WaterFurnace Versatec Ultra User Manual

• R-410A Refrigerant
• 0.75-6 Tons
Installation Information
Water Piping Connections
Hot Water Connections
Electrical
Startup Procedures
Troubleshooting
Preventive Maintenance
Versatec Ultra Series Installation Manual
IM1200AUB 05/14
Table of Contents
Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
General Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
Installing Horizontal Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Hanger Bracket Locations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Duct System and Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Water Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
System Cleaning and Flushing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Open Loop Ground Water Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Hot Water Generator Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-17
VERSATEC ULTRA SERIES INSTALLATION MANUAL
Freeze Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Electrical Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19-21
Blower Performance Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22-27
Wiring Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28-30
Controls - Aurora Base Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-34
Controls - UPC (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35-43
Unit Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Operating Limits and Operating Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
Reference Calculations and Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Refrigerant Circuit Guideline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Compressor and Thermistor Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Heat of Extraction/Rejection Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
Startup/Troubleshooting Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51-52
Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Replacement Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Service Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54-55
Revision Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
VERSATEC ULTRA SERIES INSTALLATION MANUAL
U S
1 3 4-6 7 8 9
10 11 12 14
V 036 T L 0 0 0 C A N13N15A16517N18019020SS
21-22*23
2

Model Nomenclature

Model Type
U – Versatec Ultra
Operation Range
S – Single Stage
Cabinet Configuration
V – Vertical H - Horizontal
Unit Capacity (MBTUH) 009, 012, 015, 018, 023 (Horizontal) 024, 030, 036, 041 (Vertical) 042, 048, 060, 070
Discharge Configuration
T – Top (Vertical) E – End (Horizontal) S – Side (Horizontal)
Return Air Configuration
L – Left R – Right
Voltage
0 – 208-230/60/1 2 – 265-277/60/1 (009-036) 3 – 208-230/60/3 (023-070) 4 – 460/60/3 (023-070) 5 – 575/60/3 (PSC Only 041-070)
Hot Water Generation Option
0 – No HWG, No IntelliStart® 2 – HWG w/o Pump, No IntelliStart (Vertical 015-070) 3 – No HWG, IntelliStart 5 – HWG w/o Pump, IntelliStart (Vertical 018-070)
Blower Options
0 – PSC Blower 1 – Variable Speed ECM Blower (015-070) 2 – High Static Variable Speed ECM Blower (042-048) 3 – High Static PSC Blower (024, 030, 042, 048) 4 – 5-Speed ECM Blower (015-070)
Water Coil Option
C – Copper N – CuproNickel
2
Vintage
* - Factory Use Only
Non-Standard Options
SS – Standard
Drain Pan Option
0 – Composite, No Secondary Connection 1 – Composite, Secondary Connection 2 – Stainless Steel, No Secondary Connection 3 – Stainless Steel, Secondary Connection
Cabinet Option
0 – Unpainted, 1 in MERV 4, Filter Rail 1 – Painted, 1 in MERV 4, Filter Rail 2 – Unpainted, 2 in MERV 13, Filter Rail 3 – Painted, 2 in MERV 13, Filter Rail 4 – Unpainted, 1 in MERV 4, Filter Rack 5 – Painted, 1 in MERV 4, Filter Rack 6 – Unpainted, 2 in MERV 13, Filter Rack 7 – Painted, 2 in MERV 13, Filter Rack
Phase Guard
N – No Phase Guard, No Disconnect P – Phase Guard, No Disconnect B – Phase Guard, Disconnect D – No Phase Guard, Disconnect
All-Aluminum Air Coil Option
5 – AlumiSeal 6 – AlumiSeal/Standard Range 7 – No Coating/Extended Range 8 – No Coating/Standard Range
Control Option
A – Aurora E – Aurora UPC DDC Controller F – Aurora UPC DDC Controller with LON
Water Control Option
N – None R – Water Flow Regulator (015-070) V – 2-Way Valve (015-070) B – 2-Way Valve w/ Water Flow Regulator (015-070)
Refrigeration Option
0 – None G – Hot Gas Bypass (015-072) R – Hot Gas Reheat (015-072) B – Hot Gas Bypass w/Hot Gas Reheat (015-072)
Sound Kit Option
A – None B – Sound Kit (Not Available on H009-012)
1
TM
/Extended Range
TM
Base Control (ABC)
Notes: 1 - Phase Guard Only Available on 208-230/60/3, 460/60/3, and 575/60/3 2 - IntelliStart is not available with Phase Guard
Rev.: 24 April 2014D
4

