WattMaster WCC III User Manual part 2

1. General Instructions
WCC III
1. General Instructions
T ABLE OF CONTENTS
SECTION 1: GENERAL INSTRUCTIONS
WCC III FEATURES AND MAINTENANCE ....1-1
“Where To Find” Features .....................................................1-1
WCC III SOFTWARE .....................................1-2
WCC III Installation Software CD Information ......................1-2
WCC III Software Version List ..............................................1-2
DATA ENTRY SEQUENCE ............................1-3
Recommended Data Entry Procedure..................................1-3
ANALOG INPUTS .........................................1-3
BINARY INPUTS ..........................................1-4
POINT ADDRESSES .....................................1-8
Point Addresses Table ..........................................................1-8
DATA REGISTERS ........................................ 1-9
Time Clock ............................................................................1-9
EA Driver ............................................................................1-10
Dual Limit............................................................................1-10
ALARMS.....................................................1-11
Alarm Call-Out ....................................................................1-11
Analog Alarm Limit..............................................................1-11
Run Time Alarm ..................................................................1-12
Satellite Fail Alarm ..............................................................1-12
ANALOG OUTPUTS .....................................1-6
BINARY OUTPUTS ......................................1-7
1. GENERAL INSTRUCTIONS
WCC III F eatures and Maintenance
SECTION 1: GENERAL INSTRUCTIONS
____________________________________________________
“Where T o Find” Features
The following is a list of commonly used WCC III features and the screens you should access to use them.
FEATURES SCREEN
Alarms
“ E-mail-Out-On-Alarm”
Call “All” or “Either” E-mail Address
Input E-mail Address Clear ( Acknowledge) Alarms Alarm Summary Set Alarm Limits
Analog Inputs
Run Time
Global Analog Values
Global Binary Values View Alarms
All Alarms
Global Alarms
Demand Limiting Shed/Restore Monitor Analog Inputs
(Temperature/Pressure etc.)
Find Highest or Lowest Building
Temp
Find A verage Building Temp
Present V alue
Trend Logs
Monitor Binary Inputs (air fl ow switch etc.)
Present V alue
Trend Log.
Password Entry
Assign Operator Access Codes
“ Sign-On”
“ Sign-Off”.
Schedules
Change Schedules Permanently.
Holiday Schedules
Setpoints
Change Setpoints - Satellite
Change Setpoints - TUC
Sequence Satellites After a Power Outage Satellite Summary Time and Date Modifi cations System Parameters
System Parameters
Analog Input Screen Trend Logs Global Analog Global Binary
Alarm Summary Global Summary
Global Analog-Sort Global Analog-A vg Analog Input Summary Analog Trend
Logic Switches Change of State
Sys Par/Oper Codes System Parameters Secure Screen
Week Schedules Holiday & Week Sch
Control Outputs SCUSCR
WCC III Routine Maintenance
The following maintenance items should be performed on a regular basis:
Service Item As
Req’d
Blow out keyboard
Blow out MCD assy
Check all external cable connections
Test/Verify U.P.S. operation
Clean display screen
Dim display screen
Clean fl oppy drive
Test fl oppy drive
Test MCD memory
Test display monitor
Test modem (system’s ability to e-mail-out-on­alarm)
Delete “back­up” (*.bak) les
Make “back­up” copies of program
Check disks for available space to prevent overfi lling the disk
Check loop connection on rear of MCD
Every WkEvery MoEvery
3 Mo
XX
XX
XX
XX
*X
XX
XX
XX
XX
XX
Every
6 Mo
X
X
X
X
X
Every
12 Mo
WCC III Technical Guide
1-1
1. GENERAL INSTRUCTIONS
WCC III Software
Service Item As
Req’d
Save satellite data to disk
Test satellites’ local-set capability
Test satellites’ battery (or capacitor)
Check/Reset trend logs
View/Clear all alarms
Cycle power to MCD to verify correct system re-start after a power outage
Every WkEvery MoEvery
3 Mo
XX
XX
XX
Every
X
6 Mo
Every
12 Mo
X
X
* Set the screen’s intensity to the lowest setting when the system is not being used.
