
ATADDRESS 8.
16
EACH "C" MODE SATIIITAKES UP
8
8 SATIII LOGICALADDRESSES.
4
A"C" MODE SATIII CAN COMMUNICATE
2
WITH 8 DEVICESTOTAL.
SATADDRESS
1
"D" MODEADDRESSING NOTES
"D" MODE SATIIIADDRESSING STARTS ATADDRESS 4.
EACH "D" MODE SATIIITAKES UP4
LOCALSET
SATIII LOGICALADDRESSES.
A"D" MODE SATIII CAN COMMUNICATE
STATUS
WITH 32 DEVICESTOTAL.
"C" MODE
"D" MODE
OE331
TUC-5R+
W A R M E R
C O O L
OVR
E R
HEATPUMP
UP TO 32 TOTAL FAN COIL, HEAT PUMP PD VAV TERMINALUNITS PI VAV TERMINALUNITS PARALLELFAN BOX, ETC.
WCC III-MCD
OE320
TUC-2R
W A R M E R
C O O L
OVR
E R
VAV B O X
TUC COMM LOOP
UP TO 32 TOTAL FAN COIL, HEAT PUMP PD VAV TERMINALUNITS PI VAV TERMINALUNITS PARALLELFAN BOX, ETC.
14-6
WCC III Technical Guide
14. SAT III Controller Installation Guide
WCCIII System Overview
Optional B-OUT Board
( 8 RELAY OUTS)
(2 PER SAT III)
OE210 TYPICAL SENSOR
(X8)
ON/OFF RELAY PUMPS, LIGHTS, ETC.
16 OUTPUTS PER SAT III
WCC II TO WCC III GLOBAL BRIDGE
CONNECTION TO OLD WCC II MANCHESTER COMM LOOP
WATTMASTER CONTROLS INC
SATII
UP TO 60 TOTAL SAT III OR SAT 3C/D/F/P PER LOOP. THERE ARE 4 POSSIBLE SAT III RS485 COMMUNICATIONS LOOPS (UP TO 239 SAT III MAXIMUM)
BUILDING # 2
BB
PL102335 RS-485 TO FIBER OPTIC ADAPTOR
USUALLYONE OR TWO PER FLOOR
SAT COMM LOOP
PL102224 POWER AND SWITCHABLE COMM
Optional B-INPUT Board
( 8 BINARY INPUTS)
(2 PER SAT III)
HSS PORT
+V
ATI
ON OFF
BATTON/ OFF PULSE INPUT
L
OPTION 3
O
OPTION 2 OPTION 1
A
LOCALSETDISABLE
D
LOCALSET TEST
GND
ON OFF
L16
V
L15
0-15VDC OUTPUT
L14
OUT
MIN LOAD
L13
IS 1K OHM
L12
RESISTIVE
L11
VDC ONLY
L10
2134
5678
L9
CHANNEL
ON OFF
L8 L7
2134
5678
L6 L5 L4 L3 L2
H
L1
ON OFF
COM
128 64 32 16 8
C
4
EACH CONTACT
2
IS RATED FOR 24VAC ORVDC
1
@ .5AMPMAX
GLOBALBRIDGE
PROGRAM SOCKET
YS102210 REV 1
MADE IN USA
ADDRESS
R/T
C
24VAC
GND
SHLD
PCF8583
COMMT
EEPROM
24C128
POWER
SATII STAT
485
COMM R
DRIVER
LT1785
SATIII
VBAT
COMM
CHASSIS GND
FIBER OPTIC LINES
MAXIMUM OF 2.5 MILES
(USES "ST" CONNECTORS)
SAT COMM LOOP
HSS PORT
STATUS
SATIII
SATREC
PROGRAMMABLE CONTROLLER
SATXMIT
HSS REC
HSS XMIT
LOCALSET
STATUS 1 BINARY INPUTS
STATUS 2
STATUS 3
CH
1
BINARY INPUTS
2 3 4
A4TO 20 mASENSORWILLREQUIREA 50 OHM LOAD RESISTORWHEN SETFOR A1VOLTINPUT, ORA250 OHM LOAD
5
RESISTORWHEN SETFORA5VOLTINPUT.
A2WIRE ROOM SENSORWILLREQUIRE
6
A300 OHM LOAD RESISTORWHEN SET FORA1VOLTINPUT.
