Watlow F4T, D4T Quick Start Guide

Quick Start Guide
content itemS and recommended toolS
a. F4T controller
Tools
f. Medium size pliers
1.
Slot numbers
Installed FMs
B.
inStall Flex moduleS (Fm)
C. D.
F4T Process Controller
D4T Data Logger
Follow the steps in this quick start guide to
set up your new Watlow F4T/D4T controller
For assistance contact Watlow®: www.watlow.com
1-800-WATLOW2 (1-800-928-5692)
wintechsupport@watlow.com
• http://www.watlow.com/f4T • http://www.watlow.com/d4T
1440-3329 Rev A January, 2019
F4T
D4T
b. Flex Module(s) (FM) and
label stickers
1
1
2
2
3
3
4
4
5
5
6
6
c. PC
d. Ethernet cable
e. Composer PC software
(install program from control tools DVD or website)
g. Small flathead screwdriver
h. Wire (14 to 26 AWG) and wire
stripper
Case plugs indicate empty slots
A.
FM slot diagram
To view video go to www.watlow.com/F4T
F4T Tutorials: Module Installation
Note:
Take care to protect the glass touch screen.
Best Practice:
Complete the following procedure for one FM at a time working from slot 1 to 6.
1. Select a slot for the FM.
Note:
Communications modules (FMCA­XXXX-XXXX) work only in slot 6. Slot numbers are molded into the case and shown in the diagram on the label (image A).
Note:
If a terminal block overlaps the slot, remove it temporarily, loosening it with a small screwdriver (image B).
2. Using pliers, remove slot plug
by pulling straight back (image C).
Note:
FM is right-side up when its locking tabs align with the mating holes (image D).
3. Slide FM in until it clicks firmly
in place.
E. F.
4. Using the stickers packaged
with the FM, label the terminal block with its slot number (image E).
5. Apply a matching label to the
FM (image F).
Option:
If mounting unit to equipment is desired at this stage see Step 6
before proceeding to Step 2.
2.
1. Connect F4T/D4T to power
source (image A).
F4T or D4T (digits 1, 2 and 3 of part number)
_ _ _ _ _ _ _ _ _ _ _ _
1, 2, 3 or 4: 120 to 240 VAC
5, 6, 7 or 8: 24 V (AC or DC)
Caution:
Do not connect high voltage to a
controller that requires low voltage.
2. Ethernet communication: Connect
the F4T to the network your PC is on (image B).
Note:
Note it is an option to connect the F4T/D4T via Ethernet directly to the PC. See the F4T/D4T Installation and Troubleshooting User’s Guide, chapter 3.
Optional:
To avoid open sensor error messages, temporarily jumper S1 and R1 terminals on all removable screw terminal blocks or see corresponding FM Quick Start Guide to connect sensors (image C).
(digits 4 through 15)
See safety information in the “General
Information” section of this document.
connectionS
A.
B.
C.
Warning:
3.
A. B.
1. Install Composer PC software
(install program from control tools DVD or website) setup program and follow on-screen instructions.
2. Run Composer and click the
system (image A).
3. Double-click the system in the
open systems list (image B).
4. From the “F4T (1)” or
“D4T (1)” menu, choose Pluggable Modules (image C).
: run the
5. On the first module click “Use
Detected Part Number” then click “Continue” (images D).
6. For each other module click
“Use Detected Part Number”
7. Click “Finish” and then click “Go
to Function Block Diagram”.
C.
Optional:
View the tutorial videos to learn how to set up a control loop (F4T only).
8. Select “Auto hide this window
by default” to dock the tutorial window.
9. To configure a control loop:
drag a control loop from the library to the canvas. Drag a signal from an input block to the PV receiver on the control loop. Drag a signal from the HT transmitter on the control loop to the output block (images E-G).
inStall compoSer® SoFtware and conFiGure a control loop
D.
Note:
For sensors other than type J thermocouple, double-click the input block and set the sensor type in the Parameters window (image H).
Optional:
Use additional function blocks to configure more of your application or come back to this later.
E. F.
T1
S1
R1
+
Universal Input 1
Module 1
RSP
PSP REN IDLE
OFF MAN
TUN
TDA
PV
HT CL
ƒ
(x)
ƒ
(x)
PWR CSP OSP
Loop 1
G.
T1
S1
R1
+
Universal Input 1
Module 1
H.
PV RSP PSP
REN IDLE
OFF
MAN
TUN TDA
T1
S1
R1
+
Universal Input 1
Module 1
ƒ
(x)
ƒ
(x)
Loop 1
HT
CL PWR CSP OSP
RSP
PSP REN IDLE
OFF MAN
TUN
TDA
PV
ƒ
ƒ
Loop 1
+24V
Switched DC
Output 2 Module1
(x)
(x)
HT
CL PWR CSP OSP
W2
L
Y2
+
4. 6.5.
perSonalize the F4t/d4t uSer interFace mount & wireSave and import imaGe FileS
A.
B.
1. From the Zone 1 menu, choose
Personalization (image A).
2. Select a layout option Top,
Center or Bottom for the home pages (image B).
C. E.
3. For Page 1 select the number of
content blocks to display (image C).
4. For each block on the page
choose the content to display (image D).
D.
5. Repeat steps 3 and 4 for the
other home pages as desired.
6. Setup the output view as desired
by choosing items to display or set (image E).
