WattMaster WCC III User Manual part 4

3. WCC3.EXE Screen Descriptions
WCC III
3. WCC3.EXE Screen Descriptions
T ABLE OF CONTENTS
SECTION 3: WCC3.EXE SCREEN DESCRIPTIONS
WCC III Main Menu Tool Bar ............................... 3-3
Special Purpose Keys ......................................... 3-8
Main Menu Screen ………………………………………3-10
Analog Input Summary Screen …………….………3-12
Analog Input General Screen .............................................3-14
Analog Input Pulse Screen .................................................3-18
Analog Input Thermistor Screen .........................................3-20
Analog Inputs......................................................................3-24
Analog Input Resistor Screen .............................................3-35
Analog Input Resistor+ Screen ...........................................3-38
Analog Input RawCount Screen .........................................3-41
Analog Input Thermistor+ Screen .......................................3-44
Logic Switch Summary Screen ........................3-76
Logic Switch Screen ...........................................................3-77
Binary Output Summary Screen ....................... 3-81
WCC III Binary Output Board / V-Out Board ..... 3-83
Binary Output Screen .........................................................3-85
Alarm Summary Screen .................................... 3-87
Satellite Summary Screen ................................ 3-88
Rebuild Satellite Tables ....................................3-90
Override Screen ................................................ 3-91
Holiday Schedule Screen ................................. 3-92
System Parameters Screen .............................. 3-94
Operator Codes Screen......................................................3-98
Control Output Screens …….…………………….….3-51
Control Output Summary Screen .......................................3-52
EA Driver Screen ................................................................3-54
Dual Limit Screen ...............................................................3-56
Time Clock Screen .............................................................3-59
Control Outputs ..................................................................3-61
Analog Output Summary Screen ...................... 3-63
Analog Output Screen ........................................................3-65
WCC III System Logging ................................... 3-68
SAT Trend Log Summary Screen .......................................3-69
SAT Change of State Trend Log Screen ............................3-70
SAT Run Time Trend Log Screen .......................................3-71
SA T Analog Trend Trend Log Screen .................................3-73
SAT Analog Peak Trend Log Screen ..................................3-75
On/Off and Units of Measure
Messages Screen ..............................................3-99
Alarm Messages Screen ................................. 3-100
Secure the System ......................................... 3-101
Energy Consumption Screen .......................... 3-102
Custom Screens ..............................................3-105
Bitmap Screens .............................................. 3-109
Network Information Screen .......................... 3-112
T ABLE OF CONTENTS
PID Programs .................................................. 3-113
Simple PID Programs Screen...........................................3-114
Modifi ed PID Programs Screen ........................................3-116
Digital PID Programs Screen............................................3-117
PID Tuning Screen ...........................................................3-118
Week Schedule Summary Screen .................. 3-120
Week Schedule Screen ....................................................3-121
Optimal Start Screen ...................................... 3-122
Analog Globals ................................................ 3-125
Analog Global Summary Screen ......................................3-126
Analog Global Screen.......................................................3-127
Analog Global Averaged List Screen ................................3-129
Analog Global Sorted List Screen ....................................3-130
Analog Global Integral Mode ............................................3-131
Analog Global Integral Mode Accumulation Mode............3-132
Analog Global Integral Mode Average Mode ....................3-134
Analog Global Integral Mode Sliding Window Mode ........3-137
Analog Global Math Function Mode Screen .....................3-140
Analog Global Look Up Table Mode .................................3-142
Analog Global External Mode Screen ..............................3-146
Useful Analog Actuator/V alve Control Information ............3-147
Analog Global Dual Valve Mode .......................................3-148
Analog Global Proportional Mode Screen ........................3-152
Analog Global Dual Ramp Mode Screen …………………3-154 Analog Global Multi-Proportion Mode Screen …………...3-156 Analog Global Pulse Start Mode Screen …………………3-158
Binary Global Summary Screen .....................3-160
Binary Global Screen........................................................3-162
Binary Global Combinatorial Mode Screen ......................3-163
Binary Global Compare Mode Screen ..............................3-165
Binary Global External Mode Screen ...............................3-167
Binary Global Alarm Mode Screen ...................................3-169
Binary Global Alarm-By-Class Mode Screen ....................3-171
Binary Global One Shot Mode Screen .............................3-173
Binary Global Clock Mode Screen....................................3-175
Binary Global Delay Mode Screen ...................................3-177
Binary Global PWM Mode Screen ....................................3-179
Binary Global Lead Lag Mode Screen..............................3-181
Shed/Restore Screen ...................................... 3-184
Duty Cycle Screen ..........................................3-186
Proportional Reset Screen .............................3-188
Proportional Reset Graph .................................................3-190
Tenant Override Utility List ............................ 3-191
General Message Screen................................ 3-193
WCC3.EXE SCREEN DESCRIPTIONS
Running the WCC3 Program
SECTION 3: WCC3.EXE SCREEN DESCRIPTIONS
____________________________________________________
How to Start or Run the WCC3.exe Program (SS5021)
The WCC3.exe shortcut icon should have been installed on your WCC III front end computer desktop with the WCC III Installation Software CD. The WCC III Installation Software CD is W attMaster Controls Part # DM1WC011-01X.
T o start the WCC3.exe program, double-click the left mouse button on the Shortcut Icon located on the Windows desktop.
After a short period of time, dependent upon the CPU speed of your Windows based computer and the speed of your IP connection to the internet, the WCC III T ype Connection Dialog Box will appear .
Using your mouse, left-click on the The Remote Access Dialog Window will appear.
By selecting <OK>, the WCC3.exe program will now start to connect to the selected WCC III – MCD via this selected IP address connection. It should bring up the WCC III Set Password Dialog screen within a new window. If the IP address connection fails to connect to the WCC III – MCD, then another small dialog box window will appear. This is the Cannot Communicate to Backtask Dialog Box.
If you click <Yes>, you will exit the WCC3.exe program. You will have to fi gure out why you cannot connect to the WCC III – MCD via the IP address connection.
If you click but instead you will be connected to the WCC III Main Menu. This connection to the WCC III Main Menu is not an actual IP connection, but rather a “dummy” WCC III main menu screen window with no values. This “dummy” WCC III main menu screen window will allow you to view and see what the actual WCC3.exe screens will look like – minus any data.
<No>, you will not exit the WCC3.exe program,
<Access Job Site> button.
Server IP Address:
This is the static IP address of the WCC III – MCD. An IP Address is like a phone number on the world wide web. The IP address for the WCC III – MCD must be Static (does not change) as opposed to Dynamic (constantly changing). This static IP address must be provided by your internet service provider. (A static IP address is the preferred IP connection method for the WCC III system to function.) If you actually know the static IP address of the WCC III – MCD that you wish to connect to, please enter it here in the Server IP Address fi eld, or better yet, continue to the Remote Access Dialog Window by selecting the
You can use a Dynamic IP Address with the WCC III – MCD, but you must then have what is called a static “Host Name”. This static “Host name” must then be provided by your internet service provider and is limited to 58 total characters.
Port Number:
The WCC3.exe program opens a two-way , secure communications port that then allows for communication between the WCC III – MCD and the WCC3.exe program that is running on the WCC III Front end computer. This IP Address connection is done on a higher address port number than normal (WCC III connection is port number 39289) to help reduce the risk of computer hacking.
<Access Job Site> button.
In the Set Password Dialog Screen enter an “Operator:” identifi cation and a “Code:” or password equal to at least a pass level 0 that has been previously set up on the WCCIII System
Parameter – Operator Code Screen. (See the Operator Code Screen of the System Parameter Scr een in Section 3 for information
on setting up Operator Codes) Click “Current Pass Level:” stays at 0 or higher (1, 2, or 3) then click
<OK>. By selecting <OK>, the WCC3.exe program will now start
to connect to the selected WCC III – MCD via this selected IP address connection. It should bring up the WCC III Main Menu within a new window. If the “Current Pass Level:” changes to –1 then you do not have access to the WCCIII – MCD. If you do not have access to the WCCIII – MCD and you click then this connection to the WCC III Main Menu is not an actual IP connection, but rather a “dummy” WCC III Main Menu window with no values. This “dummy” WCC III Main Menu window will allow you to view and see what the actual WCC3.exe screens will look like – minus any data.
<Check Password>, if the
<OK>
WCC III Technical Guide
3-1
WCC3.EXE SCREEN DESCRIPTIONS
Running the WCC3 Program
The Remote Access Dialog Box will allow you to enter multiple WCC III – MCD IP addresses based upon “Job Site” names. This is done by typing in the name of the jobsite you wish to call your system.
