WCC III - MCD LCD Display .....................12-73
The WCC III - MCD ...................................12-78
Using the MCD-Menu Program ...............12-79
12. WCC III INSTALLATION
GUIDE
System Requirements
SECTION 12:
WCC III INST ALLA TION GUIDE
__________________________________________
WCC III System Requirements
To accomplish remote communications via the internet, the
following items are needed in addition to the WCC III system in
order to control the building mechanical systems. The WCC III
system is not to be used in any application where Fire/Life/Safety
is an issue.
WCC III – MCD System Requirements
(On-Site WCC III – MCD Computer):
• DSL, or a Cable router/switch that connects to the
internet. Or, as an alternative, an internal jobsite
IP network that does not connect to the internet,
but when using this internal jobsite IP network, the
external internet Email of alarms from the WCC III
- MCD will not be possible. Also, external access
via the internet may not be possible.
• A fi xed static IP address or a fi xed IP domain host
name.
• Enabled port forwarding on the Firewall of the
router/switch. This is only if a fi rewall is used.
• On earlier versions, antivirus software is initially
provided by WattMaster Controls, with Norton
antivirus software for a period of 1 year. The
customer must maintain the antivirus software after
this 1-year period. Later versions are shipped with
Linux as the operating system and do not require
anti-virus software.
• An Email address that supports a SMTP
server for SENDING with a pop server for
RECEIVING Emails, and it must have “auth
login” authentication. TLS or SSL modes are not
supported. WattMaster Controls can provide an
Email address with these requirements.
• An Uninterruptible Power Supply (UPS) – 750-
Watt minimum
• A wall mounting surface is preferred.
• A dedicated 120VAC power circuit is required.
Front End Software Requirements
(Operator Console Software):
• A Microsoft Windows XP /Vista/Windows 7-based
computer.
• Minimum hardware specifi cation for the Microsoft
Windows XP / Vista based computer is a Pentium
IV running at 2.4 Giga Hertz with at least 1 GB
of RAM, and 10 GB of spare hard drive space. A
CDROM/DVD player is also required for software
installation.
• WCC III software package – Provided on a
CDROM, or is available via a download on the
WCC Controls website: www.wcc-controls.com.
The installation CDROM contains the following
programs:
• A DSL or Cable router/switch that connects to the
internet, or access to the internet via some other
method. Or, as an alternative, an internal jobsite
IP network that does not connect to the internet,
but when using this internal jobsite IP network, the
external internet Email of alarms from the WCC III
- MCD may not be possible.
* NOTE: The TenantOverride.exe program is also available
as a single program installation for the end users that are using
the simplistic graphical interface of the TenantOverride.exe
screen to locally turn on and off specifi c control points that are
applicable to the end user.
WCC III Technical Guide
12-1
12. WCC III INSTALLATION
Basic Operating Conditions and Wall Mounting
The WCC III – MCD Basic Operating
Conditions
The WCC III - MCD must be kept in a clean and dry area in the
building. The ambient temperature must be between 50 and 100 °F,
and the relative humidity must be kept between 0 and 90% (noncondensing). The interior components are cooled by ventilation
fans within the WCC III – MCD unit, and therefore the unit should
not be kept in tightly confi ned or enclosed areas. The WCC III -
MCD is primarily designed to mount on a wall with the supplied
brackets.
The WCC III – MCD computer requires 115 VAC power and must
remain powered at all times for proper operation and control. The
115 VAC power circuit must be separate and dedicated exclusively
to the WCC III – MCD computer.
The WCC III - MCD system is designed to automatically restart
after a power failure. However, the industrial computer which
acts as the WCC III Master Communications Device will not
automatically reboot unless the power is shut off cleanly and
then restored cleanly. During most power outages, the incoming
115 AC voltage could have great fl uctuations before the power fi nally fails. In a like manner, brownouts will usually cause the
industrial computer to “lock-up.” That is to say, the screen will
continue to display on the monitor, but the cursor will not respond
to the keyboard commands. To prevent this “lock-up” issue from
happening to the WCC III – MCD, an Uninterruptible Power
Supply (UPS) is required on each and every WCC III – MCD
computer.
An Uninterruptible Power Supply (UPS) provides emergency
power to keep the WCC III Master Communications Device
(personal computer) on-line for several minutes after a primary
power failure. The UPS regulates the incoming power to the
computer and shuts the power off cleanly several seconds after the
power outage, or brownout. When the primary power is restored,
the UPS brings the MCD back on-line automatically. The WCC
III system does not lose any information since all of the programs
and user entered data are stored on either a disk in the MCD, on
fi rmware, or on battery backed memory in the satellite controllers.
Figure 12-1: Installing the six screws for the two wall
mounting brackets of the WCC III – MCD Computer
Do not mount the WCC III – MCD computer straight into the
drywall. The use of a ¾-inch plywood “Backer Plate Board” is
required. You may want to paint this plywood “Backer Plate
Board” to match the color of the wall before mounting to the wall.
See Figure 12-2 for further application.
Backer Plate Mounting Notes:
Use correct type of wall mounting anchors for mounting on a
concrete wall for the mounting of the “Backer Plate Board” if and
when mounting the Backer Plate Board to a concrete wall. Use
at least 2-inch dry wall type screws if mounting the Backer Plate
Board to a “Dry-Wall” type wall. Mount the “Backer Plate Board”
so that the screws that are holding the “Backer Plate Board” are on
the 16-inch centers of the wall studs where applicable.
Mount the WCC III - MCD 4-½ to 5-½ feet off of the ground on a
suitable wall, in an air conditioned space. This area should not have
any radio transmitting or telephone switching gear in the space, or
near the space, or located on the back side of the adjacent wall.
Wall Mounting of the WCC III – MCD
It is strongly suggested that the WCC III – MCD is mounted on the
wall. General guidelines are as follows:
Always install the supplied six screws for the two supplied wall
mounting brackets for the WCC III – MCD Computer as shown in
Figure 12-1. Be sure to tighten the six screws so that they do not
loosen over time.
12-2
Do not block the airfl ow vents that are coming out of the WCC III-
MCD. Do not apply paint to the WCC III-MCD enclosure. Do not
cover the WCC III-MCD with any protective plastic while painting
with the WCC III-MCD turned on. The UPS battery backup unit
should be located within 3 or 4 feet of this WCC III – MCD.
WCC III Technical Guide
12. WCC III INSTALLATION
Wall Mounting of the WCC III - MCD
Wall Mounting of the WCC III - MCD
Front view with wall mounting brackets
GUIDE
Use 3/4 inch plywood for the backer plate board
(supplied by others)
Figure 12-2: Wall mounting instructions for the WCC III – MCD
NOTES:
at least 2-inch dry wall type screws. Mount the backer plate board so that the screws that are holding the backer plate board are on the 16inch centers of the wall where applicable.
Mount the WCC III - MCD 4-½ to 5-½ feet off of the ground on a suitable wall in an air conditioned space. This space should not have any
radio transmitting or telephone switching gear in the space, or near the space, or located on the back-side of the adjacent wall.
Do not block the airfl ow vents that are coming out of the WCC III - MCD. Do not apply paint to the WCC III - MCD enclosure. Do not
cover the WCC III - MCD with any protective plastic while painting with the WCC III - MCD turned on.