7. Set the other available
personalization options as desired.
A.
D.
Save image file:
1. From the System menu, choose
Save Image As and designate a file name (image A).
Import an image file:
2. On the Dashboard view click the
system to connect (image B).
3. Click the menu icon and choose
“Import Image” (image C).
B.
C.
4. Navigate to desired file and
select (allow several minutes to load).
Alternate method to import an image file:
1. On any system view from the
System menu choose “Import Image” (image D).
1. Cutout panel (image A).
2. Remove green
connectors that have
A.
92.0 to 93.0 mm
(3.62 to 3.65 inches)
already been wired.
3. Remove mounting collar
from unit.
4. Insert F4T/D4T
92.0 to 93.0 mm (3.62 to 3.65 inches)
controller through front panel cutout.
5. Slide on mounting collar
(image B).
B.
6. Wire remaining input
and outputs as necessary.
Product
Label
Placed
Here
Mounting
Panel
Note:
For further mounting and wiring assistance see More Support below.
L1
Neutral
DA10-24C0-0000
Heater
6
5
Limit
Contactor
+
Control Output
Limit Output
F4T Controller
Slot 1 Slot 2
X1
W1
+
Y1
T1
S1
+
R1
Slot 1 - FMMA- UCAA-AAAA Slot 2 - FMLA- LAJA-AAAA
more Supportexample SyStem wirinG diaGram General inFormation how to reach uS
You are now able to begin using the F4T/D4T controller. If you would like to see more in-depth information please visit the following website or on support tools/DVD:
http://www.watlow.com/f4T
http://www.watlow.com/d4T
Warning:
Use National Electric (NEC) or other country-specific standard wiring and safety practices when wiring and connecting this controller to a power
Documentation
1720-6742 F4T Installation and troubleshooting user’s guide
1656-9792 D4T Installation and troubleshooting user’s guide
1680-2414 F4T Setup & Operations user’s guide
98 99
K2 L2 T1
S1
+
R1
1247-5282 D4T Setup & Operations user’s guide
0600-0095-0000 Quick Start Guide Modbus® RTU Communications
Flex Modules
0600-0096-0000 Quick Start Guide High Density Input/Output Flex
Modules
0600-0097-0000 Quick Start Guide Mixed Input/Output Flex Modules
WIN-F4T-1118 F4T Specification Sheet
WIN-D4T-1118 D4T Specification Sheet
1085-8615 Support tools/DVD
source and to electrical sensors or peripheral devices. Failure to do so may result in damage to equipment and property, and/or injury or loss of life.
Avertissement:
Utilisez les pratiques de câblage et de sécurité de National Electric (NEC) ou les normes spécifiques au pays lors du câblage et de la connexion de ce régulateur à une source d’alimentation et aux capteurs électriques ou aux équipements périphériques. Tout manquement à cette règle pourrait provoquer des dégâts sur l’équipement et le matériel, et/ou des blessures personnelles ou des décès.
This User’s Guide is copyrighted by Watlow Electric Manufacturing Company, © January 2019 with all rights
Technical Assistance
To get assistance from Watlow:
• Contact a local representative
• Email: wintechsupport@watlow.com
• Call: +1 (507) 494-5656 from 7 a.m. to 5 p.m. (CST)
reserved.
Watlow® and COMPOSER® are registered trademarks of Watlow Electric Manufacturing Company.
Modbus® is a registered trademark of Schneider Automation, Inc.
Document 10-15896
Corporate Headquarters
Watlow Electric Mfg. Company
Sales: 1-800-WATLOW2 Email: info@watlow.com Website: www.watlow.com
Europe
Watlow France
Tél: +33 (0) 1 41 32 79 70 Télécopie: +33 (0) 1 47 33 36 57 Email: info@watlow.fr Website: www.watlow.com
Watlow Plasmatech GmbH
Tel: +3 0244 20129 0 Email: austria@watlow.com Website: www.watlow.com
Asia and Pacific
Watlow Singapore Pte Ltd.
Tel: +65 6773 9488 Fax: +65 6778 0323 Email: info@watlow.com.sg
Watlow Electric Manufacturing (Shanghai) Company
Local Phone: 4006 Watlow (4006 928569) International: +86 21 3381 0188 Fax: +86 21 6106 1423 Email: info-cn@watlow.com Website: www.watlow.cn
From outside the USA and Canada:
Tel: +1 (314) 878-4600 Fax: +1 (314) 878-6814
Watlow Italy S.r.l.
Tel: +39 024588841 Fax: +39 0245869954 Email: italyinfo@watlow.com Website: www.watlow.com
Watlow lbérica, S.L.U.
T. +34 91 675 12 92 F. +34 91 648 73 80 Email: info@watlow.es
Watlow Japan Ltd.
Tel: +81-3-3518-6630 Fax +81-3-3518-6632 Email: infoj@watlow.com Website: www.watlow.co.jp
Watlow Korea Co., Ltd.
Tel: +82 (2) 2169-2600 Fax +82 (2) 2169-2601 Website: www.watlow.co.kr
Latin America
Watlow de México SA. de C.V.
Tel: +52 442 217-6235 Fax: +52 442 217-6403
Watlow UK Ltd.
Telephone: (0) 115 964 0777 Fax: (0) 115 964 0071
Email: info@watlow.co.uk
From outside The United Kingdom: