WattMaster MG331-21-VAVCAV User Manual

Page 1
MG331-21-VAVCAV
r
VAV System
Description
The VAV/CAV Controller Board is designed with 7 usable analog inputs, 2 analog outputs and 5 relay outputs. The controllers input and output capabilities can be expanded by use of either 2 slot or 4 slot expansion boards that plug into the WMVAV Controller by means of a modular cable. The WMVAV Controller can be configured for control of VAV Units (with or without VAVBOX Controllers), Constant Volume Units and Air to Air Heat Pump Units. Features include the following:
Up to 8 Stages Each of Cooling and Heating (4 on board, 12 more with expansion boards)
Selectable Control Sensor
Fan Proving Interlock
Wetbulb Control of Economizer Operation
Accepts Remote Occupied Signal
Relief Pressure Control
De-Humidification Capable
Full Economizer Control
.20 Dia. Typ. of 4
7.3”
TB1
COMM
T
SHLD
R
LD6
COMM
LD7 PWR
LD8 LED1
LD9 LED2
R1
U7
INPUTS
+VDC
AIN1 AIN2 AIN3
AIN4
AIN5
GND GND AOUT1
AOUT2 AIN7 GND
PJ1
TB3
PRESSURE SENSOR
C21
RN1
1
CX5
1
RN3
+VREF
TESTPOINT
RV1 VREFADJ
C10
EXPANSION
WMVAV Controlle
6.2“
CX1
U1
U5
RS-485
COMM
HH
C1
P1
5.11V
EWDOG
R28
ADDRESS
RN5
PU1 D6 PU2
D7 PU3
D8 PU4
D9 PU5
D11 PU7
D14
C12
D15
C17
C20
R26
PJ2
U3
CX2
U2
EPROM
RAM
TUC-5RPLUS
(1MEG)
YS101816REV. 2
U6
C2
PHILIPS
C3
ADD
1 2 4 8
16
CX10
32 TOKEN
NETWORK
U10
SW1
C11
X2
0-5
0-1
VDC
VDC
JP1
U13
R15
U12
CX14
C14
R19
U14
CX13
U15
C15
R22
R24
R25
CX15
D17
PJ3
T'STAT
6.7”
D1
CX3
CX4
U4
RLY1
RLY2
PAL
1
RLY3
RN2
RLY4
CX6
X1
RLY5
1
RN4
U9
C7
R7
D10
L1
CX12
D12 R13
SC1
D19
D18
C19
C18
VR1
VR2
V1
D2D3D4D5
V2
V3
COM1-3
R1 R2 R3
R4
R5
COM4-5
TB2
V4
V5
U8
NE5090NPB3192 0PS
CX8
R6
C9
R10
D13
9936
R11
U11
MC34064A
C13
C16
TB4
GND
R27
D16
V6
POWER
7824CT
24VAC
M
6.6”
1.1”
I.A.Q. Control with C0
Sensor Monitoring Internal Trend Logging
2
7 Day, 2 Event per Day Scheduler Built In 14 Day Holiday Scheduler Built In
Optimal Start Scheduling Built In Override from Occupied to Unoccupied Mode
Supply Air Reset Capability
Accepts Remote HVAC Mode Selection
Most HVAC unit applications can be configured with the standard WMVAV Controller. If the application requires more inputs and/or outputs, optional relay expansion boards are available from the factory to provide for additional analog, binary or digi­tal inputs and outputs as required. These expansion boards are installed on either a 2 slot or 4 slot expansion base board that connects to the WMVAV Controller board via a modular cable connection.
Mounting – Factory Installed
If purchased separately the WMVAV Controller is provided with an integral backplate and can be mounted in the HVAC unit control panel or remotely located and wired to the HVAC unit.
Technical Data MG331-21-VAV Controller
Power 24 Volt AC Weight 1.5 lb. Power Consumption 8 VA Maximum Network Connection RS-485 Operating Temp
10°F to 149°F
Operating Humidity 90% RH Non-Condensing Communications RS-485 - 9600 Baud
Inputs: Outputs:
Room Temperature Type III-10kohm sensor (1) Fan-ON/OFF Supply Air Temperature Type III-10kohm sensor Outside Air Temperature Type III-10kohm sensor Static Pressure Sensor 0-5VDC Humidity Sensor 4-20Ma
Remote Occupied Signal Binary Contact Economizer Analog Output 0-10 VDC Fan Proof Of Flow Binary Contact VFD, Bypass or Inlet Vane
Three Year Warranty WattMaster reserves the right to change specifications without notice
Form: WMS-MG331-21-VAV-WMVAVController-01D.doc Page 1 of 1
Protocol HSI Open Protocol Token Passing
(5) Relays - (2 Amp @ 24 VAC)
(4) User Configurable For : Heating Or Cooling Stages, Reversing Valve, Warm-up Mode Box Com­mand, Hot Gas Reheat Control, Relief Fan Inter­lock, Preheat Coil
Analog Output 0-10 VDC
Control
Page 2
MG320-00-VAV
V
r
VAV System
Description
The MG320-00-VAV VAVBOX controller is used for controlling airflow and operation of VAV terminal units. It is a programmable digital controller, which allows for program setpoints to be stored in non­volatile memory. The controller is connected to a room sensor via a modular cable assembly, which monitors space temperature allowing the VAVBOX controller to modulate a damper in response to space temperature, duct temperature and airflow requirements in the controlled space.
The MG320-00-VAV VAVBOX Controller has three integral modular jacks for connection to the actua­tor, airflow sensor (for pressure independent appli­cations) and relay or analog expansion boards, via modular cables. A 2 wire terminal block is provided for connection of a 24VDC power transformer, a 2 wire terminal block is provided for the Room Tem­perature Sensor and a 3 wire terminal block is pro­vided for connection of the communications loop. The controller has an on-board dip switch provided for board addressing.
The VAVBOX controller is provided with two relays for tri-state control of the damper actuator. The actuator connects via a modular cable to the board and provides the VAVBOX controller with feedback monitoring for precise positioning of the actuator.
Mounting
Each VAVBOX controller is provided with a plastic snap track modular mounting base. The snap track is designed to be mounted with sheet metal screws to a flat surface using the pre-punched mounting slots provided. The VAVBOX controller is then snapped into place on the snap track providing for easy field mounting and servicing.
7.00"
AVBOX Controlle
FLOW
CX8
U8
RN1
1
B31920PS
74HC573N
D5
R27
CX9
C13
LMC662
C14
D5
R32
T'STA T
F1
562
YS101
REV. 2
24VAC
GND
Zone Controller Board
R22
ADJ
VREF
P.U .
R23
R28
R24
U11
C11
R20
C15
EWDOG
R25
D7
CX10
COMM
75176
U10
LD3
POWER
R26
250
D4
MDL
VR1
T
7824
7824C
M
4.00"
U4
MS6264L-70PC
9936
RAM
C8
ADD
1 2 4 8 16
32 TOKEN NET
LD2
LD1
REC
C7
9936
CX4
80C55 2
PHILIPS
PHILIPS
U5
U6
R14
D3
64A MC340
U7
RAM
8K
32K
EPROM
PCB80C552-5-16WP
500650=1/3
DFD9940SM
93C46
CX6
C5
R100
R13
R12C6R11
Q2
R15
Q3
U3
V4.00F C094
AZZONE
R8
C3
C4
V1
R9
R10
fTimes New
fTimes New
Roman|b0|i0|
Roman|b0|i0|c0|p18;
c0|p18;OMRON
G5L-114P-PS 24VDC CONTACT: UL / CSA 5A250VAC
K1
D1
fTimes New
fTimes New
Roman|b0|i0|
Roman|b0|i0|c0|p18;
c0|p18;OMRON
G5L-114P-PS 24VDC CONTACT:
D2
UL / CSA 5A250VAC
K2
CX3
CX1
U1
TCU32K2V
16L8
R1 R2 R3
CX2
X1
CX5
PJ1
PJ2
V2
Q1
B31920PS
74HC259
U2
C2C1
R4
R5 R6 R7
SION
EXPAN
TOR
ACTUA
R34
R18
U9
C9
C10
R19
ADDRE SS
SW1
R21
SCAN
L1
R16
R17
Snap Track
Technical Data MG320-00-VAV
VAVBOX Controller
Specifications: Inputs:
Supply Power 24 Volt AC/DC Room Temperature Sensor Type III-10kohm Sensor
Power Consumption 4 VA Maximum Air Flow Sensor
(PI Applications Only)
Operating Temperature
35°F to 125°F
Power Wire Terminals
0-5” H2O Velocity Pressure
Modular Cable Connection
Operating Humidity 90% RH Non-Condensing Communications Wire Terminal s Memory EEPROM Duct Temperature Sensor Type III-10kohm Sensor
Communications RS-485 - 9600 Baud
Outputs:
Mounting Method Snap Track Actuator Modular Cable Connection Addressing Rocker Type Dip Switch Expansion Boards- Digital or Analog Modular Cable Connection
Three Year Warranty WattMaster reserves the right to change specifications without notice
Form: WMS-MG320-VAVBOXController-1C.doc Page 1 of 1
Wire Termi nal s
Wire Termi nal s
Page 3
VAV System
Description
The OE322 - 3 Relay with Analog Out­put Expansion board is used in conjunc­tion with the MG320–00-VAVZ control­ler board to allow for control of VAV terminal units, including series and par­allel fan terminal units with up to 3 stages of electric heat, SCR electric heat or with modulating hot water heat. The OE322 Analog Output Expansion board provides 3 relay outputs for pilot duty switching control, and 1 Analog output for control of a 0-10V modulating hot water valve or SCR controlled elec­tric heating coil. The expansion board is also equipped with 24 VDC (+V and GND) output terminals for powering a 24 VDC hot water valve actuator if de­sired. A 24 VAC hot water valve actua­tor can also be used but will require the use of a separate field supplied 24 VAC transformer to power the valve actuator.
The OE322 - 3 Relay W/ Analog Output Expansion board connects to the MG320–00-VAVZ controller board by means of a modular cable provided with the OE322 board. Power is supplied to the board by means of this modular ca­ble. Screw terminals are provided for connection of field wiring to the relay and analog outputs.
The relay outputs are N.O. contacts with one common terminal. All outputs and the relay common are electrically isolated from all other circuitry on the board. All relay outputs are supplied with transient suppression devices across each set of contacts to reduce EMI and arcing. The relay output contacts are rated for pilot duty control of a maximum of 2 Amps @ 24 VAC or 24 VDC. The analog output provides a 0 – 10 VDC modulating signal output into a 1k Ohm minimum load. The 24 VDC (+V and GND) output terminals are rated for control of a 24 VDC valve actuator with a maximum load rating of 12 Watts or less.
OE322 - 3 Relay W/ Analog Output
Expansion Board
3.00"
4.18"
Mounting
The OE322 - 3 Relay W/ Analog Output Expansion Board is supplied mounted on a plastic Snap Track channel. The Snap Track channel has two mounting holes which are used to field mount the board with the provided screws. The board should be mounted in close proximity to the MG320–00-VAV controller board to allow for con­nection of the modular cable.
Technical Data OE322- 3 Relay W/ Analog Output Expansion board
Operating Temp Weight 4 oz Connection to Controller: Modular Cable
Analog Output Qty. 1 Analog Output Rating 0-10 VDC @ 1k Ohm minimum load Relay Output Qty. 3 – Electrically Isolated Relay Contact Rating 2 Amp @ 24 VAC Valve Actuator Power
Terminals Voltage
Three Year Warranty
Form: WMS-OE322-3Relay-1AnOutExpBrd-1C.doc Page 1 of 1
10°F to 149°F
24 VDC 24 VDC Valve Actuator
Operating Humidity 90% RH Non-Condensing
Outputs:
12 Watts
Maximum Load
WattMaster reserves the right to change specifications without notice
Page 4
VAV System
Description
The OE352 – 2 Slot Modular I/O Base Board is used in conjunction with the fol­lowing Modular Expansion Boards:
O354 – 4 Analog Input & 1 Analog Output
OE355 – 4 Analog Output
OE356 – 4 Digital Inputs
OE357 – 4 Relay Outputs
For easy wiring the OE352 – 2 Slot Modular I/O Base Board provides for up to (2) of the above expansion boards to be connected to it by means of an integral male/female push-in connector arrange­ment. Power is supplied to the Expans ion Boards through this connector, simplifying installation and connection. Jumpers are also provided on the OE352 Modular I/O Base Board for addressing and configu­ration of the Modular Expansion Board(s).
OE352 – 2 Slot
Modular I/O Base Board
Any combination of Modular Expansion Boards may be connected to the OE352 Modular I/O Base Board to provide the input/output capabilities required.
The main controller software used with the OE352 Modular I/O Base determ ines which Modular Expansion Boards m ay be used.
Mounting
The OE352 – 2 Slot Modular I/O Base Board is supplied m ounted on a plastic Snap Track channel. T he Snap Track channel has two mounting holes, which are used to field mount the board with the provided screws. The board should be mounted in close proximity to the MG331-21-VAV HVAC Unit Controller board to allow for con­nection of the modular cable.
Technical Data
Operating Power Operating Temp
Communications Integral I2 C Chip Weight 8 oz. Qty of Slots Provided For
Modular Expansion Boards
Three Year Warranty WattMaster reserves the right to change specifications without notice
24 VAC Power Consumption 5 VA Maximum
10°F to 149°F
Operating Humidity 90% RH Non-Condensing
Mounting Provisions Supplied with
2
OE352 – 2 Slot Modular I/O Base Board
Snap Track Base
Form: WMS-OE3522SlotBaseBoard-1B.doc Page 1 of 1
Page 5
VAV System
Description
The OE353 – 4 Slot Modular I/O Base Board is used in conjunction with the fol­lowing Modular Expansion Boards:
O354 – 4 Analog Input & 1 Analog Output
OE355 – 4 Analog Output
OE356 – 4 Digital Inputs
OE357 – 4 Relay Outputs
For easy wiring the OE353 – 4 Slot Modular I/O Base Board provides for up to (4) of the above expansion boards to be connected to it by means of an integral male/female push-in connector arrange­ment. Power is supplied to the Expans ion Boards through this connector, simplifying installation and connection. Jumpers are also provided on the OE353 Modular I/O Base Board for addressing and configu­ration of the Modular Expansion Board(s).
OE353 – 4 Slot
Modular I/O Base Board
Any combination of Modular Expansion Boards may be connected to the OE353 Modular I/O Base Board to provide the input/output capabilities required.
The main controller software used with the OE353 Modular I/O Base determ ines which Modular Expansion Boards m ay be used.