First you must select a “BLANK” line in the bottom box area with your left mouse button. (This line will then be highlighted in “Blue”.) You must then enter a Job Site name in the “Job Site” eld, along with the static IP address and Port number (39289) for the WCC III – MCD that you wish to connect to with the WCC3. exe program.
If you are using a static “Host Name” instead of a static IP address please make sure that the Dynamic Address check box has been selected, along with the static “Host Name” in the space provided. As mentioned previously, you must get this static “Host Name” from your internet service provider, and it is limited to 58 characters total.
Please note that this “Job Site” name will also be the name of a subdirectory that will automatically be created in the Local disk C:\ProgramFiles\WCCIII\WCC3 subdirectory on the WCC III Front end computer. The Remote Access Dialog Box also creates a JobSite.dat data fi le in the C:\ProgramFiles\WCCIII\WCC3 subdirectory. This data fi le is not a viewable type of fi le. The JobSite.dat fi le can be copied and then can be used on other WCC III front end computers. This reused JobSite.dat will then recreate the needed “Job Site” subdirectories on the other WCC III front end computers upon the reselection of the Job Site IP address.
In an already fi lled out Remote Access Dialog Box, you can simply select from the list of previously entered Job Sites that are displayed in the bottom box fi eld. Then left-click back to the Connection Dialog Box that was fi rst displayed. This Connection Dialog Box now should have the desired IP address in the Server IP Address location fi eld and the port number (39289) in the Port Number location fi eld for the WCC III – MCD that you wish to connect to with the WCC3.exe program.
<OK>. This will take you
IP Address:
This is the static IP address where the WCC III – MCD is located. An IP Address is like a phone number on the world wide web. The IP address for the WCC III – MCD must be static (does not change) as opposed to Dynamic (constantly changing). This static IP Address must be provided by your internet service provider. (A static IP address is the preferred IP connection method for the WCC III system to function.)
Port Number:
The WCC3.exe program opens a two-way , secure communications port that then allows for communication between the WCC III – MCD and the WCC3.exe program that is running on the WCC III front end computer. This IP Address connection is done on a higher address port number than normal (WCC III connection is port number 39289) to help reduce the risk of computer hacking.
Job Site:
This is the name of the jobsite you wish to call your system. Please note that this name will also be the name of a subdirectory that will automatically be created in the Local disk C:\ProgramFiles\ WCCIII\WCC3 subdirectory.
Host Name:
You can use a Dynamic IP Address with the WCC III – MCD, but you must then have what is called a static “Host Name”. This static “Host name” must then be provided by your internet service provider and is limited to 58 total characters.
When you have fi lled out all necessary fi elds, left-click This will take you back to the Connection Dialog Box that was rst displayed. This Connection Dialog Box now should have the desired IP address in the Server IP Address location fi eld and the port number (39289) in the Port Number location fi eld for the WCC III – MCD that you wish to connect to with the WCC3.exe program.
Left-click was fi rst displayed. The Connection Dialog Box will have the same IP address as listed originally before in the Server IP Address location fi eld and the port number (39289) in the Port Number location fi eld.
Left-click Dialog Box to your Windows system default printer on the WCC
III front end computer. This print function is provided to give you a hard paper backup copy of these IP address for the various WCC III – MCD that you may have. This print function also creates a Printscreen.dat data fi le in the C:\ProgramFiles\WCCIII\WCC3 subdirectory. This data fi le is not a viewable type of fi le.
<Cancel> to return to the Connection Dialog Box that
<Print> to send all of this data in this Remote Access
<OK>.
3-2
WCC III Technical Guide
WCC III Main Menu T ool Bar
WCC3.EXE SCREEN DESCRIPTIONS
WCC III Main Menu T ool Bar
When you open the WCC III program and each of its available screens, you will notice that the name of the screen will appear in brackets at the top of the window, for example WCC III - [Main Menu Screen]. Under that is what is referred to as the Top Menu Bar. In the Top Menu Bar are the menus
<Window>, <Action>, <PassLevel>, and <Help>.
<File>, <Edit>, <View>,
File Menu
The <File> menu contains the functions <Print>, <Print Preview>
- preview your print job before printing, <Print Setup> - setup your printer and printing options, <Print To File> - print to a fi le in order to print the fi le at a later date, <Upload Slide Screen Files>
- saves all information for the Custom Screens and Bitmap Screens on this WCCIII front end to the WCCIII – MCD,
Slide Screen Files> - downloads all information for the Custom
Screens and Bitmap Screens to this WCCIII front end from the WCCIII – MCD.
<Download
Edit Menu
View Menu
The <View> menu gives you the option to show or hide the T oolbar and Status Bar. A checkmark indicates Show. No checkmark indicates Hide. You can also view the Satellite Map. If you choose this option, the Satellite Map will appear on the screen. Press
<Esc> to return to the WCC III Main Menu.
Window Menu
The <Window> menu allows you to open more than one screen at a time. Each screen is contained in its own window.
<Cascade> will arrange all windows into a stack, with each
window offset slightly. <Tile> will display all windows equally without overlapping.
<Arrange Icons> - This function is not available at this time.
The <Edit> menu contains four functions; however, only <Copy> and <Paste> are available for use. These functions work the same as <Set Current Screen for Copying> and <Copy Screen From
Previous Screen>
located in the <Action> menu.
WCC III Technical Guide
<Open> - This function is not available at this time.
To activate a window, click the window title bar or choose the name of the window in the are numbered in the order they were opened.
<Window> menu. Multiple windows
3-3
WCC3.EXE SCREEN DESCRIPTIONS
WCC III Main Menu T ool Bar
Action Menu
To set up the printing schedule for each screen, you must then
<Action>, <Edit Print Screen Schedule>. The Edit Print
select Screen Pr ogram Window will pop-up.
You can select the printing schedule by time, interval, or global binary.
If you select <At Time>, the At Hour: and Minute: fi elds will appear. Enter the time of day with a two-digit hour value (military time) and a two-digit minute value. The hour value should be less than 24, and the minute value should be less than 60.
The <Action> menu has many functions. These functions’ availability are tied to individual screens. Available menu items will be bolded.
Edit Print Screen Schedule/ Add Current Screen
The fi rst two menu items <Edit Print Screen Schedule> and
<Add Current Scr een for Print Screen Schedule> are used to
automatically generate screen prints based on the schedule you set up for each screen.
While in a screen, if you select
to Print Screen Schedule>, the screen will be immediately added
<Action>, <Add Current Screen
to the Print Screen Schedule Pr ogram.
If you select
<With Interval>, the Interval: fi eld will appear. Enter
the interval and select minutes, hours, or days from the drop down menu. The interval should be less than 256 and greater than 0.
If you select
<Global Binary>, the Global Binary Number: fi eld
will appear. Enter a global binary number . If you wish to temporarily remove the screen from the print schedule, select
<None> from the
drop down menu. The global binary value should be less than or equal to 512 and greater than 0.
You must click
<Change> to have the system accept the assigned
schedule. If you wish to remove a screen from the schedule, highlight the screen name and then click <Delete>. To print a screen immediately, highlight the screen name and then click
<Print>
. Click <Exit> to exit the program.
Set Current Screen for Copying
To copy a set of data points from one satellite to the next, while at the point you wish to copy from the current screen or within the same satellite, select
Copying>.
<Action>,<Set Current Screen for
A message similar to the following will appear at the bottom of the screen:
3-4
Point __ of Satellite __ was tagged for copy!
WCC III Technical Guide
WCC3.EXE SCREEN DESCRIPTIONS
WCC III Main Menu T ool Bar
Copy Screen From Previous Screen
While at the Home position at the screen you wish to copy the data to, select <Action>,<Copy Screen From Previous Screen>. The data point will be copied from the previous screen to the current
screen.
Clear Structure
While at the Home position on the screen, select <Action>, <Clear
Structure> to clear/remove the data from the screen. This works
the same as pressing <Ctrl><Home>.
Acknowledge Alarm/Acknowledge All Alarms
Select <Action>,<Acknowledge Alarm> to acknowledge a single alarm. Select
<Action>,<Acknowledge All Alarms> to
acknowledge all alarms on the Alarm Summary Screen.
NOTE: Acknowledge All Alarms only works with the Alarm
Summary Sc ree n.
Clear Error/Clear All Errors
While at the Satellite Summary Screen, select <Action>,<Clear
Error>
to clear an error located in the ERR column. You must
have the desired row highlighted in order to do this. Select
<Action>,<Clear All Errors> to clear all errors.
To rebuild all tables, type a zero in the Satellite Number fi eld and select <Rebuild All Tables>. To rebuild one table, enter the satellite number and then select
<Rebuild One T able>.
