WattMaster VAV System User Manual

WattMaster VAV System
Operator Interfaces
Technical Guide
Table Of Contents
Introduction ..................................................................................................................................................... 3
Modular Service Tool .................................................................................................................................................................. 3
Modular System Manager........................................................................................................................................................... 3
System Connections........................................................................................................................................ 4
Modular Service Tool .................................................................................................................................................................. 4
Modular System Manager........................................................................................................................................................... 5
Operator Interfaces Comparison ................................................................................................................................................ 6
Service Tool And System Manager............................................................................................................................................ 7
Modular System Manager........................................................................................................................................................... 7
Modular Service Tool ................................................................................................................................................................ 10
Programming The WMVAV Controller ........................................................................................................... 12
Configuration ............................................................................................................................................................................ 12
Setpoints................................................................................................................................................................................... 16
Status........................................................................................................................................................................................ 22
Scheduling ................................................................................................................................................................................ 24
Setting Time & Date.................................................................................................................................................................. 25
Damper Force Modes ............................................................................................................................................................... 26
Outputs Force ........................................................................................................................................................................... 26
Programming The VAVBOX Controller .......................................................................................................... 28
Configuration ............................................................................................................................................................................ 28
Setpoints................................................................................................................................................................................... 29
Status........................................................................................................................................................................................ 32
Damper Force Modes ............................................................................................................................................................... 34
Programming The MiniLink PD ...................................................................................................................... 35
Configuration ............................................................................................................................................................................ 35
WattMaster Controls Inc.
WattMaster Controls Inc.
WattMaster Controls Inc. 8500 NW River Park Drive · Parkville , MO 64152
8500 NW River Park Drive · Parkville , MO 64152
8500 NW River Park Drive · Parkville , MO 64152 Toll Free Phone: 866-918-1 100
Toll Free Phone: 866-918-1 100
Toll Free Phone: 866-918-1 100 PH: (816) 505-1100 · F AX: (816) 505-1 101 · E-mail: mail@wattmaster .com
PH: (816) 505-1100 · F AX: (816) 505-1 101 · E-mail: mail@wattmaster .com
PH: (816) 505-1100 · F AX: (816) 505-1 101 · E-mail: mail@wattmaster .com Visit our web site at www.wattmaster.com
Visit our web site at www.wattmaster.com
Visit our web site at www.wattmaster.com Form: WM-SMST-TGD-01C
Form: WM-SMST-TGD-01C
Form: WM-SMST-TGD-01C Copyright 2004 W attMaster Controls, Inc.
Copyright 2004 W attMaster Controls, Inc.
Copyright 2004 W attMaster Controls, Inc. WattMaster Controls, Inc. assumes no responsibility for errors, or omissions.
WattMaster Controls, Inc. assumes no responsibility for errors, or omissions.
WattMaster Controls, Inc. assumes no responsibility for errors, or omissions. This document is subject to change without notice.
This document is subject to change without notice.
This document is subject to change without notice.
Introduction
Technical Guide
Modular Service Tool
2.02"
1.63"
Figure 1: Modular Service Tool Dimensions
Description
The OE391-05 Modular Service Tool is a system operator interface that provides a direct link to enable the system operator to view the status, configure and to adjust the setpoints of any controller on the control system communications loop. The Modular Service Tool is housed in an attractive beige colored plastic enclosure. The display area is covered with a clear plastic bezel for protection of the display screen. The Modular Service Tool has a four line by 20 character dis­play panel with adjustable contrast control and a 27 key membrane keypad for data selection and entry. All keypad operations are simple and straight forward, utilizing non-cryptic plain English language messages. Menu driven programming allows for easy setup and op­eration without the need for specialized training. The OE391-05 Modu­lar Service T ool is supplied with (4) AA (1.5V) Volt alkaline batteries a wall mount DC power supply and a communication cable terminated with an 8 pin DIN connecter for connection to the Service Tool. The cable allows the user to setup and program any WattMaster V AV con­troller with a 8 pin DIN connector socket by simply plugging in the service tool to the socket on the controller. An adapter is also provided to allow connection to the 3 pin communications terminal block on controllers which do not have the 8 pin DIN connector.
The Modular Service Tool is designed to be carried by the system in­staller or service technician. Its rugged plastic housing, provides supe­rior protection for the electronic components housed inside. The OE391­05 Modular Service Tool is a top quality service tool that will stand up to the demands of the typical job site environment for many years.