Mounting
The OE353 – 4 Slot Modular I/O Base Board is supplied mounted on a plastic Snap Track channel. The Snap Track channel has two mounting holes, which are used to field mount the board with the provided screws. The board should be mounted in close proximity to the MG331­21-VAV HVAC Unit Controller board to allow for connection of the modular cable.
Technical Data OE353 – 4 Slot
Modular I/O Base Board
Operating Power Operating Temp
Communications Integral I2 C Chip Weight 8 oz. Qty of Slots Provided For
Modular Expansion Boards
Three Year Warranty
24 VAC Power Consumption 5 VA Maximum
10°F to 149°F
Operating Humidity 90% RH Non-Condensing
Mounting Provisions Supplied with
4
WattMaster reserves the right to change specifications without notice
Snap Track Base
Form: WMS-OE353-4SlotBaseBoard-1B.doc Page 1 of 1
Page 6
OE354 – 4 Analog Input/1 Analog
VAV System
Description
The OE354 - 4 Analog Input/1 Analog Output Modular Expansion Board is us ed in conjunction with the OE352 - 2 Slot Modular I/O Base Board or the OE353 - 4 Slot Modular I/O Base Board. The OE354 Expansion Board provides 4 analog in­puts and 1 analog output.
For easy wiring the OE354 – 4 Analog Input/1 Analog Output Modular Expansion Board connects to the OE352 or OE353 Modular I/O Base Boards by means of an integral connector arrangem ent. Power is supplied to the OE354 - Expansion Board through this connector, sim plifying instal­lation and connection. Jumpers are pro­vided on the OE352 and OE353 Modular I/O Base Boards for addressing of the OE354 - Expansion Board(s).
The analog inputs have removable pull­up resistors associated with each input, which can be used for connection of thermistor type sensors or dry contact closure configuration. The pull-up resis­tors are removed when a voltage signal is to be used. Jumpers are pr ovided to con­figure the inputs for either 0-5 Volt or 0-10 Volt operation. Input and output resolution is 0.4% or (0.04 Volts).
Output Modular Expansion Board
Technical Data OE354 – 4 Analog Input/1 Analog Output
Modular Expansion Board
Operating Power Operating Temp
Communications Integral I2 C Chip Weight 4 oz.
From OE352/OE353
Modular I/O Board
10°F to 149°F
Power Consumption 2 VA Maximum
Operating Humidity 90% RH Non-Condensing
Inputs:
Analog Input Qty. 4 Analog Input Types 10K Thermistor, Dry Contact, 0-10 or 0-5 Volt
Output:
Analog Output Qty. 1 Analog Output Rating 0-10 VDC @ 1K Ohm
Three Year Warranty WattMaster reserves the right to change specifications without notice
Form: WMS-OE354-4AI-1AO-ModExpBoard-1B.doc Page 1 of 1
Page 7
OE355 – 4 Analog Output
VAV System
Description
The OE355 - 4 Analog Output Modular Expansion Board is used in conjunc tion with the OE352 - 2 Slot Modular I/O Base Board or the OE353 - 4 Slot Modular I/O Base Board. The OE355 Expansion Board provides (4) 0-10 VDC analog outputs for driving actuators, valves etc.
For easy wiring the OE355 – 4 Analog Output Modular Expansion Board con­nects to the OE352 or OE353 Modular I/O Base Boards by means of an inte­gral connector arrangement. Power is supplied to the OE355 - Expansion Board through this connector, simplify­ing installation and connection. Jumpers are also provided on the OE352 and OE353 Modular I/O Base Boards for addressing of the OE355 - Expansion Board(s).
Modular Expansion Board
The analog outputs are designed to drive a 1K Ohm minim um load. All out­puts have a resolution of 1.6% or (.16 Volts).
Technical Data
Operating Power Operating Temp
Communications Integral I2 C Chip Weight 4 oz
Analog Output Qty. 4 Analog Output Rating 0-10 VDC @ 1K Ohm
Three Year Warranty WattMaster reserves the right to change specifications without notice
From OE352/OE353
Modular I/O Board
10°F to 149°F
Power Consumption 2 VA Maximum
Operating Humidity 90% RH Non-Condensing
Outputs:
OE355 – 4 Analog Output
Modular Expansion Board
Form: WMS-OE355-4AO-ModExpBoard-1B.doc Page 1 of 1
Page 8
VAV System
Description
The OE356 - 4 Digital Input Modular Ex ­pansion Board is used in conjunction with the OE352 - 2 Slot Modular I/O Base Board or the OE353 - 4 Slot Modular I/O Base Board. The OE356 Expansion Board provides 4 digital inputs f or s ensing status of connected dry contact closures or connected voltage depending on how the external equipment is wired to the digital inputs on the OE356 board.
For easy wiring the OE356 – 4 Digital In­put Modular Expansion Board connects to the OE352 or OE353 Modular I/O Base Boards by means of an integral connector arrangement. Power is supplied to the OE356 - Expansion Board through this connector, simplifying installation and connection. Jumpers ar e also provided on the OE352 and OE353 Modular I/O Base Boards for addressing of the OE356 - Ex­pansion Board(s).
OE356 - 4 Digital Input
Modular Expansion Board
The digital inputs on the OE356 share one common terminal between the 4 inputs. The comm on terminal may be connected to either 24 VAC or the 24 VAC com mon depending on how the board is to be wired to the equipment. Inputs are opti­cally isolated from other circuitry.
Technical Data OE356 – 4 Digital Input
Modular Expansion Board
Operating Power Operating Temp
Communications Integral I2 C Chip Weight 4 oz.
Digital Input Qty. 4 Digital Input Rating 24 VAC or Dry Contact Closure
Three Year Warranty WattMaster reserves the right to change specifications without notice
From OE352/OE353
Modular I/O Board
10°F to 149°F
Power Consumption 2 VA Maximum
Operating Humidity 90% RH Non-Condensing
Inputs:
Form: WMS-OE356-DigitalInput-ModExpBoard-1B.doc Page 1 of 1
Page 9
VAV System
Description
The OE357 - 4 Relay Output Modular Expansion Board is used in conjunc tion with the OE352 - 2 Slot Modular I/O Base Board or the OE353 - 4 Slot Modular I/O Base Board. The OE357 Expansion Board provides 4 relay out­puts for pilot duty switching control.
For easy wiring the OE357 – 4 Relay Output Modular Expansion Board con­nects to the OE352 or OE353 Modular I/O Base Boards by means of an inte­gral connector arrangement. Power is supplied to the OE357 - Expansion Board through this connector, simplify­ing installation and connection. Jumpers are also provided on the OE352 and OE353 Modular I/O Base Boards for addressing of the OE357 - Expansion Board(s).
OE357 - 4 Relay Output
Modular Expansion Board
The relay outputs are N.O. contacts with one common terminal. All outputs and the relay common are electrically iso­lated from all other circuitry on the board. All relay outputs are supplied with transient suppression devices across each set of contacts to reduce EMI and arcing. The relay output con­tacts are rated for pilot duty control at a maximum of 2 Amps @ 24 VAC or 24 VDC.
Technical Data OE357 – 4 Relay Output
Modular Expansion Board
Operating Power Operating Temp
Communications Integral I2 C Chip Weight 4 oz
From OE352/OE353
Modular I/O Board
10°F to 149°F
Power Consumption 2 VA Maximum
Operating Humidity 90% RH Non-Condensing
Outputs:
Relay Qty. 4 Relay Contact Rating 2 Amps @ 24 VAC
Three Year Warranty WattMaster reserves the right to change specifications without notice
Form: WMS-OE357-4RelayOutput-ModExpBoard-1B.doc Page 1 of 1
Page 10
VAV System
Description
The patented design, OE21x series Standard Room Sensor provides accurate sensing of the room temperature. Its design allows for flush wall mounting yet rejects the influence of surface and internal wall temperatures. The Standard Room Sensor is used in conjunction with the WMVAV and the VAVBOX controllers. Wire terminals are provided on the sensor for connection to the controllers.
The Room Sensor’s attractive styling and off white casing color make it suitable for most building decors. If interior decoration requires, the Room Sensor casing can also be painted or wall papered without affecting the sensor's performance. Room Sensors are available in 4 different configurations:
OE210 Sensor Plain
OE211 Sensor with Override
OE212 Sensor with Setpoint
Adjustment
OE213 Sensor with Setpoint
Adjustment and Override
3.25“
OE210, 211, 212 & 213
Standard Room Sensors
2.75“
W
A R M E R
C O O L E R
2.00“
TMP
GND
AUX OUT
4.50“
0.88“
0.25“
2.50"
Wall Cut-Out Dimensions When Sensor Is To Be Mounted Without
2.75“
Handy Box (By Others)
Modular cable from the W MVAV or VAVBOX controllers to the Modular Room Sensor should not be run in conduit with other AC line voltage wiring, or with any conductors carrying highly inductive loads.
Mounting
The Room Sensors are designed to be mounted on a vertical, 2” x 4” electrical box recessed in the wall. If the wall cannot be penetrated, a plastic surface mount box such as those made by Wiremold, may be used to mount the sensor to the wall surface.
W W A A R R M M E E R R
C C O O
OVR OVR
OE210 OE211
Room Sensor - Plain
Room Sensor With Override
Technical Data OE210, OE211, OE212, OE213 Standard Room Sensor
Sensor Element Type III Thermistor
10k ohm @ 77º F
Accuracy
±0.4º F between 40º F to 95º F
Range -30º F to 150º F Weight 4 oz.
3 Year Warranty WattMaster reserves the right to change specifications without notice
Mounting Designed to be Flush Mounted to Wall
Line Loss 0.25º F max. error, using 22 AWG wire at 1000 ft
O O L L E E R R
OE212
Room Sensor
With Setpoint Adjust
using Vertical 2” x 4” Handy Box (by others)
OE213
Room Sensor
With Setpoint Adjust
& Overide
Form: WMS-StandardRoomSensor-1B.doc Page 1 of 1
Page 11
MG392-05
r
VAV System
Description
The MG392-05 Modular System Manager provides a direct link to enable the system operator to view the status and to adjust the setpoints of any controller on the con­trol system communications loop. The Modular System Manager is designed to be used with the WattMaster VAV Control System. The System Manager is housed in an attractive beige colored plastic en­closure. The System Manager is equipped with a four line by 20 character backlighted display panel and a 24 key membrane k eypad for data selection and entry. All keypad operations are simple and straight forward, utilizing non-cryptic plain English language messages. Menu driven programm ing allows for eas y setup and operation without the need for spe­cialized training. The System Manager also has 2 integral LED’s for user notifi­cation of system alarm conditions and override initiations. Protection from un­authorized users is provided by the Sys­tem Manager’s integral multi-level pass­code authorization programming.
Modular System Manage
9.00"
System Manager
STATUS
SETPOINTS
NEXT
SCHEDULES
OVERRIDES
ALARMS
13
2
MINUS
-
PREV
6
ESC
9
4
708
DEC
5
DOWN
ENTER
UP
CLEAR
6.25"
1.81"
The Modular System Manager is con­nected to the communic ations and power loop of the system via modular cables that simply plug into the System Manager board and are pigtailed into 6 individual wires on the other end for hard wiring into a 24 VAC transformer (by others) the lo­cal communications wiring loop.
Mounting
The Modular System Manager is designed f or wall mounting. Mounting holes are provided to attach the Modular System Manager to a standard handy box. It is recomm ended that the System Manager be m ounted at approxi­mately eye level to allow for ease of programming and r eading of the display. The System Manager is typically mounted in the building manager or s uperintendent’s office or in an equipm ent room. The attractive enclosure is quite suitable for mounting in any location or with most decors.
Technical Data MGOE392-05
Modular System Manager
Power 24 Volt AC/DC Display 4 Line by 20 Character Backlighted LCD Power Consumption 5 VA Maximum Network Connection RS-485 Operating Temp
10°F to 149°F Operating Humidity 90% RH Non-Condensing Housing Material Beige Plastic Keypad 24 Key Membrane Type Communications RS-485 - 9600 Baud
3 Year Warranty WattMaster reserves the right to change specifications without notice
Protocol HSI Open Protocol Token Passing
Form: WMS-MG392-05-ModularSystemManager-1C.doc Page 1 of 1
Page 12
VAV System
Description
The MG391-05 Modular Service Tool is a system interface that provides a direct link to enable the system op­erator to view the status, configure and to adjust the setpoints of any controller on the control system communications loop. The Modular Service Tool is housed in an attrac­tive beige colored plastic enclosure. The display area is covered with a clear plastic bezel for protection of the display screen. The Modular Service Tool has a four line by 20 character display panel with adjust­able contrast control and a 27 key membrane keypad for data selection and entry. All keypad operations are simple and straight forward, utilizing non-cryptic plain English language messages. Menu driven program­ming allows for easy setup and op­eration without the need for special­ized training. The MG391-05 Modu­lar Service Tool is supplied with (4) AA (1.5V) Volt alkaline battery, a 120 VAC/5 VDC power supply and a communication cable terminated with an 8 pin DIN connector for con­nection to the Service Tool. The ca­ble allows the user to setup and pro­gram any controller equipped with a 8 pin DIN connector to be pro­grammed by simply plugging the quick connect terminal into the socket on the controller. A PL101904 Modular Service Tool Adapter is also provided for use on controllers that do not have 8 pin DIN connectors on their circuit board.
2.02"
1.63"
MG391-05
Modular Service Tool
4.75
Mode
Selection
0 0
. 0 1
13
2
654
708
9
-
The Modular Service Tool is designed to be carried by the system installer or service technician. Its rugged plastic housing, provides superior protection for the electronic components housed inside. The OE391-054 Modular Service Tool is a top quality service tool that will stand up to the demands of the typical job site environment for many years.
Technical Data MGE391-05 Modular Service Tool
Power (4) AA (1.5V) Batteries
Supplied Power Switch Membrane Switch Network Connection RS-485 Operating Temp Operating Humid-
ity Keypad 27 Key Membrane Style Communications RS-485 9600 Baud
3 Year Warranty WattMaster reserves the right to change specifications without notice
Form: WMS-MG391-05-ModularServiceTool-1C.doc Page 1 of 1
90% RH Non-Condensing Color Beige
10°F to 149°F
Display 4 Line by 20 Character
Protocol HSI Open Protocol Token Passing
Page 13
MG364-22– MiniLink
VAV System
Description
The MG364-22 MiniLink Polling Device is a network controller that is used to inte­grate multiple local communication loops into a network communications system. “Network” loop terminals on the MiniLink Polling Device are designed to be con­nected to the CommLink II and to other MiniLink Polling Devices on the ”Network” communications loop. “Local” loop termi­nals are designed to be connected to controllers installed on the “Local” com­munications loop.