General Installation Information

VERSATEC ULTRA SERIES INSTALLATION MANUAL
Safety Considerations
WARNING: Before performing service or maintenance operations on a system, turn off main power switches to the indoor unit. If applicable, turn off the accessory heater power switch. Electrical shock could cause personal injury.
Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair or service heating and air conditioning equipment. Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning and replacing filters. All other operations should be performed by trained service personnel. When work­ing on heating and air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations and have a fire extinguisher available.
Moving and Storage
Move units in the normal “up” orientation. Horizontal units may be moved and stored per the information on the packaging. Do not stack more than three units in total height. Vertical units may be stored one upon another to a maximum height of two units. Do not attempt to move units while stacked. When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Examine units for shipping damage, removing the units from the packaging if necessary. Units in question should also be internally inspected. If any damage is noted, the carrier should make the proper notation on the delivery receipt, acknowledging the damage.
Unit Location
Locate the unit in an indoor area that allows for easy removal of the filter and access panels. Location should have enough space for service personnel to perform maintenance or repair. Provide sufficient room to make water, electrical and duct connection(s). If the unit is located in a confined space, such as a closet, provisions must be made for return air to freely enter the space by means of a louvered door, etc. Any access panel screws that would be difficult to remove after the unit is installed should be removed prior to setting the unit. On horizontal units, allow adequate room below the unit for a condensate drain trap and do not locate the unit above supply piping. Care should be taken when units are
located in unconditioned spaces to prevent damage from frozen water lines and excessive heat that could damage electrical components.
Installing Vertical Units
Prior to setting the unit in place, remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket.
Vertical units are available in left or right air return configurations. Top flow vertical units should be mounted level on a vibration absorbing pad slightly larger than the base to provide isolation between the unit and the floor. It is not necessary to anchor the unit to the floor (see figure below).
Vertical Unit Mounting
2 in. PEX Foam
5
VERSATEC ULTRA SERIES INSTALLATION MANUAL
Vertical Dimensional Data
A
RN
S
Q
AIR COIL SIDE
P
B
AIR COIL SIDE
F
4 3
FRONT
1.4 in (3.5 cm)
M
M
G
Top View - Right Return Top View - Left Return
Air coil
A
N
FRONT
1.4 in (3.5 cm)
Standard filter rails for
open return applications
Deluxe filter rack for
ductable return applications
Air coil
Q
P
B
2' (61 cm)
G
Alternate Service Access
4 3
F
2' (61 cm)
Service Access Left Return
(Right Return opposite side)
Air coil
ACCESS
PANEL
Isometric View - Left Return
U
Field installed duct flange
T
W
ACCESS
PANEL
C
1.6 in (4.1 cm) Condensate 3/4 in
PVC glue socket
1.6 in (4.1 cm)
5
H
2
E
1
D
6 8
1 in (25.4 mm)
1/2" (12.7 mm)
J
L
Power supply
knockout
Low voltage
knockout
L
K
Front View - Right Return
ACCESS
PANEL
Condensate
3/4 in PVC
glue socket
1.6 in (4.1 cm)
8 7
5 2
1
Front View - Left Return
1.6 in (4.1 cm)
H
E
D
V
C
6
ACCESS
J
8
L
PANEL
8 7
L
K
Right View - Right Return
Left View - Left Return
6
Vertical Dimensional Data cont.
VERSATEC ULTRA SERIES INSTALLATION MANUAL
Overall Cabinet
Vertical