Mode
Selection
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE - TEST
ON
4.75”
UP
PREV
ESC
13
4
708
DEC
NEXT
DOWN
CLEAR
ENTER
2
5
6
9
MINUS
-
10.00”
Modular System Manager
9.00"
13
2
5
6
4
708
9
DEC
MINUS
-
UP
PREV
ESC
DOWN
ENTER
Figure 2: Modular System Manager Dimensions
Description
The OE392-05 – Modular System Manager provides a direct link to enable the system operator to view the status and to adjust the setpoints of any controller on the control system communications loop. The Modu­lar System Manager is designed to be used with the WattMaster VAV Control System. The System Manager is housed in an attractive off­white colored plastic enclosure. The System Manager is equipped with a four line by 20 character backlighted display panel and a 24 key mem­brane keypad for data selection and entry. All keypad operations are simple and straight forward, utilizing non-cryptic plain English language messages. Menu driven programming allows for easy setup and opera­tion without the need for specialized training. The System Manager also has 2 integral LED’s for user notification of system alarm conditions and override initiations. Protection from unauthorized users is provided by the System Manager’s integral multi-level passcode authorization programming.
On W attMaster VAV Systems, the Modular System Manager is wired to the communications and power loop of the system via a pigtail cable with modular connectors on one end and stripped wire ends on the other that is provided with the System Manager. This pigtail cable allows connection of power to the Modular System Manager from a 24 VAC power source and communications wiring from the HVAC unit control­ler communication wiring terminals.
The Modular System Manager is designed for wall mounting. Mount­ing holes are provided to attach the Modular System Manager to a stan­dard handy box. It is recommended that the System Manager be mounted at approximately eye level to allow for ease of programming and read­ing of the display. The System Manager is typically mounted in the building manager or superintendent’s office or in an equipment room. The attractive enclosure is quite suitable for mounting in any location or with most decors.
STATUS
SETPOINTS
NEXT
SCHEDULES
CLEAR
OVERRIDES
ALARMS
6.25"
1.81"
Operator Interfaces 3
Technical Guide
System Connections
Modular Service Tool
W ether you have a S tand Alone, Interconnected or Networked System, the Modular Service T ool always connects to an HVAC unit controller via a prefabricated cable that is supplied with the service tool. The Modu­lar Service T ool cable is terminated on both ends with a mini DIN con­nector. Attach one end to the Modular Service Tool and the other end to the mini DIN connector on the HVAC unit controller. If this is an Inter­connected System, all controllers that are interconnected with commu-
Optional Connection For Controllers Without DIN Connector
Male DIN Connector
Connector Cable
nications cable can be programmed from any HVAC unit controller on the loop. If this is a Networked System, all controllers on the entire Networked System can be programmed from one HVAC unit control­ler.
Be sure that the Modular Service Tool has fresh batteries installed or that it is connected to a power source using the supplied power pack before attempting any programming of the controller. See Figure 3 for connection details.
PL101904 Adapter Board
COMM
T SHLD R
Typical Controller Board
The Modular Service Tool Can Be Connected To Most Controllers By Plugging One End Of The Supplied Cable Into the Modular Service Tool DIN Connector And The Other End Into The DIN Connector On The Controllers.
Some Controllers Without DIN Connectors Require Use Of The Supplied PL101904 Adapter Board Shown Above. To Connect With Adapter Board, First Unplug COMM Terminal Block From Controller Board. Plug PL101904 Adapter Board Terminal End Into Terminal Block Base On Controller. Plug DIN Connector Cable Into DIN Connector On PL101904 Adapter Board . See Optional Connection For Controllers Without DIN Connector Above For Illustration Of This Connection.
erminal
T Block Base
(Remove Terminal Block)
Female DIN Connector
Figure 3: Modular Service Tool
Mode
Selection
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE - TEST
ON
PREV
UP
NEXT
DOWN
CLEAR
ESC
ENTER
13
2
5
6
4
708
9
DEC
MINUS
-
Power On Button
Modular Service Tool
Be Sure The Modular Service Tool Is Connected To The Supplied Power Pack Or Has Fresh Batteries Installed Before Attempting Programming Of The Controller. Be Sure The Power Is Turned Off On The Modular Service Tool Before Connecting The Cable To The Controller.