WCC III Installation Software CD Information
There are three available CD-ROMs available from WattMaster Controls, Inc. - either from the factory or downloadable from the wcc-controls.com website. They are as follows:
WattMaster Part # DM1WC011-01X*
This is the contractor installation CD for the main WCC III System. This CD installs the following programs:
WCC3.EXE(SS5021), SCUSCR.EXE(SS5026), WCCUTILITY.EXE(SS5023), TENANTOVERRIDE. EXE(SS5024),TENANTREPORT.EXE(SS5025), WCC3TRENDLOG.EXE(SS5028), WGCC3. EXE(SS5029),WCC3DOWNLOAD.EXE(SS5030), WCC3GUEST.EXE(SS5022).
WattMaster Part # DM1WC012-01X*
This is the end-user installation CD for “View Only” versions of the WCC III system. This CD only installs the following programs: WCC3GUEST .EXE(SS5022) and SCUSCRLtd.EXE(SS5027).
WattMaster Part # DM1WC013-01X*
This is the end-user installation CD for the Tenant Override program. This CD only installs the following programs: TENANTOVERRIDE.EXE(SS5024).
* = Where “X” is the software version A to Z.
WCC III Software Version List
The WCC III software is updated periodically to include more features. The two fi les that change as the WCC III system is upgraded are the WCC III fi le and the BACKTASK fi le. When a WCC III fi le is installed in a system, the BACKTASK fi le may need to be changed also. The Backtask software is located in the MCD.
NOTE: Y ou can see the present WCC III and BA CKT ASK
version used by the system by looking at the lower left hand corner of the Main Menu Screen.
1-2
WCC III Technical Guide
1. GENERAL INSTRUCTIONS
8
7
SATADDRESS
2 1
4
8
A3 WIRE ROOM SENSOR WILL NOT REQUIREA LOAD RESISTORWHEN SET FORA 1 VOLTINPUT.
WattMasterControls Inc.
BINARY INPUTS
BINARY INPUTS
L8
ON OFF
128
32 16
64
L4 L3 L2 L1
L6 L5
L7
L11
L12
ON OFF
L10 L9
ON OFF
L15
L16
L14 L13
CH
4
3
5 6
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCALSET
LOCALSET DISABLE
BATTON/ OFF PULSE INPUT
OPTION 1
TEST
OPTION 3 OPTION 2
ON OFF
STATUS
HSS REC
SATXMIT
SATREC
ANALOG INPUT
JUMPER SELECTION
A2 WIRE ROOM SENSOR WILL REQUIRE A300 OHM LOAD RESISTOR WHEN SET FORA 1 VOLTINPUT.
A4 TO 20 mASENSOR WILL REQUIRE A 50OHM LOAD RESISTOR WHEN SET FOR A1 VOLTINPUT, OR A 250 OHM LOAD RESISTORWHEN SET FOR A5 VOLT INPUT.
CURRENT INPUT
THERMISTOR INPUT
0-1V
0-5V
0- 10V
THERM
0-1V
0-5V
0- 10V
THERM
0 TO10V INPUT
0TO5V INPUT
0TO1V INPUT
0- 10V
0-1V
0-5V
0- 10V
THERM
0-1V
0-5V
THERM
0-1V
0-5V
0- 10V
THERM
PROGRAMMABLECONTROLLER
SAT III
H
C
COM
CHANNEL
2134
2134
567
8
5678
V
OUT
GND
L O A D
+V
ATI
Jumper
Data Entry Sequence and Analog Inputs
Recommended Data Entry Procedure
When setting up an WCC III system, the screens can be programmed in any order. However, you may fi nd it easier to follow this sequence:
1. Make Back-Up Copies of the Program/Data Files.
2. System Parameter Screen
3. Satellite Summary Screen
4. On/Off Units Messages Screen / Alarm Message Screen —Enter the On/Off messages, units of measure messages, and alarm messages, and then print a copy of the messages. Keep a copy of these messages handy while entering data on the remaining screens.
5. W eek Schedule Screens
6. Holiday Screen
7. Analog Input Screens
8. Logic Switch Screens
9. Control Output Screens
10. TUC Screens
11. Analog Output Screens
Analog Inputs
An analog input is a numerical value (signal) sent from the SAT III controller to allow monitoring of space temperatures, duct pressures etc. The SAT III controller can accept 8 analog inputs which are named, A1-A8. (NOTE: A1-A8 may be either analog or binary inputs.) On certain screens (such as Global Analog Screens), you must indicate the satellite controller number along with the channel on the satellite controller. For example, 12A2 means satellite controller #12 analog input number 2.
The analog inputs are usually wired to the “+V” and “A TI” (Actual Temperature In) terminals on the SAT III controller (three wire sensors are wired to the “GND” terminal also.) The “+V” terminal on channels 1-7 are a 12 VDC power source. The “+V” terminal on channel 8 provides either 12 VDC or 24 VDC depending on the position of the jumper under the cover near channel 8. To get 12 VDC from the “+V” terminal on channel 8, the jumper must connect the 12 volt and center terminals. To get 24 VDC, the jumper must connect the 24 volt and center terminals.
A thermistor and 20 mA sensor can be used on the SAT III controller. You choose the type of sensor to be used by selecting the appropriate jumper (located under the SAT III cover). The choices are Thermistor, 0-10 V, 0-5 V, 0-1 V and Jumper A1 used J01, A2 used J02 and so on up to A8 uses J08.
12. Analog Global Screens
13. Binary Global Screens
14. Optimal Start Screens
15. Shed/Restore Screens
16. Duty Cycle Screens
17. Proportional Reset Screens
18. Energy Consumption Screens
19. Trend Log Screens
20. Save Satellite Data to Disk
21. Make Back-Up Copies of the Program/Data Files.
WCC III Technical Guide
(Under Cover)
1-3
1. GENERAL INSTRUCTIONS
Binary Inputs
Binary Inputs
A binary input is an On/Off (dry contact closure) signal sent to the SAT III controller to allow monitoring of air fl ow switches, switch settings, etc. The SAT III controller comes standard with 16 small switches on its front panel labeled, L1-L16 which are in effect manually controlled binary inputs. The WCC III monitors the On/Off status of these switches and can control and/or alarm based on the position of these switches. The binary input board(s) allow the manual dip switches to be replaced with a terminal strip which accepts wiring from remote mounted binary input devices.
The SAT III controller has two sets of 8 small switches on its front cover labeled L1-L16. Switches L1-L8 are housed together in one module, and switches L9-L16 are housed together in another module. One module of switches is removed for each binary input board and replaced with a ribbon cable which connects the binary input board to the SAT III controller. The binary devices to be monitored are then wired to the terminal strip of the binary input board. The binary input board requires a 24 VAC power supply.
The SAT III can also accept two HSS Binary Input Boards.
1-4
WCC III Technical Guide
1. GENERAL INSTRUCTIONS
8
7
SAT ADDRESS
2 1
4
8
A3 WIR E ROOMSENS OR WILL NOT REQUIREA LOAD RESISTOR WHENSET FORA 1 VOLT I NPUT.
WattMasterControlsInc.
BINARY INPUTS
BINARY INPUTS
L8
ON OFF
128
32 16
64
L4 L3 L2 L1
L6 L5
L7
L11
L12
ON OFF
L10 L9
ON OFF
L15
L16
L14 L13
CH
4
3
5 6
2
1
LOCALSET
STATUS 2
STATUS 3
STATUS 1
HSS XMI T
LOCALSET
LOCALSET DISABLE
BATTON/ OFF PULSEINPUT
OPTION 1
TEST
OPTION 3 OPTION 2
ON OFF
STATUS
HSS RE C
SATXMIT
SATREC
ANALOGI NPUT
JUMPER SELECTION
A2 WIR E ROOMSENSO R WI LL REQUIRE A300 OHM LOAD RESI STOR WHEN SET FORA 1 VOLT I NPUT.
A4 TO 20 mASENSOR WILLREQUIRE A 50OHM LOADRES I STOR WHENSET FOR A1 VOLT INPUT, OR A 250 OHMLOAD RESISTORWHENSET FORA 5VOLT INPUT.