Models
009-012
015-018
024-030
036
041
042-048
060
070
009-012
015-018
024-030
036
041
042-048
060
070
Condensate is 3/4 in. PVC female glue socket and is switchable from side to front.
*Dimensions for return connections are for the deluxe fi lter rack that is suitable for ducted return applications and extends 3.25 in. [8.26 cm] from the unit. The open fi lter rack, used in non-ducted returns, extends 2.2 in. [5.59 cm] from the unit.
**Discharge fl ange is fi eld installed and extends 1 in. (25.4 mm) from top of cabinet.
cm. 57.2 56.4 60.2 6.6 14.2 N/A N/A 22.4 12.7 mm N/A 18.8 8.6 13.7
cm. 57.2 56.4 91.9 6.6 19.3 3.6 7.4 27.4 19.1 mm 22.2 mm 23.9 13.7 18.8
cm. 57.2 66.5 102.1 6.6 19.3 3.6 11.2 27.4 19.1 mm 22.2 mm 25.7 15.5 20.6
cm. 57.2 66.5 112.3 6.6 19.3 3.6 11.2 27.4 19.1 mm 22.2 mm 25.7 15.5 20.6
cm. 57.2 66.5 112.3 6.6 19.3 3.6 7.4 27.4 19.1 mm 22.2 mm 25.7 15.5 20.6
cm. 64.8 79.2 112.3 6.6 19.3 3.6 11.2 27.4 25.4 mm 22.2 mm 25.7 15.5 20.6
cm. 64.8 79.2 122.4 6.6 19.3 3.6 11.2 27.4 25.4 mm 22.2 mm 25.7 15.5 20.6
cm. 64.8 79.2 132.6 6.6 19.3 3.6 11.2 27.4 25.4 mm 22.2 mm 25.7 15.5 20.6
Vertical
Models
cm. 5.6 25.4 25.4 15.5 23.9 23.9 5.3 46.0 25.4 4.8
cm. 5.6 35.6 35.6 10.4 10.9 19.6 5.3 46.0 50.8 4.8
cm. 5.6 35.6 35.6 15.5 11.4 19.6 5.3 56.1 56.1 4.8
cm. 5.6 35.6 35.6 15.5 11.4 19.6 5.3 56.1 66.3 4.8
cm. 5.6 45.7 45.7 10.4 9.9 9.9 5.3 56.1 66.3 4.8
cm. 5.6 45.7 45.7 16.8 11.7 16.0 4.1 71.4 66.0 5.1
cm. 5.6 45.7 45.7 16.8 11.7 16.0 4.1 71.4 76.2 5.1
cm. 5.6 45.7 45.7 16.8 11.7 16.0 4.1 71.4 86.4 5.1
A B C D E F G H Loop
Width Depth Height** In Out
in. 22.5 22.2 23.7 2.6 5.6 N/A N/A 8.8 1/2 N/A 7.4 3.4 5.4
in. 22.5 22.2 36.2 2.6 7.6 1.4 2.9 10.8 3/4 0.875 9.4 5.4 7.4
in. 22.5 26.2 40.2 2.6 7.6 1.4 4.4 10.8 3/4 0.875 10.1 6.1 8.1
in. 22.5 26.2 44.2 2.6 7.6 1.4 4.4 10.8 3/4 0.875 10.1 6.1 8.1
in. 22.5 26.2 44.2 2.6 7.6 1.4 2.9 10.8 3/4 0.875 10.1 6.1 8.1
in. 25.5 31.2 44.2 2.6 7.6 1.4 4.4 10.8 1 0.875 10.1 6.1 8.1
in. 25.5 31.2 48.2 2.6 7.6 1.4 4.4 10.8 1 0.875 10.1 6.1 8.1
in. 25.5 31.2 52.2 2.6 7.6 1.4 4.4 10.8 1 0.875 10.1 6.1 8.1
MNPQR S T UVW
Filter Rack
Width
in. 2.2 10.0 10.0 6.1 9.4 9.4 2.1 18.1 10.0 1.9
in. 2.2 14.0 14.0 4.1 4.3 7.7 2.1 18.1 20.0 1.9
in. 2.2 14.0 14.0 6.1 4.5 7.7 2.1 22.1 22.1 1.9
in. 2.2 14.0 14.0 6.1 4.5 7.7 2.1 22.1 26.1 1.9
in. 2.2 18.0 18.0 4.1 3.9 3.9 2.1 22.1 26.1 1.9
in. 2.2 18.0 18.0 6.6 4.6 6.3 1.6 28.1 26.0 2.0
in. 2.2 18.0 18.0 6.6 4.6 6.3 1.6 28.1 30.0 2.0
in. 2.2 18.0 18.0 6.6 4.6 6.3 1.6 28.1 34.0 2.0
Supply
Width
12345 678
Discharge Connection
duct fl ange installed (±0.10 in)
Supply
Depth
Water Connections Electrical Knockouts
HWGInHWG
Out
Cond-
ensate
Knock-
Water
FPT
out
HWG
Provisions
Return Connection*
using deluxe fi lter rack (±0.10 in)
Return Depth
JKL
1/2 in.
cond
Return Height
1/2 in.
cond
1 in.
cond
11/10/09
Vertical Disconnect
When using disconnect, do not use dimension L from the standard vertical dimensional data. Use dimension LL from the vertical disconnect dimensional data.
Vertical Models LL
009-012 015-018
024-030
036
042-048
060 070
Dimensions in inches [cm] 02/06/13
Externally Mounted
18.8 [47.8]
14.3 [36.3]
15.3 [38.9]
14.3 [36.3]
14.3 [36.3]
14.3 [36.3]
Disconnect Located on this
Side for a Right Return Disconnect Location
Alternative Power
Power
Location
Supply
LL
1.8 in.
[4.6 cm]
Vertical Shown in
Left Return Configuration
7
VERSATEC ULTRA SERIES INSTALLATION MANUAL
Horizontal Dimensional Data
Right Return
Condensate "X" PVC size
End Discharge
Deluxe filter rack option shown
H
2.3 in. [5.8 cm]
FILTER RACK
AIR COIL SIDE
2.1 in. [5.3 cm]
Right Return
End Discharge
N
BLOWER
OUTLET
A
Standard filter rails
1 in. [2.5 cm] knockout
0.5 in. [1.3 cm] knockout
Front
AP
CMP
Service Access
Side Discharge
P
M
C
L
