WattMaster WCC III User Manual part 12

12. WCC III Installation Guide
WCC III
12. WCC III Installation Guide
T ABLE OF CONTENTS
SECTION 12: WCC III INST ALLA TION GUIDE
WCC III System Requirements .................12-1
Wall Mounting of the WCC III – MCD .........12-2
WCC III – MCD Internet Access ................12-4
Sending a Text Message to a Cell Phone via an Email from
the WCC III System ................................... 12-6
WCC III System RS-485 Communication
Wiring ........................................................12-7
WCC III - MCD Typical System
Architecture ..............................................12-8
Mounting a Satellite Controller in an
Enclosure ................................................12-10
SAT 3C Controller ..................................12-49
Addressing the SAT 3C ........................... 12-51
Addressing (Numbering) of the TUC/RTU Controllers that are
Connected to the SAT 3C .......................12-53
SAT 3D Controller ...................................12-57
Addressing the SAT 3D ........................... 12-58
Addressing (Numbering) of the TUC Controllers that are Connected to the
SAT 3F Controller ....................................12-62
Addressing the SAT 3F ...........................12-63
Addressing (Numbering) of the TUC Controllers that are connected to
Satellite Controllers -
General Dimensions ...............................12-15
SAT III Controller - LED Information .......12-16
SAT III Controller - Connection Points ...12-17
Addressing (Numbering) of
SAT III Controllers ..................................12-19
SAT III Relay Outputs .............................12-21
Proportional-Integral (PI) Output
Binary Input with Time Delay Board ......12-27
SAT III Analog Inputs .............................. 12-41
TUC-2R and Four Relay Expansion
Board ......................................................12-67
TUC-2R Three Relay Expansion Board
and Damper Actuator ..............................12-68
TUC-2R Velocity Sensor ......................... 12-69
Running the WCC3 Program ...................12-70
WCC III - MCD LCD Display .....................12-73
The WCC III - MCD ...................................12-78
Using the MCD-Menu Program ...............12-79
12. WCC III INSTALLATION GUIDE
System Requirements
SECTION 12: WCC III INST ALLA TION GUIDE __________________________________________
WCC III System Requirements
To accomplish remote communications via the internet, the following items are needed in addition to the WCC III system in order to control the building mechanical systems. The WCC III system is not to be used in any application where Fire/Life/Safety is an issue.
WCC III – MCD System Requirements (On-Site WCC III – MCD Computer):
DSL, or a Cable router/switch that connects to the
internet. Or, as an alternative, an internal jobsite IP network that does not connect to the internet, but when using this internal jobsite IP network, the external internet Email of alarms from the WCC III
- MCD will not be possible. Also, external access via the internet may not be possible.
A fi xed static IP address or a fi xed IP domain host
name.
Enabled port forwarding on the Firewall of the
router/switch. This is only if a fi rewall is used.
On earlier versions, antivirus software is initially
provided by WattMaster Controls, with Norton antivirus software for a period of 1 year. The customer must maintain the antivirus software after this 1-year period. Later versions are shipped with Linux as the operating system and do not require anti-virus software.
An Email address that supports a SMTP
server for SENDING with a pop server for RECEIVING Emails, and it must have “auth login” authentication. TLS or SSL modes are not supported. WattMaster Controls can provide an Email address with these requirements.
An Uninterruptible Power Supply (UPS) – 750-
Watt minimum
A wall mounting surface is preferred.
A dedicated 120VAC power circuit is required.
Front End Software Requirements (Operator Console Software):
A Microsoft Windows XP /Vista/Windows 7-based
computer.
Minimum hardware specifi cation for the Microsoft
Windows XP / Vista based computer is a Pentium IV running at 2.4 Giga Hertz with at least 1 GB of RAM, and 10 GB of spare hard drive space. A CDROM/DVD player is also required for software installation.
WCC III software package – Provided on a
CDROM, or is available via a download on the WCC Controls website: www.wcc-controls.com. The installation CDROM contains the following programs:
WCC III.EXE (SS5021) WCCUTILITY.EXE (SS5023) SCUSCR.EXE (SS5026) WCC3Trendlog.EXE (SS5028) TenantReport.EXE (SS5025) TenantOverride.EXE* (SS5024) WGCC3.EXE (SS5029) WCC3 Download (SS5030) WCC3 Guest (SS5022)
The CDROM part number (WattMaster Part #
DM1WC011-01X, were “X” = revision level)
A DSL or Cable router/switch that connects to the
internet, or access to the internet via some other method. Or, as an alternative, an internal jobsite IP network that does not connect to the internet, but when using this internal jobsite IP network, the external internet Email of alarms from the WCC III
- MCD may not be possible.
* NOTE: The TenantOverride.exe program is also available
as a single program installation for the end users that are using the simplistic graphical interface of the TenantOverride.exe screen to locally turn on and off specifi c control points that are applicable to the end user.
WCC III Technical Guide
12-1
12. WCC III INSTALLATION
Basic Operating Conditions and Wall Mounting
The WCC III – MCD Basic Operating Conditions
The WCC III - MCD must be kept in a clean and dry area in the building. The ambient temperature must be between 50 and 100 °F, and the relative humidity must be kept between 0 and 90% (non­condensing). The interior components are cooled by ventilation fans within the WCC III – MCD unit, and therefore the unit should not be kept in tightly confi ned or enclosed areas. The WCC III - MCD is primarily designed to mount on a wall with the supplied brackets.
The WCC III – MCD computer requires 115 VAC power and must remain powered at all times for proper operation and control. The 115 VAC power circuit must be separate and dedicated exclusively to the WCC III – MCD computer.
The WCC III - MCD system is designed to automatically restart after a power failure. However, the industrial computer which acts as the WCC III Master Communications Device will not automatically reboot unless the power is shut off cleanly and then restored cleanly. During most power outages, the incoming 115 AC voltage could have great fl uctuations before the power nally fails. In a like manner, brownouts will usually cause the industrial computer to “lock-up.” That is to say, the screen will continue to display on the monitor, but the cursor will not respond to the keyboard commands. To prevent this “lock-up” issue from happening to the WCC III – MCD, an Uninterruptible Power Supply (UPS) is required on each and every WCC III – MCD computer.
An Uninterruptible Power Supply (UPS) provides emergency power to keep the WCC III Master Communications Device (personal computer) on-line for several minutes after a primary power failure. The UPS regulates the incoming power to the computer and shuts the power off cleanly several seconds after the power outage, or brownout. When the primary power is restored, the UPS brings the MCD back on-line automatically. The WCC III system does not lose any information since all of the programs and user entered data are stored on either a disk in the MCD, on rmware, or on battery backed memory in the satellite controllers.
Figure 12-1: Installing the six screws for the two wall mounting brackets of the WCC III – MCD Computer
Do not mount the WCC III – MCD computer straight into the drywall. The use of a ¾-inch plywood “Backer Plate Board” is required. You may want to paint this plywood “Backer Plate Board” to match the color of the wall before mounting to the wall.
See Figure 12-2 for further application.
Backer Plate Mounting Notes:
Use correct type of wall mounting anchors for mounting on a concrete wall for the mounting of the “Backer Plate Board” if and when mounting the Backer Plate Board to a concrete wall. Use at least 2-inch dry wall type screws if mounting the Backer Plate Board to a “Dry-Wall” type wall. Mount the “Backer Plate Board” so that the screws that are holding the “Backer Plate Board” are on the 16-inch centers of the wall studs where applicable.
Mount the WCC III - MCD 4-½ to 5-½ feet off of the ground on a suitable wall, in an air conditioned space. This area should not have any radio transmitting or telephone switching gear in the space, or near the space, or located on the back side of the adjacent wall.