CURRENT INPUT
THERMISTOR INPUT
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
0-10V
THERM
0TO 10V INPUT
0TO5V INPUT
0TO1V INPUT
0-10V
0-1V
0-5V
0-10V
THERM
0-1V
0-5V
THERM
0-1V
0-5V
0-10V
THERM
PROGRAMMAB L E CONT R OL LE R
SAT II I
H
C
COM
CHANNEL
2134
2134
567
8
5678
V
OUT
GND
L O A D
+V
ATI
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
EACHCONTACT ISRATEDFOR 24VACOR VDC @.5AMPMAX
0-15VDC OUTPUT MINL OAD IS1KOHM RESISTIVE VDCONLY
WCC3BI NARY IN W/ T I ME DELAY WATTMASTER CONTROLS, I NC
YS102072REV2
24 VAC 12 0VAC
120VACWIRING BY OTHERS
TO OTHER SAT III ORTO WCCIII - MCD
CONNECTION FROM SAT I II TO BI NARY INPUT BOARD USI NG THE "NEW" HSS CABLE CONNECT IO N MET HOD
HSS CABLE - ORDER STANDARD LENGTHS OF 1 F OOT, 1
1 2
FEET, 3 FEET, 25 FEET, 40 FEET, 80 FEET
DRY INPUT CONTACT S ONLY
24VAC
GND
TO OTHER SAT III ORTO WCCIII - MCD WI R E " T" T O " T " "R" TO"R" "SHD" TO"SHD"
TWOBINARYINPUTBOARDSMAYBEWIREDTO THE SAT II I CONTROLLER USING THI S METHOD. CONNECT THE FI RST ONE TO THE SAT II I HSS
PORT, AND THE SECOND ONE TO THE FI RS T BINARY INPUT BOARDS 2ND HSS PORT.
BINAR Y INPUT BOARD GETS POWER FROM THE HS S CABLE
SEE MANUAL FOR DI P SWITCH SETTINGS
Binary Inputs
WCC III Technical Guide
1-5
1. GENERAL INSTRUCTIONS
Analog Outputs
Analog Outputs
An analog output is a variable DC voltage signal sent from the satellite controller used for proportional control of devices with modulating actuators. The analog outputs are wired to the “ V-Out” and “ Gnd” terminals on the SAT III controller and are named P1­P8. The P stands for Proportional Output.
The SAT III controller has the capability of providing 8 analog output signals which have a maximum range of 0-15 VDC.
V-OUT CONNECTIONS
0-15VDC
OUTPUT MINLOAD IS1K OHM RESISTIVE VDCONLY
EACHCONTACT ISRATED FOR 24VACOR VDC @.5 AMP MAX
5678
2134
CHANNEL
2134
567
VDE
VDE
SA
SA
5A30VDC
5A30VDC
10A250VAC~
10A250VAC~
CHINA
CHINA
DC24V
DC24V
G5Q-1A4
OMRON
G5Q-1A4
OMRON
OMRON
8
VDE
VDE
SA
SA
5A30VDC
5A30VDC
10A250VAC~
10A250VAC~
CHINA
CHINA
DC24V
DC24V
G5Q-1A4
OMRON
G5Q-1A4
Each analog output has a limit of 15 mA. The total current output of all 8 analog outputs must be kept under 115 mA.
The SAT III controller comes standard with 8 analog outputs.
+V
ATI
GND
OUT
COM
L O A D
V
H
C
ON OFF
ON OFF
ON OFF
ON OFF
BATTON/ OFF PULSE INPUT OPTION 3 OPTION 2 OPTION 1 LOCAL SETDISABLE LOCAL SET TEST
L16 L15 L14
BINARY
L13 L12
INPUTS
L11 L10 L9
L8 L7 L6
BINARY
L5 L4
INPUTS
L3 L2 L1
128 64 32 16 8 4 2
SATADDRESS
1
STATUS
SATREC
SATXMIT
HSS REC
HSS XMIT
LOCAL SET
STATUS 1
STATUS 2
STATUS 3
1 2 3 4 5 6 7 8
CH
SAT III
PROGRAMMABLE CONTROLLER
ANALOG INPUT
JUMPER SELECTION
THERM
0TO1V
0- 10V 0-5V
INPUT
0-1V
THERM
0TO5V
0- 10V 0-5V
INPUT
0-1V
THERM
0 TO 10V
0- 10V
INPUT
0-5V 0-1V
THERM 0- 10V
THERMISTOR
0-5V
INPUT
0-1V
THERM 0- 10V
CURRENT
0-5V
INPUT
0-1V
A4 TO 20 mA SENSOR WILLREQUIRE A 50OHM LOAD RESISTOR WHEN SET FOR A1 VOLT INPUT,OR A 250 OHM LOAD RESISTORWHEN SET FOR A 5 VOLTINPUT.
A2 WIRE ROOM SENSOR WILL REQUIRE A300 OHM LOAD RESISTOR WHEN SET FORA 1 VOLTINPUT.
A3 WIRE ROOM SENSOR WILL NOT REQUIREA LOAD RESISTOR WHEN SET FORA 1 VOLTINPUT.