Set Simulate Satellite/Clear Simulate Sa tellite
While at the Satellite Summary Screen, highlight an empty satellite entry and then select <Action>,<Set Simulate Satellite> to create a simulated satellite. Select <Action>,<Clear Simulate
Satellite>
to reverse this process.
Clear the TOS/Clear all T OS
TOS stands for TUC off the system which means the satellite is no longer communicating with the Wcc3 system. To clear the alarm once communications are reestablished, do the following: While at the Satellite Summary Screen, select
<Action>,<Clear the TOS>
or <Clear all TOS> to clear one or more TUCs that are off the system.
Looking Back in Time
You have the ability to view information for any month, day, and year and time of day. The data is saved in the BACKTASK folder on the hard drive. Select <Action>, <Looking Back in Time>. The Back to Time Dialog Window will pop-up.
Delete Satellite
While at the Satellite Summary Screen, you can delete a satellite by placing the cursor on the satellite you wish to delete and selecting
<Action>,<Delete Satellite>.
Force Search Satellite
While at the Satellite Summary Screen, you can search for a satellite by placing the cursor at a satellite number you know to exist but is lacking data, by selecting
<Action>,<Force Search Satellite>.
Rebuild Satellite Unit/P attern Table
While at the Satellite Summary Screen, you can rebuild satellite tables by selecting
Table>. The following window will appear:
<Action>, <Rebuild Satellite Unit/Pattern
Use the arrow buttons at the top to move through months and years. Select the day of the month by clicking on it. Type in the hour of the day in two-digit military format. Then select <OK>.
The WCC III system will retrieve the data from the entered date and time. To return to the current date and time, simply select
<Action>,<Looking Back in Time> again.
Save As Current
Once you retrieve data from the hard disk, you can save the data to the satellite. This may be necessary if someone entered the wrong data for a satellite, for example. To save the retrieved data to the satellite as the current data, select
Current>.
<Action>, <Save As
WCC III Technical Guide
3-5
WCC3.EXE SCREEN DESCRIPTIONS
WCC III Main Menu T ool Bar
Plot
When data is available to graph, for example, in the Trend Logs screens, you can select <Action>,<Plot> and the data will be plotted on a graph. This works the same as pressing
<Ctrl><G>.
Reset
While in the Trend Log screens, you can select <Action>,<Reset> to reset the screen. This works the same as pressing <Ctrl><R>
Set Color
At any time when running WCC III, you can change your screen colors. Select will appear:
<Action>,<Set Color> and the following window
Search Description
At any time while running WCC III, you can search for a description. Select
<Action>,<Search Description>. The following window
will appear:
Enter your description in the Description fi eld and then select
<Start Search>. The example in the window shows a search for
Room. When the Search is complete, double click on the result you want to look at and its screen will appear. To return to the Sear ch Description Screen, pr ess <Home>.
Search Logic Address
At any time while running WCC III, you can search for a logic address. Select Logic Address W indow will appear:
<Action>,<Search Logic Address>. The Search
3-6
WCC III Technical Guide
WCC3.EXE SCREEN DESCRIPTIONS
WCC III Main Menu T ool Bar
When you click inside the Search For eld, the Edit Logic Address Dialog Window will appear:
Y ou can select by Satellite Number and Point Number or by Global Index and then select Search For fi eld in the Search Logic Address Window. Then click
<Start Search>. When the Search is complete, double click on
the result you want to look at, and its screen will appear. To return to the Search Logic Address Screen, press
<OK>. Your selection should appear in the
<Home>.
Auto E-mail
Auto e-mail enables/disables emails in the Backtask program. You must be a Level 4 user to access this option.
PassLev el
The PassLevel is a quick way to change a person’s passcode level. Select <PassLevel> from the Main Menu Toolbar. The Set Password Dialog Box will appear:
Logic Address Tree
The Logic Address Tree allows you to see how the system connects together. At any time while running WCC III, you can select <Action>,<Logic Address Tree>. The Edit Logic Address Dialog Window will appear. See window above.
You can select by Satellite Number and Point Number or by Global Index and then select the Logic Address Tree View Window.
Double-click the left mouse button to expand and collapse the tree. Click the right mouse button to go to that data point’s screen.
<OK>. Your selection will appear in
Enter the Operator ID and Code. They will appear as asterisks for security purposes. Click password and display the designated level access.
You can also access this operation in the System Parameters Screen.
<Check Password> to verify the
Help
The <Help> menu displays the About Wcc3 window which contains the version number of the software along with W attMaster Control’s company information. It is important to know the version number when calling WattMaster Control’s Technical Support. Select
<OK> to exit the window.
WCC III Technical Guide
3-7
WCC3.EXE SCREEN DESCRIPTIONS
Special Purpose Keys
Special Purpose Keys
The special purpose keys are a very powerful and necessary part of the WCC III system, but they can also be very dangerous if you are not sure how to use them. Therefore, most of the special purpose keys require that the operator have a Level 3 passcode.
<Ctrl><A>: Acknowledge Alarms—Used at the Analog
Input Summary Screen, Trend Log Run Time Scr een, Alarm Summary Screen, and Global Analog/Binary Summary Screen.
<Ctrl><G>: Display Graphs—Used at the Analog T rend
Screen, Pr oportional Reset Screen, and the Look-up T able Screen to plot data.
<Ctrl><K>: Clear Communication Errors—Used at
Satellite Summary Screen for troubleshooting, clears communication errors on a single satellite.
<Ctrl><R>: Manually Reset (Clear) Data—Used at the Trend Log Screen, Global Analog Integral Mode to reset accumulated consumption, Energy Consumption Screen to reset consumption.
< Ctrl><Home>: Clear Input Data from Present Screen
(clear structure)—Cursor must be in the Home position on the screen.
<Ctrl><U> Toggle Updating—Used on Custom Screens and
Bitmap Screens to “freeze/unfreeze” the data being displayed.
<Ctrl><A>: Acknowledge Alarms
When an alarm occurs within the system, the alarm condition appears on its respective summary screen as a fl ashing display generally on the right side of the screen. Once the alarm has been acknowledged, one of two possible conditions will be displayed.
The fi rst condition is when an alarm is acknowledged, but the alarm remains outside of the alarm limits. When this happens, the alarm information is still displayed on the screen, but it appears solid instead of blinking. The second condition is when an alarm is acknowledged AND the alarm is inside the alarm limits. In this case, all alarm information for that point is cleared from the screen.
To acknowledge new (blinking) alarms, position the cursor (>) at the point for which you wish to acknowledge alarms. Once positioned, press and hold
<Ctrl>, then press <A>, and then release
both keys at the same time.
<Ctrl><G>: Display Graphs
The WCC III system has graphs for the Analog Trend Screen, the Proportional Reset Scr een, and the Look-Up Table Scr een that can
be displayed on the screen and can be printed on the printer using the
<File>, <Print> command.
The graph for the Analog Trend - T rend Logging Scr een is accessed while the cursor is at the Home position of an Analog Trend Scr een. Press <Ctrl><G>. Press the <Home> key to return to the Analog Trend Screen.
<Ctrl><F> Find Logic Address—Used on Custom Screens
and Bitmap Screens to fi nd the exact location where a point was placed on the screen.
<Ctrl><D> Delete Logic Address—Used on Custom
Screens and Bitmap Screens to delete the location where a point was placed on the screen.
3-8
The Proportional Reset Screen also has a graph that can be accessed by pressing
<Ctrl><G> while the cursor is anywhere on
the Proportional Reset Screen. Press the <Home> key to return to the Proportional Reset Scr een.
To access the graph for the Look-Up Tables (GA 121-128), while the cursor is at any position on a Global Analog Look-Up Table, press
<Ctrl><G> to display the Look-Up Table graph. Press the
<Home> key to return to the Global Analog Look-Up Table.
WCC III Technical Guide
WCC3.EXE SCREEN DESCRIPTIONS
Special Purpose Keys
<Ctrl><K>: Clear Communication Errors The WCC III system keeps track of the transmission and receive
errors between the MCD Internet appliance and the satellite controllers on the Satellite Summary Screen. The <Ctrl><K> feature clears the existing number of errors and is used for trouble­shooting purposes.
<Ctrl><R>: Reset Trend Logs or Global Analog Accumulation Screens
When you are at a Trend Logging Screen and wish to reset (clear) the existing trend log data on the particular screen, simply press
<Ctrl><R>. This should automatically reset (clear) the data on the
Trend Log Scr een. On new systems, the Trend Log Screens should be reset before they have been programmed to clear out any “bad data” that might be in the satellite controller.
The
<Ctrl><R> feature is also used to reset the global analogs
using the integral mode and the Energy Consumption Scr een.