The MiniLink Polling Device is provided with a 2 wire terminal block for connection to the required 24 VAC source(by others). It also has (2) 3 wire terminal blocks for communications wiring. One of the termi­nal blocks is field connected to the “Local” communications loop and the other is field connected to the “Network” commu­nications loop.
Polling Device
The MiniLink Polling Device utilizes token passing communication architecture. The MiniLink Polling Device is designed to serve as the local communications loop master. This means that it is responsible for sending the token to all the controllers on the local communications loop. Net­work communications are of the RS-485 type operating at 19,200 baud. Local communications are also of the RS-485 type and operate at on systems requiring override or alarm indication. It also pro­vides tenant-logging capabilities for the WattMaster VAV system.
MiniLink Polling Device Is Supplied Factory Mounted To
Control Enclosure. Cover Shown Removed For Clarity
Mounting
The MiniLink Polling Device is factory mounted in a galvanized sheet metal en­closure. Mounting holes are provided in the enclosure for surface mounting.
Technical Data MGE364-22 – MiniLink
Polling Device
Power 24 Volt AC System Connection Molex® Connectors & Terminals Power Consumption 6VA Maximum Network Connection RS-485 Operating Temp Operating Humidity 90% RH Non-Condensing Housing Material 22 Ga. Galvanized Steel Communications RS-485 - 9600 Baud, Local Communications RS-485 - 19200 Baud, Network
3 Year Warranty WattMaster reserves the right to change specifications without notice
10°F to 149°F
Protocol HSI Open Protocol Token Passing
Form: WMS-MG364-22MiniLinkPollingDevice-1B.doc Page 1 of 1
Page 14
VAV System
Description
The OE361 - CommLink II Communica­tions Interface allows user ac cess to any controller connected to the controls sys­tem. The CommLink II comes packaged in an attractive beige colored plastic en­closure. The Comm Link II is powered by a small wall mounted plug-in transfor mer that is included. Locally, an optional on­site computer may be connected to the CommLink II for direct access to system control parameters. Remote access is obtained via an optional modem which is connected with the CommLink II Com­munication Interface. With a modem in­stalled, the CommLink II may be config­ured to call a number, if an alar m condi­tion occurs. With the modem option the system could be dialed and monitored from a remote location by a PC. Com­puter and modem cables (6ft long) are provided with the CommLink II.
OE361 – CommLink II
Communications Interface
Mounting
If an on-site computer is to be used for direct connection and monitoring of the system, the CommLink II should be lo­cated near the computer terminal to monitor the system. If no on-site com­puter is to be used, locate the Comm Link II near the phone line jack for ease of connection to a modem. If for any reason you use cables of greater length than those provided with the CommLink II (6 ft. long) be sure the cables that connect the CommLink II to the modem and the CommLink II to the on-site computer do not exceed twenty-five feet in length.
Technical Data OE 361 - CommLink II Communication Interface
Power 24 Volt AC Computer Connection RS-232 Plug-in Transformer 110V to 24V (Included) Network Connection RS-485 Power Consumption 14 VA Maximum Protocol HSI Open Protocol Token Passing Operating Temperature Operating Humidity 90% RH Non-Condensing Communications RS-485 - 9600 Baud
Three Year Warranty WattMaster reserves the right to change specifications without notice
10°F to 140°F
Physical Connections (2) 9 Pin/DB9 Male
Form: WMS-OE361-CommLink-1B.doc Page 1 of 1
Page 15
1.50
7.00
REAR VIEW
FRONT VIEW
VAV System
Description
The OE361-08 CommLink III Communi­cations Interface allows com puter access into the WattMas ter VAV controls system and also provides communications across multiple local communications loops on the control system.
The CommLink III comes pac kaged in an attractive beige colored plastic enclos ure. The Comm Link III is powered by a small wall mounted plug-in transformer that is included. Locally, an optional on-site Per­sonal Computer with Prism software in­stalled may be connected to the CommLink III to provide direct access to system control parameters by using the supplied USB cable (6 ft. long).
Remote telephone access to the control system can be obtained via the optional OE419-05 Modem Kit which can be field installed inside the CommLink III Com­munication Interface. With the optional modem kit installed, the control system can be accessed remotely by using a Remote Link modem (purchased sepa­rately) connected to a Personal Computer with Prism software installed at the re­mote location and dialing the phone num­ber of the phone line the CommLink III with modem kit is c onnected to. Also with the modem k it installed the CommLink III can be configured to call a pager or cell phone number, if an alarm condition oc­curs. A USB cable (6ft long) is provided with the CommLink III for connection to your computer.
OE361-08 CommLink III
Communications Interface
5.25
Mounting
If an on-site c omputer is to be used for direct c onnection and monitoring of the system, the Comm Link III s hould be located near the c omputer term inal to m onitor the system . If no on-site com puter is to be used and/or you are installing the optional modem kit, locate the CommLink III near the phone line jack for ease of connection.
Technical Data OE361-08 CommLink III Communication Interface
Power 24 Volt AC Computer Connection USB Version 1.1 or 2.0 Plug-in Transformer 110V to 24V (Included) Network Connection RS-485 Power Consumption 14 VA Maximum Protocol HSI Open Protocol Token Passing Operating Temperature Operating Humidity 90% RH Non-Condensing Communications RS-485 - 9600 Baud
Three Year Warranty WattMaster reserves the right to change specifications without notice
Form: WMS-OE361-08-CommLinkIII-01A.doc Page 1 of 1
10°F to 140°F
Cabling Included (1) 6 Ft. Long USB Cable
Page 16
1.50
7.00
REAR VIEW
FRONT VIEW
VAV System
Description
The OE361-12 Comm Link IV Communi­cations Interface allows com puter acc es s into the WattMas ter VAV controls system and also provides communications across multiple local communications loops on the control system.
The CommLink IV comes packaged in an attractive beige colored plastic enclo­sure. The Com mLink IV is powered by a small plug-in transf ormer that is included. Locally, an optional on-site personal computer with Prism software installed may be connected to the CommLink IV to provide direct access to system con­trol parameters. A USB cable ( 6 ft. long) is provided with the CommLink IV for connection to your computer.
Remote telephone acces s to the control system can be obtained by purchasing the optional OE419-06 Remote Link II modem. With the optional Rem ote Link II modem installed, the c ontrol system can be accessed remotely by using another Remote Link II m odem (purchas ed sepa­rately) connected to a personal computer with Prism software installed at the re­mote location. W ith the Remote Link in­stalled at the job site, the Com mLink IV can be configured to call a pager or cell phone number if an alarm condition oc­curs.
OE361-12 CommLink IV
Communication Interface
5.25
An optional OE415-02 IP Module Kit is also available that provides an Ethernet connection to the controls system from any computer connected to your build­ing’s LAN. It can also be configured to allow access to the control system from the Internet if your Ethernet firewall is configured for this option.
Mounting
If an on-site computer is to be used for direct c onnection and monitoring of the system, the CommLink IV should be located near the c omputer term inal to m onitor the system . If no on-site com puter is to be used and/or you are installing the Remote Link II option, locate the CommLink IV near the phone line jack for ease of connection.
Technical Data OE361-12 CommLink IV Communication Interface
Power 24 Volt AC *Remote Link II Conn. RS-232 Serial Port (9 pin) Plug-in Transformer 120V to 24VAC (Included) **Ethernet Conn. RJ-45 Ethernet Port Power Consumption 14 VA Maximum Network Loop RS-485 - 19,200 Baud Operating Temperature Operating Humidity 90% RH Non-Condensing Cabling Included (1) 6 Ft. Long USB Cable Computer Conn. USB Version 1.1 or 2.0 Local Loop RS-485 - 9600 Baud
Three Year Warranty
* This Port Is Only Used With The Optional OE419-06 Remote Link II. ** This Port Is Only Used With The Optional OE415-02 IP Module Kit.
Form: WMS-CLKIV-SUB-01A-0907 Page 1 of 1
10°F to 140°F
Protocol HSI Open Protocol Token Passing
WattMaster reserves the right to change specifications without notice
Page 17
VAV System
OE366 USB-Link
Description
The OE366 USB-Link allows com puter access into the WattMaster VAV controls system and also pro­vides communications across multiple local com­munications loops on the control system when a CommLink Communications Interface is installed on the system.
The USB-Link provides a direct link to enable the system operator to view the status and to configure and adjust the setpoints of any controller on the control system communications loop using the Prism II computer front end software.
The USB-Link is small in size and is powered by the USB port of the computer it is plugged into, making it com pletely portable and allowing connec­tion to the system from any controller.
The USB-Link is supplied with a USB cable, a mini­DIN male com munication cable, and two mini-DIN to terminal adapters. The communication cable allows the user to walk up to any controller that has a communication s ocket and plug in the USB-Link to gain access to the system. The adapters are used for boards that do not have a f emale mini-DIN plug connection.
To use the USB-Link, you will need a computer with an available USB 1.1 or 2.0 port with the in­cluded USB drivers installed. You will also need the Prism II computer front end software installed on the computer.
CAUTION: The USB-Link does not work with Prism I software. It only works with Prism II.
Technical Data OE366 USB-Link
Operating Temperature Operating Humidity 90% RH Non-Condensing Communications RS-485 - 9600 Baud
Computer Connection USB Version 1.1 or 2.0 Adapters Included PL1019054 and PL101905 Mini-DIN
Three Year Warranty
10°F to 140°F
Cabling Included (1) 6 Ft. Long USB Cable and
(1) 7 Ft. Long Communications Cable
Plug Adapters
WattMaster reserves the right to change specifications without notice
Form: WMS-OE366-USB-Link-01A.doc Page 1 of 1
Page 18
VAV System
w
w
Description
The OE419-04 Remote Link is essen­tially a 14,400 baud modem. The Re­mote Link is used f or achieving remote communications with all WattMaster VAV systems. Built in error correction (V.42/mnp 2-4) and data compression (V.42bis/mnp 5) will maximize data transfer integrity and boost average throughput up to 57.6 kbps. The Re­mote Link connects to the Com mLink II communications interface at the Orion control system location. A telephone line connects the Remote Link to the local phone service. By dialing the telephone number that the Remote Link is con­nected to, (using a modem from a re­mote location) the Orion system can be monitored and controlled using the WattMaster Prism computer front end software package.
OE419-04 Remote Link
1
4
5"
R
em
ote
Lin
k
SIG
DET
RDY
SND
REC
PWR
Front Vie
7"
1
2
1"
Mounting
The Remote Link should be mounted close to a serviceable telephone outlet. It connects via a serial data cable to the CommLink II communications interface and via a telephone cable to the tele­phone outlet jack. A molded cable for connection from the CommLink to the Remote Link is supplied with the CommLink . If an on-site com puter is re­quired, it should be connected to the CommLink at or near the location where the Remote Link is located. If for any reason you use cables of greater length than those provided with the CommLink II (6 ft. long) be sure the cables that connect the CommLink II to the Remote Link and the Comm Link II to the on-site computer do not exceed twenty-five feet in length.
SERIAL #
TELCO
LINE
SERIAL DATA
POW
ER
Rear Vie
Technical Data
OE419-04 Remote Link
Power 9 Volt DC Computer Connection RS-232, 25 Pin DB25 Female Plug-in Transformer 110V to 9V (Included) Phone Connection RJ-11 Female Power Consumption 500mA Maximum Line Speed 14,400 bps Operating Temperature
10°F to 140°F
Data Compression V.42bis/MNP 5
Operating Humidity 90% RH Non-Condensing Error Correction V.42/MNP 2-4
WattMaster reserves the right to change specifications without notice
3 Year Warranty
Form: WMS-OE419-SUB-01B Page 1 of 1
Page 19
1.50
7.00
REAR VIEW
FRONT VIEW
VAV System
OE419-06 Remote Link II
Description
The OE419-06 Remote Link II is essentially a 14,400 baud modem that connects to the CommLink IV via a serial cable. W hen it is
5.25
used as a modem ( at the remote com puter location) it connects to the remote com­puter via a USB cable. The Remote Link II is used to provide for rem ote dial-up com­munications with the CommLink II or CommLink IV communication interfaces.
The Remote Link II connects to the CommLink II or IV communications inter­face at the control system loc ation. A tele­phone line connects the Remote Link II to the local phone service. By dialing the tele­phone number at the job site that the Re­mote Link II is connected to (using another Remote Link II m odem from a r em ote loca­tion), the control system can be monitored and controlled using the Prism computer front end software package.
Mounting
The Remote Link II should be mounted close to a serviceable telephone outlet. The CommLink II or CommLink IV communica­tions interface connects to the Remote Link II with the supplied 6 ft. long serial cable.
It is recommended that a second Remote Link II be used as the dial out modem at the remote computer location. WattMaster will not support any other internal or exter­nal modems by other manuf ac turer s. A 6 ft. long USB cable is supplied with the Re­mote Link II to connect to the remote com­puter USB port when the Remote Link II is used at the remote c omputer loc ation. If an on-site computer at the job location is re­quired, it should be connected to the CommLink II or IV at or near the location where the Remote Link II is located, f or ease of connection. If you need to use a longer serial or USB cable, you will need to purchase these from an elec tronics supply store. Do not use any USB or serial cables longer than 25 ft.
Technical Data
Power 9 VDC Plug-in Transformer 120 VAC to 9 VDC
Power Consumption 500mA Maximum Phone Connection RJ-11 Female Operating Temperature Operating Humidity 90% RH Non-
CommLink Connection 6 ft. - Serial Cable Error Correction V.42/MNP 2-4
3 Year Warranty
Form: WMS-OE419-06-RemoteLnkII-01A.doc Page 1 of 1
OE419-06 Remote Link II
(Included)
10°F to 140°F
Condensing
Computer Connection For Remote Modem Use
Line Speed 14,400 bps Data Compression V.42bis/MNP 5
WattMaster reserves the right to change specifications without notice
6 ft. USB Cable For Use With
USB Version 1.1 or 2.0 Ports
Page 20
VAV System
9VDC
10BaseT
OE415 IP-Link Kit
Description
The OE415 IP-Link Kit is used to provide TCP/IP Internet and/or intranet connec­tion for Ethernet networked computer systems allowing them to communicate with the WattMaster VAV System through
V
R
T
K
C
C
E
N
R
A
S
L
the Commlink. The OE415 IP-Link Kit Includes the IP-Link device with serial cable, 110/9 Volt power supply, iLan EPROM for the CommLink, WattMaster Prism software CD and documentation, Connect One firmware and documenta­tion CD, and the IP-Link Technical Guide
Computer Front End Software & Manual
and installation instructions. The TCP/IP connection provided on the
IP-Link is a TCP connection on a single port number and is static in nature. Firewall and proxy servers can easily be configured to allow traffic to and from the IP-Link. The nature of the data is raw in form and comprised of packets native to WattMaster Prism software. The IP-Link device will respond to ICMP traffic (PING) for verification of proper configuration. Prism software is required in order to read and send data to the IP-Link and through the CommLink to the WattMaster VAV system. The CommLink must have the included iLan EPROM chip installed to communicate with the WattMaster VAV system. The IP-Link connects to the CommLink via the supplied RS232 DB9 Serial Cable. The IP-Link connects to the host Ethernet system by means of a 10BaseT, RJ-45 jack on the back of the IP-Link. Power is provided to the IP-Link by the 110/9 Volt Power supply furnished in the kit. The kit also contains a firmware CD used for set­ting up the IP-Link. Setup of the IP-Link requires a knowledgeable IT person familiar with configuring network adapters and TCP/IP systems. WattMaster Prism software is included for installation to the local intranet or re­mote Internet PC(s) that will be used to program and monitor the WattMaster VAV system.
onnect
C
Documentation
C
ne
PWR
Firmware &
onnect
www.connectone.com
ne
3.25
onnect
0 5
T
.