2' (61 cm)
1.7 in. [5.3 cm]
K
J
E
D
AP = Alternate Service Panel BP = Blower Service Panel CP = Control Access Panel CMP = Compressor Service Panel
CP
AP
A
RR Front View
1.7
CP
AP
LR Front View
Legend
1.7
1.7 in. [5.3 cm]
E
D
J
0.5 in. [1.3 cm] knockout
1 in. [2.5 cm]
K
knockout
Standard filter rails
Front
AP
CMP
2' (61 cm)
Service Access
Side Discharge
Deluxe filter rack option shown P
N
L
C
M
BLOWER
OUTLET
2.1 in. [5.3 cm]
Left Return
End Discharge
Left Return
Condensate
"X" PVC size
End Discharge
2.3 in. [5.8 cm]
AIR COIL SIDE
FILTER RACK
H
A
BP
Front
P
N
L
M
Air Coil
BLOWER
OUTLET
Right Return Side Discharge
C
FILTER RACK CONNECTION FILTER RACK CONNECTION
Right Return Side View
B
1.5 in. [3.8 cm]
AP
CMP
SQ
0.5 in. [1.3 cm]
K
Front
1 in. [2.5 cm]
knockout
J
0.5 in. [1.3 cm] knockout
T
Deluxe filter
rack option
(shown)
R
knockout
Front
C
J
K
T
R
1.5 in. [3.8 cm]
AP
CMP
S
BLOWER
OUTLET
Left Return Side Discharge
Q
B
Left Return Side View
P
N
BP
M
L
Air Coil
Front
8
Horizontal Dimensional Data cont.
VERSATEC ULTRA SERIES INSTALLATION MANUAL
Overall Cabinet
Horizontal
Models
009-012
015-023
024-030
036
042-048
060
070
Horizontal
Models
009-012
015-023
024-030
036
042-048
060
070
*Dimensions for return connections are for the deluxe fi lter rack that is suitable for ducted return applications and extends 3.25 in. [8.26 cm] from the unit. The open fi lter rack, used in non-ducted returns, extends 2.2 in. [5.59 cm] from the unit.
Condensate 3/4 in. PVC stub extends from cabinet approximately 1-1/2 in. [38.1 mm]
in. 19.2 30.9 11.9 1.8 4.8 0.8 1/2 4.5 4.5
cm. 48.8 78.5 30.2 4.6 12.2 2.0 12.7 mm 11.4 11.4
in. 22.5 42.0 17.2 1.8 6.8 0.8 3/4 7.1 7.1
cm. 57.2 106.7 43.7 4.6 17.3 2.0 19.05 mm 18.0 18.0
in. 22.5 42.0 19.2 1.8 6.8 0.8 3/4 9.2 7.1
cm. 57.2 106.7 48.8 4.6 17.3 2.0 19.05 mm 23.4 18.0
in. 22.5 45.0 19.2 1.8 6.8 0.8 3/4 9.2 7.1
cm. 57.2 114.3 48.8 4.6 17.3 2.0 19.05 mm 23.4 18.0
in. 25.5 48.0 21.2 1.8 6.8 0.8 1 9.2 9.1
cm. 64.8 121.9 53.8 4.6 17.3 2.0 25.4 mm 23.4 23.1
in. 25.5 53.0 21.2 1.8 6.8 0.8 1 9.2 9.1
cm. 64.8 134.6 53.8 4.6 17.3 2.0 25.4 mm 23.4 23.1
in. 25.5 61.0 21.2 1.8 6.8 0.8 1 9.2 9.1
cm. 64.8 154.9 53.8 4.6 17.3 2.0 25.4 mm 23.4 23.1
in. 2.3 8.0 10.0 2.3 15.4 9.4 3.0 1.4 1/2
cm. 5.8 20.3 25.4 5.8 39.1 23.9 7.6 3.6 1.3
in. 5.7 10.5 9.4 4.9 23.4 14.5 2.0 1.4 3/4
cm. 14.5 26.7 23.9 12.4 59.4 36.8 5.1 3.6 1.9
in. 6.7 10.5 9.4 4.9 27.4 16.4 2.0 1.5 3/4
cm. 17.0 26.7 23.9 12.4 69.6 41.7 5.1 3.8 1.9
in. 6.7 10.5 9.4 4.9 30.4 16.4 2.1 1.5 3/4
cm. 17.0 26.7 23.9 12.4 77.2 41.7 5.3 3.8 1.9
in. 4.9 13.6 13.2 4.6 35.4 18.6 2.4 1.5 3/4
cm. 12.4 34.5 33.5 11.7 89.9 47.2 6.1 3.8 1.9
in. 4.9 13.6 13.2 4.6 40.4 18.4 2.4 1.5 3/4
cm. 12.4 34.5 33.5 11.7 102.6 46.7 6.1 3.8 1.9
in. 4.9 13.6 13.2 4.6 45.6 18.6 2.3 1.5 3/4
cm. 12.4 34.5 33.5 11.7 115.8 47.2 5.8 3.8 1.9
A B C D E H Loop 1/2 in. cond 1 in. cond
Width Depth Height* In Out
LMNPQRS TX
Discharge Connection
duct fl ange installed (±0.10 in)
Supply
Width
Supply
Depth
123 JK
Water Connections Electrical Knockouts
Cond-
ensate
using deluxe fi lter rack option (±0.10 in)
Return
Depth
Return Connection*
Return Height
Water FPT Low Voltage
Power
Supply
PVC Size
10/29/13
Horizontal Disconnect
When using disconnect, do not use dimension K from the standard horizontal dimensional data. Use dimension KK from the horizontal disconnect dimensional data.
Horizontal Models KK
009-012
015-018
024-030
036
042-048
060 070
Dimensions in inches [cm] 02/06/13
Externally Mounted
8.2 [20.8 ]
9.2 [23.4]
9.2 [23.4]
11.2 [28.4]
10.2 [25.9]
11.2 [28.4]
Disconnect Located
on this Side for a
Left Return
9
2.1 in.
[5.3 cm]
Disconnect Location
KK
Power Supply
Horizontal Shown in
Right Return Configuration
VERSATEC ULTRA SERIES INSTALLATION MANUAL

