WattMaster WCC III User Manual part 2

1. General Instructions
WCC III
1. General Instructions
T ABLE OF CONTENTS
SECTION 1: GENERAL INSTRUCTIONS
WCC III FEATURES AND MAINTENANCE ....1-1
“Where To Find” Features .....................................................1-1
WCC III SOFTWARE .....................................1-2
WCC III Installation Software CD Information ......................1-2
WCC III Software Version List ..............................................1-2
DATA ENTRY SEQUENCE ............................1-3
Recommended Data Entry Procedure..................................1-3
ANALOG INPUTS .........................................1-3
BINARY INPUTS ..........................................1-4
POINT ADDRESSES .....................................1-8
Point Addresses Table ..........................................................1-8
DATA REGISTERS ........................................ 1-9
Time Clock ............................................................................1-9
EA Driver ............................................................................1-10
Dual Limit............................................................................1-10
ALARMS.....................................................1-11
Alarm Call-Out ....................................................................1-11
Analog Alarm Limit..............................................................1-11
Run Time Alarm ..................................................................1-12
Satellite Fail Alarm ..............................................................1-12
ANALOG OUTPUTS .....................................1-6
BINARY OUTPUTS ......................................1-7
1. GENERAL INSTRUCTIONS
WCC III F eatures and Maintenance
SECTION 1: GENERAL INSTRUCTIONS
____________________________________________________
“Where T o Find” Features
The following is a list of commonly used WCC III features and the screens you should access to use them.
FEATURES SCREEN
Alarms
“ E-mail-Out-On-Alarm”
Call “All” or “Either” E-mail Address
Input E-mail Address Clear ( Acknowledge) Alarms Alarm Summary Set Alarm Limits
Analog Inputs
Run Time
Global Analog Values
Global Binary Values View Alarms
All Alarms
Global Alarms
Demand Limiting Shed/Restore Monitor Analog Inputs
(Temperature/Pressure etc.)
Find Highest or Lowest Building
Temp
Find A verage Building Temp
Present V alue
Trend Logs
Monitor Binary Inputs (air fl ow switch etc.)
Present V alue
Trend Log.
Password Entry
Assign Operator Access Codes
“ Sign-On”
“ Sign-Off”.
Schedules
Change Schedules Permanently.
Holiday Schedules
Setpoints
Change Setpoints - Satellite
Change Setpoints - TUC
Sequence Satellites After a Power Outage Satellite Summary Time and Date Modifi cations System Parameters
System Parameters
Analog Input Screen Trend Logs Global Analog Global Binary
Alarm Summary Global Summary
Global Analog-Sort Global Analog-A vg Analog Input Summary Analog Trend
Logic Switches Change of State
Sys Par/Oper Codes System Parameters Secure Screen
Week Schedules Holiday & Week Sch
Control Outputs SCUSCR
WCC III Routine Maintenance
The following maintenance items should be performed on a regular basis:
Service Item As
Req’d
Blow out keyboard
Blow out MCD assy
Check all external cable connections
Test/Verify U.P.S. operation
Clean display screen
Dim display screen
Clean fl oppy drive
Test fl oppy drive
Test MCD memory
Test display monitor
Test modem (system’s ability to e-mail-out-on­alarm)
Delete “back­up” (*.bak) les
Make “back­up” copies of program
Check disks for available space to prevent overfi lling the disk
Check loop connection on rear of MCD
Every WkEvery MoEvery
3 Mo
XX
XX
XX
XX
*X
XX
XX
XX
XX
XX
Every
6 Mo
X
X
X
X
X
Every
12 Mo
WCC III Technical Guide
1-1
1. GENERAL INSTRUCTIONS
WCC III Software
Service Item As
Req’d
Save satellite data to disk
Test satellites’ local-set capability
Test satellites’ battery (or capacitor)
Check/Reset trend logs
View/Clear all alarms
Cycle power to MCD to verify correct system re-start after a power outage
Every WkEvery MoEvery
3 Mo
XX
XX
XX
Every
X
6 Mo
Every
12 Mo
X
X
* Set the screen’s intensity to the lowest setting when the system is not being used.
WCC III Installation Software CD Information
There are three available CD-ROMs available from WattMaster Controls, Inc. - either from the factory or downloadable from the wcc-controls.com website. They are as follows:
WattMaster Part # DM1WC011-01X*
This is the contractor installation CD for the main WCC III System. This CD installs the following programs:
WCC3.EXE(SS5021), SCUSCR.EXE(SS5026), WCCUTILITY.EXE(SS5023), TENANTOVERRIDE. EXE(SS5024),TENANTREPORT.EXE(SS5025), WCC3TRENDLOG.EXE(SS5028), WGCC3. EXE(SS5029),WCC3DOWNLOAD.EXE(SS5030), WCC3GUEST.EXE(SS5022).
WattMaster Part # DM1WC012-01X*
This is the end-user installation CD for “View Only” versions of the WCC III system. This CD only installs the following programs: WCC3GUEST .EXE(SS5022) and SCUSCRLtd.EXE(SS5027).