C
A
1
C
V
R
K
C
E
N
R
S
L
ne
PWR
5.25
Serial
Mode
Technical Data OE415 IP-Link Kit
Power Supply 9 Volt VDC, 350mA System Connection RS-232 DB9 Female Serial Port Power Consumption 2 Watts Network Connection 10BaseT Ethernet – RJ-45 MDI Socket Operating Temp
32°F to 158°F
Operating Humidity 90% RH Non-Condensing Standard Compliance Ethernet IEEE 802.3 10BaseT Data Rate Up to 230 Kbps Flow Control Hardware (DTR, RTS, CTS, DCD) and
1 Year Warranty WattMaster reserves the right to change specifications without notice
Form: WMS-OE415-IP-Link Ki-1A.doc Page 1 of 1
Internet Protocols ARP,IP,ICMP,UDP,TCP,DNS,DHCP,
SMTP, POP3, MIME, HTTP
Software
Page 21
4
VAV System
OE415-02 IP Module Kit
Description
The OE415-02 IP Module Kit (when installed and configured in the Comm Link IV communication in­terface) provides TCP/IP Internet and/or intranet
1.28”
connection for Ethernet networked computer sys­tems allowing them to comm unicate with your con­trol system. The OE415-02 IP Module Kit consists of the IP Module and a 10 ft. long CAT5 Ethernet crossover cable.
1.3
The IP Module plugs into a mating 40 pin (2 x 20) connector located on the CommLink IV circuit board. Installation is easily accomplished by re-
IP Module
moving the CommLink IV case cover screws, re­moving the case cover to acc ess the circuit board, and then plugging the IP Module into its mating socket connector. Corr ect alignment is made easy because of the (4) slot alignment tabs located around the perimeter of the processor base. It is not possible to incorrectly align the IP Module to the socket connector because of this feature.
The TCP/IP connection provided by the IP Module installed in the CommLink IV is a TCP connection on a single port number and is static in nature. Firewall and proxy servers can easily be configured to allow traffic to and fr om the Comm Link IV when the IP Module is installed. The nature of the data is raw in form and comprised of packets native to Prism software. The IP Module will respond to ICMP traffic (PING) for verification of proper con-
CAT5 Ethernet Cable
figuration. Prism software is required in order to read and send data to the IP Module and through the CommLink IV to the control system. The IP Module connects to the host Ethernet system by means of the supplied 10 ft. long CAT 5 Ethernet crossover cable which plugs into the 10/100 Base­T, RJ-45 jack on the back of the Comm Link IV and into a Ethernet router or Ether net modem on your building’s LAN. Setup of the Comm Link IV with the IP Module requires a k nowledgeable IT person fam iliar with configuring network adapters and TCP/IP system s. Prism software must be installed on the local LAN c omputer(s) and/or remote Internet computers that will be used to program and monitor the control system.
Technical Data
Operating Temperature Operating Humidity 90% RH Non-Condensing Network Connection 10/100 Base-T Ethernet
Protocols Supported ARP, UDP, TCP, Telnet,
Network Interface IEEE 802.3 RJ45 Ethernet
3 Year Warranty
Form: WMS-OE415-02-IPModuleKit-01A.doc Page 1 of 1
OE415-02 IP Module Kit
10°F to 140°F
ICMP, SNMP, DHCP, BOOTP,
Auto IP, HTTP, SMTP, TFTP
10BASE-T Or 100BASE-TX
(Auto-sensing)
Media Access Control CSMA/CD with ACK
RJ-45 MDI Socket
Flow Control XON/XOFF (Software), CTS/RTS
(Hardware), None
Management Internal Web Server, SNMP (Read
Only), Serial Login, Telnet Login,
Device Installer Software
WattMaster reserves the right to change specifications without notice
Page 22
OE310-21-LP
g
r
VAV System
Description
The OE310-21-LP Lighting Controller allows an Orion Control System to also control the building lighting systems along with the HVAC system. The Lighting Controller is provided with 7 schedules, each providing 2 start/stop events per day and 14 start/ stop holi­day events. Lighting Controller sched­ules are designed to operate from a starting time, a contact closure or a per­centage light level as sensed by a (0-
1.5kohm, 0-100%) light level sensor, thus providing maximum lighting control flexibility. As an example, a lighting schedule could be programmed to allow the lighting circuit to come on at dusk, based on a light sensor and then turned off at a given time during the night based on a time schedule. With the Lighting Controller, lighting schedules may be overridden to “on” with a user provided pushbutton. This pushbutton is wired to the analog input that corre­sponds to the schedule number, on the Lighting Controller. Schedule override time periods are programmed from the Orion Prism program. Lighting Control­ler output relays may be configured for continuous ON mode during the occu­pied schedule or a short pulse when the schedule starts and another short pulse when the schedule ends. Pulsed output requires an optional Expansion Relay Board and a GE equivalent lighting relay. The Lighting Controller may be connected to any local loop at any point on the Orion system. Orion Prism computer front end software is used to interface with the Lighting Panel Controller functions. The Lighting Controller cannot be programmed through the System Manager operator interface.
9.00
7.63
7.13
CPU
RAM
Li
hting Controlle
GND
+5V
SIG
ANALOG
INPUTS
+V +V
1
2 3 4 5 6 7 8 G G
ANALOG
OUTPUTS
EPROM
PIN 1PIN 1
PAL
A1 A2
G
PIN 1PIN 1
8.25
RR-7 or RR-9 or
1.00
Mounting
The Lighting Controller is provided with an integral backplate for mounting inside of a control enclosure. It is rec­ommended that Lighting Controller be mounted in the in a control enclosure in the building equipment room. An optional factory control enclosure for the Lighting Controller is available.
Technical Data OE310-21-GPC
GPC-17 Controller
Power 24 Volt AC Weight 1.5 lb. Power Consumption 10 VA Maximum Network Connection RS-485 Operating Temp
10°F to 149°F
Protocol HSI Open Protocol Token Passing
Operating Humidity 90% RH Non-Condensing Communications RS-485 - 9600 Baud
Inputs: Outputs:
Types Allowed Type Provided Continuous Contact Closure or
Connected to Analog Input
by Others)
be Programmed to Follow or
Total Inputs Available 1 Total Outputs Available 7
Three Year Warranty WattMaster reserves the right to change specifications without notice
Form: WMS-OE310-21-LightingController-01A.DOC Page 1 of 1
Pushbutton Override
#8 (N.O. Binary Contact
All Schedules May
Not Follow the Override
Start Pulse and Stop Pulse
for Each of the 7 Schedules
(N.O. Binary Contact)
Relay Power Rating 2 Amp @ 24 VAC
Page 23
VAV System
A
OE331-21-GPC Plus
GPC Plus Controller
Description
The OE331-21 General Purpose Con­troller Plus (GPC Plus) is used for con­trolling equipment or processes that can­not be controlled using HVAC controllers. The Prism computer front end software is used to interface with the GPC Plus con­troller functions. The GPC Plus Controller provides the flexibility to control, schedule and/or monitor equipment such as unit heaters, exhaust fans, motorized louvers, etc.. The GPC Plus has (6) configurable inputs which will accept signals from thermistor temperature sensors, 4-20mA or 0-5VDC transmitters or dry contact closures. An additional modular input is provided for connection of an OE271 static pressure sensor. The GPC Plus has (5) relay outputs for on/off control and (2) analog outputs. With the addition of the OE352 2 Slot Expansion Base Board and (1) OE357 4 Relay Expansion Board, (4) additional relay outputs are available providing for a maximum of (9) usable relay outputs. The GPC Plus also has (5) separate 2 event per day sched­ules, each with its own optimal start func­tions built in. In addition the GPC Plus provides lead/lag start capabilities.
.20 Dia. Typ. of 4
7.3”
TB1
COMM
T
SHLD
R
LD6
COMM
LD7 PWR
LD8
LED1
LD9
LED2
R1
INPUTS
+VDC AIN1 AIN2 AIN3
AIN4 AIN5
GND
GND AOUT1 AOUT2
AIN7
GND
PJ1
TB3
PRESSURE SENSOR
C21
RN1
1
CX5
1
RN3
+VREF
TEST POINT
U7
RV1 VREF ADJ
EXPANSION
6.2“
CX1
U1
U5
RS-485
COMM
HH
C1
P1
5.11V
EWDOG
R28
RN5
PU1 D6 PU2 D7 PU3 D8 PU4 D9 PU5 D11 PU7
C10
D14
C12
D15
C17
C20
R26
PJ2
U3
CX2
U2
EPROM
RAM
TUC-5R PLUS
(1 MEG)
YS101816 REV. 2
U6
C2
PHILIPS
C3
ADD
DDRESS
1 2 4 8
16
CX10
32 TOKEN NETWORK
U10
SW1
C11
X2
0-5
0-1
VDC
VDC
JP1
U13
R15
U12
CX14
C14
R19
U14
CX13
U15
C15
R22 R24 R25
CX15
D17
PJ3
T'STAT
6.7”
D1
CX3
CX4
U4
RLY1
RLY2RLY3RLY4RLY5
PAL
1
RN2
CX6
X1
1
RN4
U9
C7
R7
D10
CX12
D12 R13
SC1
D19
D18
C19
C18
VR1
VR2
V1
D2D3D4D5
V2
V3
COM1-3
R1 R2 R3 R4 R5
COM4-5
TB2
V4
V5
U8
NE5090NPB3192 0PS
CX8
R6
L1
C9
R10
D13
9936
R11
U11
MC34064A
C13
C16
TB4
GND
R27
D16
V6
POWER
7824CT
24VAC
M
6.6”
1.1”
Mounting
The GPC Plus is provided with an integral backplate for mounting inside of a control enclosure. It is recom­mended that the GPC Plus be mounted in the HVAC unit control enclosure, or in a control enclosure in the building equipment room. An optional factory control enclosure for the GPC Plus is available.
Technical Data OE331-21-GPCPLUS
GPC Plus Controller
Power 24 Volt AC Weight 1.5 lb. Power Consumption 8 VA Maximum Network Connection RS-485 Operating Temp
10°F to 149°F
Operating Humidity 90% RH Non-Condensing Communications RS-485 - 9600 Baud
Inputs: Outputs:
Types of Allowed Inputs
Total Inputs Available 7 Analog Output Qty. 2 Static Pressure Inputs 1 (Modular ) Analog Output Signal 0-10 VDC Configurable Inputs 6 Optimal Start Schedules (5) Total - (1) for Each Schedule Schedules Available (5) 2 Event per day Lead Lag Scheduling (1) Output can be Configured
Three Year Warranty WattMaster reserves the right to change specifications without notice
Type III-10kohm sensors Total Relay Qty. On Board 5
4-20ma sensors N.O. Binary Contact N.C. Binary Contact Relay Power Rating (2 Amp @ 24 VAC)
Protocol HSI Open Protocol Token Passing
Total Relay Qty. Available With Optional Expansion Board
9
Form: WMS-OE331-21-GPCPlusController-01A.doc Page 1 of 1
Page 24
OE310-21-GPC
r
VAV System
GPC-17 Controlle
Description
The GPC-17 Controller is used for con­trolling equipment or processes that can­not be controlled using standard HVAC Unit controllers. The WattMaster Prism computer front end software is used to interface with the GPC-17 controller func­tions. The GPC-17 is designed with 6 uni­versal inputs, 7 binary outputs and 2 analog output. Each input can be config­ured for use with a Type III-10k ohm thermistor temperature sensor, 4-20ma sensor, 0-5 VDC sensor or a N.O. or N.C.
9.00
binary contact closure. Sensor reading values can be selected for the specific input type, such as, %RH, Deg. F, RPM, etc.. If a thermistor type temperature sen­sor is used, a calibration option is avail­able to offset the actual temperature in relation to the displayed reading. It also has one input configures for Duct Static Pressure and one configured for Building Pressure. The 7 binary outputs may be configured to operate based on any of the 8 sensor inputs, outdoor air temperature, the GPC-17 controller’s internal schedule or an external schedule. They can also be configured to use AND/OR logic state­ments. A Relay Expansion Board can be connected to the GPC-17 to give it an extra 8 relay outputs. In addition to the relay outputs the GPC-17 contains two 0­10VDC analog outputs which can be configured for simple floating point or PID control. The analog output can also be configured to operate based on any of the 8 sensor inputs, outdoor air temperature, the GPC-17 control­ler’s internal schedule or an external schedule. In addition an Analog Output Expansion Board can be connected to the GPC-17, giving it two additional analog outputs.
7.63
7.13
RAM
CPU
EPROM
PIN 1PIN 1
PAL
GND
+5V
SIG
ANALOG
INPUTS
+V +V
1
2
3 4 5 6 7
8 G G
ANALOG
OUTPUTS
A1 A2
G
PIN 1PIN 1
8.25
1.00
Mounting
The GPC-17 is provided with an integral backplate for mounting inside of a control enclosure. It is recommended that the GPC-17 be mounted in the HVAC unit control enclosure, or in a control enclosure in the building equip­ment room. An optional factory control enclosure for the GPC-17 is available.