If the system is trying to e-mail-out an alarm and it cannot report its information for some reason, the system will continue to try and e-mail the call-out forever unless you press
<Ctrl><R> while the
cursor is at the “Disabled by” position for that alarm type on the System Parameters Screen.
<Ctrl><Home>: Clear Input Data from Present Screen
You must be a Level 3 user for <Ctrl><Home> to work. <Each screen (or point) has data which is saved in the memory of the MCD or the satellite controller. Before any processing of the data entered on a screen is performed, the system checks the point’s “structure valid” indicator to insure that the data it contains is valid and properly formed. If the point is not valid, then that point is skipped and processing continues with the next point. In addition, all summary data is removed from that point’s summary screen.
T o clear a screen (invalidate it), the cursor must be in the “Home” position on the individual screen that is to be cleared. Once there, press
<Ctrl><Home>. The data on the screen should be cleared
away. Once you have cleared a point, the data for that point is lost, and it cannot be recovered. Therefore, make sure you have the right point before using
<Ctrl-U>: Toggle Updating
<Ctrl><Home>.
The values of the WCC III points on the Custom Screen are “dynamic.” That is, the values on the screen will change as the value of the point changes. However, you have the option of “freezing” the points at their present value by pressing
<Ctrl>
and <U> while the Custom Screen is displayed on the monitor. To return to “live” data, press
<Ctrl> and <U> again.
<Ctrl-F> and <Ctrl-D>: Delete a Point Address on the Custom Screen
To delete a point on the Custom Screen, fi rst you must have the cursor in the exact location it was when the point was placed on the screen. To simplify fi nding this location, you may move the cursor near the existing point and then press <Ctrl> and <F> simultaneously to cause the cursor to move to the exact position where the point was created. You may delete the point by pr essing
<Ctrl> and <D> simultaneously, and then pr essing <Enter>. The
four slashes (////) will then appear. You may enter a new point, or to remove the slashes, leave the screen by pressing <Home> twice, and then re-access the screen.
WCC III Technical Guide
3-9
WCC3.EXE SCREEN DESCRIPTIONS
Main Menu Screen
MAIN MENU SCREEN
----------------------------------------------------------------------------------------------------------------------------------------------------------------------
08:11 1/20
WATTMASTER CONTROL CENTER III
WCC III
Sat #____ Overview Central Unit Analog Input Alarm Summary PID Programs Control Output Satellite Summary Week Schedules Analog Output Overrides Optimal Starts Trend Logs Holidays Analog Globals Logic Switches System Parameters Binary Globals Binary Output On/Off/Units Messages Shed/Restore Programs Alarm Messages Duty Cycle Programs Secure the System Proportional Programs Energy Consumption Tenant Override Custom Screens General Message
Bitmap Screens Network Information
Active alarms in classes: 16
WCC III Version 2.21 BACKTASK Version 2.18 L
The Main Menu Screen allows you to view the available screens within the WCC III system. To get to a screen listed on the Main Menu, use the arrow keys to position the cursor over the name of the screen you want to access and press <Enter>.
The Main Menu is divided into three categories: Sat #, Overview, and Central Unit.
Sat #____
The information associated with the screens within this category is stored in the satellite controllers and IS NOT stored in the MCD. It is a very good idea to save this information on a back-up disk by using the Satellite Save/Restore program located in the WCC
Utility Program.
Overview
This section allows the operator to perform operations and view screens which affect all of the satellite controllers on the system.
The information associated with the screens located in this category is stored in the MCD. When the screens in this category are programmed for the fi rst time, or when a change is made to these screens, the system automatically stores the information on the data disk.
Central Unit
The screens located in this category are GLOBAL commands. Global commands “travel” along the two-wire communication loop and are used by any or all of the satellite controllers. All of the satellites are constantly monitoring this information but only certain satellites will react to the information depending on how they have been programmed. The information associated with the screens located in this category is stored in the MCD. When the screens in this category are programmed for the fi rst time or when a change is made to these screens, the system automatically stores the information on the hard drive disk.
3-10
WCC III Technical Guide
WCC3.EXE SCREEN DESCRIPTIONS
Active alarms in classes:
If an alarm is active within the system, the alarm type number will appear at this location. You will need to go to the Alarm Summary Screen to locate the specifi c alarm.
If the alarm is highlighted, it has not been acknowledged. If the number is not highlighted, all of the alarms in that class have been acknowledged.
WCC III Version _.__ BACKTASK Version _.__
The version number of the software presently being used by the WCC III system will appear at these locations. Backtask is a portion of the WCC III software. Each version of the WCC III software operates with a specifi c version of Backtask. This has been added to insure that the right version of Backtask is operating with the WCC III software.
Main Menu Screen
WCC III Technical Guide
3-11
WCC3.EXE SCREEN DESCRIPTIONS
Analog Input Summary Screen
Analog Input Screen’s WCC III Logical Address is XXXAY, where XXX = Satellite Address, A = Analog Input, and Y = 1-8
ANALOG INPUT SUMMAR Y SCREEN
-----------------------------------------------------------------------------------------
Analog Inputs Satellite 1 S1-KC Time Date Analog Inputs 08:22 01/20 Description Current Value Alarm Limits Stat Mode Alarm Details A1: S1-A1 50.0 Deg F 65.0 80.0 ON A2: S1-A2 0 Deg F 45.0 65.0 OFF A3: S1-A3 0 Deg F -10.0 100.0 ON A4: S1-A4 0 Deg F 45.0 100.0 ON A5: S1-A5 A6: S1-A6 A7: S1-A7 9.0 Deg F A8: S1-A8 99.0 Deg F
C1: OFF C2: OFF C3: OFF C4: OFF C5: OFF C6: OFF C7: OFF C8: OFF
HOME for menu
An analog input is a signal sent to the satellite controller that can be represented by a number such as temperature, pressure, etc. The Analog Input Screen is used to “tell” the WCC III system the characteristics of the sensor and to set alarm limits. The “Binary Setpoint” option at the bottom of the Analog Input Screen can be used to convert the analog input to a binary (On/Off) input.
Analog Inputs
Specifi es the summary type to be displayed. Because this is a “choice” fi eld, the list of available choices will be displayed at the bottom of the screen:
<Analog Input, Control Output, Analog Output,
Trend Logging, Logic Switch, Binary Output>
Y ou can access one of the screens which appear in this choice fi eld without returning to the Main Menu by pressing the until the desired summary type has been selected and then pressing
<Enter>.
<space bar>
Satellite______
Specifi es the number of the satellite which you are currently communicating with. If you would like to view the analog input summary data for a different satellite, use the arrow keys to move the cursor to this fi eld, enter the desired satellite number, and press
<Enter>. 1 to 239.
T o view or edit a specifi c analog input, use the arrow keys to move the cursor (shown as “>” along the left-hand side of the screen) to the desired point and press <Enter>. The Analog Input Screen for the specifi ed point will now appear.
Time / Date
The present time and date will automatically appear at these locations.
Description:_______________
The description message which was entered on the Analog Input Screen is displayed here to help you identify the different analog
inputs within the system.
3-12
WCC III Technical Guide
WCC3.EXE SCREEN DESCRIPTIONS
Analog Input Summary Screen
Current Value
The current value of the analog input is automatically displayed here.
Alarm Limits
The alarm limits which were input on the Analog Input Screens will automatically be displayed here.
Stat
The present “ON” or “OFF” status of the binary input which is controlling the schedule for the alarm limits is shown here. For example, if week schedule #1 (W1) has been input to control the schedule of the alarm limits, the message “ON” will appear here when week schedule #1 is “ON” and “OFF” will appear when week schedule #1 is “OFF”. When W1 is “ON” the “On Schedule” alarm limits will be active, and when W1 if “OFF” the Off Schedule” alarm limits will be active.
Mode
The “alt” message will appear here when the alternate alarm limits are active. When the input value which has been entered on the Analog Input Screen to select the alternate alarm limits is “ON,” the WCC III system will use the “Alternate Alarm Limits” and the “alt” message will be displayed here.
Alarm Details
This location will automatically display the alarm message, the high or low value of the analog input, and the time and date of the occurrence of the peak value.
When an alarm occurs, the alarm message will blink on the screen. To acknowledge an alarm, position the cursor at the point for which you wish to acknowledge the alarm. Then press or left-click on <Action> to bring up the <Action> menu at which point you can select <Acknowledge Alarm> or <Acknowledge
All Alarms>.
NOTE: The <Acknowledge All Alarms> option will
only work on the Alarm Summary Screen.
<Alt><A>
At this point, one of two things should happen. If the value of the analog input is presently within the alarm limits, the message will disappear. If the value of the analog input is not within the alarm limits, the message will stay on the screen, but it will quit blinking.