WattMasterControls Inc.
1-6
WCC III Technical Guide
1. GENERAL INSTRUCTIONS
Binary Outputs
Binary Outputs
A binary output on the SAT III controller is the electronic equivalent of a relay contact which is used to complete a circuit to activate on/off devices such as relays, 2-position valves, etc. The binary output contacts can be used to complete a 24 volt DC circuit or 24 volt AC circuit at 1.0 amp maximum load. The binary output terminals are labeled H, COM, and C.
The SAT III controller is capable of providing 16 binary (on/off) outputs.
ON OFF
BATTON/ OFF PULSE INPUT OPTION 3 OPTION 2 OPTION 1 LOCAL SET DISABLE LOCAL SET TEST
ON OFF
L16 L15 L14 L13 L12 L11 L10 L9
ON OFF
L8 L7 L6 L5 L4 L3 L2 L1
ON OFF
128 64 32 16 8 4 2 1
The terminals for the binary outputs are found at the lower left hand corner of the SAT III controller. The “COM” to “H” contacts are referred to as K1h-K8h. The “COM” to “C” contacts are referred to as K1c-K8c.
The SAT III can also accept up to three WCC III V-Out Relay Boards.
STATUS
BINARY INPUTS
BINARY INPUTS
SATADDRESS
SAT REC
SAT XMIT
HSS REC
HSS XMIT
LOCAL SET
STATUS 1
STATUS 2
STATUS 3
CH
1 2 3 4 5 6 7 8
SAT III
PROGRAMMABLE CONTROLLER
ANALOG INPUT
JUMPER SELECTION
THERM
0TO1V
0 - 10V 0-5V
INPUT
0-1V
THERM
0TO5V
0 - 10V 0-5V
INPUT
0-1V
THERM
0 TO 10V
0 - 10V
INPUT
0-5V 0-1V
THERM 0 - 10V
THERMISTOR
0-5V
INPUT
0-1V
THERM 0 - 10V
CURRENT
0-5V
INPUT
0-1V
A4 TO 20 mA SENSOR WILL REQUIRE A 50 OHM LOAD RESISTORWHEN SET FOR A1 VOLT INPUT, ORA 250 OHM LOAD RESISTORWHEN SET FOR A 5 VOLTINPUT.
A2 WIRE ROOM SENSOR WILL REQUIRE A300 OHM LOAD RESISTOR WHEN SET FORA 1 VOLT INPUT.
A3 WIRE ROOM SENSOR WILL NOT REQUIREA LOAD RESISTOR WHEN SET FORA 1 VOLT INPUT.
WattMaster Controls Inc.
WCC III Technical Guide
1-7
1. GENERAL INSTRUCTIONS
Point Addresses
Point Addresses
A Point Address uniquely identifi es a point within the WCC III system. All point addresses have an associated “analog” or “binary” value. The term “analog” simply means a value which is represented by a number (such as room temperature, duct static pressure, etc.). The term “binary” means the value is represented by one of two conditions, ON or OFF. An input is a signal sent to the WCC III system, and an output is sent from the WCC III system. Therefore, room temperature is an analog input, fan status is a binary input, and controlling a fan relay is a binary output.
In addition to the inputs and outputs that are wired to the SAT III controllers, there are several software point addresses within the system. For example, the WCC III system has 128 week schedules. This means that separate day/night schedules can be assigned to 128 different areas of the building.
For example, assume that you have three different areas in a building that have different schedules as shown in the following table.
Area Occupied Time
W eek Schedule #1 1st Floor West 8:00 am - 5:00 pm, M-F W eek Schedule #2 1st Floor East 7:00 am - 7:00 pm, M-F W eek Schedule #3 2nd Floor 9:00 am - 4:00 pm, M-Th
Week Schedule #1 is named W1, and the value of W1 will be On between 8:00 am and 5:00 pm, Monday through Friday, etc.
The Name column in the table that follows is the name that you should use when specifying a point address to the system. The “n” is where a “point number” for the point address is to be entered.
Table of Point Addresses
Name Description Value
RnB Data Registers (b) Analog TnR Trend Logging Run T ime Analog TnC Trend Logging Change of State None TnA Trend Logging Analog Trend None
TnP Trend Logging Analog Peak None
Ln Logical Input On/Off
Wn W eek Schedules On/Off
Sn Optimal Starts On/Off GBn Binary Globals On/Off GAn Analog Globals Analog
On Binary Output On/Off
Constant Point Addresses
The following list shows several point addresses within the system that are always available for use on many of the data input screens.