Technical Data OE310-21-GPC
GPC-17 Controller
Power 24 Volt AC Weight 1.5 lb. Power Consumption 10 VA Maximum Network Connection RS-485 Operating Temp
10°F to 149°F
Protocol HSI Open Protocol Token Passing
Operating Humidity 90% RH Non-Condensing Communications RS-485 - 9600 Baud
Inputs: Outputs:
Types Allowed Type III-10kohm sensors Relay Qty. 7
4-20ma sensors Relay Power Rating (2 Amp @ 24 VAC)
N.O. Binary Contact Analog Output Qty. 2
N.C. Binary Contact Analog Output Signal 0-10 VDC
Total Inputs Available 8
Three Year Warranty WattMaster reserves the right to change specifications without notice
Form: WMS-OE310-21-GPC-17Controller-01A.doc Page 1 of 1
Page 25
A
VAV System
Description
The OE331-21-KWH (Kilowatt Hour)
OE331-21-KWH
KWH Module
Module provides the ability to record and display KW usage and to limit demand. Using the Prism Graphical Computer Front End, a status screen displays cur­rent demand, yesterday’s demand, and the peak demand values and times for both. Historical logs from the previous month and the current month are also available and can be downloaded for archiving via the PRISM software inter­face. A running total of power consump­tion is also displayed on the Status Screen. This value can be manually re­set at any time allowing the user to moni­tor overall power consumption over long periods of time.
Analog Input #2 on the KWH Module monitors all incoming contact closures from a KW pulse meter (usually provided by the utility company) and times them to generate the current KW Demand. A user adjustable setpoint is provided to
.20 Dia. Typ. of 4
7.3”
TB1
COMM
T
SHLD
R
LD6
COMM
LD7 PWR
LD8 LED1
LD9 LED2
R1
U7
INPUTS
+VDC
AIN1 AIN2 AIN3
AIN4
AIN5
GND
GND AOUT1
AOUT2
AIN7
GND
PJ1
TB3
PRESSURE SENSOR
C21
RN1
1
CX5
1
RN3
+VREF
TEST POINT
RV1 VREF ADJ
C10
EXPANSION
6.2“
CX1
U1
U5
RS-485
COMM
HH
C1
P1
5.11V
EWDOG
R28
RN5
PU1 D6 PU2
D7 PU3
D8 PU4
D9 PU5
D11 PU7
D14
C12
D15
C17
C20
R26
PJ2
U3
CX2
U2
EPROM
RAM
TUC-5R PLUS
(1 MEG)
YS101816 REV. 2
U6
C2
PHILIPS
C3
ADD
DDRESS
1 2 4 8
16
CX10
32 TOKEN NETWORK
U10
SW1
C11
X2
0-5
0-1
VDC
VDC
JP1
U13
R15
U12
CX14
C14
R19
U14
CX13
U15
C15
R22
R24
R25
CX15
D17
PJ3
T'STAT
6.7”
D1
CX3
CX4
U4
RLY1
RLY2RLY3RLY4RLY5
PAL
1
RN2
CX6
X1
1
RN4
U9
C7
R7
D10
L1
CX12
D12 R13
SC1
D19
D18
C19
C18
VR1
VR2
V1
D2D3D4D5
V2
V3
COM1-3
R1 R2 R3
R4
R5
COM4-5
TB2
V4
V5
U8
NE5090NPB3192 0PS
CX8
R6
C9
R10
D13
9936
R11
U11
MC34064A
C13
C16
TB4
GND
R27
D16
V6
POWER
7824CT
24VAC
M
6.6”
1.1”
define what each pulse represents in Kilowatts Per Hour. A Demand Factoring Constant is also provided if it appears that contact bounce may be affecting the operation. The Demand Factor is simply the number of times to average the current demand reading to create the final Demand Reading. It is nor­mally left at a value of '1' unless a problem is encountered.
Two additional setpoints are provided for the EMS Demand Limiting Broadcast. A Limit Setpoint and a Propor­tional Reset Range are provided so that the user can adjust when to begin shedding demand and how rapidly this occurs. Any controllers equipped to "hear" this broadcast begin spreading their heating and cooling setpoints proportionally until the maximum EMS Adjustment limit is reached. This value is also user adjustable for each individual controller so that the rate at which demand is shed can be optimally configured for special cases where not all zones can tolerate a large change in temperature.
Mounting
The KWH Module is provided with an integral backplate for mounting inside of a control enclosure. It is recom­mended that the KWH Module be mounted in the HVAC unit control enclosure, or in a control enclosure in the building equipment room. An optional factory control enclosure for the KWH Module is available.
Technical Data OE331-21-KWH
KWH Module
Power 24 Volt AC Weight 1.5 lb.
Power Consumption 8 VA Maximum Network Connection RS-485
Operating Temp
10°F to 149°F
Protocol HSI Open Protocol Token Passing
Operating Humidity 90% RH Non-Condensing Communications RS-485 - 9600 Baud
Input Available Output Available
AIN2 Dry Contact Closure from
KW Pulse Meter (By Others)
Three Year Warranty WattMaster reserves the right to change specifications without notice
Form: WMS-OE331-21-KWH-Module-01A.doc Page 1 of 1
RS-485 Communications Loop EMS Demand Limiting
Broadcast
Page 26
VAV System
Description
The OE510-XX-VAV Pressure Depend­ent Round Damper consists of a round air damper, MG320-VAV controller, and OE282 damper actuator. An optional auxiliary relay board (OE321) is avail­able for control of auxiliary heat and/or
1/2" Foil Faced Insulation
OE510-XX-VAV – Pressure
Dependent Round Damper
Round Damper Blade Assembly
Zone Controller
control of series or parallel flow fan ter­minal units.
The MG320-VAV Zone Controller is
W
A
O
IR
L
F
F
L R I
O
A
W
microprocessor based and communi­cates with the HVAC Unit Controller on the WMVAV communications loop. The VAV Controller monitors the space tem­perature and allocates the proper air-
Actuator
flow into its assigned space to achieve the desired comfort and ventilation lev­els.
Control Enclosure (Cover Removed)
Pressure Dependent Round Dampers are used in air conditioning systems that do not require pressure independent airflow control. If your system requires pressure independent control of the airflow, see the “OE511 - Pressure Independent Round Damper” data sheet for the correct specifications.
All Round Dampers are tested and certified in accordance with ARI standard 880. An ARI label is affixed to all units.
Mounting
The Round Damper assembly should be mounted according to standard duct installation practices with airflow direction as shown in the illustration above. After installation of the Round Damper in the ductwork, insulation should be applied around any remaining uninsulated surface on the air valve inlet and outlet. The Round Damper should be mounted so the control enclosure is positioned to the left or right side of the ductwork with the control enclosure in a vertical plane. Do not mount the Round Damper Assembly with the control enclosure on the top or bottom of the ductwork. Adequate clearance should be maintained between the control panel and any obstruc­tion to allow for removal of the control panel cover and access to the controls.
Technical Data
OE510-XX-VAV Pressure Dependent
VAV Controller: Air Damper Construction:
Supply Power 24 Volt AC Damper Body 24 Ga. Galv. Steel Power Consumption 12 VA Maximum Damper Blade Round -18 Ga. Galv. Steel Operating Temperature
35°F to 125°F
Damper Bearings Oil Impregnated Bronze Operating Humidity 90% RH Non-Condensing Damper Seal Communications RS-485 - 9600 Baud Leakage Less Than 1% @ 3” SP
Insulation ½” Foil Faced Fiberglass
Inputs: Dimensions:
Room Temperature Sensor Setpoint Adjustment OE520-06 (6”) 19.00 5.88 9.38 Actuator Position Feedback OE520-08 (8”) 19.00 7.88 11.38
Outputs:
Expansion Port for Auxiliary Relay Board OE520-14 (14”) 22.00 13.88 17.38 Actuator Port for Connection to Damper Actuator OE520-16 (16”) 22.00 15.88 19.38
WattMaster reserves the right to change specifications without notice
Three Year Warranty On Electronic Components One Year Warranty On Air Damper
Air Damper Model “A” “B” “C”
OE520-10 (10”) 19.00 9.88 13.38
OE520-12 (12”) 22.00 11.88 15.38
Round Damper
Volara® Type A Gasket
Form: WM-OE510-RndDmpr-Sub-01A Page 1 of 2
Page 27
VAV System
OE510-XX-VAV – Pressure
Dependent Round Damper
Round Damper Sizing
Use a load program to determine the peak load for each zone. These calculations will be used to select Round Damper sizes.
The WMVAV System utilizes a typical low pressure duct design. To reduce noise prob­lems, duct pressures should not exceed 1” W.C.
Primary trunk ducts used with WMVAV sys­tems should not be “undersized”. This is es­pecially true of “pressure dependent” sys­tems. With larger trunk ducts, it is easier to assure relatively constant pressure to each Round Damper. Runs should be as short as possible, and the trunk duct system kept as symmetrical as possible to facilitate system balancing. Wherever possible, run the trunk ducts above corridors and locate the Round Dampers above corridors to reduce the noise in the space and facilitate service of the valves. Trunk ducts should be sized for no more than 0.1” W.C. drop per 100 ft. of duct, and a maximum duct velocity of 2000 FPM.
Using the maximum acceptable velocity for a branch duct (typi­cally 1000-1500 FPM for minimal noise), find the smallest Round Damper that will deliver the required CFM as determined by the load program. Locate the branch velocity used in the duct design program in the left hand column of the Round Damper Selection Data table. Move across the table and find the Round Damper, which will provide the acceptable CFM to meet the zone airflow requirements.
Note: Compare the Round Damper size selected against
the duct size to determine if the next size up or down will provide acceptable performance without requiring a transition fitting.
Round Damper Selection Data
Round Damper Round Duct Size
(Area Ft
Velocity Through Round Damper
FPM
500
750
1000
1250
1500
1750
2000
2
)
WattMaster reserves the right to change specifications without notice
6”
(0.188)
94
(0.01)
141
(0.03)
188
(0.05)
235
(0.07)
282
(0.09)
329
(0.12)
376
(0.15)
OE510-XX-VAV Pressure Dependent
8”
(0.338)
10”
(0.532)
12”
(0.769)
Airflow Through Round Damper - CFM
(ΔP
inches W.C. w/ Damper Full Open)
S
169
(0.01)
254
(0.02)
338
(0.03)
423
(0.04)
507
(0.06)
592
(0.08)
676
(0.10)
266
(0.01)
399
(0.01)
532
(0.02)
665
(0.03)
798
(0.04)
931
(0.06)
1064
(0.07)
385
(0.01)
577
(0.02)
769
(0.03)
961
(0.04)
1154
(0.05)
1346
(0.06)
1538
(0.07)
Round Damper
14”
(1.050)
525
(0.01)
788
(0.01)
1050
(0.02)
1313
(0.03)
1575
0.04) 1838
(0.05)
2100
(0.07)
16”
(1.375)
687
(0.01)
1031
(0.01)
1375
(0.01)
1718
(0.02)
2062
(0.03)
2405
(0.04)
2749
(0.05)
Form: WM-OE510-RndDmpr-Sub-01A Page 2 of 2
Page 28
VAV System
Description
The OE511-XX-VAV Pressure Independ­ent Round Damper consists of a round air valve, MG320-VAV zone controller, OE282 damper actuator, airflow sensor and a
1/2" Foil Faced Insulation
OE511-XX-VAV–Pressure
Independent Round Damper
Round Damper Blade Assembly
Zone Controller
crossflow air pickup probe. An optional auxiliary relay board (OE321) is available for control of auxiliary heat and/or control of series or parallel flow fan terminal units.
W
A
IR
LO
F
F LO
IR
A
W
The MG320-VAV Zone Controller is micro­processor based and communicates with the HVAC Unit Controller on the WMVAV communications loop. The VAV Controller monitors the space temperature and allo-
Actuator
cates the proper airflow into its assigned space to achieve the desired comfort and ventilation levels.
Control Enclosure (Cover Removed)
The Pressure Independent Round Damper is used in systems that require pressure independent airflow control. If your system does not require pressure independent control, please see the “OE510 Pressure Dependent Round Damper” data sheet for the correct specifications.
All Round Dampers are tested and certified in accordance with ARI standard 880. An ARI label is affixed to all units.
Mounting
The Round Damper assembly should be mounted according to standard duct installation practices with airflow direction as shown in the illustration above. After installation of the Round Damper in the ductwork, insulation should be applied around any remaining uninsulated surface on the air valve inlet and outlet. The Round Damper should be mounted so the control enclosure is positioned to the left or right side of the ductwork with the control enclosure in a vertical plane. Do not mount the Round Damper with the control enclosure on the top or bottom of the ductwork. Adequate clearance should be maintained between the control panel and any obstruction to allow for removal of the control panel cover and access to the controls.
Technical Data
VAV Controller: Air Damper Construction:
Supply Power 24 Volt AC Damper Body 24 Ga. Galv. Steel Power Consumption 12 VA Maximum Damper Blade Round -18 Ga. Galv. Steel Operating Temperature Operating Humidity 90% RH Non-Condensing Damper Seal Communications RS-485 - 9600 Baud Leakage Less Than 1% @ 3” SP
35°F to 125°F
Damper Bearings Oil Impregnated Bronze
Insulation ½” Foil Faced Fiberglass
Inputs: Dimensions:
Zone Temperature Sensor Setpoint Adjustment OE521-06 (6”) 19.00 5.88 9.38
Actuator Position Feedback OE521-08 (8”) 19.00 7.88 11.38 Air Flow Sensor OE521-10 (10”) 19.00 9.88 13.38
Outputs:
Expansion Port for Auxiliary Relay Board OE521-14 (14”) 22.00 13.88 17.38
WattMaster reserves the right to change specifications without notice
Three Year Warranty On Electronic Components One Year Warranty On Air Damper
Air Damper Model “A” “B” “C”
OE521-12 (12”) 22.00 11.88 15.38
OE521-16 (16”) 22.00 15.88 19.38
OE511-XX-VAV Pressure Independent
Round Damper
Volara® Type A Gasket
Form: WM-OE511-RndDmpr-Sub-01A Page 1 of 2
Page 29
VAV System
Round Damper Sizing
Use a load program to determine the peak load for each zone. These calculations will be used in selecting the appropriate zone damper sizes.
The WMVAV System utilizes a typical low pressure duct design. To reduce noise problems, duct pressures should not ex­ceed 1” W.C.
Primary trunk ducts used with WMVAV sys­tems should not be “undersized”. This is especially true of “pressure dependent” sys­tems. With pressure independent systems this is not as critical. With larger trunk ducts, it is easier to assure relatively constant pressure to each Round Damper. Runs should be as short as possible, and the trunk duct system kept as symmetrical as possible to facilitate system balancing. Wherever possible, run the trunk ducts above corridors and locate the Round Dampers above corridors to reduce the noise in the space and facilitate service of the valves. Trunk ducts should be sized for no more than 0.1” W.C. drop per 100 ft. of duct, and a maximum duct velocity of 2000 FPM.
