SECTION 10:
RS-485 COMMUNICA TIONS AND
TROUBLESHOOTING
__________________________________________
10. RS-485 COMMUNICATIONS
RS-485 Network Loop Communications
WCC III – MCD and SAT III Type
Controllers “RS-485 Network Loop”
Communications
The SAT III type controllers use a proprietary RS-485-based
protocol, and it is based on packetized data in predefi ned parameter
blocks. Troubleshooting of the SAT III type controllers’ RS-485
communications loop is possible with a Digital Voltmeter.
(The SAT II was based on Manchester encoded data, and was
very reliable, but was impossible to troubleshoot with a Digital
Voltmeter.)
For the WCC III - MCD system, WattMaster Controls has
developed a new, isolated RS-485 communication bus that
can support 239 SAT III type controllers on up to four separate
communications channels (loop connections). A single channel
(loop connection) can support up to 60 SAT III type controllers
on one communications loop. This is for redundant operation; if
an RS-485 communications channel goes down, it does not cause
other SAT III type controllers on the any of the other loops to lose
communications.
The maximum distance specifi ed for RS-485 communications
is 4000 feet. Using multiple channels (loop connections), it is
possible to go 4000 feet in one direction and 4000 feet in yet
another direction using the two communications channels (loop
connections) that are provided on the back of the standard WCC
III - MCD.
PLEASE NOTE: There are two physical RS-485 channels
(loop connections ) on the back of the standard WCC III - MCD
computer. T wo more ph ysical RS-485 loops are available as an
option for larger loop sizes (WattMaster part PL1 0 1 97 4 ).
This WCC III communications loop should also be thought of as a
major component of the WCC III system, not just a communications
loop that only connects SAT III type controllers to SAT III type
controllers. On this proprietary RS-485 communications loop, the
following commands are broadcast many times a second: Time,
Week Schedules, Global Binary, Global Analogs, Optimal Starts,
Overrides, PID programs, Duty Cycles programs, Proportional
programs, and Tenant Overrides. These commands are broadcast
from the WCC III - MCD to all of the SAT III Controllers and all
of the SAT 3C/D/F/P Controllers, as well as any TUC Controllers
that are connected to the SAT 3C/D/F Controllers. If your RS-485
communications wiring has a faulty or intermittent connection to
any of the SA T III type controllers, then a problem will result in the
proper operation of the WCC III system.
WCC III Technical Guide
10-1
10. RS-485 COMMUNICATIONS
REAR PROFILE VIEW WCC I II - MCD (STANDARD WITH TWO SAT III COMMUNICATIONS CONNECTI ONS)REAR PROFILE VIEW WCC II I - MCD (WITH OPTIONAL TWO MORE SAT III COMMUNICATIONS CONNE CTIONS)
SA T 3C/D/F TUC Loop Communications
The SAT 3C/D/F TUC Loop
Communications
The software that is in the “old” existing TUC Controllers that
were connected to the “old” SAT 2c/d Controllers does not need
to be changed. WattMaster Controls decided to use the same
communications protocol to ease the replacement of the SA T 2C/D
controllers. Do not connect this loop to the SAT III “network”
communications loop as communication-related problems will
result.
PLEASE NOTE: Normally, all of the RS-485 wiring is
wired “R ” to “R,” “T” to “T, ” and “SHLD” to “SHLD” or
“SH.” This method of connection works for the wiring from
TUC Controller to TUC Controller. But, on the SA T 3C/D/F
Controller, the wire from the TUC “R” connection must
be wired to the SA T 3C/D/F “T” connection, and the SAT
3C/D/F Controller “R” connection must be wired to the TUC
“T” connecti on.
Figure 10-1: Rear Views of the WCC III – MCD showing SAT III RS-485 Communication Connections
Figure 10-2: Profi le of SAT III and SAT 3C/D/F showing the SAT III and TUC RS-485 Communication Connections
10-2
WCC III Technical Guide
10. RS-485 COMMUNICATIONS
<<<LOCAL LOOP>>> AZWR-LL-WG-18>>> E76191 CL2P 18AWG (UL) 012112 FT
<<<NETWORK LOOP>>> AZWR-NL-WR-18>>> E76191 CL2P 18AWG (UL) 012112 FT
WATTMASTER LOCAL LOOP WIRE
WATTMASTER NETWORK LOOP WIRE
RS-485 Wire & P ower and Switchable RS-485 Communications Board
RS-485 Wire Considerations
The RS-485 wire specifi cations are generally a stranded 18-
gauge, 2-wire twisted pair with shield. 18-gauge stranded wire is
mandatory to ensure a good connection with the ¼-inch Sta-Con
connectors which are used to terminate the wires at the WCC III MCD and at the satellite controllers.