A3WIRE ROOM SENSORWILLNOT
7
REQUIREALOAD RESISTORWHEN SET FORA1VOLTINPUT.
SATADDRESS
8
MULTIPLE PULSE INPUTS FROM POWER METERS
SINGLE PULSE INPUT FROM POWER METER
ANALOG INPUT
JUMPER SELECTION
THERM
0TO 1V
0 - 10V
0 - 5V
INPUT
0 - 1V
THERM
0 - 10V
0TO 5V
0 - 5V
INPUT
0 - 1V
THERM
0TO 10V
0 - 10V
INPUT
0 - 5V
0 - 1V
THERM
0 - 10V
THERMISTOR
0 - 5V
INPUT
0 - 1V
THERM
0 - 10V
CURRENT
0 - 5V
INPUT
0 - 1V
WattMaster Controls Inc.
OE421- SAT III CONTROLLER
+V
ATI
GND
0-15VDC OUTPUT
OUT
MIN LOAD IS 1K OHM RESISTIVE VDC ONLY
2134
5678
CHANNEL
2134
5678
COM
EACH CONTACT IS RATED FOR 24VAC ORVDC @ .5AMPMAX
OE455-P
CONTROLLER
PULSE INPUTS
P1
P2
P3
P4
P5
P6
P7
P8
GND
GND
OPTIONS
SEL
TEST LOCAL LDIS OPT1 OPT2 OPT3
POWER
24 VAC
GND
OE421- SAT III CONTROLLER
+V
ATI
ON OFF
STATUS
BATTON/ OFF PULSE INPUT
L
OPTION 3
SATIII
SATREC
O
OPTION 2
PROGRAMMABLE CONTROLLER
OPTION 1
A
SATXMIT
LOCALSETDISABLE
D
LOCALSET TEST
HSS REC
GND
V
0-15VDC OUTPUT
OUT
MIN LOAD IS 1K OHM RESISTIVE VDC ONLY
2134
5678
CHANNEL
2134
5678
COM
EACH CONTACT IS RATED FOR 24VAC ORVDC @ .5AMPMAX
TO THE ISP (INTERNET SERVICE PROVIDER) CONNECTION TO THE INTERNET (BY OTHERS)
PL102335 RS-485 TO FIBER OPTIC ADAPTOR
USED IN MULTIPLES OF TWO
ON OFF
STATUS
BATTON/ OFF PULSE INPUT
L
OPTION 3
SATIII
SATREC
O
OPTION 2
PROGRAMMABLE CONTROLLER
OPTION 1
A
SATXMIT
LOCALSETDISABLE
D
LOCALSET TEST
HSS REC
ANALOG INPUT JUMPER SELECTION
HSS XMIT
ON OFF
THERM
0 - 10V
LOCALSET
L16
V
H
C
0 - 5V
L15
0 - 1V
L14
STATUS 1
BINARY
L13
THERM
L12
0 - 10V
INPUTS
STATUS 2
L11
0 - 5V
L10
0 - 1V
L9
STATUS 3
THERM
0 - 10V
0 - 5V
ON OFF
0 - 1V
L8
CH
THERM
L7
0 - 10V
L6
1
BINARY
0 - 5V
L5
0 - 1V
L4
INPUTS
L3
2
THERM
L2
0 - 10V
L1
3
0 - 5V
0 - 1V
4
ON OFF
A4TO 20 mASENSORWILLREQUIREA 50 OHM LOAD RESISTORWHEN SETFOR A1VOLTINPUT, ORA250 OHM LOAD
128
5
RESISTORWHEN SETFORA5VOLTINPUT.
64
A2WIRE ROOM SENSORWILLREQUIRE
32
6
A300 OHM LOAD RESISTORWHEN SET
16
FORA1VOLTINPUT.
8
A3WIRE ROOM SENSORWILLNOT
4
7
REQUIREALOAD RESISTORWHEN SET
2
FORA1VOLTINPUT.
SATADDRESS
1
8
WattMaster Controls Inc.
ANALOG INPUT JUMPER SELECTION
HSS XMIT
ON OFF
THERM
0TO 1V
0 - 10V
LOCALSET
L16
0 - 5V
INPUT
L15
0 - 1V
L14
STATUS 1
BINARY
L13
THERM
L12
0 - 10V
0TO 5V
INPUTS
STATUS 2
L11
0 - 5V
INPUT
L10
0 - 1V
L9
STATUS 3
THERM
0TO 10V
0 - 10V
INPUT
0 - 5V
ON OFF
0 - 1V
L8
CH
THERM
L7
0 - 10V
L6
THERMISTOR
1
BINARY
0 - 5V
L5
INPUT
0 - 1V
L4
INPUTS
L3
2
THERM
L2
H
C
0 - 10V
L1
CURRENT
3
0 - 5V
INPUT
0 - 1V
4
ON OFF
A4TO 20 mASENSORWILLREQUIREA 50 OHM LOAD RESISTORWHEN SETFOR A1VOLTINPUT, ORA250 OHM LOAD
128
5
RESISTORWHEN SETFORA5VOLTINPUT.
64
A2WIRE ROOM SENSORWILLREQUIRE
32
6
A300 OHM LOAD RESISTORWHEN SET
16
FORA1VOLTINPUT.
8
A3WIRE ROOM SENSORWILLNOT
4
7
REQUIREALOAD RESISTORWHEN SET
2
FORA1VOLTINPUT.
SATADDRESS
1
8
WattMaster Controls Inc.
0TO 1V INPUT
0TO 5V INPUT
0TO 10V INPUT
THERMISTOR INPUT
CURRENT INPUT
0-15VDC OUTPUT MIN LOAD IS 1K OHM RESISTIVE VDC ONLY
EACH CONTACT IS RATED FOR 24VAC ORVDC @ .5AMPMAX
SAT 3P
SATIII-P
PULSE METER BOARD
ATTMASTER CONTROLS YS102268 REV0
MADE IN USA
PULSE 1
PULSE 2
TOTALWIRING FOR EACH INPUTNOT
PULSE 3
TO EXCEED 100 FEET.
PULSE 4
USE 18 GAUGETWISTED PAIR WITH SHIELD FOR EACH PULSE METER
PULSE 5
CONNECTION.
PULSE 6
CONNECTTHE SHIELD WIRETO GND.
PULSE 7
PULSE 8
STATREC
“P”MODEADDRESSING NOTES
STATXMIT
SATIIIADDRESSING STARTSAT ADDRESS NUMBER 8.
LOCALSET
EACH "P" MODE SATIIITAKES UP
STATUS
(8) SATIII LOGICALADDRESSES. THEREARE ONLY(8) USEDACTIVE INPUTS PER SAT3P. ANALOG INPUT#1 (PULSE INPUT#1) ON EACH SATIIIADDRESS ISACTIVE. ALLOTHER INPUTSAND OUTPUTS ON THE SAT3PARE NOTFUNCTIONAL.
HIGH SPEED CABLE MODEM / ROUTER
OE213
ADDRESS
ADD
1 2 4 8
16
32 64
128
TYPICAL
COMM
R
SH
T
SENSOR
OE454 / O 455 / OE456E
SAT 3C/D/F
CONTROLLER
ON OFF
ON OFF
SATREC
SATXMIT
TUC REC
TUC XMIT
BATTON/ OFF OPTION 4 OPTION 3 OPTION 2 OPTION 1 LOCALSETDISABLE LOCALSET TEST
128 64 32 16 8 4 2
SATADDRESS
1
LOCALSET
STATUS
"C" MODE
"D" MODE
SAT COMM LOOP
OE421- SAT III CONTROLLER
+V
ATI
ON OFF
STATUS
BATTON/ OFF PULSE INPUT
L
OPTION 3
SATIII
SATREC
O
OPTION 2
PROGRAMMABLE CONTROLLER
OPTION 1
A
SATXMIT
LOCALSETDISABLE
D
LOCALSET
TEST
HSS REC
GND
OUT
2134
5678
CHANNEL
2134
5678
COM
ANALOG INPUT JUMPER SELECTION
HSS XMIT
ON OFF
THERM
0 - 10V
LOCALSET
L16
0 - 5V
V
L15
0 - 1V
L14
STATUS 1
BINARY
L13
THERM
L12
0 - 10V
INPUTS
STATUS 2
L11
0 - 5V
L10
0 - 1V
L9
STATUS 3
THERM
0 - 10V
0 - 5V
ON OFF
0 - 1V
L8
CH
THERM
L7
0 - 10V
L6
1
BINARY
0 - 5V
L5
0 - 1V
L4
INPUTS
L3
2
THERM
L2
H
0 - 10V
L1
3
0 - 5V
0 - 1V
4
ON OFF
A4TO 20 mASENSORWILLREQUIREA 50 OHM LOAD RESISTORWHEN SETFOR A1VOLTINPUT, ORA250 OHM LOAD
128
5
RESISTORWHEN SETFORA5VOLTINPUT.