WCC III Technical Guide
3-13
WCC3.EXE SCREEN DESCRIPTIONS
Analog Input General Screen
Analog Input Screen’s WCC III Logical Address is XXXAY, where XXX = Satellite Address, A = Analog Input, and Y = 1-8
ANALOG INPUT GENERAL SCREEN
Satellite # 1 ANALOG INPUT # 1
Description: RM101 Type: Analog General Pattern for values associated with this input: xxx.x Units @ 0% scale: 0.0 DEG. Units of Measure message #: 1 @ full scale: 100.0 DEG. Filter time constant: 8 seconds
ALARMS Controlled by: W1 Limits Low High Alarm Type: 1 On 65.0 80.0 DEG. Alarm Message #’s: Low 2 High 1 Off 50.0 100.0 DEG.
Alternate limits selected by: .... On (alt) 0.0 0.0 DEG.
Off (alt) 0.0 0.0 DEG.
Limit overlap time after control change: 20 minutes Local set 55.0 90.0 DEG.
BINARY SETPOINT OFF Above 0.0 DEG. On Message #: 0 OFF Below 0.0 DEG. Off Message #: 0
HOME for menu
Satellite # _______
Specifi es the number of the satellite which you are currently editing. If you would like to edit a different satellite, use the arrow keys to move the cursor to this fi eld, type in the desired satellite number, and press
Analog Input # ________
This “fi eld” actually contains two separate fi elds. The fi rst fi eld specifi es the point “type” (i.e., analog input, control output, analog output, etc.) and displays the current type in textual form. Because this is a “choice” fi eld, the list of available choices will be displayed at the bottom of the screen:
<ANALOG INPUT, CONTROL OUTPUT, ANALOG OUTPUT,
TREND LOGGING, LOGIC SWITCH, BINARY OUTPUT>
You may make your selection by pressing the <space bar> until the desired choice appears and then pressing <Enter>. (If you select a point type that is different than that currently being displayed, the screen will be rewritten with the appropriate screen and data.)
<Enter>.
Additionally, this fi eld specifi es the point number to edit. For the Analog Input Screen, this number can range from one to eight, corresponding from A1 to A8, respectively. If you would like to edit a different point, move the cursor to this fi eld by using the arrow keys, enter the desired point number, and press
Description:
A short message is entered here which is displayed on Summary Screens to help you remember points within the system. You may
enter up to ten characters (control codes, ALT codes, and the double quote character are not allowed).
Type: Analog General
This fi eld is automatically fi lled in by the system. On screens 2-8, this will always read “ANALOG.” On screen number 1, it will read either “ANALOG” or “PULSE” depending on the position of the pulse switch on the satellite controller.
<Enter>.
3-14
WCC III Technical Guide
WCC3.EXE SCREEN DESCRIPTIONS
Analog Input General Screen
Sensor Type
This is a choice fi eld for Analog types only. A list of available choices will be displayed at the bottom of the screen:
<General, Thermistor, Resistor,
Resistor+, RawCount, Thermistor+>
You may make your selection by pressing the <space bar> until the desired Analog Type has been selected and then pressing
<Enter>.
General = A general use user programmable analog input screen.
Pulse = Specifi es the calibration information for the pulse meter connected to channel 1 of the satellite controller.
Thermistor = Used to setup WattMaster 10K type 3 curve thermistors.
Resistor = Used to measure resistance of a variable potentiometer.
Resistor+ = Used to setup different types of thermistors. WattMaster thermistors are 10K type 3 curve. You would enter values on the screen to correspond to different values and type curves of thermistors.
RawCount = Is the raw count value straight from the 12 bit A to D converter. Used for testing and or calibrating to see if the analog signal is linear, so that you may test the non-linear curve of any sensor to determine if any offset is needed.
Thermistor+ = T o be used if you are using a thermistor type sensor that WattMaster Controls has not provided. Other thermistor type sensors can be connected to the Satellite controller’s analog inputs with this screen. Please consult the WattMaster Controls factory for all other thermistor type sensors that you wish to connect to the Satellite Controller. WattMaster Controls can provide the correct b0, b1, b3 values at our option.
Pattern for Values Associated With This Input:
Specifi es where you would like the decimal point to appear in the value displayed by the system. Because this is a “choice” fi eld, a list of available choices will be displayed at the bottom of the screen:
< x,xxx , xxx.x , xx.xx , x.xxx >
You may make your selection by pressing the <space bar> until the desired data pattern has been selected and then pressing
<Enter>.
Units @ 0% scale: @ Full scale:
If the screen type is “ANALOG,” this specifi es the scaling information used by the system to proportionally scale the input value to the desired range. The raw input value to the satellite controller ranges from zero to one volt. If the scaling information has been set to 0 at 0% scale, and 100 at Full scale, a raw input value of 0.6 volts would produce a scaled value of 60.
If the screen type is “PULSE,” this specifi es the calibration information for the pulse meter connected to channel 1 of the satellite controller. The fi rst input is a “choice” fi eld, and therefore a list of available choices will be displayed at the bottom of the screen.
_______ Pulses = _______ Hours
< 100, 1000 >
The second input is used to “scale” or “calibrate” the particular sensor that is being used. For example, consider a pulse meter which measures the kwh of a building. Electrical meters are basically a small motor whose speed is proportional to power being used. Let’s consider a meter where one revolution equals one kwh, and the meter sends 5 pulses to the satellite controller for every 6 revolutions. Therefore, we would enter “100 Pulses = 120 kwh Hours.” (NOTE: maximum pulse rate allowed = 4 pulses per second.)
5 pulses = 6 revolutions 1 revolution = 1 kwh 5 pulses = 6 kwh 100 pulses = 120 kwh
Units of Measure Message #: 1
A number is entered here that references a message on the On/Off Units Messages Screen. For example, if units-of-measure message
#1 is “Deg F,” entering “1” will cause “Deg F” to be displayed as the units-of-measure for the analog input.
Filter Time Constant: ____ Seconds
Specifi es the sampling rate of the analog input. This is used by the satellites to “fi lter” (or smooth) the analog input signal. This can be used on inputs that “jump around” to reduce sporadic load control. Because this is a “choice” fi eld, the list of available choices will be displayed at the bottom of the screen:
< 0, 1, 2, 4, 8, 16, 32, 64 >
You may make your selection by pressing the <space bar> until the desired fi lter time constant has been selected and then pressing
<Enter>.
WCC III Technical Guide
3-15
WCC3.EXE SCREEN DESCRIPTIONS
Analog Input General Screen
------ALARMS------
Controlled by:
Specifi es the binary value that selects the ON or OFF alarm limits. When this value is OFF , the OFF alarm limits are selected; when it is ON, the ON alarm limits are selected.
Alarm Type:
Specifi es the priority (or “importance”) level for any alarms generated by this input. Alarm types range from one (highest priority) to eight (lowest priority). The system displays and e-mails higher priority alarms fi rst. (The fi rst fi ve alarm priorities (1-5) have e-mail-out-on-alarm capabilities.)
Alarm Message # Low: ___ High: ___
Specifi es a pair of message numbers, one for LOW alarms and the second for any HIGH alarms. These numbers are used by the system to reference a message which is entered on the Alarm Message Screen.
Alternate Limits Selected By:
Specifi es the point that initiates the Alternate mode. When this address is zero (or OFF), the Normal alarm limits are selected; when it is one (or ON), the Alternate alarm limits are selected.
Limits Low High On _____ _____ °. F Off _____ _____ °. F On (alt) _____ _____ °. F Off (alt) _____ _____ °. F Local Set _____ _____ °. F
There are two fi elds on this screen that determine which set of limits are active—the status of the “Controlled by” fi eld and the status of the “Alternate Limits selected by” fi eld. When the value that has been input in the “Controlled by” fi eld is ON, either the “On” limits or the “On (Alt)” limits are active depending on the status of the value input in the “Alternate Limits selected by” fi eld. If the value in the “Alternate” fi eld is On, the “On (Alt)” limits are used, and when the “Alternate” value is OFF, the “On” limits are used.
Alternate Limits Active Alarm Controlled by: Selected by: Limits:
On Off On On On On (Alt) Off Off Off Off On Off (Alt)
The local set alarm limits become active if the MCD quits communicating with the satellite controller. After communications are re-established, any alarms that occurred while the satellite was in local set will be reported.
Limit overlap time after control change:
This specifi es the amount of time the WCC software will wait after a control change (i.e., on/off schedule, alternate mode, local set mode) before deciding to generate an alarm. The fi rst input is a user-entered number from 1 to 60, and the second input is either seconds or minutes. This second input is a “choice” fi eld; the list of available choices will be displayed at the bottom of the screen:
<Seconds, Minutes>
This group of inputs specifi es the alarm limits for the “Normal,” “Alternate,” and “Local Set” modes. Each mode has a LOW and HIGH limit. When the value of the analog input goes out of these limits, an alarm is generated, and the alarm will automatically display and e-mail out.