Installing Horizontal Units

Installing Horizontal Units
Remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket prior to setting the unit in place. Horizontal units are available with side or end discharge.
NOTE: Left (Right) Return Side Discharge cannot be converted to Left (Right) Return End Discharge or vice versa, without additional custom sheet metal parts. Horizontal units are normally suspended from a ceiling by four (009-060 models) or five (070-072 models) 3/8 in. diameter threaded rods. The rods are usually attached to the unit by hanger bracket kits furnished with each unit.
Lay out the threaded rods per the Hanger Bracket Dimensions table. Assemble the hangers to the unit as shown. Securely tighten the brackets to the unit using the weld nuts located on the underside of the bottom panel. When attaching the hanger rods to the bracket, a double nut is required since vibration could loosen a single nut.
To allow filter access, install hanger brackets as illustrated in the Hanger Bracket Locations section. The unit should be pitched approximately 1/4 in. towards the drain in both directions to facilitate the removal of condensate. Use only the bolts provided in the kit to attach hanger brackets. The use of longer bolts could damage internal parts.
Some applications require the installation of horizontal units on an attic floor. In this case, the unit should be set in a full size secondary drain pan on top of a vibration absorbing pad. The secondary drain pan prevents possible condensate overflow or water leakage damage to the ceiling. The secondary drain pan is usually placed on a plywood base isolated from the ceiling joists by additional layers of vibration absorbing material.
CAUTION: Do not use rods smaller than 3/8 in. diameter since they may not be strong enough to support the unit. The rods must be securely anchored to the ceiling.
10