Wall Mounting of the WCC III – MCD
It is strongly suggested that the WCC III – MCD is mounted on the wall. General guidelines are as follows:
Always install the supplied six screws for the two supplied wall mounting brackets for the WCC III – MCD Computer as shown in
Figure 12-1. Be sure to tighten the six screws so that they do not
loosen over time.
12-2
Do not block the airfl ow vents that are coming out of the WCC III- MCD. Do not apply paint to the WCC III-MCD enclosure. Do not cover the WCC III-MCD with any protective plastic while painting with the WCC III-MCD turned on. The UPS battery backup unit should be located within 3 or 4 feet of this WCC III – MCD.
WCC III Technical Guide
12. WCC III INSTALLATION
Wall Mounting of the WCC III - MCD
Wall Mounting of the WCC III - MCD
Front view with wall mounting brackets
GUIDE
Use 3/4 inch plywood for the backer plate board
(supplied by others)
Figure 12-2: Wall mounting instructions for the WCC III – MCD
NOTES:
at least 2-inch dry wall type screws. Mount the backer plate board so that the screws that are holding the backer plate board are on the 16­inch centers of the wall where applicable.
Mount the WCC III - MCD 4-½ to 5-½ feet off of the ground on a suitable wall in an air conditioned space. This space should not have any radio transmitting or telephone switching gear in the space, or near the space, or located on the back-side of the adjacent wall.
Do not block the airfl ow vents that are coming out of the WCC III - MCD. Do not apply paint to the WCC III - MCD enclosure. Do not cover the WCC III - MCD with any protective plastic while painting with the WCC III - MCD turned on.
The UPS should be located within 3 or 4 feet of this WCC III - MCD.
WCC III Technical Guide
Use approved anchors when mounting backer plate board on a concrete wall. If mounting backer plate board to dry wall, use
12-3
12. WCC III INSTALLATION
WCC III - MCD Internet Access
WCC III – MCD Internet Access
The most common question asked is: Why does the WCC III – MCD computer need to have Internet access?
If WattMaster Controls factory assistance or troubleshooting is required for a WCC III system, a representative from the factory can access the system with a remote computer and view the same WCC III Screens as the end user or contractor in the building. This allows the end user or the contractor for the building installation to talk to the factory representative while they are both viewing the same screens.
The Emailing of important alarm notifi cations for up to 60 Email Addresses is provided for from the WCC III – MCD.
The ability to send alarm notifi cation via a text message to a cellular phone.
Secure Remote communications package (WCC III software) is provided for FREE. A CD-ROM is supplied for installation.
World-wide, multiple remote connections (up to 255 simultaneous connections possible)
On earlier versions, antivirus software is initially provided by WattMaster Controls, with Norton antivirus software for a period of 1 year. The customer must maintain the antivirus software after this 1-year period. Later versions are shipped with Linux as the operating system and do not require anti-virus software.
The ability for internet based tenant override requires internet access.
WCC III – MCD Cable Modem/Router T echnical Considerations
The WCC III-MCD uses internet access to e-mail alarms and to provide remote IP access for multiple remote WCC III operator programs.
The DSL / Cable modem USB connection should not be connected to any of the USB ports on the WCC III – MCD. The DSL / Cable modem Ethernet connection should only be connected to the Ethernet port on the WCC III – MCD if the DSL / Cable modem has a built-in internal router with Ethernet switch.
The use of a DSL / Cable modem with an external router that is then connected to the WCC III - MCD is also a recommended way to connect the internet to the WCC III – MCD. The use of only a plain DSL / Cable modem without an internal router with a built-in switch is not currently recommended by WattMaster Controls.
It is recommended that the WCC III-MCD computer be connected to the internet via a high-speed cable modem or NAT enabled router.
This is best accomplished by what is called Port Forwarding (also sometimes referred to as tunneling) and is the act of forwarding a network port (located External on the internet) to another network node (located Internal on the LAN). This technique can allow an external user (The WCC III program) to reach a port that is on a private LAN (Local Area Network) IP address (The WCC III ­MCD) from the outside via a NAT enabled router. This external port number that is used for the WCC III – MCD computer is port
39289.
Custom remote WCC III system programming or analyzing of the existing WCC III program is also available for a nominal charge.
Some cable modem devices may incorporate a router along with the cable modem functionality, to provide the LAN with its own IP network addressing. From a data forwarding and network topology perspective, this router functionality is typically kept distinct from the cable modem functionality (at least logically) even though the two may share a single enclosure and appear as one unit. So, the cable modem function will have its own IP address and MAC address as will the router.
Figure 12-3: Typical small business type routers—a Broadband Firewall Router, and a Cable/DSL VPN Router
12-4
WCC III Technical Guide
12. WCC III INSTALLATION GUIDE
WCC III - MCD Internet Access
In a typical WCC III - MCD networking setup, internet access is through a DSL or Cable modem. This modem may then be connected to a router with a built in switch, (or typically the router with switch is also built-in to the modem) which is then connected to the internal LAN of networked computers by Ethernet cabling. The NAT enabled router is the only device that the Internet sees as it holds the public IP address. On the other hand, the WCC III – MCD, located behind the NAT enabled router, is invisible to the Internet as it holds a local IP address on the NAT enabled router. Port forwarding is necessary in the NAT enabled router because computers that are running the WCC III program will send information that is directed to the public IP address and the NAT enabled router needs to know where to send and then redirect that information to the WCC III – MCD.
NOTE: A DSL modem is not recommended due to yet
another layer of setup complexity. DSL modem/routers also have a maximum distance from the local telephone company’s
main central offi ce. That distance is 18,000 feet.
Step 1: You will need a high-speed cable or DSL modem/router
that is NAT enabled and it must be setup by the ISP, or by IT (Information Technology) knowledgeable personnel, and it must also be connected to the Internet.
The default IP addresses that the WCC III – MCD is shipped with are:
WCC III-MCD IP Address: 192.168.100.100
WCC III-MCD Subnet Mask: 255.255.255.0
WCC III-MCD Default Gateway: 192.168.100.1
WCC III-MCD Preferred DNS Server: 208.67.222.222
WCC III-MCD Alternate DNS Server: 208.67.220.220
The external port number that is used for the WCC III – MCD computer is port 39289.
For WCC III – MCD’s running windows set up the WCC III – MCD BACKTASK.EXE Program
Com Port # ____________
External Port Range ____________
Default for the backtask.exe program is Comm port # 5 and port # 39289.
Step 2: The following three items are needed from your ISP
(Internet Service Provider) in order to set up the Cable / DSL modem/router for stand alone internet access. The ISP should have already supplied a sheet of paper that has this important information on it.
WCC III-MCD IP Address: _______._______._______._______
WCC III-MCD Subnet Mask: _______._______._______.______
WCC III-MCD Default Gateway: _______.______.______._____
WCC III-MCD Preferred DNS Server: _________._________.__
______._______
WCC III-MCD Alternate DNS Server: _________._________.__ ______._______
WCC III Technical Guide
12-5
12. WCC III INSTALLATION
WCC III - MCD Internet Access
Supported Networks
Only Microsoft based networks are currently supported by the WCC III system. Any of the older 10 base T only networks are not supported by the WCC III system, only 100 base T or faster networks are supported. (10/100 base T are OK) The slower the network, the slower the data returned from the WCC III-MCD will be displayed, and the faster speed is always better.