3-16
WCC III Technical Guide
WCC3.EXE SCREEN DESCRIPTIONS
Analog Input General Screen
------ BINARY SETPOINTS ------
____Above:____ ____Below:____
These inputs are used to convert the analog signal to a binary (On/ Off) signal. The value that is going ON and OFF is a software point referred to as a comparator. Each analog input has a comparator associated with it named “Cn.” The comparator for analog input #1 is “C1,” analog input number 2 is “C2,” and so on. The status of the comparator can be seen on the Analog Input Summary Screen.
When the user has selected:
OFF Above & OFF Below:
OFF Above & ON Below:
ON Above & OFF Below:
ON Above & ON Below:
The value of the comparator is:
OFF when the Analog Input value is greater than the ABOVE setpoint or less than the BELOW setpoint, and ON when the Analog Input value is equal to either one or between the two setpoints.
OFF when the Analog Input value is greater than or equal to the ABOVE setpoint or until the Analog Input value becomes less than the BELOW setpoint, and ON when the Analog Input value is less than or equal to BELOW setpoint or until the Analog Input value becomes greater than the ABOVE setpoint.
OFF when the Analog Input value is less than or equal to the BELOW setpoint or until the Analog Input value becomes greater than the ABOVE setpoint, and ON when the Analog Input value is greater than or equal to the ABOVE setpoint or until the Analog Input value becomes less than the BELOW setpoint.
OFF when the Analog input value is equal to either one or between the two setpoints, and ON when the Analog Input value is greater than the ABOVE setpoint or less than the BELOW setpoint.
Because this is a “choice” fi eld, a list of available choices will be displayed at the bottom of the screen:
<ON, OFF>
You may make your selection by pressing the <space bar> until the desired choice is selected and then pressing <Enter>.
On Message #: Off Message #:
Specifi es a pair of message numbers, the fi rst for the ON state and the second for the OFF state of the comparator. These numbers are used by the system to reference a message on the ON/OFF Units Message Screen. For example, the comparator might be set up to come on when the outside air temperature is below 55 °F for economizer operation. Set up the On/Off Message Screen so that message #3 is “ECON” and message #4 is “REFRIG.” The “On Message” number would be “3” (ECON), and the “OFF Message” number would be “4” (REFRIG).
WCC III Technical Guide
3-17
WCC3.EXE SCREEN DESCRIPTIONS
Analog Input Pulse Screen
Analog Input Screen’s WCC III Logical Address is XXXAY, where XXX = Satellite Address, A = Analog Input, and Y = 1-8
ANALOG INPUT PULSE SCREEN
Satellite # _______
Specifi es the number of the satellite which you are currently editing. If you would like to edit a different satellite, use the arrow keys to move the cursor to this fi eld, type in the desired satellite number, and press
Analog Input # ________
This “fi eld” actually contains two separate fi elds. The fi rst fi eld specifi es the point “type” (i.e., analog input, control output, analog output, etc.) and displays the current type in textual form. Because this is a “choice” fi eld, the list of available choices will be displayed at the bottom of the screen:
<ANALOG INPUT, CONTROL OUTPUT, ANALOG OUTPUT,
TREND LOGGING, LOGIC SWITCH, BINARY OUTPUT>
You may make your selection by pressing the <space bar> until the desired choice appears and then pressing <Enter>. (If you select a point type that is different than that currently being displayed, the screen will be rewritten with the appropriate screen and data.)
<Enter>.
Additionally, this fi eld specifi es the point number to edit. For the Analog Input Screen, this number can range from one to eight, corresponding from A1 to A8, respectively. If you would like to edit a different point, move the cursor to this fi eld by using the arrow keys, enter the desired point number, and press
Description:
A short message is entered here which is displayed on Summary Screens to help you remember points within the system. You
may enter up to ten characters (control codes, ALT codes, and the double quote character are not allowed).
Type: Pulse
This fi eld is automatically fi lled in by the system. On screens 2-8, this will always read “ANALOG.” On screen number 1, it will read either “ANALOG” or “PULSE” depending on the position of the pulse switch on the satellite controller.
Pulse specifi es the calibration information for the pulse meter connected to channel 1 of the satellite controller.
<Enter>.
3-18
WCC III Technical Guide
WCC3.EXE SCREEN DESCRIPTIONS
Analog Input Pulse Screen
Pattern for Values Associated With This Input:
Specifi es where you would like the decimal point to appear in the value displayed by the system. Because this is a “choice” fi eld, a list of available choices will be displayed at the bottom of the screen:
< x,xxx , xxx.x , xx.xx , x.xxx > You may make your selection by pressing the <space bar>
until the desired data pattern has been selected and then pressing
<Enter>.
Units of Measure Message #: 2
A number is entered here that references a message on the On/Off Units Messages Screen. For example, if units-of-measure message
#2 is “Deg F,” entering “2” will cause “Deg F” to be displayed as the units-of-measure for the analog input.
100 Pulses = 120 KW Hours
If the screen type is “ANALOG,” this specifi es the scaling information used by the system to proportionally scale the input value to the desired range. The raw input value to the satellite controller ranges from zero to one volt. If the scaling information has been set to 0 at 0% scale, and 100 at Full scale, a raw input value of 0.6 volts would produce a scaled value of 60.
If the screen type is “PULSE,” this specifi es the calibration information for the pulse meter connected to channel 1 of the satellite controller.
_______ Pulses = _______ Hours
The fi rst input is a “choice” fi eld, and therefore a list of available choices will be displayed at the bottom of the screen.
Filter Time Constant: ____ Seconds
Specifi es the sampling rate of the analog input. This is used by the satellites to “fi lter” (or smooth) the analog input signal. This can be used on inputs that “jump around” to reduce sporadic load control. Because this is a “choice” fi eld, the list of available choices will be displayed at the bottom of the screen:
< 0, 1, 2, 4, 8, 16, 32, 64 >
You may make your selection by pressing the <space bar> until the desired fi lter time constant has been selected and then pressing
<Enter>.
------ALARMS------
Controlled by:
Specifi es the binary value that selects the ON or OFF alarm limits. When this value is OFF , the OFF alarm limits are selected; when it is ON, the ON alarm limits are selected.
Alarm Type:
Specifi es the priority (or “importance”) level for any alarms generated by this input. Alarm types range from one (highest priority) to eight (lowest priority). The system displays and e-mails higher priority alarms fi rst. (The fi rst fi ve alarm priorities (1-5) have e-mail-out-on-alarm capabilities.)
Alarm Message # Low: ___ High: ___
Specifi es a pair of message numbers, one for LOW alarms and the second for any HIGH alarms. These numbers are used by the system to reference a message which is entered on the Alarm Message Screen.
< 100, 1000 >
You may make your selection by pressing the <space bar> until the desired amount of pulses has been selected and then pressing
<Enter>.
The second input is used to “scale” or “calibrate” the particular sensor that is being used. For example, consider a pulse meter which measures the kwh of a building. Electrical meters are basically a small motor whose speed is proportional to power being used. Let’s consider a meter where one revolution equals one kwh, and the meter sends 5 pulses to the satellite controller for every 6 revolutions. Therefore, we would enter “100 Pulses = 120 kwh Hours.” (NOTE: maximum pulse rate allowed = 4 pulses per second.)
5 pulses = 6 revolutions 1 revolution = 1 kwh 5 pulses = 6 kwh 100 pulses = 120 kwh
WCC III Technical Guide
Alternate Limits Selected By:
Specifi es the point that initiates the Alternate mode. When this address is zero (or OFF), the Normal alarm limits are selected; when it is one (or ON), the Alternate alarm limits are selected.
Limits Low High On _____ _____ °. F Off _____ _____ °. F On (alt) _____ _____ °. F Off (alt) _____ _____ °. F Local Set _____ _____ °. F
This group of inputs specifi es the alarm limits for the “Normal,” “Alternate,” and “Local Set” modes. Each mode has a LOW and HIGH limit. When the value of the analog input goes out of these limits, an alarm is generated, and the alarm will automatically display and e-mail out.
3-19
WCC3.EXE SCREEN DESCRIPTIONS
Analog Input Pulse Screen
There are two fi elds on this screen that determine which set of limits are active—the status of the “Controlled by” fi eld and the status of the “Alternate Limits selected by” fi eld. When the value that has been input in the “Controlled by” fi eld is ON, either the “On” limits or the “On (Alt)” limits are active depending on the status of the value input in the “Alternate Limits selected by” fi eld. If the value in the “Alternate” fi eld is On, the “On (Alt)” limits are used, and when the “Alternate” value is OFF, the “On” limits are used.