Hanger Bracket Locations

VERSATEC ULTRA SERIES INSTALLATION MANUAL
D
Compressor
Section
B
E
Hanger Dimensions
Model
009-012
015-023
024-030
036
042-048
060
070
Hanger Kit
Part Number
in.
99S500A04
cm [80.5] [55.4] [46.0]
in.
99S500A04
cm [108.6] [63.8] [54.4]
in.
99S500A04
cm [108.7] [63.8] [54.4]
in.
99S500A04
cm [116.3] [63.8] [54.4]
in.
99S500A04
cm [124.0] [71.4] [62.0]
in.
99S500A04
cm [136.7] [71.4] [62.0]
in.
99S500A04
cm [157.0] [71.4] [62.0]
Right
F
C
Air Handler
Section
G
A
3/8”
Threaded Rod
(not supplied)
Bolt and Lockwasher
Unit Hanger Dimensions
ABC
31.7 21.8 18.1
42.8 25.1 21.4
42.8 25.1 21.4
45.8 25.1 21.4
48.8 28.1 24.4
53.8 28.1 24.4
61.8 28.1 24.4
10/29/13
E
Compressor
Section
D
Vibration Isolator
Washer
Hex Nuts (not supplied)
Weight Distribution
Model
009
012
015
018
023
024
030
036
041
042
048
060
070
Vertical
Shipping
Weight
lb. 110 120 46 23 26 25 kg [50] [54] [21] [11] [12] [11] lb. 115 125 48 24 27 26 kg [52] [57] [22] [11] [12] [12] lb. 165 175 67 34 37 36 kg [75] [79] [31] [15] [17] [17] lb. 170 180 69 35 38 38 kg [77] [82] [31] [16] [17] [17] lb. na 185 71 36 39 39 kg na [84] [32] [16] [18] [17] lb. 230 245 94 47 52 51 kg [104] [111] [43] [22] [24] [23] lb. 240 255 98 49 54 53 kg [109] [116] [44] [22] [25] [24] lb. 265 285 110 55 61 59 kg [120] [129] [50] [25] [28] [27] lb. 275 na na na na na kg [125] na na na na na lb. 285 300 115 58 64 63 kg [129] [136] [52] [26] [29] [28] lb. 290 310 119 60 66 65 kg [132] [141] [54] [27] [30] [29] lb. 335 360 138 70 77 75 kg [152] [163] [63] [32] [35] [34] lb. 380 405 156 78 86 84 kg [172] [184] [71] [36] [39] [38]
Horizontal
Shipping
Weight
Left
G
Air Handler
Section
F
Horizontal Weight Distribution
Front Back
DEFG
11/10/09
11
VERSATEC ULTRA SERIES INSTALLATION MANUAL

Duct System

An air outlet collar is provided on vertical top flow units and all horizontal units to facilitate a duct connection. A flexible connector is recommended for discharge and return air duct connections on metal duct systems. Uninsulated duct should be insulated with a minimum of 1-inch duct insulation. Application of the unit to uninsulated ductwork in an unconditioned space is not recommended as the unit’s performance will be adversely affected.
If the unit is connected to existing ductwork, check the duct system to ensure that it has the capacity to accommodate the air required for the unit application. If the duct is too small, as in the replacement of heating only systems, larger ductwork should be installed. All existing ductwork should be checked for leaks and repaired if necessary.

Water Piping

The proper water flow must be provided to each unit whenever the unit operates. To assure proper flow, use pressure/temperature ports to determine the flow rate. These ports should be located at the supply and return water connections on the unit. The proper flow rate cannot be accurately set without measuring the water pressure drop through the refrigerant-to-water heat exchanger.
The duct system should be sized to handle the design airflow quietly and efficiently. To maximize sound attenuation of the unit blower, the supply and return plenums should include an internal duct liner of fiberglass or constructed of ductboard for the first few feet. On systems employing a sheet metal duct system, canvas connectors should be used between the unit and the ductwork. If air noise or excessive airflow is a problem, the blower speed can be changed.
All source water connections on commercial units are fittings that accept a male pipe thread (MPT). Insert the connectors by hand, then tighten the fitting with a wrench to provide a leakproof joint. When connecting to an open loop (groundwater) system, thread any copper MPT fitting into the connector and tighten in the same manner as described above.