The UPS should be located within 3 or 4 feet of this WCC III - MCD.
WCC III Technical Guide
Use approved anchors when mounting backer plate board on a concrete wall. If mounting backer plate board to dry wall, use
12-3
12. WCC III INSTALLATION
WCC III - MCD Internet Access
WCC III – MCD Internet Access
The most common question asked is: Why does the WCC III –
MCD computer need to have Internet access?
If WattMaster Controls factory assistance or troubleshooting is
required for a WCC III system, a representative from the factory
can access the system with a remote computer and view the same
WCC III Screens as the end user or contractor in the building. This
allows the end user or the contractor for the building installation to
talk to the factory representative while they are both viewing the
same screens.
The Emailing of important alarm notifi cations for up to 60 Email
Addresses is provided for from the WCC III – MCD.
The ability to send alarm notifi cation via a text message to a
cellular phone.
Secure Remote communications package (WCC III software) is
provided for FREE. A CD-ROM is supplied for installation.
World-wide, multiple remote connections (up to 255 simultaneous
connections possible)
On earlier versions, antivirus software is initially provided by
WattMaster Controls, with Norton antivirus software for a period
of 1 year. The customer must maintain the antivirus software after
this 1-year period. Later versions are shipped with Linux as the
operating system and do not require anti-virus software.
The ability for internet based tenant override requires internet
access.
WCC III – MCD Cable Modem/Router
T echnical Considerations
The WCC III-MCD uses internet access to e-mail alarms and to
provide remote IP access for multiple remote WCC III operator
programs.
The DSL / Cable modem USB connection should not be connected
to any of the USB ports on the WCC III – MCD. The DSL / Cable
modem Ethernet connection should only be connected to the
Ethernet port on the WCC III – MCD if the DSL / Cable modem
has a built-in internal router with Ethernet switch.
The use of a DSL / Cable modem with an external router that is
then connected to the WCC III - MCD is also a recommended way
to connect the internet to the WCC III – MCD. The use of only a
plain DSL / Cable modem without an internal router with a built-in
switch is not currently recommended by WattMaster Controls.
It is recommended that the WCC III-MCD computer be connected
to the internet via a high-speed cable modem or NAT enabled
router.
This is best accomplished by what is called Port Forwarding (also
sometimes referred to as tunneling) and is the act of forwarding a
network port (located External on the internet) to another network
node (located Internal on the LAN). This technique can allow an
external user (The WCC III program) to reach a port that is on
a private LAN (Local Area Network) IP address (The WCC III MCD) from the outside via a NAT enabled router. This external
port number that is used for the WCC III – MCD computer is port
39289.
Custom remote WCC III system programming or analyzing of the
existing WCC III program is also available for a nominal charge.
Some cable modem devices may incorporate a router along with
the cable modem functionality, to provide the LAN with its own IP
network addressing. From a data forwarding and network topology
perspective, this router functionality is typically kept distinct from
the cable modem functionality (at least logically) even though
the two may share a single enclosure and appear as one unit. So,
the cable modem function will have its own IP address and MAC
address as will the router.
Figure 12-3: Typical small business type routers—a Broadband Firewall Router, and a Cable/DSL VPN Router
12-4
WCC III Technical Guide
12. WCC III INSTALLATION
GUIDE
WCC III - MCD Internet Access
In a typical WCC III - MCD networking setup, internet access
is through a DSL or Cable modem. This modem may then be
connected to a router with a built in switch, (or typically the router
with switch is also built-in to the modem) which is then connected
to the internal LAN of networked computers by Ethernet cabling.
The NAT enabled router is the only device that the Internet sees
as it holds the public IP address. On the other hand, the WCC III
– MCD, located behind the NAT enabled router, is invisible to the
Internet as it holds a local IP address on the NAT enabled router.
Port forwarding is necessary in the NAT enabled router because
computers that are running the WCC III program will send
information that is directed to the public IP address and the NAT
enabled router needs to know where to send and then redirect that
information to the WCC III – MCD.
NOTE: A DSL modem is not recommended due to yet
another layer of setup complexity. DSL modem/routers also
have a maximum distance from the local telephone company’s
main central offi ce. That distance is 18,000 feet.
Step 1: You will need a high-speed cable or DSL modem/router
that is NAT enabled and it must be setup by the ISP, or by IT
(Information Technology) knowledgeable personnel, and it must
also be connected to the Internet.
The default IP addresses that the WCC III – MCD is shipped with
are:
WCC III-MCD IP Address: 192.168.100.100
WCC III-MCD Subnet Mask: 255.255.255.0
WCC III-MCD Default Gateway: 192.168.100.1
WCC III-MCD Preferred DNS Server: 208.67.222.222
WCC III-MCD Alternate DNS Server: 208.67.220.220
The external port number that is used for the WCC III – MCD
computer is port 39289.
For WCC III – MCD’s running windows set up the WCC III –
MCD BACKTASK.EXE Program
Com Port # ____________
External Port Range ____________
Default for the backtask.exe program is Comm port # 5 and port
# 39289.
Step 2: The following three items are needed from your ISP
(Internet Service Provider) in order to set up the Cable / DSL
modem/router for stand alone internet access. The ISP should
have already supplied a sheet of paper that has this important
information on it.
WCC III-MCD IP Address: _______._______._______._______
WCC III-MCD Preferred DNS Server: _________._________.__
______._______
WCC III-MCD Alternate DNS Server: _________._________.__
______._______
WCC III Technical Guide
12-5
12. WCC III INSTALLATION
WCC III - MCD Internet Access
Supported Networks
Only Microsoft based networks are currently supported by the
WCC III system. Any of the older 10 base T only networks are
not supported by the WCC III system, only 100 base T or faster
networks are supported. (10/100 base T are OK) The slower the
network, the slower the data returned from the WCC III-MCD will
be displayed, and the faster speed is always better.
Also, network “hub” devices are not recommended, because
“hub” devices divide the network’s bandwidth amongst the active
connections that are connected to the network hub. For example,
if you have a 16-port network hub on a 100 base T connection
with 10 active connections, then your effective network speed is
the same as a 10 base T connection.
A 10/100 base T network switch is the recommended connection
to the WCC III-MCD device. A network switch device has a full
100 base T connection to all active ports at the same time.
Benefi ts of Using a Separate DSL /
Cable Modem Internet connection for
the WCC III-MCD
1. It provides a layer of network isolation. A connection to the
building’s internal computer network may not be desirable to the IT
department. If the WCC III – MCD is connected to the building’s
internal computer network an additional fi rewall into the building’s
internal computer network may be required.
2. A dedicated high speed internet connection is a faster connection.
WCC III displayed data will be displayed quicker and updated
faster.
How to send a T e xt Message to a
Cellular phone via an Email from the
WCC III system
Most cellular telephone providers have as a free* option (Charges
may apply in some instances) an Email-to-TEXT service for their
cellular phone plans. *Usually the cellular telephone providers
will have an unlimited text messaging option in one or more of
their plans.
When using Verizon cellular service, the text messaging email
address for your phone is your 10-digit phone number followed
by @VTEXT.com. For example, if your phone number is 1-555555-5555, your email address (for TEXT MESSAGING) would
be 5555555555@VTEXT.com
When using Sprint cellular service, the text messaging email
address for your phone is your 10-digit phone number followed by
@messaging.sprintpcs.com. For example, if your phone number
is 1-555-555-5555, your email address (for TEXT MESSAGING)
would be 5555555555@messaging.sprintpcs.com.
When using AT&T cellular service, the text messaging email
address for your phone is your 10-digit phone number followed
by @txt.att.net. For example, if your phone number is 1-555-5555555, your email address (for TEXT MESSAGING) would be
5555555555@txt.att.net.
Example: 5555555555@VTEXT.com, 5555555555@messaging.
sprintpcs.com, or 5555555555@txt.att.net would be programmed
into the WCC III System parameters screen as an Email address.
Any alarm type level that is generated would be sent to that cellular
telephone number as a text message.
3. Network outages should be less frequent, due to the fact that
there is no overhead of a pre-existing internal computer network.
A pre-existing internal computer network will always require
periodic “downing of the network servers” to do maintenance
work to the existing computer network regardless of having the
WCC III-MCD connected to the pre-existing internal computer
network.
4. The need for having an onsite IT person to setup, and then
administer the WCC III-MCD will be reduced.
5. Setup and maintenance of e-mail accounts would be easier,
because they would be automatically provided by the Internet
Service Provider.
12-6
WCC III Technical Guide
12. WCC III INSTALLATION
<<<LOCAL LOOP>>> AZWR-LL-WG-18>>> E76191 CL2P 18AWG (UL) 012112 FT
<<<NETWORK LOOP>>> AZWR-NL-WR-18>>> E76191 CL2P 18AWG (UL) 012112 FT
WATTMASTER LOCAL LOOP WIRE
WATTMASTER NETWORK LOOP WIRE
GUIDE
RS-485 Communication Wiring
The WCC III System RS-485
Communication Wiring
The WCC III - MCD can communicate with up to 239 satellite
controllers via a two-wire RS-485 communication loop. On the
back of the WCC III – MCD there are two RS-485 communication
loop ports that come as standard. Each one of these communications
loop ports can communicate with up to 60 satellites for a total of
120 satellites.
Two more additional RS-485 communication loop ports can be
added at an additional cost for any WCC III system that has more
than 120 satellites. The two-wire RS-485 communication loop
should be stranded 2 wire twisted pair of 18-gauge wire with a
shield wire, and it also must be plenum rated were applicable.
The use of stranded wire is mandatory to ensure a good connection
with the ¼ inch Sta-Con connectors which are used to terminate
the wires at the satellite controllers. The RS-485 communication
wire does not have to be run from each satellite controller back to
the WCC III – MCD, but rather the RS-485 communication wire
can be “daisy-chained,” which means that only one twisted pair of
wires is connected to each of the WCC III - MCD communications
loops. The maximum allowable length of wire from the WCC
III - MCD to the farthest satellite is 4000 feet per RS-485
communications loop.
The RS-485 wire specifi cations are generally a stranded 18-
gauge - 2 wire twisted pair with shield. 18-gauge stranded wire is
mandatory to ensure a good connection with the ¼ inch Sta-Con
connectors, which are used to terminate the wires at the WCC III
- MCD and at the satellite controllers. The old SAT II Manchester
communications loop was supposed to have used a 2-wire twisted
pair with shield, but this was not used in every installation. This
old SAT II communications loop should not be used for the new
SAT III communications loop. A new RS-485 communications
loop should be ran to each new replacement SAT III controller.
The shield wire must be used on the new SAT III controller, as
it provides a “ground” reference for the RS-485 communication
loop. WattMaster Controls sells two versions of 18-gauge - 2-wire
twisted pair with shield communications wire— (1) WattMaster
part #WR-NL-WR-18 which is marked “Network Loop” with a
red stripe for rapid identifi cation. This connection is intended to
run from the WCC III – MCD to the SAT III, SAT 3C/D/F, SAT
3P, and then to the next SAT 3 type controllers. (2) WattMaster part
# WR-LL-WG-18 which is marked “Local Loop” with a green
stripe for rapid identifi cation for the TUC loops that run from the
SAT 3C/D/F controllers out to the TUC controllers.
“Wire Nuts” on the RS-485 communications loop should be avoided
at all costs. As an alternative to the “Wire Nuts”, WattMaster
Controls has a Power and Switchable RS-485 communications
board, and the WattMaster part number is PL102224. This Power
and Switchable RS-485 communications board can be thought of
as a 24-VAC power and communication distribution system for
the SAT III communications loop, and this board will aid in initial
startup and future troubleshooting of the SAT III communications
loop. These boards should be used on a fl oor-by-fl oor basis. This
Power and Switchable RS-485 communications board is also
available in a small metal electrical enclosure.
Figure 12-4 WattMaster Controls various communications loop wire
WCC III Technical Guide
12-7
12. WCC III INSTALLATION
WCC III - MCD Typical System Architecture
Figure 12-5: The WCC III typical system architecture with POWER and SWITCHABLE COMM boards
Figure 12-6: WCC III typical system architecture without the POWER and SWITCHABLE COMM boards
12-8
WCC III Technical Guide
12. WCC III INSTALLATION
GUIDE
WCC III - MCD Typical System Architecture
The wire that makes up the communication loop should be
shielded. Shielded cable has an aluminum jacket over the wires
that could act as an “antenna” to carry away any “stray” electrical
signals that could interfere with the communication process. The
shield should be grounded throughout the SAT Loop.
The SAT RS-485 communication loop wires are connected to the
“R” and “T” and shield terminals on the satellite controllers using
¼-inch Sta-Con connectors. Make sure the polarity is correct.
That is to say, the wire connected to the “R” and “T” terminal on
the MCD must be connected to the “R” and “T” terminal on the
satellite controllers. If the “R” and “T” and shield wires are crossed,
the WCC III system will not communicate. The shield should be
connected together when the cable is cut in order to terminate the
wires at the satellite controller.
The communication loop wire from the WCC III - MCD is
connected to one of the “R” and one of the “T” terminals on the
satellite controller, which is physically located nearest the WCC
III - MCD. The other “R” and “T” terminals located on the satellite
controller can be used to extend the two-wire loop to the next
satellite controller, or the wires can branch off of a two-wire loop
running through the center of a building as shown in Figure 12-6.
NOTE: The shield wire must be connected at each and every
Satellite Controller also.
WCC III Technical Guide
12-9
12. WCC III INSTALLATION
8
7
SATADDRESS
2
1
4
8
A3WIREROOM SENSORWILLNOT
REQUIREALOAD RESISTOR WHEN SET
FORA1 VOLT INPUT .
WattMasterControlsInc.
BINARY
INPUTS
BINARY
INPUTS
L8
ON OFF
128
32
16
64
L4
L3
L2
L1
L6
L5
L7
L11
L12
ON OFF
L10
L9
ON OFF
L15
L16
L14
L13
CH
4
3
5
6
2
1
LOCALSET
STATUS2
STATUS3
STATUS1
HSSXMIT
LOCALSET
LOCALSETDISABLE
BATTON/OFF
PULSEINPUT
OPTION1
TEST
OPTION3
OPTION2
ON OFF
STATUS
HSSREC
SATXMIT
SATREC
ANALOGINPUT
JUMPERSELECTION
A2WIREROOM SENSORWILLREQUIRE
A300OHM LOAD RESI STOR WHEN SET
FORA1 VOLT INPUT .
A4TO2 0 mA SENSOR WILLREQUIREA
50OHMLOAD RES ISTOR WHEN SE T FOR
A1VOLTINPUT, ORA 250 OHM LOAD
RESISTORWHENSETFO R A 5 VOLT INPUT.
CURRENT
INPUT
THERMISTOR
INPUT
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
0-10V
THERM
0TO10V
INPUT
0TO5V
INPUT
0TO1V
INPUT
0-10V
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
THERM
0-1V
0-5V
0-10V
THERM
PROGRAMMABLE CO NTROLL ER
SAT III
H
C
COM
CHANNEL
2134
2134
567
8
5678
V
OUT
GND
L
O
A
D
+V
ATI
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
EACHCONTACT
ISRATEDFOR
24VACOR VDC
@.5AMPMAX
0-15VDC
OUTPUT
MINLOAD
IS1KOHM
RESISTIVE
VDCONLY
100VA
TRANSFORMER
SWITCH
DISCONNECT
INTER PANEL
Satellite Controller Enclosure Mounting
Satellite Controller
Mounting in an Enclosure
The satellite controllers are designed to mount in any NEMA 1 or
NEMA 3 standard, six-inch deep, electrical enclosure. Typically,
this is a fi eld-mounted enclosure that contains transformers and
any accessory items required such as a binary input board, V-Out
Binary output board, control relays, etc. The best location for these
satellite panels is mounted on a wall in equipment or storage areas
or rooms at eye level near the controlled loads.
The satellite controllers may be ordered with or without the
NEMA type enclosures. If you order the satellite controller from
the factory without an enclosure, the SAT III and SAT 3C/D/F
dimensions as shown in Figure 12-13 and Figure 12-14 may be
helpful when selecting a suitable NEMA type enclosure.
The satellite controller must be mounted in an electrical enclosure.
If you do not order the satellite controller with an electrical
enclosure, you must provide your own electrical enclosure and
then provide and then install your own fused disconnect switch,
transformer, and terminal strip.
The size of the standard single SAT enclosure is designed to hold
only one satellite controller (or up to two SAT 3C/D/F controllers),
one fused disconnect switch, one transformer, one fi lter, and one
terminal strip which is normally about 15” x 15” x 6” deep with an
inter panel for mounting the SAT III controller, fuse block, 100VA
transformer, etc. The size of the standard dual SAT enclosure is
designed to hold two satellite controllers (or up to four SAT 3C/D/F
controllers), one fused disconnect switch, two transformers, two
fi lters, and two terminal strips is 30” x 18” x 6” deep with an inter
panel for mounting the two SAT III controllers, fuse block, 100VA
transformer, etc. If you install the satellite controller yourself,
make sure you leave room for wires that need to be connected to
the following terminals that are located on the sides of the SAT III
satellite controller (minimum recommended clearance is 2 inches):
You can also have both a SAT III controller and up to two SAT
3C/D/F controllers in the same dual enclosure.
24-VAC power source (100VA recommended)
RS-485 Communication loop
SAT III HSS Port connection
Figure 12-7: A typical SAT III controller in a single electrical panel (120-V AC po wered)
12-10
WCC III Technical Guide
12. WCC III INSTALLATION
8
7
SATADDRESS
2
1
4
8
A3WIREROOMSENSORWILLNOT
REQUIREALOAD RESISTOR WHENSET
FORA1 VO LT INPUT.
WattMasterControlsInc.
BINARY
INPUTS
BINARY
INPUTS
L8
ON OFF
128
32
16
64
L4
L3
L2
L1
L6
L5
L7
L11
L12
ON OFF
L10
L9
ON OFF
L15
L16
L14
L13
CH
4
3
5
6
2
1
LOCALSET
STATUS2
STATUS3
STATUS1
HSSXMIT
LOCALSET
LOCALSETDISABLE
BATTON/OFF
PULSEINPUT
OPTION1
TEST
OPTION3
OPTION2
ON OFF
STATUS
HSSREC
SATXMIT
SATREC
ANALOGINPUT
JUMPERSELECTION
A2WIRE ROOMSENSORWILL REQUI RE
A300OHM LOAD RESISTOR WHENSET
FORA1 VO LT INPUT.
A4TO20 mA SENSORWILLREQUIREA
50OHMLOAD RESISTOR WHEN SET FOR
A1VOLTINPUT, OR A 250 OHM LOAD
RESISTORWHEN SET FO R A 5 VOLT INPUT.
A4TO 20 mA SENSOR WILL REQUIREA
50OHMLOAD RESISTOR WHEN SETFOR
A1VOLT INPU T, OR A250OHMLOAD
RESISTORWHEN SETFORA5 VOL T INPUT.
CURRENT
INPUT
THERMISTOR
INPUT
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
0-10V
THERM
0TO10V
INPUT
0TO5V
INPUT
0TO1V
INPUT
0-10V
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
THERM
0-1V
0-5V
0-10V
THERM
PROGRAMMABLECONTROLLER
SAT III
H
C
COM
CHANNEL
2134
2134
567
8
5678
V
OUT
GND
L
O
A
D
+V
ATI
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
EACHCONTAC T
ISRATEDFOR
24VACORVDC
@.5AMPMA X
0-15VDC
OUTPUT
MINLOAD
IS1KOHM
RESISTIVE
VDCONLY
INTER PANEL
100VA
TRANSFORMER
GUIDE
Satellite Controller Enclosure Mounting
Figure 12-8: Two SA T III controllers in a typical dual electrical panel (120-VA C pow ered)
WCC III Technical Guide
12-11
12. WCC III INSTALLATION
Satellite Controller Enclosure Mounting
Figure 12-9: A typical SAT 3C/D/F controller in a single electrical panel (120-V AC po wered)
Figure 12-10: A typical SAT 3C/D/F controller in a (single) dual electrical panel (120-V AC po wered)
12-12
WCC III Technical Guide
12. WCC III INSTALLATION
GUIDE
Satellite Controller Enclosure Mounting
Figure 12-11: A typical SAT 3C/D/F controller in a (dual) quad electrical panel (120-V A C pow ered)
WCC III Technical Guide
12-13
12. WCC III INSTALLATION
GND 24VAC
100VA
2AMP
MDL
BLK
WHT
L
N
ORG
BRN
BLK
WHT
ORG
BRN
24VAC
GND
GND
24VAC
GND
SIG
+V
FLUSHMOUNT
TYPICAL 7 PLACES
SENSOR
Satellite Controller Wiring
If you order the satellite controller in an enclosure, the factory will
provide and install the wires from the transformer to the satellite.
If you order the satellite controller separately, you must provide a
NEMA panel with an inter panel, disconnect switch, transformer(s),
fusing, terminal block(s), wire, crimp connectors, and then install
the wires from the transformer to the satellite controller. A typical
satellite controller wiring diagram is shown below:
Figure 12-12: SAT III controller typical single panel wiring diagram
12-14
WCC III Technical Guide
Satellite Controllers - General Dimensions
8
7
SATADDRESS
2
1
4
8
A3 WIRE ROOM SENSOR WILLNOT
REQUIREA LOAD RESISTOR W HEN SET
FORA 1VOLT IN PUT.
WattMaster Controls Inc.
BINARY
INPUTS
BINARY
INPUTS
L8
ON OFF
128
32
16
64
L4
L3
L2
L1
L6
L5
L7
L11
L12
ON OFF
L10
L9
ON OFF
L15
L16
L14
L13
CH
4
3
5
6
2
1
LOCALSET
STATUS2
STATUS3
STATUS1
HSSXMIT
LOCALSET
LOCALSET DISABLE
BATTON/ OFF
PULSEI NPUT
OPTION1
TEST
OPTION3
OPTION2
ON OFF
STATUS
HSS REC
SATXMIT
SATREC
ANALOGINPUT
JUMPERSELECTION
A2 WIRE ROOM SENSOR WILLREQUIRE
A300OHM LOAD RESISTORWHENSET
FORA 1VOLT IN PUT.
A4 TO 20mA SE NSOR WILLRE QUIRE A
50OHM LOAD R ESISTOR WHENSET FOR
A1VOL T INPUT, OR A 250 OHM LOAD
RESISTORWHENSETFOR A5 VOLTINPUT.
CURRENT
INPUT
THERMISTOR
INPUT
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
0-10V
THERM
0TO10V
INPUT
0TO5V
INPUT
0TO1V
INPUT
0-10V
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
THERM
0-1V
0-5V
0-10V
THERM
PROGRAMMABLE CONTROLLER
SAT III
H
C
COM
CHANNEL
2134
2134
567
8
5678
V
OUT
GND
L
O
A
D
+V
ATI
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
123456
123456
+VSENSORS
R1
R212R3R4R5
R6
3456
C
78
C
H
VOUT
GND
7 8
R
R7
R8
78
AT
EACHCONTACT
ISRATEDFOR
24VACORVDC
@.5AMPMAX
0-15VDC
OUTPUT
MINLOAD
IS1K OHM
RESISTIVE
VDCONLY
MADE IN
THEUSA
K16
K15
K14
K13
V16 V15 V14 V13
11.90
11.25
5.85
7.18
GND
24 VAC
24 VAC
POWER
SAT
COMMUNICATION
RT
SHIELD
IN /OUT
HSS EXP
COMM
SATIIISIDE PROFILE VIEW (POWER INPUT)
SATIIISIDE PROFILE VIEW (SAT COMM & HSS PORT)
SATIII SIDE PROFILE VIEW (ANALOG IN/OUT - CONTROL OUTPUT)
3.00
7.18
12. WCC III INSTALLATION
GUIDE
Satellite Controller Dimensions
Figure 12-13: SAT III controller dimensions. All dimensions are in inches.
Figure 12-14: SAT 3C/D/F controller dimensions. All dimensions are in inches.
WCC III Technical Guide
12-15
12. WCC III INSTALLATION
8
7
SAT ADDRESS
2
1
4
8
A3 WI RE ROOM SENSOR WILL NOT
REQUIRE A LOAD RESISTOR WHE N SET
FORA 1 V OLT INPUT.
WattMaster Controls Inc.
BINARY
INPUTS
BINARY
INPUTS
L8
ON OFF
128
32
16
64
L4
L3
L2
L1
L6
L5
L7
L11
L12
ON OFF
L10
L9
ON OFF
L15
L16
L14
L13
CH
4
3
5
6
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCAL SET
LOCAL SET DISABLE
BATT ON/ OFF
PULSE INPUT
OPTION 1
TEST
OPTION 3
OPTION 2
ON OFF
STATUS
HSS REC
SAT XMIT
SAT REC
ANALOG INPUT
JUMPER SELECTION
A2 WI RE ROOM SENSOR WILL REQUIRE
A30 0 OHM LOAD RESISTOR WHEN SET
FORA 1 V OLT INPUT.
A4 T O 20m A SENSOR WILL REQUIRE A
50OHM LOADRESISTORWHEN SETFOR
A1 V OLT INPUT, OR A 250 OHM LOAD
RESISTORWHENSET FOR A5 VOLT INPUT.
CURRENT
INPUT
THERMISTOR
INPUT
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
0-10V
THERM
0 TO 10V
INPUT
0TO5V
INPUT
0TO1V
INPUT
0-10V
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
THERM
0-1V
0-5V
0-10V
THERM
PROGRAMMABLECONTROLLER
SAT III
H
C
COM
CHANNEL
2134
2134
567
8
5678
V
OUT
GND
L
O
A
D
+V
ATI
10A250VAC ~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC ~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC ~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC ~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
EACH CONTACT
IS RATED FOR
24VACOR VDC
@ .5 AMP MAX
0-15VDC
OUTPUT
MINLOAD
IS 1K OHM
RESISTIVE
VDCONL Y
SA T III LED Descriptions
SA T III Controller—LED Information
(SS5003)
The SAT III Controller has 24 LEDs on the cover of the SAT III
controller. The top 8 Status LED functions are as follows:
SAT REC - This LED will be lit when communications are being
received by the SAT III Communications Loop.
SAT XMIT - This LED will be lit when communications are being
transmitted by the SAT III Communications Loop.
HSS REC - This LED will be lit when communications are being
received from the HSS port.
HSS XMIT - This LED will be lit when communications are
being transmitted to the HSS port.
LOCAL SET - This LED will be lit when communications
with the WCC III-MCD has not occurred for at least the last two
minutes. This means that the SAT III is not communicating on the
SAT III communications loop. Setpoint control in the SAT III is
dependent on the LOCAL SET parameters which are programmed
into each control point by the user.
STATUS 1 - LED blinks every 1 second if SAT III is alive.
STATUS 2 - LED blinks every 1 second during power on delay,
and then blinks every 8 seconds when watchdog is enabled.
STATUS 3 - LED blinks for every internal calculation loop
completion.
The lower 16 LEDs display the status of the 16 “H” and “C” Relay
Outputs. The 16 LEDs display the status of the eight “H” and eight
“C” contacts.
Figure 12-15: SAT III LED locations
12-16
WCC III Technical Guide
12. WCC III INSTALLATION
GUIDE
SA T III Connection Points
SA T III Controller — Connection
Points
All of the external SAT III connection points are single tab ¼-inch
Sta-Con connectors. With the exception of the “old” connection
method of connecting the Binary Inputs which are 16-pin dip cable
connections and the HSS EXP COMM port which is a 6-pin premade MOLEX type mini-fi t cable connection.
+V Connections.
There are eight +12-VDC connections that power analog type
sensors of which the fi rst seven of these connections are fi xed to
+12VDC only. The eighth +V connector is jumper (JP1) selectable
for either +12VDC, or +24VDC. This (JP1) jumper can be set
to +12VDC, or +24VDC so that the voltage at the eighth +V
connection point is either +12VDC or +24VDC. The +24VDC
is useful when connecting 4-to-20 mA sensors that require a
connection voltage greater than +12VDC. You may connect up to
eight 4-to-20 mA sensors to this eight +V (+24VDC) connection
point. This JP1 jumper is located under the cover of the SAT III
controller, just to the right of the eighth +V connector.
A TI Connections
These eight connections are connection points for ATI #1 to ATI #8
analog inputs. ATI is the acronym for Analog Temperature Input.
