WattMaster WCC III User Manual part 19

18. SAT 3P (Pulsemeter) Controller Manual
WCC III
18. SAT 3P (Pulsemeter) Controller Manual
T ABLE OF CONTENTS
SECTION 18: SA T 3P (PULSEMETER) CONTROLLER MANU AL
SAT 3P Pulse Input and Components ....... 18-2
SAT 3P Addressing .....................................8-4
SAT 3P Basic Wiring .................................18-5
SAT 3P Typical Wiring ..............................18-6
Analog Input Screen ...................................8-7
Energy Consumption Screen ..................18-10
18. SAT 3P INSTALLATION GUIDE
Overview
SECTION 18: SA T 3P (PULSEMETER) CONTROLLER MANU AL (SS5013)
__________________________________________
Each SAT III controller has a single general purpose AIN 1 input that is an Analog Input / high speed binary capture input which can also be used as a pulse meter input. The SAT III controller can only interface to 1 pulse meter.
The SA T 3P controller is in the simplest terms a stripped down SAT III controller. The SAT 3P controller has no binary logic inputs, no relay outputs, no analog inputs, no analog outputs, and no HSS expansion port. The SAT 3P controller has eight high speed binary capture inputs used for pulse meter type inputs.
Why would you want to purchase a SAT 3P controller? Cost and labor are the major factors. To do tenant sub-metering for 16 tenants, you would normally need to buy 16 SAT III controllers. This would be a fairly high and costly expenditure. The same 16 tenant sub-metering can now be accomplished by using two SAT 3P controllers. Also, wiring is an issue. It is easier to wire 16 pulse meter outputs to two SAT 3P controllers than it is to wire to 16 SAT III controllers that could be scattered throughout the building. The SAT 3P controllers should ideally be located next to the pulse meters. This is so that the binary outputs from the pulse meters can readily and easily be connected to the inputs of the SAT 3P controller.
The SAT 3P controller is used to interface up to 8 pulse meters per SAT 3P controller. The SAT 3P simulates 8 SAT III satellites on the WCC III communications loop. The one and only input that is used per simulated satellite is AIN 1. This AIN1 input is no longer a general purpose analog input on the SAT 3P controller. This AIN 1 input is a specialized high speed capture binary input, and is designed to detect pulse type inputs. All other satellite inputs and outputs are non-functional on these 8 simulated satellites. The Trendlog capabilities are still functional on these 8 simulated satellites.
Figure 18-1: SAT 3P Controller
WCC III Technical Guide
18-1
18. SAT 3P INSTALLATION GUIDE
SA T 3P Pulse Input and Components
When used in conjunction with the WCC III system, the SAT III controllers and SAT 3P controllers are capable of recording ener gy demand, energy consumption, as well as sub-metering, and then automated logging of tenant power usage. Sophisticated turning OFF of high usage energy equipment when there is high energy peak demand time is also possible with what is called “Shed and Restore Program” via the WCC III system. This can be accomplished by using a pulse meter on the building incoming power that outputs a binary contact closure to a pulse meter input on a SAT III or SAT 3P controller. Then, by making global analog and/or global binary determinations, make an intelligent decision as to what equipment to keep on and what equipment to turn off.
The binary outputs from the pulse meter(s) must be of the isolated output type. They can be of the optically coupled open-collector current sink transistor output type or an actual dry contact type of output. Please consult with WattMaster Controls if you have any questions at all about the type of connection from the Pulse Meter to the SAT 3P controller(s).
The binary input circuit equivalent of the SAT 3P controller is summarized in Figure 18-2:
The E-Mon D-Mon P2 Pulser output module is an optically coupler interface device that allows the Class 2000 kWh or KWh/Demand meter to be connected to an energy/building management system (EMS) for the purpose of data-gathering and/or load control. The pulse width and value are selected using the 2 DIP switches and can be tailored to fi t you specifi c requirements in the fi eld. A modular plug connects the P2 Pulser output module to the E-Mon D-Mon meter. A two position screw terminal block provides an easy connection to the EMS (SAT 3P controller). An LED on the P2 Pulser output module shows the rate and duration of the pulse output that is going to the EMS (SA T 3P Controller). The P2 Pulser output module has an output operation of 4.5 to 28 volts DC that is to be supplied by the EMS. (SAT 3P Controller)
Please refer to Figure 18-3 for referencing the following components of the SAT 3P controller:
Communications T erminal Block (Labeled TB2)
The SA T 3P connects to the WCC III system the same way as other SAT III, and SAT 3C/D,F controllers do via a proprietary RS-485 network. The physical network layer consists of a two -wire twisted pair with shield wire. WattMaster Controls can provide a detailed specifi cation for this wire as well as provide 500’ or 1000’ spools of this wire. All terminated wiring is by three position unpluggable terminal blocks or single unpluggable ¼ inch spade connections. When terminating wire, connect “R” to “R”, “T” to “T”, and “SHLD” TO “SH” throughout the whole WCC III system.