4
Operator Interfaces
Technical Guide
V62C518256L-70P
CX12
CX13
PCB80C552-5-16WPP442860=2/5 PDfD9722V7Y
PHILIPS
24C128
470uF50v
COMMOUT
COMMIN
MC34064A
74HC540
Modular System Manager Back of Front Cover
P1
P2
VAR1
U13
RS-485P COMM
R14
U6
V62C518256L-70PV62C518256L-70P
CX11
CX12
U12
U11
CX7
PAL
EPROM
RAM
CX13
75176
U8
74HC573
CX8
RN1
SC1
YS101830PREV.YS101830PREV. 2PMODULARPSYSTEM MANAGER
PCB80C552-5-16WPP442860=2/5PCB80C552-5-16WPP442860=2/5PDfD9722V7YPDfD9722V7Y
C2
U7
X1
C1
R1
R4
EWDOGEWDOG
PHILIPS
X2
C3
PHILIPSPHILIPS
U3
CX5
R3
R9
8583
CX6
D3
U4
24C12824C128
CX4
74HC259
U1
U2
CX2
R3
R2
U14
C8
CX9
C7
470uF50v
1000uF10v
470uF50v
1000uF10v
R12
R11
COMMOUTCOMMOUT COMMINCOMMIN
D6
C4
R13
MC34064AMC34064A
U9
9936
D5
L1
U10
74HC540
CX14
C6
P3
CX10
C5
74HC92374HC923
R10
D4
CX3
82B71582B715
PJ1
D2
R6
R5
D1
U3
DSPY1DSPY1
R7
RV1
Class 2 Transformer
Rated For 6 VA Minimum
(By Others)
Handy Box , Conduit,
Fittings, Wire Nuts,
Butt Splices Etc.,
( By Others)
Controller Board
T
SHLD
R
HZ000121 Modular Pigtail Cable Supplied With System Manager
WHITE(
T )
B LA
C K (R )
RED(24 VAC)
BROWN(GND)
GREEN(
G ND)
Drain Wire (Shld)
LINE VOLTAGE
LINE VOLTAGE
2-Conductor Shielded
18-Guage
Communications Wire
Modular System Manager
Power and communications are supplied to the System Manager via a modular/pigtail cable that is supplied with the System Manager. This cable has a male Molex connector on one end for connection to the female Molex connector on the System Manager. On the other end are 5 insulated wires with a drain wire which are used for connection to the
YS101830PREV. 2PMODULARPSYSTEM MANAGER
U1
74HC259
R1
R4
C1
X1
C2
U7
PAL
CX7
CX11
U11
CX12
U12
Use Supplied Modular
For Connection To Terminal
U2
EWDOG
CX4
U3
R3
PHILIPS
PCB80C552-5-16WPP442860=2/5
24C128
PDfD9722V7Y
PHILIPS
CX5
CX6
C3
8583
X2
U6
RN1
CX8
74HC573
U8
SC1
EPROM
RAM
V62C518256L-70P
Cable With Stripped Ends
Block And Transformer
WHITE (T) DRAIN WIRE (SHLD) BLACK (R)
RED (24 VAC) BROWN (GND) GREEN (GND)
CX2
R3
R2
U4
R9
D3
VAR1
CX13
75176
RS-485P COMM
R14
Rated For 6 VA Minimum
DSPY1
U3
CX3
D1
R5
82B715
R6
D2
PJ1
COMMOUT
P1
COMMIN
P2
U13
R10
D5
R11
D4
R12
L1
CX10
U9
C4
9936
D6
MC34064A
C5
R13
CX9
1000uF10v
470uF50v
C6
C8
C7
1000uF10v
470uF50v
74HC540
CX14
Class 2 Transformer
RV1
R7
74HC923
U10
P3
U14
Modular System Manager Back of Front Cover
T SHLD
R
WMVAV Controller Board
Connection Shown
May Also Be Connected To Any
VAVBOX Controller On Loop
communication and power wiring from the transformer and from the local loop communications terminal on the WMVAV controller or any VAVBOX controller ’s communication terminal. A class II, 24 VAC transformer (by others) rated at 6 VA or greater load capacity is required for powering the System Manager.
See Figure 4 & 5 for System Manager connection and wiring details.
Figure 4 Schematic for Wiring System Manager Using Modular Cable Pigtail
Operator Interfaces
Figure 5: Detailed Typical System Manager Wiring Using Modular Cable Pigtail
5
Technical Guide
General Programming Information
Operator Interfaces Comparison
In order to configure and program the W attMaster VAV System control­lers you must have a central operators interface or a personal computer with the Prism computer front end software installed. Two dif ferent cen­tral operators interfaces are available for programming of the W attMas­ter VA V Controls System. You may use either the Modular Service T ool and/or the Modular System Manager to access the status and set- points of any controller on your communications loop.
Mode
Selection
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE - TEST
ON
Modular Service Tool
13
2
MINUS
PREV
6
9
-
4
708
DEC
5
Modular System Manager
UP
ENTER
DOWN
NEXT
CLEAR
2
5
6
9
MINUS
-
PREV
ESC
13
4
708
DEC
System Manager
UP
NEXT
DOWN
ENTER
CLEAR
ESC
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
The Modular Service Tool or the System Manager allow the user to view any temperature or output condition and change any setpoint to fine tune the operations of the total system. All keypad operations are simple and straightforward, utilizing non-cryptic plain English messages.
Display Screens & Data Entry Keys
The System Manager display screens and the Modular Service Tool display screens are very similar. For most setpoints and modes the only difference between using the Service T ool and the System Manager is a few differences in the function of the keypads. In this manual where a difference in the keypad input or the screens displayed exists between the two operators interfaces, both screens or keypads will be shown. See the chart below for a list of the keypad descriptions and functions.
Keypad
Description
ESC
System Manager Modular Service Tool
Used to exit from screens or from data entry. Use
Key Function
Same f u nction as
System Manager this screen to return to the main menu f r om any screen in the system
ENTER
This key is used to close a
data entry field and
Same f u nction as
System Manager
advance to the next item
or screen
Clear
If a data entry mistake is
made, press this key to
clear the data entry field
and start over
Same f u nction as
System Manager but
also turns off the
power to the Service
Tool when on the
main menu screen
Minus
If a setpoint with a
negative value is required,
Same f u nction as
System Manager
press this key for the
minus sign
DEC
Press this key when
entering data that requires
Same f u nction as
System Manager
a decimal point
Steps the user to the next controller on the loop on
Same f u nction as
System Manager
interconnected or
networked systems
⇑ ⇓
Steps the user backward or
forward through the
screens
Same f u nction as
System Manager
Mode Selection Buttons
Both the System Manager and the Modular Service Tool are provided with “Mode Selection Buttons” . These buttons give the user instant access to the specific mode desired without having to scroll through several menu screens to get there. The Modular Service Tool has 2 extra function keys (“Configuration” and “Balance-Test”) that are not available on the System Manager.
6
Operator Interfaces
Technical Guide
t
Service Tool And System Manager
Entering Unit ID (Address)
Button
Description
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE-TEST
Notes:
Modular Service Tool System Manager
Pressing this button
takes you directly to
“Status” screens
Pressing this button
takes you directly to
“Setpoints” screens
Pressing this button
takes you directly to
“Schedules” scr een s
Pressing this button
takes you directly to
“Overrides” screen.
See the “Override
Button” section of
this manual for a
description of this
See Note 1 below.
Pressing this button
takes you directly to
“Alarms” screen.
See the “Alarms
Button” section of
this manual for a
description of this
See Note 1 below.
Pressing this button
takes you directly to
“Configuration”
Pressing this button
takes you directly to
Mode Selection Buttons
the controller
the controller
the controller
the controller
function.
the controller
function.
the controller
screens
the controller
“Balance-Test”
screens
Pressing this button
takes you directly to
the controller
“Status” screens
Pressing this button
takes you directly to
the controller
“Setpoints” and
“Configuration”
Menu
Pressing this button
takes you directly to
the controller
“Schedules” screens
Pressing this button
takes you directly to
the controller
“Overrides” screen.
See the “Override
Button” section of
this manualfor a
description of this
function.
See Notes 1 & 2
below.
Pressing this button
takes you directly to
the controller
“Alarms” screen.
See the “Alarms
Button” section of
this manual for a
description of this
function.
See Notes 1 & 2
below.
Not Available
Use “Setpoints”
Button To Access
Menu
Not Available
1.) This button only functions w hen the system is configured for “Network Mode” or “Multiple MGRS Mode”. It will no function in ‘Stand Alone M ode”.
2.) The “Search For Units” functio n must be p erformed on the System Manager upon initial system setup before this function will be available. See the “System Manager NM & MM Loop Search” section of this manual for complete instructions on performing a loop search.
With both the Modular Service Tool and the Modular System Manager You must enter the ID (Address) of the controller you wish to program
Unit Selection Enter Unit ID# Selected ID#: xxxx
With the main menu screen displayed, press the function key associated with the operation (setpoints, configuration, etc.) you want to perform. The screen shown above will appear asking you to enter a unit I.D.# (controller address). Put in the ID# of the controller you wish to com­municate with then press the “ENTER” key.
If this is Multiple Loop Network System the Unit ID is actually two separate numbers, combined into one value. The first part of the num­ber contains the Loop Address at which the controller is located. The second part of the number contains the actual controller address. See Examples #1 & #2 below.
EXAMPLE #1
You would like to view the 3rd controller on the 5th loop. Enter “503” as the Unit ID.
EXAMPLE #2
Y ou would like to view the 12th controller on the 24th loop. Enter “2412” as the Unit ID
EXAMPLE #3
You would like to view the only controller on the loop. Enter 1 as the Unit ID. No loop number is required since there is only one loop.
Hit the “Enter” key after entering the unit ID. If you are using the Modular Service T ool you will be taken directly to the first screen for the opera­tion you are trying to program.
Modular System Manager
System Manager Initialization Screens
When the System Manager is powered up, the first screen displays the current version of the software installed in your System Manager and whether your system is configured for Network or Stand-Alone opera­tion. On a Networked System, all controllers on the communications loop are available for programming by entering their loop address (ID).
If the System Manager is configured for Stand-Alone operation, only the HVAC unit controller that the System Manger is connected to is available for programming. The Stand-Alone feature is only used for servicing and testing. For normal operation the System Manager must be configured for Network mode.
Operator Interfaces
7
Technical Guide
General Programming Information
Initializing System Manager vX.XX Wattmaster Controls Network Mode
System Manager vX.XX Monday Operations 09/09/99 04:26 PM NM Outdoor Air 87°F
The screen above will appear a few seconds later. The last line of the display will have the letters SA (Stand Alone Mode), MM (Multiple System Manager Mode) or NM (Network Mode) followed by the cur­rent outdoor air temperature. The System Manager normally ships from the factory set for NM (Network Mode). If you have only one System Manager, the system must be set for NM (Network Mode). If you have multiple System Managers on your system, the system must be set for MM (Multiple System Managers Mode). If you believe your system is incorrectly configured, please follow the instructions that follow. If your system is configured correctly, proceed to the System Manager Net­work Mode Loop
Configuring For Stand-Alone Mode, Multiple System Managers Mode or Network Mode
1) Set Time & Date
2) Communications
->) Next Menu ESC) Exit Menu
Press the “2” key on the keypad to enter the communications screen.
THIS ACTION REQUIRES A SPECIAL HIGH LEVEL PASSCODE CLEARANCE Enter: xxxxxxx
Enter the seven digit passcode “2337377” to access the next screen. These seven digits spell the word “ADDRESS” on your telephone key­pad if you forget what they are.
Y ou will then see the screen below displayed. You must use the keypad to enter the correct number for the mode of operation needed for your system.
0) Stand Alone 1-60) Multiple MGRS
63) Network System Enter Mode Of Op:.xx
As previously described the System Manager must be configured for the correct mode of operation for your system. Again, there are 3 modes of operation available for the W attMaster VAV System. They are “Stand Alone Mode”, “Multiple MGRS Mode” or “Network Mode”.
Look at the bottom line of the display as mentioned in the previous paragraph and determine which one your System Manager is currently set for. If you have a single System Manager for your entire system, then you need to operate in “Network Mode” and the first two charac­ters on the bottom line of the display should be “NM”. If you have multiple System Managers on your system then you need to operate in “Multiple MGRS Mode” and the first two characters on the bottom line of the display should be “MM”. The System Manager should never be set to “Stand-Alone” mode unless you have been instructed to con­figure this setting by WattMaster Technical Support.
If your display indicates a different mode than the one you need, press the “Enter” key and the following screen will appear.
For “Multiple MGRS Mode” enter the address at which you want this particular System Manager to be set. When multiple System Managers are used on a local loop, each must be set with a unique address differ­ent from any other device on that loop. You must perform this same operation again for each System Manager installed. If you want one of these System Managers to be able to indicate alarms and overrides for the entire system you must enter “63” for “Network Mode” on that particular System Manager.
For “Network Mode” (or as explained above for Multiple System Managers when one is to be set to indicate alarms and overrides) enter “63”.