Also, network “hub” devices are not recommended, because “hub” devices divide the network’s bandwidth amongst the active connections that are connected to the network hub. For example, if you have a 16-port network hub on a 100 base T connection with 10 active connections, then your effective network speed is the same as a 10 base T connection.
A 10/100 base T network switch is the recommended connection to the WCC III-MCD device. A network switch device has a full 100 base T connection to all active ports at the same time.
Benefi ts of Using a Separate DSL / Cable Modem Internet connection for the WCC III-MCD
1. It provides a layer of network isolation. A connection to the building’s internal computer network may not be desirable to the IT department. If the WCC III – MCD is connected to the building’s internal computer network an additional fi rewall into the building’s internal computer network may be required.
2. A dedicated high speed internet connection is a faster connection. WCC III displayed data will be displayed quicker and updated faster.
How to send a T e xt Message to a Cellular phone via an Email from the WCC III system
Most cellular telephone providers have as a free* option (Charges may apply in some instances) an Email-to-TEXT service for their cellular phone plans. *Usually the cellular telephone providers will have an unlimited text messaging option in one or more of their plans.
When using Verizon cellular service, the text messaging email address for your phone is your 10-digit phone number followed by @VTEXT.com. For example, if your phone number is 1-555­555-5555, your email address (for TEXT MESSAGING) would be 5555555555@VTEXT.com
When using Sprint cellular service, the text messaging email address for your phone is your 10-digit phone number followed by @messaging.sprintpcs.com. For example, if your phone number is 1-555-555-5555, your email address (for TEXT MESSAGING) would be 5555555555@messaging.sprintpcs.com.
When using AT&T cellular service, the text messaging email address for your phone is your 10-digit phone number followed by @txt.att.net. For example, if your phone number is 1-555-555­5555, your email address (for TEXT MESSAGING) would be 5555555555@txt.att.net.
Example: 5555555555@VTEXT.com, 5555555555@messaging. sprintpcs.com, or 5555555555@txt.att.net would be programmed into the WCC III System parameters screen as an Email address. Any alarm type level that is generated would be sent to that cellular telephone number as a text message.
3. Network outages should be less frequent, due to the fact that there is no overhead of a pre-existing internal computer network. A pre-existing internal computer network will always require periodic “downing of the network servers” to do maintenance work to the existing computer network regardless of having the WCC III-MCD connected to the pre-existing internal computer network.
4. The need for having an onsite IT person to setup, and then administer the WCC III-MCD will be reduced.
5. Setup and maintenance of e-mail accounts would be easier, because they would be automatically provided by the Internet Service Provider.
12-6
WCC III Technical Guide
12. WCC III INSTALLATION
<<<LOCAL LOOP>>> AZWR-LL-WG-18>>> E76191 CL2P 18AWG (UL) 012112 FT
<<<NETWORK LOOP>>> AZWR-NL-WR-18>>> E76191 CL2P 18AWG (UL) 012112 FT
WATTMASTER LOCAL LOOP WIRE
WATTMASTER NETWORK LOOP WIRE
GUIDE
RS-485 Communication Wiring
The WCC III System RS-485 Communication Wiring
The WCC III - MCD can communicate with up to 239 satellite controllers via a two-wire RS-485 communication loop. On the back of the WCC III – MCD there are two RS-485 communication loop ports that come as standard. Each one of these communications loop ports can communicate with up to 60 satellites for a total of 120 satellites.
Two more additional RS-485 communication loop ports can be added at an additional cost for any WCC III system that has more than 120 satellites. The two-wire RS-485 communication loop should be stranded 2 wire twisted pair of 18-gauge wire with a shield wire, and it also must be plenum rated were applicable.
The use of stranded wire is mandatory to ensure a good connection with the ¼ inch Sta-Con connectors which are used to terminate the wires at the satellite controllers. The RS-485 communication wire does not have to be run from each satellite controller back to the WCC III – MCD, but rather the RS-485 communication wire can be “daisy-chained,” which means that only one twisted pair of wires is connected to each of the WCC III - MCD communications loops. The maximum allowable length of wire from the WCC III - MCD to the farthest satellite is 4000 feet per RS-485 communications loop.
The RS-485 wire specifi cations are generally a stranded 18- gauge - 2 wire twisted pair with shield. 18-gauge stranded wire is mandatory to ensure a good connection with the ¼ inch Sta-Con connectors, which are used to terminate the wires at the WCC III
- MCD and at the satellite controllers. The old SAT II Manchester communications loop was supposed to have used a 2-wire twisted pair with shield, but this was not used in every installation. This old SAT II communications loop should not be used for the new SAT III communications loop. A new RS-485 communications loop should be ran to each new replacement SAT III controller. The shield wire must be used on the new SAT III controller, as it provides a “ground” reference for the RS-485 communication loop. WattMaster Controls sells two versions of 18-gauge - 2-wire twisted pair with shield communications wire— (1) WattMaster part #WR-NL-WR-18 which is marked “Network Loop” with a red stripe for rapid identifi cation. This connection is intended to run from the WCC III – MCD to the SAT III, SAT 3C/D/F, SAT 3P, and then to the next SAT 3 type controllers. (2) WattMaster part # WR-LL-WG-18 which is marked “Local Loop” with a green stripe for rapid identifi cation for the TUC loops that run from the SAT 3C/D/F controllers out to the TUC controllers.
“Wire Nuts” on the RS-485 communications loop should be avoided at all costs. As an alternative to the “Wire Nuts”, WattMaster Controls has a Power and Switchable RS-485 communications board, and the WattMaster part number is PL102224. This Power and Switchable RS-485 communications board can be thought of as a 24-VAC power and communication distribution system for the SAT III communications loop, and this board will aid in initial startup and future troubleshooting of the SAT III communications loop. These boards should be used on a fl oor-by-fl oor basis. This Power and Switchable RS-485 communications board is also available in a small metal electrical enclosure.
Figure 12-4 WattMaster Controls various communications loop wire
WCC III Technical Guide
12-7
12. WCC III INSTALLATION
WCC III - MCD Typical System Architecture
Figure 12-5: The WCC III typical system architecture with POWER and SWITCHABLE COMM boards
Figure 12-6: WCC III typical system architecture without the POWER and SWITCHABLE COMM boards
12-8
WCC III Technical Guide
12. WCC III INSTALLATION GUIDE
WCC III - MCD Typical System Architecture
The wire that makes up the communication loop should be shielded. Shielded cable has an aluminum jacket over the wires that could act as an “antenna” to carry away any “stray” electrical signals that could interfere with the communication process. The shield should be grounded throughout the SAT Loop.
The SAT RS-485 communication loop wires are connected to the “R” and “T” and shield terminals on the satellite controllers using ¼-inch Sta-Con connectors. Make sure the polarity is correct. That is to say, the wire connected to the “R” and “T” terminal on the MCD must be connected to the “R” and “T” terminal on the satellite controllers. If the “R” and “T” and shield wires are crossed, the WCC III system will not communicate. The shield should be connected together when the cable is cut in order to terminate the wires at the satellite controller.
The communication loop wire from the WCC III - MCD is connected to one of the “R” and one of the “T” terminals on the satellite controller, which is physically located nearest the WCC III - MCD. The other “R” and “T” terminals located on the satellite controller can be used to extend the two-wire loop to the next satellite controller, or the wires can branch off of a two-wire loop
running through the center of a building as shown in Figure 12-6.
NOTE: The shield wire must be connected at each and every
Satellite Controller also.
WCC III Technical Guide
12-9
12. WCC III INSTALLATION
8
7
SATADDRESS
2 1
4
8
A3WIREROOM SENSORWILLNOT REQUIREALOAD RESISTOR WHEN SET FORA1 VOLT INPUT .