The old SAT II Manchester communications loop was supposed to
have used a 2-wire twisted pair with shield, but this was not used
in every installation. This old SAT II communications loop should
not be used for the new SAT III communications loop. A new RS485 communications loop should be run to each new replacement
SAT III Controller. The shield wire must be used on the new SAT
III Controller as it provides a “ground” reference for the RS-485
communication loop.
W attMaster Controls sells two versions of 18-gauge, 2-wire twisted
pair with shield communications wire:
• W attMaster part #WR-NL-WR-18 - marked “Network
Loop” with a red stripe for rapid identifi cation. This
wire should be run from the WCC III - MCD to the
SAT III, SAT 3C/D/F, SAT 3P, and then to the next
SAT 3-type controllers.
• W attMaster part #WR-LL-WG-18 - marked “Local
Loop” with a green stripe for rapid identifi cation for the
TUC loops that run from the SAT 3C/D/F controllers to
the TUC controllers.
Figure 10-3: WattMaster Controls various communications loop wire
Power and Switc hable RS-485
Communications Board
“Wire Nuts” on the RS-485 communications loop should be avoided
at all costs. As an alternative to the “Wire Nuts”, WattMaster
Controls has a Power and Switchable RS-485 Communications
Board - WattMaster part #PL102224. The Power and Switchable
RS-485 Communications Board can be thought of as a 24-VAC
power and communication distribution system for the SAT III
communications loop that will aid in initial startup and future
troubleshooting of the SAT III communications loop. The Power
and Switch Boards should be used on a fl oor-by-fl oor basis. The
board is sold alone or in a small metal electrical enclosure. See
Figure 10-4.
This circuit board was designed to be used as a central connection
point for the SAT III communications loop. The eight switches are
provided only to disconnect the RS-485 communications loop for
troubleshooting purposes.
Wiring for the communication connections are as follows: “R”
to “R,” “T” to “T,” and “SHLD” to “SHLD” or “SH.” Connect
the wiring from the SAT III to a SAT III, SAT 3C/D/F, or SAT 3P
Controller. These eight push-button switches only disconnect the
communications loop. THEY DO NOT SWITCH POWER ON/
OFF .
This circuit board may be also used as a separate central connection
point for the SAT 3C/D/F - TUC communications loop.
Wiring for the communications connections are as follows: “R” to
“R,” “T” to “T,” and “SHLD” to “SHLD” or “SH.” Connect the
wiring from TUC controller to TUC controller. But on the SAT
3C/D/F controller, the TUC “R” connection must be wired to the
SAT 3C/D/F “T” connection, and the SAT 3C/D/F controller “R”
connection must be wired to the TUC “T” connection.
WCC III Technical Guide
10-3
10. RS-485 COMMUNICATIONS
Pow er and Switchable RS-485 Communications Board
10-4
Figure 10-4: Power and Switchable RS-485 Communications Board Application Drawing
WCC III Technical Guide
10. RS-485 COMMUNICATIONS
24V AC Pow er Wiring
24V AC P o wer Wiring Considerations
You do not have to use the 24VAC connections on the Power
and Switchable RS-485 Communications Board, as each SAT
III panel should have its own 120VAC-to-24VAC transformer.
However, WattMaster Controls included the 24VAC connections
on the Power and Switchable RS-485 Communications Board as a
convenience option for 24VAC power distribution wiring.
When using the Power and Switchable RS-485 Communications
Board with a common 24VAC (250VA MAX) transformer,
the24VAC and GND polarity must be maintained on each and
every 24VAC & GND power connection.
• Each SAT III draws - 15VA (No more than 15
SAT III max per board with a 250 VA - 24 VAC
transformer)
• Each SAT 3C/D/F draws - 10VA (No more than
24 SAT 3C/D/F max per board with a 250 VA - 24
VAC transformer)
• Each TUC-2R draws - 5VA (No more than 32
TUC-2R max per board with a 250 VA - 24 VAC
transformer)
WIRE RESISTANCE STANDARDS
• 18-Gauge WIRE OHMS PER FOOT = 0.00639
• 16-Gauge WIRE OHMS PER FOOT = 0.00402
AMPERAGE CURRENT DRAW for WattMaster Controls
products
• SAT III controller is 0.63 AMPS
• SAT 3C/D/F controller is 0.42 AMPS
• TUC-2R controller is 0.21 AMPS with actuator
• TUC5-R controller is 0.34 AMPS
Example 1:
A single SAT III controller will have a voltage drop of 0.50 volts
with 100 feet of wire run when using 16-gauge wire. No more than
2 volts of drop is allowed for any WattMaster product. Two SAT
III controllers on the same loop will have twice the voltage drop
for the same distance.
0.506 Volts of loss = “0.63” x “0.00402” x “100 feet” x “2”
• Each TUC-5R draws - 8VA (No more than 28
TUC-R max per board with a 250 VA - 24 VAC
transformer)
• External relays and contactors are not included, but
need to be considered for total VA draw.