OE511-XX-VAV–Pressure
Independent Round Damper
With pressure independent systems it is possible to exceed this rule by up to 50%. However it is advised that unless you are ex­perienced with VAV duct design the 2000 FPM rule should be used. Using the maximum acceptable velocity for a branch duct (typically 1000-1500 FPM for minimal noise), find the smallest damper that will deliver the required CFM as determined by the load program.
Locate the branch velocity used in the duct design program in the left hand column of the Round Damper Selection Data table. Move across the table and find the damper, which will provide the acceptable CFM to meet the zone airflow requirements.
Note: Compare the Round Damper size selected against
the duct size to determine if the next size up or down will provide acceptable performance without requir­ing a transition fitting.
Round Damper Selection Data
Round Damper Round Duct Size
(Area Ft
CFM @ 1” Velocity Pressure (Air Flow Probe “K” Factor)
Velocity Through Round Damper
FPM
500
750
1000
1250
1500
1750
2000
2
)
WattMaster reserves the right to change specifications without notice
OE511-XX-VAV Pressure Independent
Round Damper
6”
(0.188)
474 950 1417 2120 2908 3700
8”
(0.338)
10”
(0.532)
12”
(0.769)
14”
(1.050)
16”
(1.375)
Airflow Through Round Damper - CFM
(ΔP
inches W.C. w/ Air Damper Full Open)
S
94
(0.01)
141
(0.03)
188
(0.05)
235
(0.07)
282
(0.09)
329
(0.12)
376
(0.15)
169
(0.01)
254
(0.02)
338
(0.03)
423
(0.04)
507
(0.06)
592
(0.08)
676
(0.10)
266
(0.01)
399
(0.01)
532
(0.02)
665
(0.03)
798
(0.04)
931
(0.06)
1064
(0.07)
385
(0.01)
577
(0.02)
769
(0.03)
961
(0.04)
1154
(0.05)
1346
(0.06)
1538
(0.07)
525
(0.01)
788
(0.01)
1050
(0.02)
1313
(0.03)
1575
0.04) 1838
(0.05)
2100
(0.07)
687
(0.01)
1031
(0.01)
1375
(0.01)
1718
(0.02)
2062
(0.03)
2405
(0.04)
2749
(0.05)
Form: WM-OE511-RndDmpr-Sub-01A Page 2 of 2
Page 30
VAV System
r
OE255 & OE256 – CO2Senso
Description
The OE255 & OE256 CO2 Sensors are used in conjunction with various other WattMaster controllers to monitor and control CO
levels in the building envi-
2
ronment. Some typical applications are:
Controlling ventilation in a building
where the occupancy varies fre­quently
Controlling ventilation to ensure ex-
cess outside air is not causing en­ergy waste
To ensure good air distribution
throughout building zones
The OE256 is used for monitoring room
levels and is designed for wall
CO
2
mounting in the required space. The OE255 is designed to be mounted on the return air duct of the HVAC unit and in­cludes a aspiration box with a probe that samples air from the return air stream.
3-1/4"
1-1/8"
5-5/8"
Both models use the patented dual beam Absorption Infrared
technology. This technology provides a very accu­rate and stable sensor that is guaranteed to maintain its accuracy for a minimum of 5 years between calibrations. The OE255 & OE256 CO
Sensors accuracy is ± 50 ppm @1000 ppm. Annual drift is 10 ppm per year. Repeat-
2
ability is ±20 ppm.
Application
Both models utilize a sub-base mounting plate with terminal blocks providing for quick and easy mounting and wiring. The OE256 wall mounted sensor’s sub-base is compatible with standard junction boxes for ease of wall mounting and wiring. A locking screw secures the whole assembly to the wall. The OE255 duct mounted sensor has a enclosure with pickup probe assembly that is mounted to the ductwork. The standard sensor sub-base and housing is then attached to the enclosure to provide for secure mounting of the sensor. The OE255 also is sup­plied with a clear enclosure cover to seal the sensor from dust and dirt.
Technical Data OE255 & OE256 – CO2 Sensor
Input Power 18-30 VAC RMS, 50/60 Hz
Half Wave Rectified Operating Temperature Sample Method Diffusion Or Flow –through
Sensitivity Analog Output 0-10 VDC
One Year Warranty WattMaster reserves the right to change specifications without notice
32°F to 122°F
50-100 ml/min
±10 ppm
4-20 mA
Power Consumption 1.75 VA Maximum Average
2.75 VA Peak Power Operating Humidity 0-95% RH Non-Condensing Measurement Range 0 to 2000 ppm
(Adjustable to 10,000 ppm). Resolution Agency Certification FCC Part 15 Class B
±1 ppm
Form: WMS-OE255-6-CO2Sensor-1B.doc Page 1 of 3
Page 31
VAV System
r
OE255 & OE256 – CO2Senso
2-7/8''
2-3/8''
2-3/8''
4-1/4''
3-3/4''
4. Relay Common
5. Relay Norm Closed
6. 4-20mA Output
3. Relay Norm Open
1. - Not Used
2. - Not Used
7. Signal Ground
8. 0-10V Output
Pin Designations
1. AC+/DC+
2. AC/GND
CO2 Sensor Sub-base
(Used On OE255 & OE256)
Pin Designations
3-1/2''
3-1/4''
5-1/16''
4-1/4''
8''
Aspiration Tube
1-1/8''
7''
Shown W/ Cover Removed
6-1/2''
1-1/16'' and 1-1/8'' Knockouts
7/8'' Knockouts
Aspiration Box
(Included & Used With OE255 Only)
Form: WMS-OE255-6-CO2Sensor-1B.doc Page 2 of 3
Page 32
VAV System
r
Sensor Mounting Base
OE255 & OE256 – CO2 Senso
Clear Cover
Sensor & Sub-base
CO
2
Aspiration Tube
OE255 – Duct Mounted CO2 Sensor Assembly
For optimum sensing, the 3 holes located on the inlet tube must face the duct airflow.
OE255 – Duct Mounted CO2 Sensor Mounting
Form: WMS-OE255-6-CO2Sensor-1B.doc Page 3 of 3
Page 33
VAV System
r
Description
The OE258 Building Static Pressure Sen­sor is used to sense building pr essure in applications where monitoring of the building static pressure is required to in­sure the building maintains the proper air pressurization.
OE258 – Building Pressure Senso
0.95
MODEL 265
0.156 DIA. HOLE TYP. 2 PL.
The OE258 Building Pressure Sensor case is molded from fire retardant glass filled polyester. The sensor utilizes a ten­sioned stainless steel diaphragm and in­sulated stainless steel electrode. This arrangement allows up to 10 PSI over­pressure without damage to the unit. T he sensor provides a 0.0 to 5.0 VDC output in response to a –0.25 to +0.25 inch WC pressure differential. Ac curacy is ± 1% of full scale of the sensor.
For easy wiring the OE258 Building Static Pressure Sensor has (3) 6- 32 screw ter­minal wiring connectors. The sensor has (2) ¼” barbed fittings provided for the connection of tubing to the high and low pressure ports.
The OE258 Static Pressure Sensor is designed to be mounted to a flat surf ace by means of the (2) 0.156 diam eter holes provided in the sensor casing. For accu­rate readings the sensor must be mounted in a vertical position.
2.74
HIGH
setra
LOW
-
0.95
+
1.89
3.16
+
+
1.64
Technical Data OE258 - Building Static
Pressure Sensor
Operating Pressure Range
Operating Temp Circuit 3 Wire Non-repeatability Accuracy
Three Year Warranty WattMaster reserves the right to change specifications without notice
Form: WMS-OE258-6-BuildingPressureSensor-1B.doc Page 1 of 1
-0.25” WC to +0.25” WC Pressure Differential
0°F to 150°F
± 1% of full scale
Power Input Signal Output Hysteresis
Weight 3 ounces
± 0.1% of full scale
± 0.05% of full scale
9-30 VDC
0 to 5 VDC
Page 34
VAV System
r
Description
The OE282 Damper Actuator is a shaft mounted, floating point control actuator. Actuators are 24VAC/24VDC with a 10K ohm feedback signal for position monitor­ing. Wiring connection to the actuator is by means of a modular phone cable connector located on the actuator cover. The actuator is rated for 35 in-lb of torque. All actuators are electronically protected against over­load. The angle of rotation is mechanically limited to 95°. When the end position of the actuator or damper is reached, the actuator automatically stops. For adjustment pur­poses, the gears can be manually disen­gaged by pushing the manual override button on the actuator cover.
Applications
The OE282 Damper Actuator is used to provide control of air volume dampers in the WattMaster VAV systems. It is gener­ally used in conjunction with an MG3204­00-VABOX controller board.
OE282 - Damper Actuato
Mounting
The Damper Actuator is designed to fit ei­ther a 3/8” diameter or 1/2” diameter damper shaft. T he Damper Actuator slides over the damper shaft through its integral U-bolt clamp and is then tightened in place using the 2 nuts provided on the U-bolt clamp.
Technical Data OE282
Damper Actuator
Power Supply Life Cycle Rating 2.5 Million Cycles with Mechanical Stops Power Consumption 3 VA Maximum Power Connection RJ-11 Modular Jack Operating Temp Operating Humidity 5 to 95% RH Non-Condensing Quality Standard ISO 9001 Overload Protection
Feedback Signal 10K ohm 1W Potentiometer Torque Minimum 35 in-lb Running Time 80-110 Seconds. Weight 1.2 lb.
Three Year Warranty WattMaster reserves the right to change specifications without notice
24VAC ± 20% 50/60HZ
-22°F to 122°F
Electronic Throughout 0 to 95° Rotation
Angle of Rotation
Servicing Maintenance Free
Agency Listings UL873 listed
Max. 95°, Adjustable
CSA 4813 02 Certified
Form: WMS-OE282-DamperActuator-1B.doc Page 1 of 1
Page 35
OE271 - For
Applications
0-5” H O Pressure Range - 5 VDC Operation
2
Minimum Typical Maximum
Full Scale Output (Positive Pressure)
Null Offset
Span*
Non-Linearity
Hystereisis And Repeatability
Temperature Error
Null +10 To 40 C°° Span +10 To 40 C°°
Stability (1 Year)
Supply Voltage (Vs)
Common Mode Pressure
Pressure Overload
Positive Pressure (Hi Side) Negative Pressure (Lo Side)
Burst Pressure
Positive Pressure (Hi Side) Negative Pressure (Lo Side)
*Span Is The Algebraic Difference Between End Points (Null OffsetAnd Full Scale Output)
3.92 VDC
0.17 VDC 0.2-0.3 VDC 0.33 VDC
3.59 VDC 3.91 VDC
4.75 VDC 5.0 VDC
Requiring 0-5” H O Pressure Range
3.95-4.05 VDC
3.65-3.85 VDC
±0.3 % Span ±0.5 % Span
±0.03 % Span
±1.0 % Span ±1.0 % Span
±0.5 % Span
Airflow Sensor
2
4.08 VDC
±0.05 % Span
±1.5 % Span ±1.5 % Span
8.0 VDC
15 PSI
25“ H O
2
15“ H O
2
50“ H O
2
25“ H O
2
1.29"
2.94"
0.15"
2.50"
2.20"
IN (Red)
GND
OUT
IN
UP
OE271
S.P. Sensor
(-)LO
Top View
12.0" APPROX.
OUT (Black)
GND (Green)
0.15" DIA.
0.60"
0.200" (3/16" Tubing Conn.)
0.125" (1/8" Tubing Conn.)
Warning!
The plastic housing on the sensor is electrically conductive. Avoid contact with any electrical components. It is acceptable to mount the sensor on grounded sheet metal such as ductwork, electrical panels, etc.
Warning!
Use extreme care when mounting the sensor to avoid damage to the plastic housing. Do not overtighten the mounting screws! Do not use mounting screws which are too large for the holes!
General Notes
Caution:
1.) The Airflow Sensor Should Be Mounted In A Vertical Position As Shown With Arrow Pointing Up. ( Tubing Connections Pointing Down). If This Mounting Position Is Not Possible In Your Application, It May Be Mounted In A Horizontal Position. When Mounted In A Horizontal Position Accuracy Will Be Affected By Approximately 2% Full Scale Null Shift Due To Diaphragm Gravity Effect Error.
Duct Static Pressure Sensor Applications Mounting Information
When The OE271 Is Used As A Duct
Pressure Sensor
Ductwork Near The Static Pressure Pickup Tube. If The Sensor Is Mounted In This Manner, Away From The Controller, The Modular Plug Must Be Cut Off And 3-conductor 24 Gauge Minimum Wire Must Be Butt Spliced Between The Sensor And The Modular Plug To Extend The Sensor Wire Length. Total Wire Length Should Not Exceed 100Ft. If Desired The Sensor May Also Be Located Near The Controller, With The Modular Plug On The Sensor Directly Connected To The Mating Controller Jack. When This Method Is Used Tubing Must Be Run From The Sensor To The Static Pressure Pickup Tube. Tubing Should Not Exceed 250 Ft. And Must Be Continuous Without Any Splices.
It May Be Mounted To The
0.35"
2.)All Wiring To Be In Accordance With Local And National Electrical Codes And Specifications.
VAV Pressure Independent Airflow Sensor Applications Mounting Information
Static
When The OE271 Is Used As An Airflow For VAV Applications It Should Be Mounted In The VAV Box Control Enclosure Near The Box Controller Board. The Modular Plug should be Connected To The VAV Controller Board Connection. Tubing Must Be Run From The Sensor to The Airflow Pickup Probe Tubing Connection.
G-OE271TRAN1.CDR
DATE:
PAGE
1
FILENAME
08/19/08
1.95"
Side View
Sensor
JOB NAME
DRAWN BY:
DESCRIPTION:
OE271
Pressure Sensor
0.55"
1.00"
B. CREWS
Page 36
OE230 (6" Probe) & OE231 (12" Probe)
Caution!
The Duct Sensor Is Used For Sensing Supply Or Return Air Temperatures. Location Of The Sensors Is Very Important In Order To Obtain Accurate Temperature Readings. The Following Recommendations Should Be Followed:
Supply Air
When Used As A Supply Air Sensor The Sensor Should Be Mounted In The Supply Air Duct As Close To The HVAC Unit As Possible And Upstream Of The Bypass Damper (If Used) For Best Results. For Best Accuracy, Apply Insulation On The Outside Of The Ductwork Over The Sensor. This Will Help Thermal Gradients From Affecting The Sensor.
Return Air
When Used As A Return Air Sensor The Sensor Should Be Mounted In The Return Air Duct As Close To The HVAC Unit As Possible And Upstream Of The Bypass Damper (If Used) For Best Results. For Best Accuracy, Apply Insulation On The Outside Of The Ductwork Over The Sensor. This Will Help Thermal Gradients From Affecting The Sensor.