WattMasterControlsInc.
BINARY INPUTS
BINARY INPUTS
L8
ON OFF
128
32 16
64
L4 L3 L2 L1
L6 L5
L7
L11
L12
ON OFF
L10 L9
ON OFF
L15
L16
L14 L13
CH
4
3
5 6
2
1
LOCALSET
STATUS2
STATUS3
STATUS1
HSSXMIT
LOCALSET
LOCALSETDISABLE
BATTON/OFF PULSEINPUT
OPTION1
TEST
OPTION3 OPTION2
ON OFF
STATUS
HSSREC
SATXMIT
SATREC
ANALOGINPUT
JUMPERSELECTION
A2WIREROOM SENSORWILLREQUIRE A300OHM LOAD RESI STOR WHEN SET FORA1 VOLT INPUT .
A4TO2 0 mA SENSOR WILLREQUIREA 50OHMLOAD RES ISTOR WHEN SE T FOR A1VOLTINPUT, ORA 250 OHM LOAD RESISTORWHENSETFO R A 5 VOLT INPUT.
CURRENT INPUT
THERMISTOR INPUT
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
0-10V
THERM
0TO10V INPUT
0TO5V INPUT
0TO1V INPUT
0-10V
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
THERM
0-1V
0-5V
0-10V
THERM
PROGRAMMABLE CO NTROLL ER
SAT III
H
C
COM
CHANNEL
2134
2134
567
8
5678
V
OUT
GND
L O A D
+V
ATI
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
EACHCONTACT ISRATEDFOR 24VACOR VDC @.5AMPMAX
0-15VDC OUTPUT MINLOAD IS1KOHM RESISTIVE VDCONLY
100VA
TRANSFORMER
SWITCH DISCONNECT
INTER PANEL
Satellite Controller Enclosure Mounting
Satellite Controller
Mounting in an Enclosure
The satellite controllers are designed to mount in any NEMA 1 or NEMA 3 standard, six-inch deep, electrical enclosure. Typically, this is a fi eld-mounted enclosure that contains transformers and any accessory items required such as a binary input board, V-Out Binary output board, control relays, etc. The best location for these satellite panels is mounted on a wall in equipment or storage areas or rooms at eye level near the controlled loads.
The satellite controllers may be ordered with or without the NEMA type enclosures. If you order the satellite controller from the factory without an enclosure, the SAT III and SAT 3C/D/F
dimensions as shown in Figure 12-13 and Figure 12-14 may be
helpful when selecting a suitable NEMA type enclosure.
The satellite controller must be mounted in an electrical enclosure. If you do not order the satellite controller with an electrical enclosure, you must provide your own electrical enclosure and then provide and then install your own fused disconnect switch, transformer, and terminal strip.
The size of the standard single SAT enclosure is designed to hold only one satellite controller (or up to two SAT 3C/D/F controllers), one fused disconnect switch, one transformer, one fi lter, and one terminal strip which is normally about 15” x 15” x 6” deep with an inter panel for mounting the SAT III controller, fuse block, 100VA transformer, etc. The size of the standard dual SAT enclosure is designed to hold two satellite controllers (or up to four SAT 3C/D/F controllers), one fused disconnect switch, two transformers, two lters, and two terminal strips is 30” x 18” x 6” deep with an inter panel for mounting the two SAT III controllers, fuse block, 100VA transformer, etc. If you install the satellite controller yourself, make sure you leave room for wires that need to be connected to the following terminals that are located on the sides of the SAT III satellite controller (minimum recommended clearance is 2 inches):
You can also have both a SAT III controller and up to two SAT 3C/D/F controllers in the same dual enclosure.
24-VAC power source (100VA recommended)
RS-485 Communication loop
SAT III HSS Port connection
Figure 12-7: A typical SAT III controller in a single electrical panel (120-V AC po wered)
12-10
WCC III Technical Guide
12. WCC III INSTALLATION
8
7
SATADDRESS
2 1
4
8
A3WIREROOMSENSORWILLNOT REQUIREALOAD RESISTOR WHENSET FORA1 VO LT INPUT.
WattMasterControlsInc.
BINARY INPUTS
BINARY INPUTS
L8
ON OFF
128
32 16
64
L4 L3 L2 L1
L6 L5
L7
L11
L12
ON OFF
L10 L9
ON OFF
L15
L16
L14 L13
CH
4
3
5 6
2
1
LOCALSET
STATUS2
STATUS3
STATUS1
HSSXMIT
LOCALSET
LOCALSETDISABLE
BATTON/OFF PULSEINPUT
OPTION1
TEST
OPTION3 OPTION2
ON OFF
STATUS
HSSREC
SATXMIT
SATREC
ANALOGINPUT
JUMPERSELECTION
A2WIRE ROOMSENSORWILL REQUI RE A300OHM LOAD RESISTOR WHENSET FORA1 VO LT INPUT.
A4TO20 mA SENSORWILLREQUIREA 50OHMLOAD RESISTOR WHEN SET FOR A1VOLTINPUT, OR A 250 OHM LOAD RESISTORWHEN SET FO R A 5 VOLT INPUT.
CURRENT INPUT
THERMISTOR INPUT
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
0-10V
THERM
0TO10V INPUT
0TO5V INPUT
0TO1V INPUT
0-10V
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
THERM
0-1V
0-5V
0-10V
THERM
PROGRAMMABLECONTROLLER
SAT III
H
C
COM
CHANNEL
2134
2134
567
8
5678
V
OUT
GND
L O A D
+V
ATI
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
EACHCONTACT ISRATEDFOR 24VACORVDC @.5AMPMAX
0-15VDC OUTPUT MINLOAD IS1KOHM RESISTIVE VDCONLY
100VA
TRANSFORMER
SWITCH DISCONNECT
8
7
SATADDRESS
2 1
4
8
A3WIREROOM SENSOR WILLNOT REQUIREALOADRESISTORWHENSET FORA1VOLTINPUT.
WattMasterControlsInc.
BINARY INPUTS
BINARY INPUTS
L8
ON OFF
128
32 16
64
L4 L3 L2 L1
L6 L5
L7
L11
L12
ON OFF
L10 L9
ON OFF
L15
L16
L14 L13
CH
4
3
5 6
2
1
LOCALSET
STATUS2
STATUS3
STATUS1
HSSXMIT
LOCALSET
LOCALSET DI SABLE
BATTON/OFF PULSEINPUT
OPTION1
TEST
OPTION3 OPTION2
ON OFF
STATUS
HSSREC
SATXMIT
SATREC
ANALOGINPUT JUMPERSELECTION
A2WIREROOM SENSOR WILLREQUIRE A300OHMLOADRESISTORWHENSET FORA1VOLTINPUT.
A4TO 20 mA SENSOR WILL REQUIREA 50OHMLOAD RESISTOR WHEN SETFOR A1VOLT INPU T, OR A250OHMLOAD RESISTORWHEN SETFORA5 VOL T INPUT.