Name Description Associated Data Type
0 Logical Zero Always Off 1 Logical One Always On
//// Logical Null Ignored
. . . . Logical Off Always Off/Not Used
NOTE: When a point option is not required, replace the
default value (/ / / /) with either a zero (0) or dot (. . . .)
to force the system to realize that the option is always OFF. If the slashes are not replaced, the system will ignore that input and the system can, in rare cases, see the slashes as being ON.
Name Description Value
Cn Comparator (See analog input
screen binary setpoint) An Analog Inputs Analog Pn Analog Outputs Analog
KnH Control Outputs
(H Contacts)
KnC Control Outputs
(C Contacts)
RnA Data Registers (a) Analog
1-8
On/Off
On/Off
On/Off
Name Description
Analog 0 Initiates a 0 (zero) value
TIME Current Time (in HH:MM format)
TIMEB Current Time (in minutes-since-midnight format) NEWSEC New Second NEWMIN New Minute
NEWHR New Hour
NEWDA Y New Day
NEWMON New Month
WCC III Technical Guide
1. GENERAL INSTRUCTIONS
Data Registers
Time & TimeB
These logical addresses are the actual time on HH:MM (TIME) and minutes-since-midnight (TIMEB) formats. They are considered analog values and have value ranges of 0000 to 2359 (TIME), and 0000 to 1439 (TIMEB).
Typical application of these logical addresses includes use in the Dual Limit mode, allowing such modes of control as “On­Between-Times” and “Off-Between-Times.”
NEWSEC, NEWMIN, NEWHR, NEWDAY, & NEWMON
These logical addresses are considered binary values and are based on real-time. They have a pulse-type nature in that each of these addresses has a value of one (or ON) for one second after the occurrence of the specifi ed event. After the one second ON period has elapsed, the value returns to zero (or OFF).
These addresses have several uses throughout the system. One example would be the generation of a variable duty cycle output. When used in conjunction with the separate “Minimum ON/OFF” timers, these addresses can achieve cycles of from one second to several days with a wide range of cycles.
Examples of “point addresses” within the system:
Name Description
GA12 Global Analog #12 135A5 Satellite #135, Analog Input #5
A5 Analog Input #5, Current Satellite
W12 W eek Schedule #12
S27 Optimal Start #27
C1 Setpoint Comparator on Analog Input #1
K1h
14P3
When K1h is ON, the relay within the satellite
controller which connects the electrical path
between the “H” and “COM” terminals on
channel 1 of the satellite controller is closed.
When K1h is OFF , the circuit is open.
Satellite #14, Analog Output #3.
Data Registers
The WCC III system has some capabilities built into the software that are very helpful, and you should be aware of them. There is a Data Register associated with each of the H/C Control Output Screens. A H/C Control Output Screen allows the user to tell the satellite controller when to open and close the binary output contacts. A H/C Control Output Screen can be a Time Clock, EA Driver, or Dual Limit Mode Scr een.
Time Clock
When the H/C Control contact on the satellite controller is controlled by a Time Clock Screen, the contact opens and closes based on time only. For example, a T ime Clock Scr een can be used to run a water circulating pump from 8:00 am to 5:00 pm, Monday through Friday. Each Time Clock Screen has a Data Register associated with it.
The Data Register is an analog value which is the time in seconds since the satellite controller binary output contact closed. Assume the water circulating pump is controlled by satellite controller contact K1h. That is to say, the “COM” to “H” contact on channel 1 of the satellite controller closes to complete a 24 VAC signal to run the pump.
The Data Register for a Time Clock Screen is named RnA or RnB. R stands for data register, n refers to channel 1-8 of the satellite controller, A means the “COM” to “H” contact, and B means the “COM” to “C” contact. Therefore, the Data Register for contact K1h is R1A. As contact K1h closes, the Data Register for contact Klh (R1A) starts recording time in seconds. That is to say , the value of R1A is the time in seconds since contact K1h closed.