WattMaster Part # DM1WC013-01X*
This is the end-user installation CD for the Tenant Override program. This CD only installs the following programs: TENANTOVERRIDE.EXE(SS5024).
* = Where “X” is the software version A to Z.
WCC III Software Version List
The WCC III software is updated periodically to include more features. The two fi les that change as the WCC III system is upgraded are the WCC III fi le and the BACKTASK fi le. When a WCC III fi le is installed in a system, the BACKTASK fi le may need to be changed also. The Backtask software is located in the MCD.
NOTE: Y ou can see the present WCC III and BA CKT ASK
version used by the system by looking at the lower left hand corner of the Main Menu Screen.
1-2
WCC III Technical Guide
1. GENERAL INSTRUCTIONS
8
7
SATADDRESS
2 1
4
8
A3 WIRE ROOM SENSOR WILL NOT REQUIREA LOAD RESISTORWHEN SET FORA 1 VOLTINPUT.
WattMasterControls Inc.
BINARY INPUTS
BINARY INPUTS
L8
ON OFF
128
32 16
64
L4 L3 L2 L1
L6 L5
L7
L11
L12
ON OFF
L10 L9
ON OFF
L15
L16
L14 L13
CH
4
3
5 6
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCALSET
LOCALSET DISABLE
BATTON/ OFF PULSE INPUT
OPTION 1
TEST
OPTION 3 OPTION 2
ON OFF
STATUS
HSS REC
SATXMIT
SATREC
ANALOG INPUT
JUMPER SELECTION
A2 WIRE ROOM SENSOR WILL REQUIRE A300 OHM LOAD RESISTOR WHEN SET FORA 1 VOLTINPUT.
A4 TO 20 mASENSOR WILL REQUIRE A 50OHM LOAD RESISTOR WHEN SET FOR A1 VOLTINPUT, OR A 250 OHM LOAD RESISTORWHEN SET FOR A5 VOLT INPUT.
CURRENT INPUT
THERMISTOR INPUT
0-1V
0-5V
0- 10V
THERM
0-1V
0-5V
0- 10V
THERM
0 TO10V INPUT
0TO5V INPUT
0TO1V INPUT
0- 10V
0-1V
0-5V
0- 10V
THERM
0-1V
0-5V
THERM
0-1V
0-5V
0- 10V
THERM
PROGRAMMABLECONTROLLER
SAT III
H
C
COM
CHANNEL
2134
2134
567
8
5678
V
OUT
GND
L O A D
+V
ATI
Jumper
Data Entry Sequence and Analog Inputs
Recommended Data Entry Procedure
When setting up an WCC III system, the screens can be programmed in any order. However, you may fi nd it easier to follow this sequence:
1. Make Back-Up Copies of the Program/Data Files.
2. System Parameter Screen
3. Satellite Summary Screen
4. On/Off Units Messages Screen / Alarm Message Screen —Enter the On/Off messages, units of measure messages, and alarm messages, and then print a copy of the messages. Keep a copy of these messages handy while entering data on the remaining screens.
5. W eek Schedule Screens
6. Holiday Screen
7. Analog Input Screens
8. Logic Switch Screens
9. Control Output Screens
10. TUC Screens
11. Analog Output Screens
Analog Inputs
An analog input is a numerical value (signal) sent from the SAT III controller to allow monitoring of space temperatures, duct pressures etc. The SAT III controller can accept 8 analog inputs which are named, A1-A8. (NOTE: A1-A8 may be either analog or binary inputs.) On certain screens (such as Global Analog Screens), you must indicate the satellite controller number along with the channel on the satellite controller. For example, 12A2 means satellite controller #12 analog input number 2.
The analog inputs are usually wired to the “+V” and “A TI” (Actual Temperature In) terminals on the SAT III controller (three wire sensors are wired to the “GND” terminal also.) The “+V” terminal on channels 1-7 are a 12 VDC power source. The “+V” terminal on channel 8 provides either 12 VDC or 24 VDC depending on the position of the jumper under the cover near channel 8. To get 12 VDC from the “+V” terminal on channel 8, the jumper must connect the 12 volt and center terminals. To get 24 VDC, the jumper must connect the 24 volt and center terminals.
A thermistor and 20 mA sensor can be used on the SAT III controller. You choose the type of sensor to be used by selecting the appropriate jumper (located under the SAT III cover). The choices are Thermistor, 0-10 V, 0-5 V, 0-1 V and Jumper A1 used J01, A2 used J02 and so on up to A8 uses J08.
12. Analog Global Screens
13. Binary Global Screens
14. Optimal Start Screens
15. Shed/Restore Screens
16. Duty Cycle Screens
17. Proportional Reset Screens
18. Energy Consumption Screens
19. Trend Log Screens
20. Save Satellite Data to Disk
21. Make Back-Up Copies of the Program/Data Files.
WCC III Technical Guide
(Under Cover)
1-3
Loading...
+ 9 hidden pages