See The Systems Installation And Operation Manual For Other Design Considerations And Recommendations Regarding Duct Temperature Sensor Location.
Duct Temperature Sensors
Thread Together
5-1/2" (OE230)
11-1/2" (OE231)
Leads Are Non-polarized. Butt Splice Leads To 24 Gauge Wire Minimum. Connect Leads To "Analog In" And "Ground" At Controller.
4.0"
3/4"
Mounting Plate
1/4" Hex Head Sheet Metal Screws
Mounting Plate
Gasket
Adhesive Backed Drill Guide Mounting Template
Duct Work
Temp Resistance* Voltage
F Ohms @ Input*
°
-10.............93333 ........4.620
-5...............80531 ........4.550
0 ...............69822 ........4.474
5 ...............60552 ........4.390
10..............52500 ........4.297
15..............45902 ........4.200
20..............40147 ........4.095
25..............35165 ........3.982
30..............30805 ........3.862
35..............27140 ........3.737
40..............23874 ........3.605
*Chart Notes:
1. Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered).
2. Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts. Place the "-"(minus) lead on GND terminal and the "+"(plus) lead on the sensor input terminal being investigated. If the voltage is above 5.08 VDC, the sensor or wiring is "open." If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.
Notes:
1.)All Wiring To Be In Accordance With Local And National Electrical Codes And Specifications.
Drill 5/16" Hole In Ductwork For Probe
Temperature Sensor Resistance/Voltage Chart
Temp Resistance* Voltage
F Ohms @ Input*°
45..............21094 ........3.470
50..............18655 ........3.330
52..............17799 ........3.275
54..............16956 ........3.217
56..............16164 ........3.160
58..............15385 ........3.100
60..............14681 ........3.042
62..............14014 ........2.985
64..............13382 ........2.927
66..............12758 ........2.867
68..............12191 ........2.810
Temp Resistance* Voltage
F Ohms @ Input*°
69..............11906 ........2.780
70..............11652 ........2.752
71..............11379 ........2.722
72..............11136 ........2.695
73..............10878 ........2.665
74..............10625 ........2.635
75..............10398 ........2.607
76..............10158 ........2.570
78..............9711 ..........2.520
80..............9302 ..........2.465
82..............8893 ..........2.407
Temp Resistance* Voltage
F Ohms @ Input*
°
84..............8514 ..........2.352
86..............8153 ..........2.297
88..............7805 ..........2.242
90..............7472 ..........2.187
95..............6716 ..........2.055
100............6047 ..........1.927
105............5453 ..........1.805
110............4923 ..........1.687
115............4449 ..........1.575
120............4030 ..........1.469
125............3656 ..........1.369
JOB NAME
FILENAME
G-DUCSENS1.CDR
DATE:
04/25/02
PAGE
1
DESCRIPTION:
OE230 & OE231
Duct Temperature Sensor
DRAWN BY:
B. CREWS
Page 37
Static Pressure Pickup Tube OE290
Connect This End Of Tubing To “Hi” Port Of Pressure Sensor
1/4“ O.D. X 3/16” I.D. x 14” Long - Fire Rated Tubing Slide Over 1/4“ Barb Fitting Tubing Not To Exceed 250 Ft. Length. Do Not Splice Tubing.
1/8“ MPT Threaded Pipe
Thread Together
1/4“ Barb Fitting
3/4"
2-3/4“
1/4" Hex Head Sheet Metal Screws
Drill 5/16" Hole In Ductwork For Probe
Mounting Plate
Mounting Plate
Gasket
Adhesive Backed Drill Guide Mounting Template
Duct Work
4.0"
Caution!
In Order To Obtain Accurate Static Pressure Readings The Static pressure Pickup Probe Should Be Mounted Per The Following Recommendations:
1.)The Probe Should Be Mounted In a Straight Section Of Ductwork Approx. 2/3 The Length Of the Supply Duct, Downstream Of The HVAC Unit.
2.)The Probe Should Not Be Mounted Less Than 3 Duct Diameters Downstream Or Not Less Than 2 Duct Diameters Upstream Of Any Elbow or Takeoff.
See The Systems Installation And Operation Manual For Other Design Considerations And Recommendations Regarding Static Pressure Pickup Tube Location.
Notes:
1.)The Static Probe(OE290) Is Supplied With A 14“ Length Of Tubing For Connection To The Static Pressure Sensor. The Static Pressure Sensor (OE271) Is Designed To Be Mounted Adjacent To The Location Where The Static Pickup Tube Is Mounted And Wired Back To The Controller Board. The Static Pressure Sensor Can Also Be Mounted Close To The Controller Board And Tubing (By Others) Routed From The Sensor To The Static Pickup Probe. Be Sure Not To Kink The Tubing Between The Static Pickup Probe And The Static Pressure Sensor.
FILENAME
G-SPUTUBE1.CDR
04/29/02
DATE:
PAGE
1
Static Pressure Pickup Tube
JOB NAME
DRAWN BY:
DESCRIPTION:
OE290
B. CREWS
Page 38
Gasketed Cover
CAUTION! See Note 3
2.88“
Cover Mounting Screw
- Typ.
2.25“
0.19 Dia. Hole Typ.
3.19“
Closure Plug
CAUTION! See Note 2
Mounting Bar & Screws - Typ.
4.63“
6.00
3.50“
1/2
Wiring Terminal. Connect Wiring To Controller Using 24 Gauge Minimum Wire. Only 2 Conductors are Required.
Sensor Tube
CAUTION! See Note 1
Closure Plug
CAUTION! See Note 2
1.63"
Front View Side View Back View
See Note #1
Incorrect
Correct
Sensor Mounting
Postion
Outside Air Relative Humidity Sensor OE265-03
*Chart Notes:
1. Be sure that +24VDC power is being supplied to the sensor. For voltage measurement s meter to DC Volts. C board that is connected to the sensor. The input on the controller board must have a 250 ohm resistor to ground installed and have it’s associated pull-up resistor removed for the sensor to function properly. For current measurement set the ammeter to DC Amps and connect the meter’s lead in series with the T1 terminal on the sensor. Use an accurate humidity measurement device to determine RH (relative humidity) such as an aspirating psychrometer. Use the Output VDC column to read the Output Voltage or the Output mA column to read the Output Amperage corresponding with the RH percentage measured with the psychrometer. If the measured voltage or amperage is within 3% of what is listed for the corresponding RH, then the sensor is functioning properly.
Notes:
1.)The Outside Air Sensor Must Be
Mounted In A Horizontal Position As Shown (Sensor Tube Pointing Left or Right with Slots Pointing Down).
Water Must Not Be Allowed To Stand In Sensor Tube. Rainwater Will Damage Sensor.
Be Located Where It Will Not Be Affected By Direct Sunlight Or Heat Producing Equipment. If Possible Mount Under Roof Eave Or Similar Protected Location. If Sensor Is Not Located As Specified, Erroneous Outside Air Humidity Readings Will Result.
onnect the meter between ground and the input terminal on the controller
2.)Unused Conduit Opening(s) Must Have Closure Plugs Installed And Must Be Coated with Sealing Compound To Provide Raintight Seal. Rainwater Will
Damage Sensor!
Sensor Must
3.)Gasket Must Be Installed Under Cover Plate To Provide Raintight Seal.
Rainwater Will Damage Sensor!
4.)All Wiring To Be In Accordance With Local And National Electrical Codes And Specifications.
et the
Humidity Sensor Current/Voltage Chart
RH Output* Output
%
0 ...............4.00 ...........1.00
5 ...............4.80 ...........1.20
10..............5.60 ...........1.40
15..............6.40 ...........1.60
20..............7.20 ...........1.80
25..............8.00 ...........2.00
30..............8.80 ...........2.20
35..............9.60 ...........2.40
40..............10.40 .........2.60
45..............11.20 .........2.80
50..............12.00 .........3.00
mA VDC*
FILENAME
G-OA-HUMID1.CDR
DATE:
05/14/01
PAGE
1
Outside Air Humidity Sensor
RH Output* Output
% mA VDC*
55..............12.80 .........3.20
60..............13.60 .........3.40
65..............14.40 .........3.60
70..............15.20 .........3.80
75..............16.00 .........4.00
80..............16.80 .........4.20
85..............17.60 .........4.40
90..............18.40 .........4.60
95..............19.20 .........4.80
100............20.00......... 5.00
JOB NAME
DRAWN BY:
DESCRIPTION:
OE265-03
B. CREWS
Page 39
VAV System
Description
The OE265-06 Wall Mounted Humidistat is used with the WMVAV controller to initi­ate dehumidification mode when the rela­tive humidity rises above the user adjust­able setpoint.
The Wall Mounted Humidistat is adjustable for relative humidity between 10% to 90% with a differential relative humidity of 5%.
OE265-06 – Wall Mounted
Humidistat
2.88"
1.63”
The electrical switch on the Humidstat is a snap-acting SPDT type. The switch is rated
% Relative Humidity
40 60 80
20
at 8 Amps resistive load and 60 VA pilot duty load at 24 VAC.
3.31”
4.38”
The Humidistat is enclosed in an attractive beige plastic housing with a removable cover. The cover face is of brushed bronze with relative humidity markings indicating relative humidity setpoints between 10% to 90%. A removable dial is provided for the adjustment of the relative humidity set­point. The Humidistat is also provided with
Mounting Holes In Humidistat Base
a blank cover plate to facilitate tamper proof installations. The external setpoint cover plate is first removed and then the blank cover plate is installed. An Allen screw and 5/64” Allen wrench is also pro­vided to complete the tamper proof hard­ware..
Six inch long color coded leads are pro­vided on the back of the Humidistat base for wiring connections. A green grounding lead is provided for grounding requirements.
Mounting
The Humidistat can be mounted to a electrical handy box using the provided screws. It can also be mounted di­rectly to the wall if your wiring codes allow for mounting of 24 Volt devices without a handy box. Mounting screws for direct wall mounting must be provided by others.
Technical Data
Humidity Sensing Element
Control Dial Settings 10 to 90% RH Location NEMA 1 Indoor Locations Only Differential 5% RH Housing Beige Plastic with Brushed Bronze Cover
Operating Humidity 5% to 95% RH Non-
Operating Temp
Three Year Warranty
Form: WMS-OE265-06-Humidistat-1A.doc Page 1 of 1
Nylon Ribbon Electrical Switch Snap acting SPDT Rated at 8 Amps
Connections 6” Long Color Coded Wire Leads with
condensing
40°F to 125°F
Weight 1 Lb.
WattMaster reserves the right to change specifications without notice
OE265-06 Wall Mounted Humidistat
Resistive Load. 60 VA Pilot Duty Load
Plate. Also includes Tamper Proof Cover
Plate and Tamper Resistant Hardware
Ground Wire
Page 40
OE265-07 – Duct Mounted
VAV System
Description
The OE265-07 Duct Mounted Humidistat is used with the HVAC unit controller to initiate dehumidification mode when the relative humidity in the return air duct rises above the user adjust­able setpoint. The Duct Mounted Humidistat is designed to be mounted on the side of the HVAC unit return air duct.
The Duct Mounted Humidistat is adjustable for relative humidity setpoints between 15% to 95%. The Duct Mounted Humidistat has a relative humidity differential of 5%.
The electrical switch on the Duct Mounted Humidstat is of the snap-acting SPDT type. The switch is rated at 8 Amps resis­tive load and 345 VA pilot duty load at 120 VAC.
4.75”
6.50”
3
0
2
0
1
% HUMIDITY
6
50
0
4
0
Humidistat
2.24"
0
7
0
8
0
9
0
1.25"
2.81"
The Humidistat is enclosed in a metal housing with a removable cover and duct mounting plate. The mounting base plate face is labeled with relative humidity markings indicating relative humidity setpoints between 15% to 95%. A dial knob is provided for the adjustment of the relative humidity setpoint. The dial knob can be locked at the setpoint position by tightening the dial lock screw to facilitate tamper proof installations.
Color coded wiring terminals are provided for wiring connections to the humidistat. A green grounding lead is provided for grounding requirements.
Mounting
The Duct Mounted Humidistat is designed to be mounted on the side of the HVAC unit return air duct. 4 screws are provided for mounting the humidistat to the return air duct. A mounting template is also provided to help lo­cate the mounting holes and the duct cut-out on the duct wall.
Technical Data
Humidity Sensing Element
Control Dial Settings 15 to 95% RH Location NEMA 1 Indoor Locations Only Differential 5% RH Housing Painted Metal Operating Humidity 5% to 95% RH Non-
Operating Temp
Three Year Warranty
Nylon Ribbon Electrical Switch Snap acting SPDT Rated at 8 Amps
Connections Color Coded Wire Terminals with Ground
condensing
40°F to 125°F
Weight 1.5 Lb.
WattMaster reserves the right to change specifications without notice
OE265-07 Duct Mounted Humidistat
Resistive Load. 345 VA Pilot Duty Load
Terminal
Form: WMS-OE265-07-Humidistat-1A.doc Page 1 of 1
Page 41
Gasketed Cover
CAUTION! See Note3
2.88“
Cover Mounting Screw
- Typ.
2.25“
8.00“
0.19 Dia. Hole Typ.
3.19“
Closure Plug
CAUTION! See Note 2
4.63“
0.38“
Front View
Wiring Terminal. Connect Wiring To Controller Using 24 Gauge Minimum Wire. Only 2 Conductors are Required.
Side View
Return Air Relative Humidity Sensor OE265-04
Humidity Sensor Current/Voltage Chart
RH Output* Output
%
0 ...............4.00 ...........1.00
5 ...............4.80 ...........1.20
10..............5.60 ...........1.40
15..............6.40 ...........1.60
20..............7.20 ...........1.80
25..............8.00 ...........2.00
30..............8.80 ...........2.20
35..............9.60 ...........2.40
40..............10.40 .........2.60
45..............11.20 .........2.80
50..............12.00 .........3.00
*Chart Notes:
1. Be sure that +24VDC power is being supplied to the sensor. For voltage measurement s meter to DC Volts. C board that is connected to the sensor. The input on the controller board must have a 250 ohm resistor to ground installed and have it’s associated pull-up resistor removed for the sensor to function properly. For current measurement set the ammeter to DC Amps and connect the meter’s lead in series with the T1 terminal on the sensor. Use an accurate humidity measurement device to determine RH (relative humidity) such as an aspirating psychrometer. Use the Output VDC column to read the Output Voltage or the Output mA column to read the Output Amperage corresponding with the RH percentage measured with the psychrometer. If the measured voltage or amperage is within 3% of what is listed for the corresponding RH, then the sensor is functioning properly.
mA VDC*
onnect the meter between ground and the input terminal on the controller
RH Output* Output
% mA VDC*
55..............12.80 .........3.20
60..............13.60 .........3.40
65..............14.40 .........3.60
70..............15.20 .........3.80
75..............16.00 .........4.00
80..............16.80 .........4.20
85..............17.60 .........4.40
90..............18.40 .........4.60
95..............19.20 .........4.80
100............20.00......... 5.00
et the
3.50“
1/2
Back View
Mounting Sensor to Duct
Mounting Tab & Screw - Typ.