RnA = Time in seconds since COM to H contact closed (9999 sec max) RnB = Time in seconds since COM to C contact closed (9999 sec max)
The Data Register for a Time Clock Screen might be used to start one piece of equipment after another has been started. For example, assume we want to start an air handler two minutes after the water circulating pump starts. The pump would be controlled by a Time Clock Scr een as mentioned above. The air handler would be controlled using a Dual Limit Screen. The analog input value for the Dual Limit Screen would be R1A, which is time in seconds since the pump started. The Dual Limit Screen is set up to close the contact for the air handler when the value of R1A is between 120 seconds and infi nity.
WCC III Technical Guide
The data register will also record time in negative seconds. When the contact opens, the data register value will begin counting -1,
-2, etc.
1-9
1. GENERAL INSTRUCTIONS
Data Registers
EA Driver
The EA Driver Mode is “3-point fl oating” control. For example, assume that the H/C control outputs on channel 2 of the satellite controller are used to control a VAV box using the EA Driver Mode. When the space needs heat, the “COM” to “H” contacts on the satellite controller will close to drive the damper in the VAV box to the closed position. When the space needs cooling, the “COM” to “C” contact on the satellite controller will close to open the damper in the VA V box.
There are two Data Registers associated with an EA Driver Screen. The value of the fi rst Data Register is equal to the setpoint entered on the EA Driver Screen and is referred to as “RnA.” The value of the second Data Register is equal to the difference between the setpoint and the actual temperature and is referred to as “RnB.” “R” stands for data register, and “n” refers to channel 1-8 of the satellite controller.
RnA = Setpoint RnB = Difference between Setpoint and Measured Value (error)
For example, assume that the setpoint for the room in question is 72 °F, and the actual temperature is 70 °F. The value of Data Register R2A (setpoint) is 72 °F, and the value of Data Register R2B (error) is -2 °F, since the actual space temperature is 2 °F below the setpoint.
The Data Register could be used to turn on a second stage of heat whenever the space temperature falls 2 °F below setpoint. Assume that the second stage of heat is a heating coil which is energized when satellite controller contact K3h is closed. A Dual Limit Scr een is used to control contact K3h. Data Register R2B is entered as the analog input value for the Dual Limit Screen. When the value of R2B is -2 or less (the space temperature is at least 2 °F below setpoint), contact K3h closes to turn on the second stage of heat.
The Data Register for a Dual Limit Screen is named “RnA” or RnB.” “R” stands for data register, “n” refers to channel 1-8 of the satellite controller, “A” means the “COM” to “H” contact, and “B” means the “COM” to “C” contact. Therefore, the Data Register for contact Klh is R1A.
RnA = Difference between Setpoint and Measured Value (COM to H)
RnB = Difference between Setpoint and Measured Value (COM to C)
The Dual Limit Scr een has two setpoints, the high limit and the low limit. Since the Data Register is the difference between the setpoint and the actual temperature, you have to “tell” the system what you are considering the setpoint to be. Therefore, the Data Register is measured from either the “Midpoint” or “Nearest Limit” of the setpoints, depending on how the Dual Limit Screen is set up.
For example, assume that a Dual Limit Screen is used to control a heat pump compressor to have the compressor off if the space is between 70 and 74 °F . If the space temperature is below 70 °F, the compressor will be on for heating, and if the space temperature is above 74 °F, the compressor will be on for cooling. Assume the actual space temperature is 76 °F .
The Data Register can be measured from either the “Midpoint” or the “Nearest Limit.” If the Data Register is measured from the “Midpoint,” the value of the Data is 4 °F .
Low Limit High Limit Actual T emperature 70 72 74 76 4 Deg Midpoint
Data Register
Dual Limit
When the H/C control output contact on the satellite controller is controlled by a Dual Limit Screen, the contact opens and closes based on how the analog input value compares to a pair of setpoints. There is one Data Register for each contact on the satellite controller which is controlled by a Dual Limit Screen. The value of the Data Register is the difference between the setpoint and the actual temperature.
1-10
Difference between actual temperature and the “Midpoint” of the setpoints = 4 °F, and therefore, the value of the Data Register is 4 °F .
If the Data Register is measured from the nearest limit, the value of the Data Register is 2 °F .
Low Limit High Limit Actual Temperature 70 74 76 2 Deg Nearest Limit Data Register
WCC III Technical Guide
1. GENERAL INSTRUCTIONS
Alarms
Alarm Call-Out
The WCC III will automatically e-mail a report of the alarms to an e-mail address. There are eight different alarm types or alarm priorities. The fi rst fi ve alarm types can “e-mail-out”; each of these ve alarm types can e-mail 3 separate e-mail addresses.