These eight connection points are for Analog Inputs. This is where
analog type sensors are connected to the SAT III controller. The
types of sensors inputs that are supported on the SAT III controllers
are: 0-1V, 0-5V, 0-10V, 10K Type 3 Thermistor, 4-20mA (On both
the 0-1V, and 0-5V inputs). There are also eight Analog Input
selection jumpers that are located under the cover of the SAT III
controller near the Analog Inputs that actually set the type input
voltage ranges for each of the eight analog inputs. These Analog
Input selection jumpers are labeled JO1 to JO8. JO1 corresponds
to analog input #1, JO2 corresponds to analog input #2, JO3
corresponds to analog input #3, JO4 corresponds to analog input
#4, JO5 corresponds to analog input #5, JO6 corresponds to analog
input #6, JO7 corresponds to analog input #7, JO8 corresponds
to analog input #8. Each of these Analog Input selection jumpers
has four jumper options: 0-1V, 0-5V, 0-10V, and THERM. See
Figure 12-34 and 12-35 for further wiring details. See Section 3
for further programming instructions.
GND Connections
These GND connections are analog ground common connection
points for all of the analog input (ATI), and analog output (VOUT)
connections.
VOUT 1 to V OUT 8 Connections
These eight analog outputs are set up to provide 0 to +15 DC
Volts outputs at up to 15 milli-amps per output. These outputs are
typically used to drive a VFD, 0-10VDC or 2-10VDC actuator or
valve. VOUT is the acronym for Voltage Output. See Section 3 for
additional programming instructions.
H 1 to H 8 Connections
The eight “H” connection points of the SAT III controller were
originally classifi ed and labeled as “HEAT” contacts starting with
the SAT 0, SAT I, and SAT II controllers. They do not need to
be used only for “HEAT” contacts, as these contacts are general
purpose relay outputs. There is a load protection device called a
varistor across each of the eight “H” output connections that limit
the allowable voltage to no more than 32 volts AC\DC maximum
at 1 amp current draw for each contact. Attempting to switch
any voltage greater than 32 Volts, or current draws of more than
1 amp per contact could and will result in damage to the SAT
III controller. These “H” and “C” contact outputs are meant to
control tri-state actuators, contactors, relays, solenoids, and the PI
board AKA “ECC II ANALOG OUTPUT” board that WattMaster
Controls used to manufacture. See Figure 12-18 for further wiring
details. See Section 3 for additional programming instructions.
COM 1 to COM 8 Connections
The COM1 connection point is a common connection point for
H1 and C1 Relays. None of the COM connections are connected
to any of the other seven COM connection points. A jumper cable
is available to connect all of the COM connection points together.
Each corresponding “H” and “C” contact are connected to a single
corresponding “COM” connection point. So “H1” and “C1” are
connected to “COM1”, “H2” and “C2” are connected to “COM2”,
etc. See Figure 12-18 for further wiring details.
WCC III Technical Guide
12-17
12. WCC III INSTALLATION
SA T III Connection Points
C 1 to C 8 Connections
The eight “C” connection points of the SAT III controller were
originally classifi ed and labeled as “COOL” contacts starting with
the SAT 0, SAT I, and SAT II controllers. They do not need to
be used only for “COOL” contacts, as these contacts are general
purpose relay outputs. There is a load protection device called
a varistor across each of the eight “COOL” output connections
that limits the allowable voltage to no more than 32 volts AC\DC
maximum at 1 amp current draw for each contact. Attempting to
switch any voltage greater than 32 Volts, or current draws of more
than 1 amp per contact could and will result in damage to the SAT
III controller. These “H” and “C” contact outputs are meant to
control tri-state actuators, contactors, relays, solenoids, and the PI
board AKA “ECC II ANALOG OUTPUT” board that WattMaster
Controls used to manufacture. See Figure 12-18 for further wiring
details. See Section 3 for additional programming instructions.
Binary Inputs
The SAT III controller has two sets of eight-position dipswitches
on its front panel labeled L1 - L8 and L9 - L16. Switches L1-L8 are
housed together in one dipswitch, and switches L9-L16 are housed
together in another dipswitch. For the old connection method one
dipswitch is removed for each Binary Input with Time Delay board,
and is then replaced with a ribbon cable which connects the Binary
Input with Time Delay board to the SAT III controller. The binary
devices to be monitored are then wired to the terminal strip of the
Binary Input with Time Delay board. The Binary Input with Time
Delay board requires a 24-VAC power source. Warning you must
observe polarity on the 24-VAC and GND connections of both the
Binary Input with Time Delay board and the SAT III controller,
as the grounds must be the same. Or, an alternative connection
method to the SAT III controller is now provided by the 6-pin HSS
expansion port on the side of the SAT III controller. See Figures 12-26, 12-27, & 12-28 for further wiring details.
24V AC & GND Connection
Located on the bottom side of the SAT III controller is a 24 VAC
and GND connection. This is the main power connection to the
SAT III controller. Each SAT III Controller draws - 15VA. External
relays and contactors are not included, but need to be considered
for total VA draw. The GND connection points must be the same
between all of the externally powered expansion boards and the
SAT III Controller. See Figure 12-27 for further wiring details.
SA T Communica tion Connection
These connection points are for wiring of the RS-485 communication
loop. There are two “T” (Transmit) connections, two “R” (Receive)
connections and two “SHIELD” connection points. There are two
connection points provided for each connection for easy “daisy
chaining” to the next Satellite Controller. When connecting the
RS-485 wiring from SAT III to SAT III or SAT 3C/D/F, or SAT 3P
controller the wiring connections are as follows: connect “R” TO
“R”, “T” TO “T”, AND “SHIELD” TO “SHIELD” OR “SH”. The
RS-485 wire specifi cations are plenum-rated, jacketed stranded
18-gauge, 2-wire twisted pair with shield. 18-gauge stranded wire
is mandatory to ensure a good connection with the ¼-inch Sta-Con
connectors which are used to terminate the wires at the WCC III MCD and at the satellite controllers.
HSS EXP COMM Connection
The HSS EXP (Expansion) Port enables newer versions of the
satellite expansion boards, most notably the Binary Input with
Time Delay Board and V-Out RELAY Board to work without
connecting the previous way (separate power and hard wiring was
required). The SAT III has a single connection via the built-in HSS
EXP port on the side of the SAT III. It is designed to connect and
power up 5 HSS Expansion Boards. Connecting more than 5 HSS
Boards is possible, but each additional board will require a 24VAC
power supply.
The HSS EXP port provides power and ground, along with
communications on a 6-pin pre-made MOLEX type mini-fi t cable
connection. This cable is made with 16-gauge wire.
Each HSS Expansion Board has an 8-position address dipswitch
that is used to set up the function of the board.
The HSS EXP port can be daisy chained to the next board. The
HSS cable connections allow the HSS expansion boards to be
located up to 150 feet away from the SAT III Controller.
HSS connection cables are available in the following sizes: 6-inch,
12-inch, 18-inch, 3 feet, 25 feet, 40 feet, 80 feet, and 120 feet.
12-18
WCC III Technical Guide
12. WCC III INSTALLATION
8
SAT ADDRESS
2
1
4
ON OFF
128
32
16
64
SAT III ADDRESS SWITCH
GUIDE
SA T III Addressing
Addressing (Numbering) of SA T III
Controllers
The WCC III system can have up to 239 SAT III controllers. In
order for the central computer to communicate properly with each
individual SAT III controller, each controller must be assigned a
separate number, or address. The number is assigned by placing
the small dip switches on the front of the SAT III controller marked
“SAT ADDRESS” in the proper position.