CURRENT INPUT
THERMISTOR INPUT
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
0-10V
THERM
0TO10V INPUT
0TO5V INPUT
0TO1V INPUT
0-10V
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
THERM
0-1V
0-5V
0-10V
THERM
PROGRAMMABLECONTROLLER
SAT III
H
C
COM
CHANNEL
2134
2134
567
8
5678
V
OUT
GND
L O A D
+V
ATI
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
EACHCONTAC T ISRATEDFOR 24VACORVDC @.5AMPMA X
0-15VDC OUTPUT MINLOAD IS1KOHM RESISTIVE VDCONLY
INTER PANEL
100VA
TRANSFORMER
GUIDE
Satellite Controller Enclosure Mounting
Figure 12-8: Two SA T III controllers in a typical dual electrical panel (120-VA C pow ered)
WCC III Technical Guide
12-11
12. WCC III INSTALLATION
Satellite Controller Enclosure Mounting
Figure 12-9: A typical SAT 3C/D/F controller in a single electrical panel (120-V AC po wered)
Figure 12-10: A typical SAT 3C/D/F controller in a (single) dual electrical panel (120-V AC po wered)
12-12
WCC III Technical Guide
12. WCC III INSTALLATION GUIDE
Satellite Controller Enclosure Mounting
Figure 12-11: A typical SAT 3C/D/F controller in a (dual) quad electrical panel (120-V A C pow ered)
WCC III Technical Guide
12-13
12. WCC III INSTALLATION
GND 24VAC
100VA
2AMP
MDL
BLK
WHT
L
N
ORG
BRN
BLK
WHT
ORG
BRN
24VAC
GND
GND
24VAC
GND
SIG
+V
FLUSHMOUNT
TYPICAL 7 PLACES
SENSOR
Satellite Controller Wiring
If you order the satellite controller in an enclosure, the factory will provide and install the wires from the transformer to the satellite. If you order the satellite controller separately, you must provide a NEMA panel with an inter panel, disconnect switch, transformer(s), fusing, terminal block(s), wire, crimp connectors, and then install the wires from the transformer to the satellite controller. A typical satellite controller wiring diagram is shown below:
Figure 12-12: SAT III controller typical single panel wiring diagram
12-14
WCC III Technical Guide
Satellite Controllers - General Dimensions
8
7
SATADDRESS
2 1
4
8
A3 WIRE ROOM SENSOR WILLNOT REQUIREA LOAD RESISTOR W HEN SET FORA 1VOLT IN PUT.
WattMaster Controls Inc.
BINARY INPUTS
BINARY INPUTS
L8
ON OFF
128
32 16
64
L4 L3 L2 L1
L6 L5
L7
L11
L12
ON OFF
L10 L9
ON OFF
L15
L16
L14 L13
CH
4
3
5 6
2
1
LOCALSET
STATUS2
STATUS3
STATUS1
HSSXMIT
LOCALSET
LOCALSET DISABLE
BATTON/ OFF PULSEI NPUT
OPTION1
TEST
OPTION3 OPTION2
ON OFF
STATUS
HSS REC
SATXMIT
SATREC
ANALOGINPUT
JUMPERSELECTION
A2 WIRE ROOM SENSOR WILLREQUIRE A300OHM LOAD RESISTORWHENSET FORA 1VOLT IN PUT.
A4 TO 20mA SE NSOR WILLRE QUIRE A 50OHM LOAD R ESISTOR WHENSET FOR A1VOL T INPUT, OR A 250 OHM LOAD RESISTORWHENSETFOR A5 VOLTINPUT.
CURRENT INPUT
THERMISTOR INPUT
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
0-10V
THERM
0TO10V INPUT
0TO5V INPUT
0TO1V INPUT
0-10V
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
THERM
0-1V
0-5V
0-10V
THERM
PROGRAMMABLE CONTROLLER
SAT III
H
C
COM
CHANNEL
2134
2134
567
8
5678
V
OUT
GND
L O A D
+V
ATI
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
123456
123456
+VSENSORS
R1
R212R3R4R5
R6
3456
C
78
C
H
VOUT
GND
7 8
R
R7
R8
78
AT
EACHCONTACT ISRATEDFOR 24VACORVDC @.5AMPMAX
0-15VDC
OUTPUT MINLOAD IS1K OHM RESISTIVE VDCONLY
MADE IN
THEUSA
K16
K15
K14
K13
V16 V15 V14 V13
11.90
11.25
5.85
7.18
GND
24 VAC
24 VAC POWER
SAT
COMMUNICATION
RT
SHIELD
IN /OUT
HSS EXP
COMM
SATIIISIDE PROFILE VIEW (POWER INPUT)
SATIIISIDE PROFILE VIEW (SAT COMM & HSS PORT)
SATIII SIDE PROFILE VIEW (ANALOG IN/OUT - CONTROL OUTPUT)
3.00
7.18
12. WCC III INSTALLATION GUIDE
Satellite Controller Dimensions
Figure 12-13: SAT III controller dimensions. All dimensions are in inches.
Figure 12-14: SAT 3C/D/F controller dimensions. All dimensions are in inches.
WCC III Technical Guide
12-15
12. WCC III INSTALLATION
8
7
SAT ADDRESS
2 1
4
8
A3 WI RE ROOM SENSOR WILL NOT REQUIRE A LOAD RESISTOR WHE N SET FORA 1 V OLT INPUT.
WattMaster Controls Inc.
BINARY INPUTS
BINARY INPUTS
L8
ON OFF
128
32 16
64
L4 L3 L2 L1
L6 L5
L7
L11
L12
ON OFF
L10 L9
ON OFF
L15
L16
L14 L13
CH
4
3
5 6
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCAL SET
LOCAL SET DISABLE
BATT ON/ OFF PULSE INPUT
OPTION 1
TEST
OPTION 3 OPTION 2
ON OFF
STATUS
HSS REC
SAT XMIT
SAT REC
ANALOG INPUT
JUMPER SELECTION
A2 WI RE ROOM SENSOR WILL REQUIRE A30 0 OHM LOAD RESISTOR WHEN SET FORA 1 V OLT INPUT.
A4 T O 20m A SENSOR WILL REQUIRE A 50OHM LOADRESISTORWHEN SETFOR A1 V OLT INPUT, OR A 250 OHM LOAD RESISTORWHENSET FOR A5 VOLT INPUT.
CURRENT INPUT
THERMISTOR INPUT
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
0-10V
THERM
0 TO 10V INPUT
0TO5V INPUT
0TO1V INPUT
0-10V
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
THERM
0-1V
0-5V
0-10V
THERM
PROGRAMMABLECONTROLLER
SAT III
H
C
COM
CHANNEL
2134
2134
567
8
5678
V
OUT
GND
L O A D
+V
ATI
10A250VAC ~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC ~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC ~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC ~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
EACH CONTACT IS RATED FOR 24VACOR VDC @ .5 AMP MAX
0-15VDC
OUTPUT MINLOAD IS 1K OHM RESISTIVE VDCONL Y
SA T III LED Descriptions
SA T III Controller—LED Information (SS5003)
The SAT III Controller has 24 LEDs on the cover of the SAT III controller. The top 8 Status LED functions are as follows:
SAT REC - This LED will be lit when communications are being
received by the SAT III Communications Loop.
SAT XMIT - This LED will be lit when communications are being
transmitted by the SAT III Communications Loop.
HSS REC - This LED will be lit when communications are being
received from the HSS port.
HSS XMIT - This LED will be lit when communications are
being transmitted to the HSS port.
LOCAL SET - This LED will be lit when communications
with the WCC III-MCD has not occurred for at least the last two minutes. This means that the SAT III is not communicating on the SAT III communications loop. Setpoint control in the SAT III is dependent on the LOCAL SET parameters which are programmed into each control point by the user.
STATUS 1 - LED blinks every 1 second if SAT III is alive. STATUS 2 - LED blinks every 1 second during power on delay,
and then blinks every 8 seconds when watchdog is enabled.
STATUS 3 - LED blinks for every internal calculation loop
completion.
The lower 16 LEDs display the status of the 16 “H” and “C” Relay Outputs. The 16 LEDs display the status of the eight “H” and eight “C” contacts.
