Output Rating Curves
Maximum Ambient Temperature ºF
50 68
70
86
104 122
140
158
176
Series CZR
Solid State Contactor
60
50
40
30
Current (Amps)
20
10
0
10
Wiring
40
20
30
50
60
Maximum Ambient Temperature ºC
Model number dependent
Vı (ac/dc) +
Vı (ac/dc) -
INPUT
70
80
CZ42
CZ34
CZ24
CZ18
User’s Guide
1241 Bundy Boulevard, P.O. Box 5580,
Winona, Minnesota USA 55987-5580
Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507
Internet: http://www.watlow.com
10% Postconsumer Waste
Printed on Recycled Paper
Unit Dimensions
Front
A
B
INPUT
90-140V
RMS
SIGNAL
Mounting
Hole/Slot
0.17 (4.3) Dia.
A B C D E F G H I
MODEL
18 Amp
Warnings
1
∫
2
∫
3
∫
4
Output
Semiconductor
Heater
Fuse
Limit Control
Contacts
(If Required)
240VÅ (ac)
and above
L1
L2
120VÅ (ac)
and 277VÅ (ac)
L1
Neutral
Wiring must conform to National Electric Code
(NEC) safety standards, as well as locally applicable codes. Failure to do so could result in death or
personal injury.
Wiring examples show L2 in 240VÅ (ac) or 480Å
(ac) configuration. In 120VÅ (ac) or 277VÅ (ac)
applications, L2 is neutral and must not be fused
or switched. Failure to follow this guideline could
result in death or personal injury.
Installation and service by qualified personnel
only. Failure to do so could result in death or
personal injury.
Hot surface, do not touch heat sink. Failure to follow this guideline could result in personal injury.
Top
SOLID STATE RELAY
Series
CZR
R
480 VAC
45A
50/60HZ
C
D E
12.7mm (0.5 in)
25.4mm (1.0 in)
F
G
H
Pull to release
from DIN rail
ç Mount cooling fins vertical
N/A
66.0mm (2.6 in)
81.3mm (3.2 in)
88.9mm (3.5 in)
22.6mm (0.89 in)
19.1mm (0.75 in)
63.5mm (2.5 in)
76.2mm (3.0 in)
88.9mm (3.5 in)
44.5mm (1.75 in)
I
12.7mm (0.5 in)
99.0mm (3.9 in)
81.3mm (3.2 in)
24-42 Amp
22.9mm (0.9 in)
109.2mm (4.3 in)
76.2mm (3.0 in)
Side
Heatsink:
Black Anodized
Aluminum
0600-0037-0000 Rev D WATLOW Series CZR User's Guide
June 2010, North American English
1
Specifications
(1992)
Control Mode
• Zero cross
Operator Interface
• Command signal input
• Input signal indication LED
Input Command Signal
• Input Type DC1
• Turn ON voltage 4VÎ (dc) max., turn OFF voltage 1VÎ (dc) min.
• Input current: DC typ. 10mA @ 4VÎ (dc), 13mA @ 32VÎ (dc)
• Input Type AC1
• 90-140Vrms, must turn ON at 90 VÅ(ac), must turn OFF
at 10VÅ(ac)
• Input current: 15mA typical @ 120VÅ(ac)
Output Voltage
• 24 volt; 24VÅ(ac) min. to 280VÅ(ac) max.
• 480 volt: 48VÅ (ac) min. to 530VÅ(ac) max.
• 600 volt: 48VÅ (ac) min. to 660VÅ(ac) max. (not available on 18
amp version)
• Off State Leakage
1mA at 25°C/77°F max. for 600VÅ(ac) models; 10mA at
25°C/77°F max. for 24 through 480VÅ(ac) models
• Holding current: 250mA max.
Output Amperage
• See output rating curve on page 1. Ratings are into a resistive
heater load.
24Output Amperage 34 42
250 625 1000
260
Max. surge current
16.6mSec
Max. I2t for fusing
18
625
1620 1620 4150
Agency Approvals
• Class II construction
• UL 508 recognition file number E73741
• CSA file LR 700195
Ordering Information
(1993)
Part Number C — — — - A — — V - — — — 0
• 2006/95/EC CE Low Voltage Directive
Output Terminals
• Compression type
• For 18 amp models:
• Maximum wire size 3.0mm (10 AWG), torque to 0.6Nm (5.3
in. lbs.)
• For 24 to 42 amp models:
• Maximum wire size 16.0mm (6 AWG stranded), torque to
1.5-1.7Nm (13-15 in. lbs.)
Operating Environment
• Up to 80˚C/176˚F. See output rating curves for your application.
• 0 to 90% RH, non-condensing.
• Insulation only tested to 3,000 meters.
• Units are suitable for “Pollution degree 2.”
• Cycle time should be less than 3 seconds.
Mounting
Options include DIN rail or standard back panel mounting.
• The DIN rail specification:
DIN EN 50022,
35mm x 7.5mm.
• Min. clipping distance:
34.8mm (1.37 in).
• Max. clipping distance:
35.3mm (1.39 in)
• Mount cooling fins vertical
Weight/Dimensions
• 260g (9.2 oz.)
• 24 to 42 amp models: 100 mm (3.95 in) high x 45 mm (1.75
in) wide x 109 mm (4.3 in) deep
• 18 amp models: 100 mm (3.95 in) high x 22.6 mm (0.89 in)
wide x 99 mm (3.9 in) deep
Specification subject to change without notice.
Control Mode
Z = Zero cross
Output Amperage
18 = 18 amp
24 = 24 amp
34 = 34 amp
42 = 42 amp
Output Voltage
24 = 24 to 280
48 = 48 to 530
60 = 60 to 660
VÅ (ac)
VÅ (ac)
VÅ (ac)
Input Type (Contactor)
DC1 = 4 to 32VÎ (dc)
AC1 = 90 to 140
NOTE: Do not use the AC1 input type models with temperature
VÅ (ac)
control outputs that include an AC snubber filter. This could
cause the CZR to stay full on.
Recommended Semiconductor Fuses
CZR Model Fuse* Fuse Holder
18A 17-8025 17-5110
24A 17-8030 17-5114
34A 17-8040 17-5114
42A 17-8063 17-5122
*Recommended at base rating.
WATLOW Series CZR User's Guide
2
Warranty
The Series CZR is warranted to be free of defects
in material and workmanship for 24 months after
delivery to the first purchaser for use, providing
that the units have not been misapplied. Since
Watlow has no control over their use, and sometimes misuse, we cannot guarantee against failure.
Watlow's obligations hereunder, at Watlow's option, are limited
to replacement, repair or refund of purchase price, and parts
which upon examination prove to be defective within the
warranty period specified. This warranty does not apply to damage resulting from transportation, alteration, misuse, abuse or
improper fusing.
Returns
1. Call Customer Service: 507-454-5300, or fax: 507-452-4507,
for a Return Material Authorization (RMA) number before
returning any item for repair.
2. Make sure the RMA number is on the outside of the carton,
and on all paperwork returned. Ship on a freight prepaid basis.
3. A restocking charge of 20% of the net price applies for all
returned stock controls and accessories in like new condition
and within 120 days after shipment. Non-stock and modified
stock items are not returnable.
4. If the unit is unrepairable, it will be returned to you with a letter of explanation. Repair costs will not exceed 50% of the
original cost.