The address dip switches are additive; that is to say placing
switches 1 and 2 in the ON position will cause the SAT III
controller to be identifi ed as satellite controller number 3. The SAT
III controller looks at the position of these switches only when it
is going through its initialization process after being powered up.
Simply changing the switch positions on a SAT III controller that is
currently “on-line” will not change its number. The switches need
to be placed in the proper position before powering up the SAT III
controller, or the SAT III must be powered down and then back up
for the SAT III to “read” the new position of the switches. When
placing the switches in the desired position, make sure the switch
has “clicked” into place and is properly seated.
Figure 12-16: SAT III address switch loca tion
WCC III Technical Guide
12-19
12. WCC III INSTALLATION
SA T III Addressing
Care must be taken to ensure that two SAT III controllers do not
have the same address. When this condition is present, the central
computer does not know where to send the information, and the
information that should be sent to the SAT III controller is usually
lost.
You should be aware of the symptoms caused by two satellite
controllers having the same number. Let’s consider a new job in
which the satellite controllers have not yet been programmed and
2 SAT III controllers are named number #3. When you call up
satellite controller #3 to enter data, everything will appear to be
fi ne. You will be able to enter data on the screens as if nothing is
wrong. However, when you leave a screen and then return to the
same screen, all of the data you entered will be missing. Also, if
you fi nish programming the analog inputs for example, and then
go to the analog input summary screen to review your inputs, all
of the data you have entered will be missing.
Another situation that you might encounter is adding a SAT III
controller to an existing system and accidentally giving it the same
number as a SAT III presently “on-line.” Again, when you begin
to program the new SAT III controller, everything will appear fi ne
until you leave a screen or if you go to a summary screen. Only
now, all of the data is usually not missing. Generally, you get parts
of your data back and parts will be missing.
If you suspect you might have two SAT III controllers with the
same address (number 3 for example) the best thing to do is go
to the SAT III controller that you know is number 3, and remove
the 2-wire RS-485 communication loop from it. Then, go back to
the computer and call up satellite controller #3. If the computer
can still “talk” to satellite controller #3, there is another satellite
controller that is addressed #3 connected somewhere on the RS485 communication loop.
If a satellite controller was accidentally addressed #3, there will
be a satellite number missing. For example, if satellite controller
#7 was accidentally misaddressed to #3, satellite controller #7 will
not be present. One way of telling which satellite controllers are
“on-line” is to go to the Satellite Summary Screen (see Section
3) and see which satellite controllers the computer recognizes as
being “on-line.”
If satellite controller #7 was accidentally miss-addressed #3, there
would not be a satellite controller at address #7, and the computer
will give a “Non-Existing” message for satellite controller #7.
Option 1, 2, and 3 Switches
Option switches 2 and 3 do nothing. But, the SAT III controller
option “1” switch selects the A-to-D converter type that is on the
mother board. With the switch turned OFF, the A-to-D curve is
selected for the Maxim MAX147 part, and with the switch turned
“ON” for the TI-ADS7844 (BB marked) the software will use the
special A-to-D curve for the TI-ADS7844 part. See Section 3 for
proper A-to-D identifi cation.
BA TT ON/OFF s witc h
This switch is used to turn the Battery (Rechargeable Super cap) ON
and OFF to the SRAM located inside of the SAT III processor.
Since version 2.00 of the Satellite software the non-volatile
memory is now also stored in the EEPROM, instead of the SRAM,
and upon power up the memory is read from the EEPROM back
into the SRAM. This switch is not of any importance anymore.
Local Set Switch
When the LOCAL dipswitch is in the ON position, the SAT
III controller will operate according to their predefi ned user
programmed “local set” setpoints. That is, if the SAT III controller
was programmed by the user to correctly operate when and if the
WCC III - MCD is off-line or disconnected.
Local Set Disable Switch
When the LOCAL SET Disable dipswitch is in the ON position,
the SAT III controller will operate according to their predefi ned
user programmed “On” setpoints. That is, if the SAT III controller
were programmed by the user to correctly operate when and if the
WCC III - MCD is off-line or disconnected.
Test Switc h
The test mode is active only if the TEST dipswitch is in the ON
position. The word “TEST” can be input as the binary value within
the SAT III. Example of use would be if the user programmed the
word “TEST” into one of the control point values in the SAT III
controller to check the operation of the SAT III controller with an
alternate setpoint or schedule, the user could then place the TEST
switch in the ON position to make this function work with out
physically having to go back to the front-end computer to change a
setpoint via the computer.
12-20
WCC III Technical Guide
12. WCC III INSTALLATION
8
7
SAT ADDRESS
2
1
4
8
A3 WI RE ROOM SE NSOR WILL NO T
REQUIREA LOADRESIST OR WHEN SET
FORA 1VOLT INPUT.
WattMaster Controls Inc.
BINARY
INPUTS
BINARY
INPUTS
L8
ON OFF
128
32
16
64
L4
L3
L2
L1
L6
L5
L7
L11
L12
ON OFF
L10
L9
ON OFF
L15
L16
L14
L13
CH
4
3
5
6
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCAL SET
LOCAL SET DISABLE
BATT ON/ OFF
PULSE INPUT
OPTION 1
TEST
OPTION 3
OPTION 2
ON OFF
STATUS
HSS REC
SAT XMIT
SAT REC
ANALOG INPUT
JUMPER SELECTI ON
A2 WI RE ROOM SE NSOR WILL REQUIRE
A300 OHMLOAD RESISTORWHEN SET
FORA 1VOLT INPUT.
A4TO20mASENSORWILLREQUIREA
50OHM LOADR ESISTOR WHEN SET FOR
A1 VO LT INPUT , OR A 250 OHML OAD
RESISTORWH EN SET FOR A 5 VOL T INPUT.
CURRENT
INPUT
THERMISTOR
INPUT
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
0-10V
THERM
0TO10V
INPUT
0TO5V
INPUT
0TO1V
INPUT
0-10V
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
THERM
0-1V
0-5V
0-10V
THERM
PROGRAMMABLECONTROLLER
SAT III
H
C
COM
CHANNEL
2134567
8
10A250VAC ~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC ~
5A30VDC
SA
VDE
-1A4
ON
24V
CHINA
10A250VAC ~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
NTACT
FOR
VDC
AX
GUIDE
SA T III Relay Outputs
SA T III Relay Outputs
The standard SAT III controller is capable of providing 16 binary
(on/off) relay outputs. These 16 relay outputs are for driving pilot
duty relays. There is a load protection device called a varistor
across each of the 16 output connections that limits the allowable
voltage to no more than 32 volts AC\DC maximum at 1.0 or 1 amp
current draw for each contact.
Attempting to switch any voltage greater than 32 Volts, or current
draws of more than 1.0 or 1 amp per contact could and will result
in damage to the SAT III controller. These “H” and “C” contact
outputs are meant to control tri-state actuators, contactors, relays,
solenoids, and the PI board AKA “ECC II ANALOG OUTPUT”
board that WattMaster Controls used to manufacture. These relay
outputs can be programmed in three different types of modes of
basic operation: Time Clock, Dual Limit, and EA Mode. See
Section 3 for further details on Satellite programming instructions.
Figure 12-17: SAT III “H” and “C” control output wiring connections
WCC III Technical Guide
12-21
12. WCC III INSTALLATION
H
COM
C
12345678
12345678
SA T III Relay Outputs
The terminals for the binary outputs are found at the lower lefthand corner of the SAT III controller and are labeled “H”, “COM”,
and “C”. The relay contact can make or break a 24-VAC or 24VDC circuit between the COM to H or COM to C terminals.
The COM to H contacts are referred to as XXXK1h-K8h in the
WCC III point addressing scheme, and the COM to C contacts
are referred to as XXXK1c-K8c in the WCC III point addressing
scheme. XXX is the Satellite address number 1 to 239, “K” stands
for contact, and the numbers 1-8 stand for the channel on the SAT
III controller.
Each “H” and “C” contact connection has a “COM” connection
associated with it. Please note that each one of the sets of the
corresponding “H” and “C” contacts are also isolated from each
other. The “COM” connection means common. When wiring
the control outputs, typically all of the “COM” connections are
wired together, using the supplied jumper wire (PL100867). This
“COM” common connection can either be connected to 24VAC /
24VDC or GROUND depending on the application.
Figure 12-18: SAT III “H” and “C” control output schematic
Figure 12-19: A control output common jumper wire is provided (PL100867) for connecting the eight “COM”
connections together
The pre-made control output common jumper wire is provided
in the initial spare parts kit that came with the SAT III controller.
This spare parts kit contains various input load resistor packs,
spare fuse, and the control output common jumper. The spare parts
kit is WattMaster part number PL102029.
12-22
WCC III Technical Guide
1
1
1
1
COM - 24VACCOM - GROUND
H
C
H
C
Figure 12-20: COM connection as 24 VAC or as GR OUND
12. WCC III INSTALLATION
SA T III Relay Outputs
GUIDE
The “COM” or common connection point can either be connected
to 24 VAC / 24 VDC or GROUND. It is basically a point of view
of turning power “on” to a device, or removing “ground” going
to the device. It makes no difference, as both methods will work
equally well, and really depends on the application you are trying
to control.
WCC III Technical Guide
12-23
12. WCC III INSTALLATION
Proportional-Integral (PI) Output Board
Proportional-Integral (PI) Output
Board
The Proportional-Integral (PI) Board is a separate integrated circuit
board which works in conjunction with the SAT III controller to
convert a pair of SAT III binary outputs to a varying DC voltage
signal. When one contact on the SAT III controller closes, the
voltage supplied by the PI board will ramp down at a pre-set rate.
When the other SAT III contact closes, the voltage ramps up at
the preset rate. When both contacts are open, the voltage supplied
by the PI board will remain at its present value. The maximum
DC voltage range is 0-14.5 volts, and the minimum allowable
resistance of the controlled device is 1000 ohms. See Section 3 for
further details on Satellite programming instructions.
Figure 12-21: ECC II Analog Output Board
12-24
WCC III Technical Guide
12. WCC III INSTALLATION
GUIDE
PI Board Connection Points
The DC voltage range along with the ramp speed is set at the PI
board. The ramp speed can be adjusted from 23 seconds to 38
minutes, and the maximum range is 0-14.5 volts DC.
To control a VFD drive from a SAT III controller using the
Proportional-Integral board, you must use two control outputs and
a circuit board (PI Board) that we no longer make. WattMaster
Controls does not make the PI Output Board anymore, but Kele
makes a similar circuit board that should work. It is a Tri-State-toAnalog Output circuit board (Kele Part # PWA-2T).
If only one contact closure is available to drive the PI Board, move
jumper J01 on the WattMaster PI board to the B-C position and use
the SAT III’s control output in the Dual Limit mode to control the
PI Board. Although when using this method with the WattMaster PI
Board, the DC voltages supplied by the WattMaster PI Board will
either be increasing or decreasing at the set ramp speed depending
on if the contact is open or closed.
The Global Analog Mode 9 Dual Ramp Screen was created to help
emulate the old WattMaster PI board in software. It basically uses
the control set points of two control outputs on a satellite controller
to control a single analog output on a satellite controller and should
be used when controlling an analog actuator or VFD that needs to
have an analog control setpoint. See Section 3 for further details on
Satellite programming instructions.
The Proportional-Integral (PI) Board connection points
All of external connections to Proportional-Integral (PI) Board
connection points are non de-pluggable screw-cage type of wire
clamped based terminal blocks.
24 V AC (TB1-5) & GND (TB1-6)
ANALOG OUT (TB2-1) & GND (TB2-3&4)
The “ANALOG OUT” and “GND” terminals supply the DC
voltage from the PI board.
Adjust Minimum Voltage
The PI board is factory set for a minimum voltage of 0 VDC +/-
0.2 VDC. If you want a minimum voltage other than 0 VDC, you
can reset it by adjusting the potentiometer (pot) labeled “R9.” The
voltage between test point #3 (labeled “TP #3” on the PI board)
and ground is set 300 mV lower than the desired minimum voltage.
That is to say, if you want 5 VDC as the minimum voltage to be
supplied between the “ANALOG OUT” and “GND” terminals,
adjust pot “R9” to get 4.7 VDC between “TP #3” and “GND.”
NOTE: The minimum voltage setpoint must be lower than the
maximum voltage setpoint.
Adjust Maximum Voltage
The PI board is factory set for a maximum voltage of 14.5 VDC
+/- 0.2 VDC. If you want a maximum voltage other than 14.5
VDC, you can reset it by adjusting the potentiometer (pot) labeled
“R10.” The voltage between test point #2 (labeled “TP #2” on the
PI board) and ground is set at 300 mV above the desired maximum
voltage. That is to say, if you want a maximum voltage of 10 VDC
to be supplied by the “ANALOG OUT” and “GND” terminals,
adjust pot “R10” to get 10.3 VDC between “TP #2” and “GND.”
NOTE: The maximum voltage setpoint must be higher than
the minimum voltage setpoint.
The PI board requires a 24 VAC power supply which is connected
to these terminals. The PI board is generally powered by the same
24 VAC transformer that powers the satellite controller. The GND
connection points must be the same between the PI board and the
SAT III Controller.
HEA T (TB1-1) & COM1 (TB1-2)
When 24 volts AC is supplied between the “HEAT” and “COM1”
terminals, the DC voltage supplied by the PI board will start
increasing at the set ramp speed.
COOL (TB1-1) & COM2 (TB1-4)
When 24 volts AC is supplied between the “COOL” and “COM2”
terminals, the voltage supplied by the PI board will start decreasing
at the set ramp speed.
WCC III Technical Guide
Adjust “Ramp” Speed
The ramp speed is the time it takes for the DC voltage between
the “ANALOG OUT” and “GND” terminals to change from the
minimum voltage to the maximum voltage and vice versa. The ramp
speed is factory set at about 19 minutes. If you want a ramp speed
other than 19 minutes, you can reset it by adjusting the potentiometer
(pot) located at R2. When R2 is fully counterclockwise, the ramp
speed is 38 minutes (+/- 10%). When R2 is fully clockwise, the
ramp speed is 23 seconds (+/- 10%). As the voltage is ramping up,
the small light labeled D1 will fl ash and as the voltage is ramping
down, the small light labeled D2 will fl ash.
12-25
Loading...
+ 61 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.