Alternate Limits Active Alarm Controlled by: Selected by: Limits:
On Off On On On On (Alt) Off Off Off Off On Off (Alt)
The local set alarm limits become active if the MCD quits communicating with the satellite controller. After communications are re-established, any alarms that occurred while the satellite was in local set will be reported.
Limit overlap time after control change:
This specifi es the amount of time the WCC software will wait after a control change (i.e., on/off schedule, alternate mode, local set mode) before deciding to generate an alarm. The fi rst input is a user-entered number from 1 to 60, and the second input is either seconds or minutes. This second input is a “choice” fi eld; the list of available choices will be displayed at the bottom of the screen:
<Seconds, Minutes>
------ BINARY SETPOINTS ------
____Above:____ ____Below:____
These inputs are used to convert the analog signal to a binary (On/ Off) signal. The value that is going ON and OFF is a software point referred to as a comparator. Each analog input has a comparator associated with it named “Cn.” The comparator for analog input #1 is “C1,” analog input number 2 is “C2,” and so on. The status of the comparator can be seen on the Analog Input Summary Screen.
When the user has selected:
OFF Above & OFF Below:
OFF Above & ON Below:
ON Above & OFF Below:
ON Above & ON Below:
The value of the comparator is:
OFF when the Analog Input value is greater than the ABOVE setpoint or less than the BELOW setpoint, and ON when the Analog Input value is equal to either one or between the two setpoints.
OFF when the Analog Input value is greater than or equal to the ABOVE setpoint or until the Analog Input value becomes less than the BELOW setpoint, and ON when the Analog Input value is less than or equal to BELOW setpoint or until the Analog Input value becomes greater than the ABOVE setpoint.
OFF when the Analog Input value is less than or equal to the BELOW setpoint or until the Analog Input value becomes greater than the ABOVE setpoint, and ON when the Analog Input value is greater than or equal to the ABOVE setpoint or until the Analog Input value becomes less than the BELOW setpoint.
OFF when the Analog input value is equal to either one or between the two setpoints, and ON when the Analog Input value is greater than the ABOVE setpoint or less than the BELOW setpoint.
3-20
Because this is a “choice” fi eld, a list of available choices will be displayed at the bottom of the screen:
<ON, OFF>
You may make your selection by pressing the <space bar> until the desired choice is selected and then pressing
On Message #: Off Message #:
<Enter>.
Specifi es a pair of message numbers, the fi rst for the ON state and the second for the OFF state of the comparator. These numbers are used by the system to reference a message on the ON/OFF Units Message Screen. For example, the comparator might be set up to come on when the outside air temperature is below 55 °F for economizer operation. Set up the On/Off Message Screen so that message #3 is “ECON” and message #4 is “REFRIG.” The “On Message” number would be “3” (ECON), and the “OFF Message” number would be “4” (REFRIG).
WCC III Technical Guide
WCC3.EXE SCREEN DESCRIPTIONS
Analog Input Thermistor Screen
Analog Input Screen’s WCC III Logical Address is XXXAY, where XXX = Satellite Address, A = Analog Input, and Y = 1-8
ANALOG INPUT THERMIST OR SCREEN
Satellite # _______
Specifi es the number of the satellite which you are currently editing. If you would like to edit a different satellite, use the arrow keys to move the cursor to this fi eld, type in the desired satellite number, and press
Analog Input # ________
This “fi eld” actually contains two separate fi elds. The fi rst fi eld specifi es the point “type” (i.e., analog input, control output, analog output, etc.) and displays the current type in textual form. Because this is a “choice” fi eld, the list of available choices will be displayed at the bottom of the screen:
<ANALOG INPUT, CONTROL OUTPUT, ANALOG OUTPUT,
TREND LOGGING, LOGIC SWITCH, BINARY OUTPUT>
You may make your selection by pressing the <space bar> until the desired choice appears and then pressing <Enter>. (If you select a point type that is different than that currently being displayed, the screen will be rewritten with the appropriate screen and data.)
<Enter>.
Additionally, this fi eld specifi es the point number to edit. For the Analog Input Screen, this number can range from one to eight, corresponding from A1 to A8, respectively. If you would like to edit a different point, move the cursor to this fi eld by using the arrow keys, enter the desired point number, and press
Description:
A short message is entered here which is displayed on Summary Screens to help you remember points within the system. You
may enter up to ten characters (control codes, ALT codes, and the double quote character are not allowed).
Type: Analog Thermistor
This fi eld is automatically fi lled in by the system. On screens 2-8, this will always read “ANALOG.” On screen number 1, it will read either “ANALOG” or “PULSE” depending on the position of the pulse switch on the satellite controller.
<Enter>.
WCC III Technical Guide
3-21
WCC3.EXE SCREEN DESCRIPTIONS
Analog Input Thermistor Screen
Sensor Type
This is a choice fi eld for Analog types only. A list of available choices will be displayed at the bottom of the screen:
<General, Thermistor, Resistor,
Resistor+, RawCount, Thermistor+>
You may make your selection by pressing the <space bar> until the desired Analog Type has been selected and then pressing
<Enter>.
Thermistor = Used to setup WattMaster 10K type 3 curve thermistors.
NOTE: The associated analog input jumper on the satellite
controller must also be set to “THERM” in order for this screen to display the proper temperature value.
Pattern for Values Associated With This Input:
Specifi es where you would like the decimal point to appear in the value displayed by the system. Because this is a “choice” fi eld, a list of available choices will be displayed at the bottom of the screen:
< x,xxx , xxx.x , xx.xx , x.xxx >
You may make your selection by pressing the <space bar> until the desired data pattern has been selected and then pressing
<Enter>.
Degree Type:
Specifi es how you would like the temperature displayed, in Fahrenheit or Celsius. Because this is a “choice” fi eld, a list of available choices will be displayed at the bottom of the screen:
< ºF, ºC >
You may make your selection by pressing the <space bar> until the desired temperature choice has been selected and then pressing
<Enter>.
Offset:
There is an option to change the calibration of a thermistor sensor (Usually due to the position or location of the thermistor sensor) a few degrees plus or minus from the actual temperature that the thermistor sensor is actually reading. Acceptable values in this eld are numerical with both positive and negative (+/-) values.
Units of Measure Message #: 1
A number is entered here that references a message on the On/Off Units Messages Screen. For example, if units-of-measure message
#1 is “Deg F,” entering “1” will cause “Deg F” to be displayed as the units-of-measure for the analog input.
Filter Time Constant: ____ Seconds
Specifi es the sampling rate of the analog input. This is used by the satellites to “fi lter” (or smooth) the analog input signal. This can be used on inputs that “jump around” to reduce sporadic load control. Because this is a “choice” fi eld, the list of available choices will be displayed at the bottom of the screen:
< 0, 1, 2, 4, 8, 16, 32, 64 >
You may make your selection by pressing the <space bar> until the desired fi lter time constant has been selected and then pressing
<Enter>.
------ALARMS------
Controlled by:
Specifi es the binary value that selects the ON or OFF alarm limits. When this value is OFF , the OFF alarm limits are selected; when it is ON, the ON alarm limits are selected.
Alarm Type:
Specifi es the priority (or “importance”) level for any alarms generated by this input. Alarm types range from one (highest priority) to eight (lowest priority). The system displays and e-mails higher priority alarms fi rst. (The fi rst fi ve alarm priorities (1-5) have e-mail-out-on-alarm capabilities.)
Alarm Message # Low: ___ High: ___
Specifi es a pair of message numbers, one for LOW alarms and the second for any HIGH alarms. These numbers are used by the system to reference a message which is entered on the Alarm Message Screen.
3-22
Alternate Limits Selected By:
Specifi es the point that initiates the Alternate mode. When this address is zero (or OFF), the Normal alarm limits are selected; when it is one (or ON), the Alternate alarm limits are selected.
WCC III Technical Guide
WCC3.EXE SCREEN DESCRIPTIONS
Analog Input Thermistor Screen
Limits Low High On _____ _____ °. F Off _____ _____ °. F On (alt) _____ _____ °. F Off (alt) _____ _____ °. F Local Set _____ _____ °. F
This group of inputs specifi es the alarm limits for the “Normal,” “Alternate,” and “Local Set” modes. Each mode has a LOW and HIGH limit. When the value of the analog input goes out of these limits, an alarm is generated, and the alarm will automatically display and e-mail out.
