WattMaster WCC III User Manual part 11

11. WCC III Alarming
WCC III
11. WCC III Alarming
T ABLE OF CONTENTS
SECTION 11: WCC III ALARMING
Alarm Call-Out .......................................... 11-1
Run Time Alarm ........................................11-2
Satellite SOS Alarm .................................11-3
TUC TOS Alarm .........................................11-3
Alarm Logs ................................................11-3
Sending a Text Message to a Cell Phone via an Email from the
WCC III System ......................................... 11-4
Analog Global and Binary Global
Alarms ....................................................... 11-5
ALARM MESSAGES SCREEN .....................11-6
ALARM SUMMARY SCREEN ...................... 11-7
SYSTEM PARAMETERS SCREEN ..............11-8
11. WCC III ALARMING
Alarm Call-Out
SECTION 11: WCC III ALARMING
__________________________________________
Alarm Call-Out
The WCC III - MCD will automatically E-mail an alarm or alarms to an E-mail address or to multiple E-mail addresses. There are eight different alarm types or alarm classes - each with their own priorities. Only the fi rst fi ve alarm types or classes can “E-mail out”; each of these fi ve alarm types can E-mail up to 12 separate E-mail addresses. You could also send an E-mail to Text message your cell phone, depending on your service plan with your cellular phone provider.
ANALOG INPUT SCREEN
Analog Alarm Limit
Each analog input on a satellite can have a low and high limit assigned to it on the Analog Input Screen. If the value of the analog input falls below the low limit or rises above the high limit, the system automatically generates an alarm.
For example, assume that the analog input in question is a room temperature sensor located in an offi ce space. If the space temperature falls below 68 °F or rises above 80 °F during the occupied period, we want an alarm to be generated. To set up the alarm limits, fi rst sign on by accessing the System Parameters Screen and entering your password. An access level of 1 or greater is required to enter or change alarm limits. An access level of 2 or greater is required to enter or change what the alarm is controlled by, the alarm type, and the alarm messages. After you are signed on, return to the Main Menu, place the cursor over “ANALOG INPUT” and press <Enter>. Then place the cursor over one of the eight analog inputs and press <Enter>. An Analog Input Screen similar to what is shown in Figure 1 1-1 should come into view:
Satellite # 1 ANALOG INPUT # 1
Description: RM101 Type: Analog General Pattern for values associated with this input: xxx.x Units @ 0% scale: 0.0 DEG. Units of Measure message #: 1 @ full scale: 100.0 DEG. Filter time constant: 8 seconds
ALARMS Controlled by: W1 Limits Low High Alarm Type: 1 On 65.0 80.0 DEG. Alarm Message #’s: Low 2 High 1 Off 50.0 100.0 DEG.
Alternate limits selected by: .... On (alt) 0.0 0.0 DEG.
Off (alt) 0.0 0.0 DEG.
Limit overlap time after control change: 20 minutes Local set 55.0 90.0 DEG.
BINARY SETPOINT OFF Above 0.0 DEG. On Message #: 0 OFF Below 0.0 DEG. Off Message #: 0
HOME for menu
Figure 11-1: Analog Input Screen
WCC III Technical Guide
11-1
11. WCC III ALARMING
Run Time Alarm
The alarm limits along with the alarm type and alarm message numbers are assigned on this screen (see the Analog Input Screen in Section 3 of this guide for more information). If the space temperature drifts out of the entered alarm limits, the system will automatically generate an alarm. For example, assume that the space temperature rises above the high limit value of 80 °F . Alarm message #1 (High T emperature) along with the time and date of the alarm and the high peak value of the room temperature will appear on the Analog Input Summary Screen and the Alarm Summary Screen. Within one minute from the time the alarm appears on the screen, it will automatically be e-mailed if enabled.
To acknowledge alarms, select <Action> from the Top Menu Bar and then select <Acknowledge Alarm> or <Acknowledge All
Alarm> described in the Action Menu, Analog Input Summary
Screen, and Alarm Summary Screen in Section 3 - Screen
Descriptions.