Figure 12-15: SAT III LED locations
12-16
WCC III Technical Guide
12. WCC III INSTALLATION GUIDE
SA T III Connection Points
SA T III Controller — Connection Points
All of the external SAT III connection points are single tab ¼-inch Sta-Con connectors. With the exception of the “old” connection method of connecting the Binary Inputs which are 16-pin dip cable connections and the HSS EXP COMM port which is a 6-pin pre­made MOLEX type mini-fi t cable connection.
+V Connections.
There are eight +12-VDC connections that power analog type sensors of which the fi rst seven of these connections are fi xed to +12VDC only. The eighth +V connector is jumper (JP1) selectable for either +12VDC, or +24VDC. This (JP1) jumper can be set to +12VDC, or +24VDC so that the voltage at the eighth +V connection point is either +12VDC or +24VDC. The +24VDC is useful when connecting 4-to-20 mA sensors that require a connection voltage greater than +12VDC. You may connect up to eight 4-to-20 mA sensors to this eight +V (+24VDC) connection point. This JP1 jumper is located under the cover of the SAT III controller, just to the right of the eighth +V connector.
A TI Connections
These eight connections are connection points for ATI #1 to ATI #8 analog inputs. ATI is the acronym for Analog Temperature Input. These eight connection points are for Analog Inputs. This is where analog type sensors are connected to the SAT III controller. The types of sensors inputs that are supported on the SAT III controllers are: 0-1V, 0-5V, 0-10V, 10K Type 3 Thermistor, 4-20mA (On both the 0-1V, and 0-5V inputs). There are also eight Analog Input selection jumpers that are located under the cover of the SAT III controller near the Analog Inputs that actually set the type input voltage ranges for each of the eight analog inputs. These Analog Input selection jumpers are labeled JO1 to JO8. JO1 corresponds to analog input #1, JO2 corresponds to analog input #2, JO3 corresponds to analog input #3, JO4 corresponds to analog input #4, JO5 corresponds to analog input #5, JO6 corresponds to analog input #6, JO7 corresponds to analog input #7, JO8 corresponds to analog input #8. Each of these Analog Input selection jumpers has four jumper options: 0-1V, 0-5V, 0-10V, and THERM. See
Figure 12-34 and 12-35 for further wiring details. See Section 3
for further programming instructions.
GND Connections
These GND connections are analog ground common connection points for all of the analog input (ATI), and analog output (VOUT) connections.
VOUT 1 to V OUT 8 Connections
These eight analog outputs are set up to provide 0 to +15 DC Volts outputs at up to 15 milli-amps per output. These outputs are typically used to drive a VFD, 0-10VDC or 2-10VDC actuator or
valve. VOUT is the acronym for Voltage Output. See Section 3 for
additional programming instructions.
H 1 to H 8 Connections
The eight “H” connection points of the SAT III controller were originally classifi ed and labeled as “HEAT” contacts starting with the SAT 0, SAT I, and SAT II controllers. They do not need to be used only for “HEAT” contacts, as these contacts are general purpose relay outputs. There is a load protection device called a varistor across each of the eight “H” output connections that limit the allowable voltage to no more than 32 volts AC\DC maximum at 1 amp current draw for each contact. Attempting to switch any voltage greater than 32 Volts, or current draws of more than 1 amp per contact could and will result in damage to the SAT III controller. These “H” and “C” contact outputs are meant to control tri-state actuators, contactors, relays, solenoids, and the PI board AKA “ECC II ANALOG OUTPUT” board that WattMaster
Controls used to manufacture. See Figure 12-18 for further wiring details. See Section 3 for additional programming instructions.
COM 1 to COM 8 Connections
The COM1 connection point is a common connection point for H1 and C1 Relays. None of the COM connections are connected to any of the other seven COM connection points. A jumper cable is available to connect all of the COM connection points together. Each corresponding “H” and “C” contact are connected to a single corresponding “COM” connection point. So “H1” and “C1” are connected to “COM1”, “H2” and “C2” are connected to “COM2”,
etc. See Figure 12-18 for further wiring details.
WCC III Technical Guide
12-17
12. WCC III INSTALLATION
SA T III Connection Points
C 1 to C 8 Connections
The eight “C” connection points of the SAT III controller were originally classifi ed and labeled as “COOL” contacts starting with the SAT 0, SAT I, and SAT II controllers. They do not need to be used only for “COOL” contacts, as these contacts are general purpose relay outputs. There is a load protection device called a varistor across each of the eight “COOL” output connections that limits the allowable voltage to no more than 32 volts AC\DC maximum at 1 amp current draw for each contact. Attempting to switch any voltage greater than 32 Volts, or current draws of more than 1 amp per contact could and will result in damage to the SAT III controller. These “H” and “C” contact outputs are meant to control tri-state actuators, contactors, relays, solenoids, and the PI board AKA “ECC II ANALOG OUTPUT” board that WattMaster
Controls used to manufacture. See Figure 12-18 for further wiring details. See Section 3 for additional programming instructions.
Binary Inputs
The SAT III controller has two sets of eight-position dipswitches on its front panel labeled L1 - L8 and L9 - L16. Switches L1-L8 are housed together in one dipswitch, and switches L9-L16 are housed together in another dipswitch. For the old connection method one dipswitch is removed for each Binary Input with Time Delay board, and is then replaced with a ribbon cable which connects the Binary Input with Time Delay board to the SAT III controller. The binary devices to be monitored are then wired to the terminal strip of the Binary Input with Time Delay board. The Binary Input with Time Delay board requires a 24-VAC power source. Warning you must observe polarity on the 24-VAC and GND connections of both the Binary Input with Time Delay board and the SAT III controller, as the grounds must be the same. Or, an alternative connection method to the SAT III controller is now provided by the 6-pin HSS
expansion port on the side of the SAT III controller. See Figures 12-26, 12-27, & 12-28 for further wiring details.
24V AC & GND Connection
Located on the bottom side of the SAT III controller is a 24 VAC and GND connection. This is the main power connection to the SAT III controller. Each SAT III Controller draws - 15VA. External relays and contactors are not included, but need to be considered for total VA draw. The GND connection points must be the same between all of the externally powered expansion boards and the
SAT III Controller. See Figure 12-27 for further wiring details.
SA T Communica tion Connection
These connection points are for wiring of the RS-485 communication loop. There are two “T” (Transmit) connections, two “R” (Receive) connections and two “SHIELD” connection points. There are two connection points provided for each connection for easy “daisy chaining” to the next Satellite Controller. When connecting the RS-485 wiring from SAT III to SAT III or SAT 3C/D/F, or SAT 3P controller the wiring connections are as follows: connect “R” TO “R”, “T” TO “T”, AND “SHIELD” TO “SHIELD” OR “SH”. The RS-485 wire specifi cations are plenum-rated, jacketed stranded 18-gauge, 2-wire twisted pair with shield. 18-gauge stranded wire is mandatory to ensure a good connection with the ¼-inch Sta-Con connectors which are used to terminate the wires at the WCC III ­MCD and at the satellite controllers.
HSS EXP COMM Connection
The HSS EXP (Expansion) Port enables newer versions of the satellite expansion boards, most notably the Binary Input with Time Delay Board and V-Out RELAY Board to work without connecting the previous way (separate power and hard wiring was required). The SAT III has a single connection via the built-in HSS EXP port on the side of the SAT III. It is designed to connect and power up 5 HSS Expansion Boards. Connecting more than 5 HSS Boards is possible, but each additional board will require a 24VAC power supply.