PLEASE NOTE: Vol tage loss in wire calculations must also
be considered and are listed below .
You must use the formula below when calculating max wire
distance and the resulting voltage loss that can and will occur
when running SAT III and TUC power wiring.
The formula is as follows: “VL” = “A” x “WR” x “DIF” x “2”
VL = Voltage Loss, A = AMP Draw , WR = Wire Resistance, DIF =
Distance In Feet, 2 = 2 Wires (1 Wire in each direction!)
Example 2:
A single TUC-2R controller will have a voltage drop of 0.671 volts
with 250 feet of wire run when using 18-gauge wire. No more than
2 volts of drop is allowed for any WattMaster product. Two TUC2R controllers on the same loop will have twice the voltage drop
for the same distance.
0.671 Volts of loss = “0.21” x “0.00639” x “250 feet” x “2”
Example 3:
A single SAT 3C/D/F controller will have a voltage drop of 1.69
volts with 500 feet of wire run when using 16-gauge wire. No
more than 2 volts of drop is allowed for any WattMaster product.
Two SAT III controllers on the same loop will have twice the
voltage drop for the same distance.
1.689 Volts of loss = “0.42” x “0.00402” x “500 feet” x “2”
SAT III IN A ENCLOSURESAT3D INAENCLOSURESAT3D IN A ENCLOSURE
SAT III IN A ENCL OSURESAT III IN A ENCLOSURE
SAT 3D IN A ENCL OSURE
Wrong Communications Wiring
Figure 10-5: Typical WCC III System Communications Wiring – Not the recommended and preferred way
Wiring of the WCC III RS-485 communications loop as represented
in Figure 10-5 is not recommend for the following reasons:
1. The use of “Wire Nuts” to connect the communications wire at
a central hub (the 4x4 handy box) and inside of a SA T III enclosure
is not a good idea. The connections will oxidize over time and the
resistance of the “Wire-Nutted” connections will increase over
time. Generally speaking, the use of “Wire Nuts” can and will
cause a problem with the WCC III communication loop at some
point. Also, tugging or pulling on the WCC III communications
wiring during troubleshooting or during routine maintenance can
and generally will cause these “Wire Nuts” connections to break
apart.
10-6
2. The haphazard way the WCC III communications wiring was
run in Figure 10-5 is also not recommended. In this example,
wiring was run from the 2nd fl oor to the 4th fl oor and then back
to the 2nd fl oor and then back to the 4th fl oor again. The WCC III
communications wiring should make sense and never jump fl oors
or go back down a fl oor and then go back up a fl oor. See Figure 10-6 which shows a diagram of how the WCC III communications
wiring should be run and to use for troubleshooting purposes.
3. A Power and Switchable RS-485 communication board
(PL102224) was not used on a fl oor-by-fl oor basis. Use of this
board will aid in initial startup and in future troubleshooting.
SATIIIINAENCLOSURESAT 3D IN A ENCL OSURESAT 3D IN A ENC LOSURE
SAT III IN A ENCLOSURESAT III IN A ENCLOSURE
SAT 3D IN A ENCL OSURE
POWER & SWITCHABLE
COMMBOARD (PL102224)
POWER & SWITCHABLE
COMMBOARD (PL102224)
POWER & SWITCHABLE
COMMBOARD (PL102224)
POWER & SWITCHABLE
COMMBOARD (PL102224)
POWER & SWITCHABLE
COMMBOARD (PL102224)
Recommended Communications Wiring
Figure 10-6: Typical WCC III System Communications Wiring – The recommended and preferred way
Wiring of the WCC III RS-485 communications loop as represented
in Figure 10-6 is recommended for the following reasons:
1. “Wire Nuts” were not used.
2. The way the WCC III communications wiring was run is also
recommended. Making a main WCC III communications trunk
line and wiring from the basement to the 1st fl oor, then to the 2nd fl oor, then 3rd fl oor, and then to the 4th fl oor, makes logical sense.
The location of the WCC III - MCD is not shown, but it could be
3. A Power and Switchable RS-485 Communication Board
(PL102224) was used on a fl oor-by-fl oor basis. Use of this board
will aid in initial startup and in future troubleshooting. This Power
and Switchable RS-485 Communication Board (PL102224) has
push buttons on each of the 8 communications connections going
out from it. You can connect as many SAT III / SAT 3C/D/F
controllers as you wish to each switchable connection, but
remember that you can only isolate down to that loop of X number
of SAT III controllers.
anywhere in the building as long as it is connected to the main
trunk line. Also, lighting protection devices should be added on
every fl oor as a preventive measure.
WCC III Technical Guide
10-7
Loading...
+ 21 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.