64
A2WIRE ROOM SENSORWILLREQUIRE
32
6
A300 OHM LOAD RESISTORWHEN SET
16
FORA1VOLTINPUT.
8
C
A3WIRE ROOM SENSORWILLNOT
4
7
REQUIREALOAD RESISTORWHEN SET
2
FORA1VOLTINPUT.
SATADDRESS
1
8
WattMaster Controls Inc.
SATIIICD
Communcations Interface
"C" MODEADDRESSING NOTES
"C" MODE SATIIIADDRESSING STARTS ATADDRESS 8.
EACH "C" MODE SATIIITAKES UP 8 SATIII LOGICALADDRESSES. A"C" MODE SATIII CAN COMMUNICATE
WITH 8 DEVICESTOTAL.
"D" MODEADDRESSING NOTES
"D" MODE SATIIIADDRESSING STARTS
ATADDRESS 4.
EACH "D" MODE SATIIITAKES UP4
SATIII LOGICALADDRESSES.
A"D" MODE SATIII CAN COMMUNICATE
WITH 32 DEVICESTOTAL.
ETHERNET CABLE
0TO 1V INPUT
0TO 5V INPUT
0TO 10V INPUT
THERMISTOR INPUT
CURRENT INPUT
W A R M E R
C O O L
OVR
E R
OE320
TUC-2R
VAV B O X
WCC III-MCD
OE213 TYPICAL SPACE SENSOR
OE455
SAT 3D
CONTROLLER
SATREC
SATIIICD
SATXMIT
Communcations Interface
TUC REC
TUC XMIT
ON OFF
BATTON/ OFF OPTION 4 OPTION 3 OPTION 2 OPTION 1 LOCALSETDISABLE LOCALSET TEST
ON OFF
128
"C" MODEADDRESSING NOTES
64
"C" MODE SATIIIADDRESSING STARTS
32
ATADDRESS 8.
16
EACH "C" MODE SATIIITAKES UP
8
8 SATIII LOGICALADDRESSES.
4
A"C" MODE SATIII CAN COMMUNICATE
2
WITH 8 DEVICESTOTAL.
SATADDRESS
1
"D" MODEADDRESSING NOTES
"D" MODE SATIIIADDRESSING STARTS ATADDRESS 4. EACH "D" MODE SATIIITAKES UP4
LOCALSET
SATIII LOGICALADDRESSES. A"D" MODE SATIII CAN COMMUNICATE
STATUS
WITH 32 DEVICESTOTAL.
"C" MODE
"D" MODE
OE213 TYPICAL SENSOR
OVR
W A R M E R
C O O L
OVR
E R
OE320
TUC-2R
W A R M E R
C O O L E R
VAV B O X
TUC COMM LOOP
UP TO 32 TOTAL FAN COIL, HEAT PUMP PD VAV TERMINALUNITS PI VAV TERMINALUNITS PARALLEL FAN BOX, ETC.
OE331
TUC-5R+
G5LE-14P 24VDC CONTACT: UL/ CSA10A250VAC
G5LE-14P 24VDC CONTACT: UL/ CSA10A250VAC
G5LE-14P 24VDC CONTACT: UL/ CSA10A250VAC
G5LE-14P 24VDC CONTACT: UL/ CSA10A250VAC
G5LE-14P 24VDC CONTACT: UL/ CSA10A250VAC
HEAT PUMP
UP TO 32 TOTAL FAN COIL, HEAT PUMP PD VAV TERMINALUNITS PI VAV TERMINALUNITS PARALLEL FAN BOX, ETC.
WCC III Technical Guide
14-7
Loading...
+ 21 hidden pages