See Note #1
Notes:
1.)The Sensor Should Be Mounted so that the 8“ Probe is in the Center of the Return Air Duct. It Should be Mounted Away from Fans, Elbows, Heating or Cooling Coils or Other Equipment that Could Affect the Measurement of Relative Humidity. Also, the Sensor Should be Mounted in an Area that Receives Adequate Air Flow for Accurate Operation. The Sensor may be Mounted Horizontally or Vertically to the Return Air Duct..
2.)Unused Conduit Opening(s) Must Have Closure Plugs Installed to Prevent Dust or Insects Infiltrating the Sensor Electrical Box..
3.)TheSensor Probe Gasket Must Be Installed Between the Back of the Sensor Box and the Duct to Provide an Airtight Seal.
4.)All Wiring To Be In Accordance With Local And National Electrical Codes And Specifications.
FILENAME
G-HUMSRIR1.CDR
DATE:
04/25/02
PAGE
1
Return Air Humidity Sensor
JOB NAME
DRAWN BY:
DESCRIPTION:
OE265-04
B. CREWS
Page 42
3.23”
1.25"
OptionalCustomer SuppliedHandibox
CoverMounting 1/16”AllenScrews
FrontView
WallMountRelativeHumiditySensor OE265-01
HumiditySensorCurrent/VoltageChart
RHOutput*Output
%
0...............4.00...........1.00
5...............4.80...........1.20
10..............5.60...........1.40
15..............6.40...........1.60
20..............7.20...........1.80
25..............8.00...........2.00
30..............8.80...........2.20
35..............9.60...........2.40
40..............10.40.........2.60
45..............11.20.........2.80
50..............12.00.........3.00
*ChartNotes:
1.Besurethat+24VDCpowerisbeingsuppliedtothesensor.For voltagemeasurementsonnectthe meterbetweengroundandtheinputterminalonthecontroller boardthatisconnectedtothesensor.Theinputonthecontroller boardmusthavea250ohmresistortogroundinstalledandhave it’sassociatedpull-upresistorremovedforthesensortofunction properly.ForcurrentmeasurementsettheammetertoDCAmps andconnectthemeter’sleadinserieswiththeT1terminalonthe sensor.Useanaccuratehumiditymeasurementdeviceto determineRH(relativehumidity)suchasanaspirating psychrometer.UsetheOutputVDCcolumntoreadtheOutput VoltageortheOutputmAcolumntoreadtheOutputAmperage correspondingwiththeRHpercentagemeasuredwiththe psychrometer.Ifthemeasuredvoltageoramperageiswithin3% ofwhatislistedforthecorrespondingRH,thenthesensoris functioningproperly.
mAVDC*
etthemetertoDCVolts.C
RHOutput*Output
%mAVDC*
55..............12.80.........3.20
60..............13.60.........3.40
65..............14.40.........3.60
70..............15.20.........3.80
75..............16.00.........4.00
80..............16.80.........4.20
85..............17.60.........4.40
90..............18.40.........4.60
95..............19.20.........4.80
100............20.00.........5.00
SideView
TerminalsFor ThermistorAnd/Or MembraneSwitch Option(N.O.Only)
SwitchPinsFor MembraneSwitch Option
Optional Thermistor Soldering Connector Pins
MountingDiagram
SeeNote1
Power Supply 24VDC
4-20Ma Signal
ToTemperatureInput (WhenUsed)
CalibrationPotZero
HumiditySensingElement
TypicalWiringDiagram
SeeNote3
Notes:
1.)Thesensorisdesignedtobewall mountedinroomswhereappearance isimportant.Itmaybemounted directlyondrywalloronanysingle gangelectricaloutletboxwithno adaptersrequired.Toggleboltsor otherdirectwallmountscrewscanbe usedwhereconduitisnotrequired.It includesadetachablemountingplate. Thecoverissecuredwithtamper­resistanthexscrews.Thesensor shouldbemountedapproximatelyfive feetabovethefloor,onaninteriorwall, awayfromanyheatingorcooling generatingdevices.Plugthewireway holetopreventfalsereadingsbyair draftswithinthewall.
2.)AllWiringToBeInAccordanceWith LocalAndNationalElectricalCodes AndSpecifications.
3.)TheseWiringInstructionsAre TypicalForAllSensorApplications. SeeControllerWiringDiagramsFor DetailedWiringInstructionsand TerminationsForYourSpecific Application.
FILENAME
G-HUMSRWALL1.CDR
DATE:
012/18/02
PAGE
1
WallMountedHumiditySensor
JOBNAME
DRAWNBY:
DESCRIPTION:
OE265-01
B.CREWS
Page 43
GasketedCover
CAUTION! SeeNote3
3.00”
Cover Mounting Screw-Typ.
SensorTube
CAUTION! SeeNote1
2.30”
MountingTab &Screw-Typ.
ClosurePlug
CAUTION! SeeNote2
2.70”
ClosurePlug
CAUTION! SeeNote2
0.21"Dia.x0.73 Lg.Slot-Typ.
MountingTab &Screws-Typ.
Incorrect
SeeNote#1
FrontView SideView
BackView
Incorrect
SensorMounting
OutsideAirSensor OE250
TemperatureSensorResistance/VoltageChart
TempResistance*Voltage
FOhms@Input*
°
-10.............93333........4.620
-5...............80531........4.550
0...............69822........4.474
5...............60552........4.390
10..............52500........4.297
15..............45902........4.200
20..............40147........4.095
25..............35165........3.982
30..............30805........3.862
35..............27140........3.737
40..............23874........3.605
*ChartNotes:
1.Usetheresistancecolumntocheckthethermistorsensorwhiledisconnectedfromthecontrollers(notpowered).
2.Usethevoltagecolumntochecksensorswhileconnectedtopoweredcontrollers.ReadvoltagewithmetersetonDC volts.Placethe"-"(minus)leadonGNDterminalandthe"+"(plus)leadonthesensorinputterminalbeinginvestigated.If thevoltageisabove5.08VDC,thenthesensororwiringis"open."Ifthevoltageislessthan0.05VDC,thesensoror wiringisshorted.
TempResistance*Voltage
FOhms@Input*°
45..............21094........3.470
50..............18655........3.330
52..............17799........3.275
54..............16956........3.217
56..............16164........3.160
58..............15385........3.100
60..............14681........3.042
62..............14014........2.985
64..............13382........2.927
66..............12758........2.867
68..............12191........2.810
TempResistance*Voltage
FOhms@Input*°
69..............11906........2.780
70..............11652........2.752
71..............11379........2.722
72..............11136........2.695
73..............10878........2.665
74..............10625........2.635
75..............10398........2.607
76..............10158........2.570
78..............9711..........2.520
80..............9302..........2.465
82..............8893..........2.407
TempResistance*Voltage
FOhms@Input*
°
84..............8514..........2.352
86..............8153..........2.297
88..............7805..........2.242
90..............7472..........2.187
95..............6716..........2.055
100............6047..........1.927
105............5453..........1.805
110............4923..........1.687
115............4449..........1.575
120............4030..........1.469
Correct
Postion
Notes:
1.)TheOutsideAirSensorMustBe MountedInAVerticalPositionAs Shown(SensorTubePointing Down).
WaterMustNotBe AllowedToStandInSensor Tube.RainwaterWillDamage Sensor.
SensorMustBeLocated WhereItWillNotBeAffectedBy DirectSunlightOrHeatProducing Equipment.IfPossibleMountUnder RoofEaveOrSimilarProtected Location.IfSensorIsNotLocated AsSpecified,ErroneousOutsideAir TemperatureReadingsWillResult.
2.)UnusedConduitOpening(s)Must HaveClosurePlugsInstalledAndMust BeCoatedwithSealingCompoundTo ProvideRaintightSeal.WaterCan
DamageSensor!
3.)GasketMustBeInstalledUnderCover PlateToProvideRaintightSeal.
RainwaterCanDamageSensor!
4.)AllWiringToBeInAccordanceWith LocalAndNationalElectricalCodes AndSpecifications.
FILENAME
G-OE250-OAS-PDWG.CDR
DATE:
PAGE
1
04/25/02
OutsideAirTemperatureSensor
JOBNAME
DRAWNBY:
DESCRIPTION:
OE250
B.CREWS
Page 44
Butt Splice Wire Leads To Extend Wires To Controller Terminals. Connect One Wire Lead To Return Water Temperature Or Supply Water Temperature Terminal At The Controller As Required By Intended Use. Secure Other Wire Lead To Ground Terminal At The Controller. See Note 3.
Secure Sensor Element And Thermal Mastic Strip To Pipe With Supplied Wire Tie. Be Sure To Tighten Wire Tie Snugly To Ensure Good Thermal Contact Between Pipe And Sensing Element.
Sensing Element (Supplied)
Install Sensing Element With Curved Face Touching Pipe Surface As Shown
Wire Tie (Supplied)
Supply Or Return Water Pipe. See Note1&2.
Important Note: For Accurate Temperature Readings It Is Necessary To Place Insulation Over The Sensor After Installation. This Prevents The Ambient Temperature From Affecting The Sensor. Insulation Should Cover The Sensor And Extend 6“ to 12” Beyond Each End Of The Sensor.
Temp Resistance* Voltage
F Ohms @ Input*
°
-10.............93333 ........4.620
-5...............80531 ........4.550
0 ...............69822 ........4.474
5 ...............60552 ........4.390
10..............52500 ........4.297
15..............45902 ........4.200
20..............40147 ........4.095
25..............35165 ........3.982
30..............30805 ........3.862
35..............27140 ........3.737
40..............23874 ........3.605
*Chart Notes:
1. Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered).
2. Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts. Place the "-"(minus) lead on GND terminal and the "+"(plus) lead on the sensor input terminal being investigated. If the voltage is above 5.08 VDC, the sensor or wiring is "open." If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.
Notes:
1.)Sensor Should Be Mounted At Location Along Pipe Length That Best Represents Desired Temperature Reading.
2.)Sensing Element Shown Mounted To Top Of Pipe. The Sensor Element May Be Located
At Any Location Around Pipe.
3.)All Wiring To Be In Accordance With Local And National Electrical Codes And Specifications.
Thermal Mastic
Place Between Pipe And Sensing Element. Pipe Should Be Clean And Smooth To Provide Proper Thermal Contact With Sensing Element.
Thermal Mastic Strip (Supplied)
Temperature Sensor Resistance/Voltage Chart
Temp Resistance* Voltage
F Ohms @ Input*°
45..............21094 ........3.470
50..............18655 ........3.330
52..............17799 ........3.275
54..............16956 ........3.217
56..............16164 ........3.160
58..............15385 ........3.100
60..............14681 ........3.042
62..............14014 ........2.985
64..............13382 ........2.927
66..............12758 ........2.867
68..............12191 ........2.810
Temp Resistance* Voltage
F Ohms @ Input*°
69..............11906 ........2.780
70..............11652 ........2.752
71..............11379 ........2.722
72..............11136 ........2.695
73..............10878 ........2.665
74..............10625 ........2.635
75..............10398 ........2.607
76..............10158 ........2.570
78..............9711 ..........2.520
80..............9302 ..........2.465
82..............8893 ..........2.407
FILENAME
G-OE233-W-TempSnsr1a.CDR
DATE: 01/03/05
PAGE
OE233 - Strap-On Temperature
1
Temp Resistance* Voltage
F Ohms @ Input*
°
84..............8514 ..........2.352
86..............8153 ..........2.297
88..............7805 ..........2.242
90..............7472 ..........2.187
95..............6716 ..........2.055
100............6047 ..........1.927
105............5453 ..........1.805
110............4923 ..........1.687
115............4449 ..........1.575
120............4030 ..........1.469
125............3656 ..........1.369
JOB NAME
CONTROLS
DRAWN BY:
DESCRIPTION:
B. CREWS
Sensor Kit Installation
Page 45
GasketedCover
CAUTION! SeeNote3
SensorWire LeadsInside WeatherProof Enclosure
AmbientLight SensorEye ThreadedInto WaterProof Enclosure
3.00”
Cover Mounting Screw-Typ.
2.30”
FrontView SideView
AmbientLightSensor OE259
MountingTab &Screw-Typ.
ClosurePlug
CAUTION! SeeNote2
2.70”
0.21"Dia.x0.73 Lg.Slot-Typ.
MountingTab &Screws-Typ.
ClosurePlug
CAUTION! SeeNote2
BackView
TheAmbientLightSensorIsAPhotoSensitiveResistorHousedInAWaterProofEnclosure. ItIsUsedInConjunctionWithTheOE310-21-LPLightingControllerToSenseThePresenceOrAbsence OfAmbientLightForTheControlOfLightingCircuitsConnectedToTheController.TheSensor HasAResistanceInExcessOf1MOhmsInDarknessAndRangesDownToLessThan1.5KOhmsIn BrightLight.TheSensorWireConnectionsAreNon-Polarized.SeeTheOE310-21-LPWiringDiagramFor CorrectWiringConnections.SeeNote1ForMountingLocationCautions.
Notes:
1.)TheAmbientLightSensorShould BeInstalledOutdoorsWhereItCan SenseTheAmbientLightLevel.Do NotMountInAShadyAreaOrNear AnyObstructionsThatWouldBlock TheSensorEye.TheAmbientLight SensorShouldBeMountedOnIts SideInAHorizontalPositionSo WaterWillNotPuddleAroundThe SensorEye.
2.)UnusedConduitOpening(s)Must HaveClosurePlugsInstalledAndMust BeCoatedwithSealingCompoundTo ProvideRaintightSeal.WaterCan
DamageSensor!
CorrectMountingPosition IncorrectMountingPosition
3.)GasketMustBeInstalledUnderCover PlateToProvideRaintightSeal.
RainwaterCanDamageSensor!
4.)AllWiringToBeInAccordanceWith LocalAndNationalElectricalCodes AndSpecifications.
FILENAME
G-OE259-AmbLightSnsr1A.CDR
DATE: B.CREWS
PAGE
1
06/17/03
DESCRIPTION:
AmbientLightSensor
JOBNAME
DRAWNBY:
OE259
Loading...