For “Stand Alone Mode” enter “0”.
Once you have the correct number per the display above displayed, press the ENTER key. The following screen will appear telling you that you have changed the system mode. Press any key on the keyboard to exit this screen.
You Have Changed The System Manager Mode Press Any Key To Continue
8
Operator Interfaces
Technical Guide
System Manager NM & MM Mode Loop Search
When the System Manager is configured for Network Mode a loop search must initially be performed for the System Manager to recognize alarms or overrides. Also, when you have a system that has multiple System Managers and you have one of the System Managers set to (63) Net­work Mode for alarm and override indication, you must also perform a loop search for that System Manager. This allows the System Manager to be aware of all alarms and overrides for all local loops on the entire system. .
Note: The Loop Search function is only required when using
the System Manager(s), not the Modular Service Tool.
To access the Loop Search screen, do the following. From the main menu screen press enter to display the following screen.
1) Set Time & Date
2) Communications
->) Next Menu ESC) Exit Menu
Press the “Next” arrow key. The following screen will be displayed.
1) Change Passcodes
2) Loop Search <-) Prev. Menu ESC)Exit Menu
Once the search is completed the following screen will be displayed.
Loop Search Finished Loops Found = XX Press ESC to Exit
The screen will display the number of loops found on your system. The information will be saved into the System Manager’s memory. No fur­ther loop searches will be required unless an additional MiniLink Poll­ing Device is added to the Network System.
System Manager Alarm Search
The System Manager can be used to search for all active alarms on the system. The MiniLink PD must be configured to allow for “Alarm Poll­ing” for each controller that alarming is desired on for this function to work. See the MiniLink PD programming section of this manual for setting information. Press the “Alarm” key. The Unit Selection screen below will be displayed. Enter the Unit ID of any unit on the system and press “Enter”. This is the unit ID of where the alarm search begins. The entire system is searched from this point.
Unit Selection Enter Unit ID# Selected ID#: xxxx
The following screen will appear. The System Manager will search for any active alarms on the entire system.
Press the “2” .The following screen will be displayed.
Loop Search Current Loop = XX Loops Found = XX Searching
The System Manager will now proceed to search all loops to find the MiniLink Polling Devices that are connected to the system. The screen will display the current loop being searched and the number of loops currently found.
Alarm Screen
SEARCHING!
After the System Manager completes it’s search, it will list the first unit on the system that currently has an active alarm. Press “Enter” to scroll through all the alarms on that particular unit. T o move to the next unit or back to the previous unit use the “Prev” or “Next” arrows to move be­tween units with alarms.
Alarm Search Screen Loop = 1 Unit = 59 Space Sensor Failure
T o clear any alarms that are found you must fix the problem indicated in the alarm. Once the problem is fixed, the alarm will clear from the screen the next time the unit is polled.
Operator Interfaces
9
Technical Guide
General Programming Information
System Manager Override Search
When a space sensor with override option is used with any VAVBOX controller or WMVAV controller, the System Manager can determine and report any controllers which are currently operating in an override condition. The MiniLink PD must be configured to allow for “Alarm Polling” for each controller that alarming is desired on for this function to work. See the MiniLink PD programming section of this manual for setting information
To access the Space Sensor Overrides screen, press the “Override” but­ton located on the System Manager . A screen will appear asking you to enter a unit ID. Enter an ID for any active controller on the system and press "Enter". The following screen will appear.
Overrides Screen
SEARCHING!
After the System Manager completes its search, it will list the first unit on the system that is currently in the override mode. Press the previous or next button to scroll through all units that are in the Override Mode.
Overrides Screen Loop = 1 Unit = 59 Override Unit
If you wish to change either Level 1 or Level 2 passcodes please see the instructions that follow.
From the main status screen press "Enter", The following screen will appear.
1) Set Time & Date
2) Communications
->) Next Menu ESC) Exit Menu
Press the “Next” arrow key. The following screen will be displayed.
1) Change Passcodes
2) Loop Search <-) Prev. Menu ESC)Exit Menu
Press the “1” .The following screen will be displayed.
Enter New Passcode
Level 1.....: xxxx
Level 2.....: xxxx
[Must Be 4 Digits]
Anytime you enter a unit ID with the Modular System Manager you will be asked for a passcode. Passcodes are not required to view Status Screens. The screen below will appear if this action requires passcode clearance.