NOTE: The <Acknowledge All Alarms> option will
only work on the Alarm Summary Screen.
Run Time Alarm
The WCC III system also has the capability of alarming if the total ON time of a binary (on/off) value has exceeded the run time alarm limit. T o assign a run time alarm limit, fi rst sign on by accessing the System Parameter Screen and entering your password. An access level of 2 or greater is required to enter or change alarm limits. After you are signed on, return to the Main Menu and place the cursor over “TREND LOGS” and press <Enter>. The Trend Log
Summary Screen should come into view. To access a Run Time Trend Logging Screen, use the arrow keys to place the cursor (>)
by the desired run time point and press <Enter>. The following screen should come into view (Figure 1 1-2):
In this example screen, we are recording the total “ON” time of contact KlH (COM to H contact closure) on satellite controller #1. When contact KlH is closed, or “ON”, Fan #1 runs. Run time recorder #1 records total accumulated run time of the fan. Alarm message #7 (Grease Bearings) will automatically appear on the Alarm Summary Screen when the total accumulated run time of the fan exceeds 500 hours. Within one minute after the alarm appears on the screen, it will automatically e-mail if enabled. (See the Alarm Summary Screen in Section 3 for information about how to acknowledge a run time alarm, and see the Run Time Trend Logging Screen in Section 3 for information about how to reset the accumulated run time to zero.)
SA T RUN TIME TREND LOG SCREEN
Satellite # 1 TREND LOGGING # 1 of Type: RUN TIME
Records total ON time Starting at : *:* on */* for Klh S1-Kh Reset by: //// being ON
Alarm Type: 5 Alarm Message #: 7 Current run time: 1871 Hours Alarm Limit: 500 Hours
HOME for menu
Figure 11-2: SAT Run Time Trend Logging Screen
11-2
WCC III Technical Guide
11. WCC III ALARMING
Alarm Logs
Satellite SOS Alarm
If the Master Communications Device loses communications with a satellite controller, a Satellite SOS Alarm on the Satellite Summary Screen will state which satellite is out of service.
TUC TOS Alarm
If for some reason the SA T3C/D/F controller loses communications with its loop of TUC controllers, then the Satellite will report back to the WCC III – MCD that there are TUCs OFF SYSTEM with a TOS alarm on the Satellite Summary Screen. There is a series of minus’s (-) and asterisks (*) that show which TUCs are communicating. The minus’s (-) represent missing or non­existent TUCs and the asterisks (*) are TUCs that are currently communicating.
WCC III Auto System Logging
The WCC III auto system logging features are logged by the Backtask.exe program, and these log fi les are then stored on the hard drive of the WCC III - MCD. These log fi les may then be retrieved by using the WCCUtility.exe program. The WCC III automatic system logging features are defi ned as the following: System Log, Alarm Log, Data Log, Acknowledge Alarms Log, System Event Log, and MCD Comm Error Log. These log fi les are described in detail in Section 5.
WCC III System Alarm Log
The WCC III System will automatically log an alarm, the alarm type, and the date and time at which the alarm occurred.
WCC III System Data Log
The WCC III System will automatically log any data point that has been changed or overridden, the logged in operator ID that changed it, and the date and time that it was changed.
WCC III System Acknowledge Alarm Log
The WCC III System will automatically log all alarms that have been acknowledged, the logged in operator ID that acknowledged the alarm(s), and the time and date of the acknowledgement.
WCC III System Event Log
The WCC III System will automatically log system events such as new connections through the internet, when a internet connection is closed, E-mails sent out, and satellites found or lost on the Comm loop.
WCC III MCD Communication Error Log
WCC III System Log
The WCC III system will automatically log the operator ID, IP address, time, and date when an operator signs on or off the system.
The WCC III System will automatically log all communication errors between the MCD and the satellites on the communication loop.
WCC III Technical Guide
11-3
Loading...
+ 9 hidden pages