The HSS EXP port provides power and ground, along with communications on a 6-pin pre-made MOLEX type mini-fi t cable connection. This cable is made with 16-gauge wire.
Each HSS Expansion Board has an 8-position address dipswitch that is used to set up the function of the board.
The HSS EXP port can be daisy chained to the next board. The HSS cable connections allow the HSS expansion boards to be located up to 150 feet away from the SAT III Controller.
HSS connection cables are available in the following sizes: 6-inch, 12-inch, 18-inch, 3 feet, 25 feet, 40 feet, 80 feet, and 120 feet.
12-18
WCC III Technical Guide
12. WCC III INSTALLATION
8
SAT ADDRESS
2 1
4
ON OFF
128
32 16
64
SAT III ADDRESS SWITCH
GUIDE
SA T III Addressing
Addressing (Numbering) of SA T III Controllers
The WCC III system can have up to 239 SAT III controllers. In order for the central computer to communicate properly with each individual SAT III controller, each controller must be assigned a separate number, or address. The number is assigned by placing the small dip switches on the front of the SAT III controller marked “SAT ADDRESS” in the proper position.
The address dip switches are additive; that is to say placing switches 1 and 2 in the ON position will cause the SAT III controller to be identifi ed as satellite controller number 3. The SAT III controller looks at the position of these switches only when it is going through its initialization process after being powered up. Simply changing the switch positions on a SAT III controller that is currently “on-line” will not change its number. The switches need to be placed in the proper position before powering up the SAT III controller, or the SAT III must be powered down and then back up for the SAT III to “read” the new position of the switches. When placing the switches in the desired position, make sure the switch has “clicked” into place and is properly seated.
Figure 12-16: SAT III address switch loca tion
WCC III Technical Guide
12-19
12. WCC III INSTALLATION
SA T III Addressing
Care must be taken to ensure that two SAT III controllers do not have the same address. When this condition is present, the central computer does not know where to send the information, and the information that should be sent to the SAT III controller is usually lost.
You should be aware of the symptoms caused by two satellite controllers having the same number. Let’s consider a new job in which the satellite controllers have not yet been programmed and 2 SAT III controllers are named number #3. When you call up satellite controller #3 to enter data, everything will appear to be ne. You will be able to enter data on the screens as if nothing is wrong. However, when you leave a screen and then return to the same screen, all of the data you entered will be missing. Also, if you fi nish programming the analog inputs for example, and then go to the analog input summary screen to review your inputs, all of the data you have entered will be missing.
Another situation that you might encounter is adding a SAT III controller to an existing system and accidentally giving it the same number as a SAT III presently “on-line.” Again, when you begin to program the new SAT III controller, everything will appear fi ne until you leave a screen or if you go to a summary screen. Only now, all of the data is usually not missing. Generally, you get parts of your data back and parts will be missing.
If you suspect you might have two SAT III controllers with the same address (number 3 for example) the best thing to do is go to the SAT III controller that you know is number 3, and remove the 2-wire RS-485 communication loop from it. Then, go back to the computer and call up satellite controller #3. If the computer can still “talk” to satellite controller #3, there is another satellite controller that is addressed #3 connected somewhere on the RS­485 communication loop.
If a satellite controller was accidentally addressed #3, there will be a satellite number missing. For example, if satellite controller #7 was accidentally misaddressed to #3, satellite controller #7 will not be present. One way of telling which satellite controllers are
“on-line” is to go to the Satellite Summary Screen (see Section
3) and see which satellite controllers the computer recognizes as
being “on-line.”
If satellite controller #7 was accidentally miss-addressed #3, there would not be a satellite controller at address #7, and the computer will give a “Non-Existing” message for satellite controller #7.
Option 1, 2, and 3 Switches
Option switches 2 and 3 do nothing. But, the SAT III controller option “1” switch selects the A-to-D converter type that is on the mother board. With the switch turned OFF, the A-to-D curve is selected for the Maxim MAX147 part, and with the switch turned “ON” for the TI-ADS7844 (BB marked) the software will use the
special A-to-D curve for the TI-ADS7844 part. See Section 3 for
proper A-to-D identifi cation.
BA TT ON/OFF s witc h
This switch is used to turn the Battery (Rechargeable Super cap) ON and OFF to the SRAM located inside of the SAT III processor.
Since version 2.00 of the Satellite software the non-volatile memory is now also stored in the EEPROM, instead of the SRAM, and upon power up the memory is read from the EEPROM back into the SRAM. This switch is not of any importance anymore.
Local Set Switch
When the LOCAL dipswitch is in the ON position, the SAT III controller will operate according to their predefi ned user programmed “local set” setpoints. That is, if the SAT III controller was programmed by the user to correctly operate when and if the WCC III - MCD is off-line or disconnected.
Local Set Disable Switch
When the LOCAL SET Disable dipswitch is in the ON position, the SAT III controller will operate according to their predefi ned user programmed “On” setpoints. That is, if the SAT III controller were programmed by the user to correctly operate when and if the WCC III - MCD is off-line or disconnected.
Test Switc h
The test mode is active only if the TEST dipswitch is in the ON position. The word “TEST” can be input as the binary value within the SAT III. Example of use would be if the user programmed the word “TEST” into one of the control point values in the SAT III controller to check the operation of the SAT III controller with an alternate setpoint or schedule, the user could then place the TEST switch in the ON position to make this function work with out physically having to go back to the front-end computer to change a setpoint via the computer.
12-20
WCC III Technical Guide
12. WCC III INSTALLATION
8
7
SAT ADDRESS
2 1
4
8
A3 WI RE ROOM SE NSOR WILL NO T REQUIREA LOADRESIST OR WHEN SET FORA 1VOLT INPUT.
WattMaster Controls Inc.
BINARY INPUTS
BINARY INPUTS
L8
ON OFF
128
32 16
64
L4 L3 L2 L1
L6 L5
L7
L11
L12
ON OFF
L10 L9
ON OFF
L15
L16
L14 L13
CH
4
3
5 6
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCAL SET
LOCAL SET DISABLE
BATT ON/ OFF PULSE INPUT
OPTION 1
TEST
OPTION 3 OPTION 2
ON OFF
STATUS
HSS REC
SAT XMIT
SAT REC
ANALOG INPUT
JUMPER SELECTI ON
A2 WI RE ROOM SE NSOR WILL REQUIRE A300 OHMLOAD RESISTORWHEN SET FORA 1VOLT INPUT.
A4TO20mASENSORWILLREQUIREA
50OHM LOADR ESISTOR WHEN SET FOR
A1 VO LT INPUT , OR A 250 OHML OAD
RESISTORWH EN SET FOR A 5 VOL T INPUT.
CURRENT INPUT
THERMISTOR INPUT
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
0-10V
THERM
0TO10V INPUT
0TO5V INPUT
0TO1V INPUT
0-10V
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
THERM
0-1V
0-5V
0-10V
THERM
PROGRAMMABLECONTROLLER
SAT III
H
C
COM
CHANNEL
2134567
8
10A250VAC ~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC ~
5A30VDC
SA
VDE
-1A4
ON
24V
CHINA
10A250VAC ~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
NTACT
FOR
VDC
AX
GUIDE
SA T III Relay Outputs
SA T III Relay Outputs
The standard SAT III controller is capable of providing 16 binary (on/off) relay outputs. These 16 relay outputs are for driving pilot duty relays. There is a load protection device called a varistor across each of the 16 output connections that limits the allowable voltage to no more than 32 volts AC\DC maximum at 1.0 or 1 amp current draw for each contact.