Condensate Drain

On vertical units, the internal condensate drain assembly consists of a drain tube which is connected to the drain pan, a 3/4 in. PVC female adapter and a flexible connecting hose. The female adapter may exit either the front or the side of the cabinet. The adapter should be glued to the field-installed PVC condensate piping. On vertical units, a condensate hose is inside all cabinets as a trapping loop; therefore, an external trap is not necessary.
Vent (if needed)
1/2” or 3/4” PVC 1/8 in. per foot
1/2” or 3/4”
PVC tube stub
1/2” or 3/4” PVC Coupling
1.5 in.
Tube Stub
1.5 in.
On horizontal units, a PVC stub or stainless steel tube is provided for condensate drain piping connection. An external trap is required (see below). If a vent is necessary, an open stand pipe may be applied to a tee in the field­installed condensate piping.
Unit Pitch for DrainHorizontal Drain Connection (Composite Drain Pan)
1/2'' Pitch
Drain
12

Water Quality

VERSATEC ULTRA SERIES INSTALLATION MANUAL
In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period
with extremely hard water, the owner should be informed that the heat exchanger may require occasional flushing. Failure to adhere to the guidelines in the water quality table
could result in loss of warranty. of time, lose heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualified service mechanic, as special solutions and pumping equipment are required. Hot water generator coils can likewise become scaled and possibly plugged. In areas
Material Copper 90/10 Cupronickel 316 Stainless Steel
pH Acidity/Alkalinity
Scaling
Corrosion
Iron Fouling
(Biological Growth)
Erosion
NOTES: Grains = ppm divided by 17
mg/L is equivalent to ppm
Calcium and
Magnesium Carbonate
Hydrogen Sulfide
Chlorine Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Chlorides Less than 20 ppm Less than 125 ppm Less than 300 ppm
Carbon Dioxide Less than 50 ppm 10 - 50 ppm 10 - 50 ppm
Ammonia Less than 2 ppm Less than 2 ppm Less than 20 ppm
Ammonia Chloride Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Nitrate Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Hydroxide Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Sulfate Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Total Dissolved Solids (TDS) Less than 1000 ppm 1000 - 1500 ppm 1000 - 1500 ppm
LSI Index +0.5 to -0.5 +0.5 to -0.5 +0.5 to -0.5
Iron, FE
Bacterial Iron Potential
Iron Oxide
Suspended Solids
Threshold Velocity
(Fresh Water)
Less than 0.5 ppm (rotten egg
Sulfates Less than 125 ppm Less than 125 ppm Less than 200 ppm
2
+ (Ferrous)
smell appears at 0.5 ppm)
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
7 - 9 7 - 9 7 - 9
(Total Hardness)
less than 350 ppm
< 0.2 ppm < 0.2 ppm < 0.2 ppm
< 6 ft/sec < 6 ft/sec < 6 ft/sec
Units with cupronickel heat exchangers are recommended
for open loop applications due to the increased resistance
to build-up and corrosion, along with reduced wear caused
by acid cleaning.
(Total Hardness)
less than 350 ppm
10 - 50 ppm Less than 1 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
(Total Hardness)
less than 350 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
2/22/12
13
VERSATEC ULTRA SERIES INSTALLATION MANUAL