Analog Alarm Limit
Each analog input can have a low and high limit assigned to it on the Analog Input Screen. If the value of the analog input falls below the low limit or rises above the high limit, the system automatically generates an alarm. For example, assume that the analog input in question is a room temperature sensor located in an offi ce space. If the space temperature falls below 68 °F or rises above 80 °F during the occupied period, we want an alarm to call out. T o set up the alarm limits, fi rst sign on by accessing the System Parameter Screen and entering your password. An access level of 1 or greater is required to enter or change alarm limits. After you
are signed on, return to the Main Menu and place the cursor over “ANALOG INPUT” and press <Enter>. An Analog Input Screen similar to what is shown below should come into view:
The alarm limits along with the alarm type and alarm message numbers are assigned on this screen (see the Analog Input Screen in Section 3 for more information). If the space temperature drifts out of the entered alarm limits, the system will automatically generate an alarm. For example, assume that the space temperature rises above the high limit value of 80 °F . Alarm message #1 (High Temperature) along with the time and date of the alarm and the high peak value of the room temperature will appear on Analog Input Summary Screen and the Alarm Summary Screen. Within one minute from the time the alarm appears on the screen, it will automatically be e-mailed if enabled. (To acknowledge alarms, select <Action> from the Top Menu Bar and then select
<Acknowledge Alarm> or <Acknowledge All Alarm> described
in the Help Screen, Analog Input Summary Screen, and Alarm Summary Screen in Section 3 of this guide.
Satellite #1 ANALOG INPUT #1
Description: RM 101 Type: Analog Pattern for values associated with this input: xxx.x Units @ 0% scale: 0.0 Deg F Units of Measure Message #: 1 @ full scale: 100.0 Deg F Filter Time Constant: 8 seconds
-------------------ALARMS--------------------
Controlled by: W1 Limits Low High Alarm Type: 1 On 68.0 80.0 Deg F Alarm Message #’s: Low 2 High 1 Off 50.0 90.0 Deg F
Alternate Limits selected by:.... On (alt) 0.0 0.0 Deg F
Off (alt) 0.0 0.0 Deg F
Limit overlap time after control change: 20 Minutes Local set 55.0 90.0 Deg F
----------------------BINARY SETPOINT----------------------­ OFF Above 0.0 Deg F On Message #: 0 OFF Below 0.0 Deg F Off Message #: 0
HOME for menu
WCC III Technical Guide
1-11
1. GENERAL INSTRUCTIONS
Alarms
Run Time Alarm
The WCC III system also has the capability of alarming if the total ON time of a binary (on/off) value has exceeded the run time alarm limit. T o assign a run time alarm limit, fi rst sign on by accessing the System Parameter Screen and entering your password. An access level of 2 or greater is required to enter or change alarm limits. After you are signed on, return to the Main Menu and place the cursor over “TREND LOGS” and press <Enter>. The Trend Log
Summary Screen should come into view. To access a Run Time Trend Logging Screen, use the arrow keys to place the cursor (>)
by the desired run time point, and press <Enter>. The following screen should come into view:
In this example screen, we are recording the total “ON” time of contact Klc (COM to C contact closure) on satellite controller #1. When contact Klc is closed, or “ON”, Fan #1 runs. Run time recorder #1 records total accumulated run time of the fan. Alarm message #7 (Grease Bearings) will automatically appear on the Alarm Summary Screen when the total accumulated run time of the fan exceeds 500 hours. Within one minute after the alarm appears on the screen, it will automatically e-mail if enabled. (See the Alarm Summary Screen in Section 3 for information about how to acknowledge a run time alarm, and see the Run Time Trend Logging Screen section in Section 3 of this manual for information about how to reset the accumulated run time to zero.)
Satellite Fail Alarm
If the Master Communications Device loses communications with a satellite controller, a Satellite SOS Alarm will show which satellite is out of service and the time and date of the alarm.
Satellite # 1 TREND LOGGING # 1 of Type: RUN TIME
Records total ON time Starting at : *:* on */* for K1c Fan # 1 Reset by: L16 being ON
Alarm Type: 6 Alarm Message #: 7
Current run time: 250 Hours Alarm Limit: 500 Hours
HOME for menu
1-12
WCC III Technical Guide
Loading...