There are two fi elds on this screen that determine which set of limits are active—the status of the “Controlled by” fi eld and the status of the “Alternate Limits selected by” fi eld. When the value that has been input in the “Controlled by” fi eld is ON, either the “On” limits or the “On (Alt)” limits are active depending on the status of the value input in the “Alternate Limits selected by” fi eld. If the value in the “Alternate” fi eld is On, the “On (Alt)” limits are used, and when the “Alternate” value is OFF, the “On” limits are used.
Alternate Limits Active Alarm Controlled by: Selected by: Limits:
On Off On On On On (Alt) Off Off Off Off On Off (Alt)
The local set alarm limits become active if the MCD quits communicating with the satellite controller. After communications are re-established, any alarms that occurred while the satellite was in local set will be reported.
Limit overlap time after control change:
This specifi es the amount of time the WCC software will wait after a control change (i.e., on/off schedule, alternate mode, local set mode) before deciding to generate an alarm. The fi rst input is a user-entered number from 1 to 60, and the second input is either seconds or minutes. This second input is a “choice” fi eld; the list of available choices will be displayed at the bottom of the screen:
<Seconds, Minutes>
------ BINARY SETPOINTS ------
____Above:____ ____Below:____
These inputs are used to convert the analog signal to a binary (On/ Off) signal. The value that is going ON and OFF is a software point referred to as a comparator. Each analog input has a comparator associated with it named “Cn.” The comparator for analog input #1 is “C1,” analog input number 2 is “C2,” and so on. The status of the comparator can be seen on the Analog Input Summary Screen.
When the user has selected:
OFF Above & OFF Below:
OFF Above & ON Below:
ON Above & OFF Below:
ON Above & ON Below:
Because this is a “choice” fi eld, a list of available choices will be displayed at the bottom of the screen:
You may make your selection by pressing the <space bar> until the desired choice is selected and then pressing
On Message #: Off Message #:
Specifi es a pair of message numbers, the fi rst for the ON state and the second for the OFF state of the comparator. These numbers are used by the system to reference a message on the ON/OFF Units Message Screen. For example, the comparator might be set up to come on when the outside air temperature is below 55 °F for economizer operation. Set up the On/Off Message Screen so that message #3 is “ECON” and message #4 is “REFRIG.” The “On Message” number would be “3” (ECON), and the “OFF Message” number would be “4” (REFRIG).
The value of the comparator is:
OFF when the Analog Input value is greater than the ABOVE setpoint or less than the BELOW setpoint, and ON when the Analog Input value is equal to either one or between the two setpoints.
OFF when the Analog Input value is greater than or equal to the ABOVE setpoint or until the Analog Input value becomes less than the BELOW setpoint, and ON when the Analog Input value is less than or equal to BELOW setpoint or until the Analog Input value becomes greater than the ABOVE setpoint.
OFF when the Analog Input value is less than or equal to the BELOW setpoint or until the Analog Input value becomes greater than the ABOVE setpoint, and ON when the Analog Input value is greater than or equal to the ABOVE setpoint or until the Analog Input value becomes less than the BELOW setpoint.
OFF when the Analog input value is equal to either one or between the two setpoints, and ON when the Analog Input value is greater than the ABOVE setpoint or less than the BELOW setpoint.
<ON, OFF>
<Enter>.
WCC III Technical Guide
3-23
WCC3.EXE SCREEN DESCRIPTIONS
Analog Input Screen
3-24
WCC III Technical Guide
WCC3.EXE SCREEN DESCRIPTIONS
Analog Input Screen
REV. 0
YS101724
RV2
RV1
2 WIRE THERMISTOR TYPE - Thermistor Scaling Factor FLUSHMOUNT SENSOR (WM PART # OE210)
10K OHM
TYPE 3 THERMISTOR
TB1
TM
R1
GND
AUX OUT
T
SHLD
R
TB2
C1
S1
P1
CONNECTIONS ON
SAT III CONTROLLER
1TO 8
1TO 8
+V
AT I
NONE LOAD RESISTOR
GND
V
OUT
JOX
THERM
Identify the Sensor Circuit Board YS# YS101724
0-10V 0-5V 0-1V
ANALOG INPUT SCALING - From Sat Analog Input Screen Description: Type: Thermistor Pattern for values associated with this input: xxx.x Degree Type: F Units of measure message#: 1
An Input Load Resistor must not be used. Internally, the SAT III controller calculates the resistance of the thermistor back to a Voltage so that the SAT III controller can calculate the proper temperature. RX corresponds to X = 1 to 8 for the Analog Input load resistor. Example as follows: R1 is for Analog Input #1 (NO RESISTOR SHOULD BE INSTALLED) R8 is for Analog Input #8 (NO RESISTOR SHOULD BE INSTALLED) Testing with an Ohmmeter: Disconnected from the SAT III controller, measure from TMP to GND on the sensor. You should get an ohm meter measurement that corresponds to the Temperature. 10,000 ohms equals 77.0 DegF
Input Jumper must be set to THERM There are berg jumpers that are under the SAT III cover that must be set. JOX corresponds to X = 1 to 8 for the Analog Input jumper. Example: JO1 is for Analog Input #1 JO8 is for Analog Input #8
Filter time constant: 0 Seconds
WCC III Technical Guide
3-25
WCC3.EXE SCREEN DESCRIPTIONS
Analog Input Screen
3 WIRE VOLTAGE TYPE - 0 to 1 Volt Scaling Factor FLUSHMOUNT SENSOR (WM PART # OE222)
YS101545
RV1
+V
TB1
C1
R3
R2
TMP
ATI
GND
AUX
OUT
TB1
U1
R1
C2
REV. 2
RV2
S1
ORANGE WIRE
BROWN
WIRE
VIOLET WIRE
LM-34 Type Temp Sensor
1 TO 8
AT I
NONE LOAD RESISTOR
GND
1 TO 8
V
OUT
ANALOG INPUT SCALING - From Sat Analog Input Screen
Description: Type: Analog General Pattern for values associated with this input: xxx.x Units @ 0 % Scale 0.0 DegF Units of measure message #: 1
@ full scale: 100.0 DegF Filter time constant: 8 Seconds
An Input Load Resistor must not be used to convert the Voltage so that the
SAT III controller can calculate the proper temperature. RX
corresponds to X = 1 to 8 for the Analog Input load resistor. Example as follows: R1 is for Analog Input #1 (NO RESISTOR SHOULD BE INSTALLED) R8 is for Analog Input #8 (NO RESISTOR SHOULD BE INSTALLED) Testing with a voltmeter: Measure from ATI to GND. You should get a voltage measurement that corresponds to the Temperature. 0.72 Volts DC equals 72.0 Deg F
CONNECTIONS ON
SAT III CONTROLLER
Input Jumper must be set to 0-1V There are berg jumpers that are under the SAT III cover that must be set. JOX corresponds to X = 1 to 8 for the Analog Input jumper. Example: JO1 is for Analog Input #1 JO8 is for Analog Input #8
Identify the Sensor Circuit Board YS# YS101545
JOX
THERM 0-10V 0-5V 0-1V
3 WIRE VOLTAGE TYPE - 0 to 5 Volt Scaling Factor FLUSHMOUNT SENSOR (WM PART # OE222)
3-26
+V
TB1
C1
R3
R2
TMP
ATI
GND
AUX
OUT
RV1
REV. 2
YS101545
RV2
TB1
U1
R1
C2
S1
ORANGE WIRE
BROWN WIRE
VIOLET WIRE
LM-34 Type Temp Sensor
1TO 8
AT I
NONE LOAD RESISTOR
GND
1TO 8
V
OUT
ANALOG INPUT SCALING - From Sat Analog Input Screen Description: Type: Analog General Pattern for values associated with this input: xxx.x Units @ 0 % Scale 0.0 Deg F Units of measure message #: 1
@ full scale: 500.0 Deg F Filter time constant: 8 Seconds
An Input Load Resistor must not be used to convert the Voltage so that the SAT III controller can calculate the proper temperature. RX corresponds to X = 1 to 8 for the Analog Input load resistor. Example as follows: R1 is for Analog Input #1 (NO RESISTOR SHOULD BE INSTALLED) R8 is for Analog Input #8 (NO RESISTOR SHOULD BE INSTALLED) Testing with a voltmeter: Measure from ATI to GND. You should get a voltage measurement that corresponds to the Temperature. 0.72 Volts DC equals 72.0 Deg F
CONNECTIONS ON
SAT III CONTROLLER
Identify the Sensor Circuit Board YS# YS101545
JOX
THERM 0-10V 0-5V 0-1V
Input Jumper must be set to 0-5V There are berg jumpers that are under the SAT III cover that must be set. JOX corresponds to X = 1 to 8 for the Analog Input jumper. Example: JO1 is for Analog Input #1 JO8 is for Analog Input #8
WCC III Technical Guide
Loading...
+ 168 hidden pages