Figure 18-2: Schematic showing the SA T 3P Pulse Input equivalent circuit multiplied times eight circuits
The two position Removable Berg Jumper on each of the eight Pulse Inputs on the SAT 3P controller are normally connected. These Removable Berg Jumpers connect a +5 volt DC pull up via a 10K ohm current limit resistor to each of the eight Pulse Inputs on the SAT 3P controller. These Removable Berg Jumpers are to be removed only if an external voltage source is to be used with the pulse meter output.
WattMaster Controls-approved pulse meter with isolated outputs are E-Mon D-Mon Class 2000 Three-Phase kWh or KWh/Demand meter with the optional E-Mon D-Mon P2 Pulser output module.
Comm LED
This LED is tied to the “DIR” line of the RS-485 driver chip (LT1785 – WM Part # ID001785). It will slightly blink on receipt of a communications packet.
Power In Terminal Block (Labeled TB3)
Connect 24VAC and Ground from a transformer. Warning:
Observe Polarity. We recommend using a separate transformer,
but as long as the same polarity is used for 24VAC and GND on all Satellite connections, then multiple Satellite controllers can be powered off of a single transformer, as long as you do not exceed the VA rating of the transformer. Use a self-fusing transformer or use a suitable sized fuse for your transformer that accounts for the total VA draw. The Sat 3P draws 3 VA, SAT III draws 15VA, and the SAT 3C/D/F draws 10VA.
Power LED
This LED is tied to the +5 Volt DC power supply of the SAT 3P controller. This LED should always be “ON” and never blink.
18-2
WCC III Technical Guide
18. SAT 3P INSTALLATION GUIDE
SA T 3P Components
Figure 18-3: SAT 3P P oints of Interest
Pulse Input Terminal Block (LABELED TB1)
This 10-position terminal block is connected to the Pulse meter(s) output. There are eight input connections and two ground terminals provided for ground connections. See Figure 18-5.
Output LEDs
PULSE 1 to PULSE 8 LEDs. These LEDs are not physically connected to the actual high speed binary capture inputs. They are software controlled outputs from the microprocessor that is on the SAT 3P controller. This enables true output status to be displayed of the actual pulse inputs.
STAT LEDs
There are two STAT LEDs—STAT REC and STAT XMIT. Whenever the microprocessor transmits a communications packet, the ST A T XMIT LED will be “ON”. Whenever the microprocessor receives a communications packet, the STAT REC LED will be “ON”. The ST ATUS LED blinks out a heart beat status of the SA T 3P controller.
LOCAL SET LED
This LED is normally off, but when the SAT 3P is not communicating to the WCC III – MCD, this LED will be “ON” solid.
Option Switches
TEST Switch—When this switch is “ON,” then the SAT 3P will operate to any input condition that has the word “TEST” programmed into the setpoint.
LOCAL Switch—When this switch is “ON,” then the SAT 3P operates to the LOCAL SET conditions. Also the SAT 3P controller will operate in the LOCAL SET conditions when it has lost communications to the rest of the WCC III communications loop. This Local set condition should be indicated by the LOCAL SET LED being “ON”.
L DIS Switch—When this switch is “ON,” then the SAT 3P will not operate to the LOCAL SET conditions. It should control to setpoints that are based on the “ON” schedule.
OPT 1, OPT 2, OPT 3 switches—These three switches are not used at this time.
Mounting Holes
Use the three supplied sheet metal screws to mount the SAT 3P controller in a suitable enclosure. You must use all three screws to mount the SAT 3P controller.
WCC III Technical Guide
18-3
Loading...
+ 9 hidden pages