Attempting to switch any voltage greater than 32 Volts, or current draws of more than 1.0 or 1 amp per contact could and will result in damage to the SAT III controller. These “H” and “C” contact outputs are meant to control tri-state actuators, contactors, relays, solenoids, and the PI board AKA “ECC II ANALOG OUTPUT” board that WattMaster Controls used to manufacture. These relay outputs can be programmed in three different types of modes of basic operation: Time Clock, Dual Limit, and EA Mode. See
Section 3 for further details on Satellite programming instructions.
Figure 12-17: SAT III “H” and “C” control output wiring connections
WCC III Technical Guide
12-21
12. WCC III INSTALLATION
H
COM
C
12345678
12345678
SA T III Relay Outputs
The terminals for the binary outputs are found at the lower left­hand corner of the SAT III controller and are labeled “H”, “COM”, and “C”. The relay contact can make or break a 24-VAC or 24­VDC circuit between the COM to H or COM to C terminals. The COM to H contacts are referred to as XXXK1h-K8h in the WCC III point addressing scheme, and the COM to C contacts are referred to as XXXK1c-K8c in the WCC III point addressing scheme. XXX is the Satellite address number 1 to 239, “K” stands for contact, and the numbers 1-8 stand for the channel on the SAT III controller.
Each “H” and “C” contact connection has a “COM” connection associated with it. Please note that each one of the sets of the corresponding “H” and “C” contacts are also isolated from each other. The “COM” connection means common. When wiring the control outputs, typically all of the “COM” connections are wired together, using the supplied jumper wire (PL100867). This “COM” common connection can either be connected to 24VAC / 24VDC or GROUND depending on the application.
Figure 12-18: SAT III “H” and “C” control output schematic
Figure 12-19: A control output common jumper wire is provided (PL100867) for connecting the eight “COM” connections together
The pre-made control output common jumper wire is provided in the initial spare parts kit that came with the SAT III controller. This spare parts kit contains various input load resistor packs, spare fuse, and the control output common jumper. The spare parts kit is WattMaster part number PL102029.
12-22
WCC III Technical Guide
1
1
1
1
COM - 24VAC COM - GROUND
H
C
H
C
Figure 12-20: COM connection as 24 VAC or as GR OUND
12. WCC III INSTALLATION
SA T III Relay Outputs
GUIDE
The “COM” or common connection point can either be connected to 24 VAC / 24 VDC or GROUND. It is basically a point of view of turning power “on” to a device, or removing “ground” going to the device. It makes no difference, as both methods will work equally well, and really depends on the application you are trying to control.
WCC III Technical Guide
12-23
12. WCC III INSTALLATION
Proportional-Integral (PI) Output Board
Proportional-Integral (PI) Output Board
The Proportional-Integral (PI) Board is a separate integrated circuit board which works in conjunction with the SAT III controller to convert a pair of SAT III binary outputs to a varying DC voltage signal. When one contact on the SAT III controller closes, the voltage supplied by the PI board will ramp down at a pre-set rate. When the other SAT III contact closes, the voltage ramps up at the preset rate. When both contacts are open, the voltage supplied by the PI board will remain at its present value. The maximum DC voltage range is 0-14.5 volts, and the minimum allowable
resistance of the controlled device is 1000 ohms. See Section 3 for
further details on Satellite programming instructions.
Figure 12-21: ECC II Analog Output Board
12-24
WCC III Technical Guide
12. WCC III INSTALLATION GUIDE
PI Board Connection Points
The DC voltage range along with the ramp speed is set at the PI board. The ramp speed can be adjusted from 23 seconds to 38 minutes, and the maximum range is 0-14.5 volts DC.
To control a VFD drive from a SAT III controller using the Proportional-Integral board, you must use two control outputs and a circuit board (PI Board) that we no longer make. WattMaster Controls does not make the PI Output Board anymore, but Kele makes a similar circuit board that should work. It is a Tri-State-to­Analog Output circuit board (Kele Part # PWA-2T).
If only one contact closure is available to drive the PI Board, move jumper J01 on the WattMaster PI board to the B-C position and use the SAT III’s control output in the Dual Limit mode to control the PI Board. Although when using this method with the WattMaster PI Board, the DC voltages supplied by the WattMaster PI Board will either be increasing or decreasing at the set ramp speed depending on if the contact is open or closed.
The Global Analog Mode 9 Dual Ramp Screen was created to help emulate the old WattMaster PI board in software. It basically uses the control set points of two control outputs on a satellite controller to control a single analog output on a satellite controller and should be used when controlling an analog actuator or VFD that needs to
have an analog control setpoint. See Section 3 for further details on
Satellite programming instructions.
The Proportional-Integral (PI) Board ­connection points
All of external connections to Proportional-Integral (PI) Board connection points are non de-pluggable screw-cage type of wire clamped based terminal blocks.
24 V AC (TB1-5) & GND (TB1-6)
ANALOG OUT (TB2-1) & GND (TB2-3&4)
The “ANALOG OUT” and “GND” terminals supply the DC voltage from the PI board.
Adjust Minimum Voltage
The PI board is factory set for a minimum voltage of 0 VDC +/-
0.2 VDC. If you want a minimum voltage other than 0 VDC, you can reset it by adjusting the potentiometer (pot) labeled “R9.” The voltage between test point #3 (labeled “TP #3” on the PI board) and ground is set 300 mV lower than the desired minimum voltage. That is to say, if you want 5 VDC as the minimum voltage to be supplied between the “ANALOG OUT” and “GND” terminals, adjust pot “R9” to get 4.7 VDC between “TP #3” and “GND.”
NOTE: The minimum voltage setpoint must be lower than the
maximum voltage setpoint.
Adjust Maximum Voltage
The PI board is factory set for a maximum voltage of 14.5 VDC +/- 0.2 VDC. If you want a maximum voltage other than 14.5 VDC, you can reset it by adjusting the potentiometer (pot) labeled “R10.” The voltage between test point #2 (labeled “TP #2” on the PI board) and ground is set at 300 mV above the desired maximum voltage. That is to say, if you want a maximum voltage of 10 VDC to be supplied by the “ANALOG OUT” and “GND” terminals, adjust pot “R10” to get 10.3 VDC between “TP #2” and “GND.”
NOTE: The maximum voltage setpoint must be higher than
the minimum voltage setpoint.
The PI board requires a 24 VAC power supply which is connected to these terminals. The PI board is generally powered by the same 24 VAC transformer that powers the satellite controller. The GND connection points must be the same between the PI board and the SAT III Controller.
HEA T (TB1-1) & COM1 (TB1-2)
When 24 volts AC is supplied between the “HEAT” and “COM1” terminals, the DC voltage supplied by the PI board will start increasing at the set ramp speed.
COOL (TB1-1) & COM2 (TB1-4)
When 24 volts AC is supplied between the “COOL” and “COM2” terminals, the voltage supplied by the PI board will start decreasing at the set ramp speed.
WCC III Technical Guide
Adjust “Ramp” Speed
The ramp speed is the time it takes for the DC voltage between the “ANALOG OUT” and “GND” terminals to change from the minimum voltage to the maximum voltage and vice versa. The ramp speed is factory set at about 19 minutes. If you want a ramp speed other than 19 minutes, you can reset it by adjusting the potentiometer (pot) located at R2. When R2 is fully counterclockwise, the ramp speed is 38 minutes (+/- 10%). When R2 is fully clockwise, the ramp speed is 23 seconds (+/- 10%). As the voltage is ramping up, the small light labeled D1 will fl ash and as the voltage is ramping down, the small light labeled D2 will fl ash.
12-25
Loading...
+ 61 hidden pages