System Manager Passcodes
Anytime you enter a unit ID with the Modular System Manager you will be asked for a passcode. Passcodes are not required to view Status Screens. The screen below will appear if this action requires passcode clearance.
THIS ACTION REQUIRES PASSCODE CLEARANCE Enter Passcode: xxxx
The System Manager has two levels of user access. Level 1 users are limited to viewing or changing the Time, Date, Operating Schedules and Heating and Cooling Setpoints. Level 2 users have complete sys­tem access. Any status or setpoint field can be read or reset from the System Manager.
This screen allows you to enter new Level 1 or Level 2 passcodes. The actual digits in your passcodes are never displayed. An “X” is used as a place holder for each digit entered. Passcodes must always be four dig­its in length, so the usable range of numbers is 1000 to 9999.
Caution: If you change the Level 2 passcode and cannot
remember what it is, you will be locked out of your system!
Modular Service Tool
The Modular Service Tool is very similar to the System Manager in its operations as stated previously. Two exceptions to this are that the Ser­vice Tool unlike the System Manager does not check the entire system when performing an “Alarm” or “Override” search and it does not have any passcoding capability.
Note: When the Alarms or Overrides buttons are pressed on
the Modular Service Tool it will search only the loop number of the unit ID that has been entered, therefore each local loop must be searched individually to access all alarms or overrides on the system.
These two levels of passcodes are programmable by any Level 2 user. The default Level 1 passcode is “111 1” and the default Level 2 passcode is “2222.”
10
Operator Interfaces
Technical Guide
Modular Service Tool Initialization Screen
After connecting the Service Tool to the controller with the supplied cable, press the “On” key. The following screen will appear.
Service Tool vX.XX Monday Operations 09/09/02 04:26 PM Stand Alone Mode
Configuring The Modular Service Tool For Network Or Stand-Alone Operation
As with the System Manager described previously, you must determine if the mode displayed is correct for your system. Normally for most applications the words “Network Mode” should be displayed in the window. If it has been configured for Stand Alone mode you will see the words “Stand Alone Mode” on the bottom line of the display. S tand Alone Mode is only used when servicing or troubleshooting and is nor­mally not used for general setup and programming as it only allows the user to access the controller it is attached to and not the entire net­worked system
If your display indicates a different mode than the one you need, press the "Enter" key and the following screen will appear.
1) Set Time & Date
2) Communications
3) Energy Saving ESC) Exit Menu
Press the “2” key on the keypad to enter the communications screen.
Modular Service Tool Alarm Search
First, press the “Alarm” key. The Unit Selection screen below will be displayed. Enter the Unit ID of any controller on the system and press “Enter”. This is the unit ID of the loop where the alarm search will be done. Unlike the System Manager, only the alarms on this loop will be searched, not the entire system.
Unit Selection Enter Unit ID# Selected ID#: xxxx
The following screen will appear. The System Manager will search for any active alarms on the local loop.
Alarm Screen
SEARCHING!
After the Modular Service T ool completes it’ s search, it will list the first unit on the local loop, whose ID was entered, that currently has an ac­tive alarm. Press “Enter” to scroll through all the alarms for controllers on that particular loop. To move to the next controller or back to the previous unit use the “Prev” or “Next” arrows to move between con­trollers with alarms on the loop.
Alarm Search Screen Loop = 1 Unit = 59 Space Sensor Failure
0) Stand Alone
1) Network System
Enter Mode Of Op:.xx
As the screen indicates, press the right or left arrow keys to select the proper mode of operation. When you are finished press “Enter” to move back to the main menu screen.
You Have Changed The System Mode Press Any Key To Continue
Operator Interfaces
T o clear any alarms that are found you must fix the problem indicated in the alarm. Once the problem is fixed, the alarm will clear from the screen the next time the unit is polled.
Modular Service Tool Override Search
When a space sensor with override option is used with any VAVBOX controller or WMVAV controller, the Modular Service Tool can deter­mine and report any controllers which are currently operating in an over­ride condition on the local loop whose ID (Address) has been entered before running the search.
T o access the Space Sensor Overrides screen, press the “Override” but­ton located on the Modular Service Tool . A screen will appear asking you to enter a unit ID. Enter an ID for any active controller on the particular local loop you wish to search and press "Enter". Unlike the System Manager, only the overrides on this loop will be searched, not the entire system. The following screen will appear .
11
Loading...
+ 25 hidden pages