System Cleaning and Flushing

Cleaning and Flushing
Prior to start up of any heat pump, the water circulating system must be cleaned and flushed of all dirt and debris.
If the system is equipped with water shutoff valves, the supply and return runouts must be connected together at each unit location (This will prevent the introduction of dirt into the unit, see Flushing with Water Shutoff Valve Equipped Systems illustration). The system should be filled at the water make-up connection with all air vents open. After filling, vents should be closed.
Flushing with Water Shutoff Valve Equipped Systems
Return Runout
Supply Runout
Mains
Rubber Hose
Runouts Initially Connected Together
The contractor should start the main circulator with the pressure reducing valve makeup open. Vents should be checked in sequence to bleed off any trapped air and to verify circulation through all components of the system.
As water circulates through the system, the contractor should check and repair any leaks found in the piping system. Drain(s) at the lowest point(s) in the system should be opened for initial flush and blowdown, making sure water fill valves are set at the same rate. Check the pressure gauge at the pump suction and manually adjust the make­up water valve to hold the same positive pressure both before and after opening the drain valves. Flushing should continue for at least two hours, or longer if required, until drain water is clean and clear.
The supplemental heater and/or circulator pump, if used, should be shut off. All drains and vents should be opened to completely drain the system. Short-circuited supply and return runouts should now be connected to the unit supply and return connections.
Refill the system with clean water. Test the system water for acidity and treat as required to leave the water slightly alkaline (pH 7.5 to 8.5). The specified percentage of antifreeze may also be added at this time. Use commercial grade antifreeze designed for HVAC systems only. Environol™ brand antifreeze is recommended.
Once the system has been filled with clean water and antifreeze (if used), precautions should be taken to protect the system from dirty water conditions. Dirty water will result in system-wide degradation of performance, and solids may clog valves, strainers, flow regulators, etc. Additionally, the heat exchanger may become clogged which reduces compressor service life and can cause premature unit failure.
In boiler/tower application, set the loop control panel set points to desired temperatures. Supply power to all motors and start the circulating pumps. After full flow has been established through all components including the heat rejector (regardless of season), air vented and loop temperatures stabilized, each of the units will be ready for check, test and start up and for air and water balancing.

Ground Source Loop System Checkout

Once piping is completed between the unit pumping system and ground loop, final purging and charging of the loop is needed. A high pressure pump is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from the loop itself. Antifreeze solution is used in most areas to prevent freezing. Flush the system adequately to remove as much air as possible; then pressurize the loop to a static pressure of 40-50 PSI (summer) or 50-75 PSI (winter). This is normally adequate for good system operation. Loop static pressure may decrease soon after initial installation, due to pipe expansion and loop temperature change. Running the unit for at least 30 minutes after the system has been completely purged of air will allow for the “break-in” period. It may be necessary to adjust static loop pressure (by adding water) after the unit has run for the first time. Loop static pressure will also fluctuate with the seasons. Pressures will be higher in the winter months than during the cooling season. This fluctuation is normal and should be considered when charging the system initially.
Ensure the pump provides adequate flow through the unit by checking pressure drop across the heat exchanger. Usually 2.25-3.0 gpm of flow per ton of cooling capacity is recommended in earth loop applications.
14

Open Loop Ground Water Systems

VERSATEC ULTRA SERIES INSTALLATION MANUAL
Typical open loop piping is shown below. Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit to prevent mineral precipitation. Use a closed, bladder-type expansion tank to minimize mineral formation due to air exposure. Insure proper water flow through the unit by checking pressure drop across the heat exchanger and comparing it to the figures in unit capacity data tables in the specification catalog. 1.5-2 gpm of flow per ton of cooling capacity is recommended in open loop applications. Due to only minor differences in flow rate from low to high, only one solenoid valve should be used. The valve should be sized for full flow.
Open System - Groundwater Application
Unit Supply
Aux. Heat Supply
Flexible Duct Collar
Rubber Bladder Expansion Tank
Hot Water Generator
Connections
Solenoid
Valve
Drain
Disconnects
(IfApplicable)
Compressor Line Voltage
Low Voltage
to Thermostat
and Valve
P/T Plugs
Vibration
Absorbing Pad
Strainer
Boiler Drains
For HX Flushing
Shut Off Valves
(to isolate solenoid
valve while acid flushing)
Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways, depending on local codes, i.e. recharge well, storm sewer, drain field, adjacent stream or pond, etc. Most local codes forbid the use of sanitary sewer for disposal. Consult your local building and zoning departments to assure compliance in your area.
Flow Control
Valve
(on outlet of
Solenoid Valve)
Water Out
Water In
Shut Off Valves
15
VERSATEC ULTRA SERIES INSTALLATION MANUAL

Hot Water Generator Connections

The heat reclaiming hot water generator coil is of vented double-wall copper construction and is suitable for potable water.
To maximize the benefits of the hot water generator a minimum 50-gallon water heater is recommended. For higher demand applications, use an 80-gallon water heater or two 50-gallon water heaters connected in a series as shown below. Electric water heaters are recommended. Make sure all local electrical and plumbing codes are met for installing a hot water generator. A water softener is recommended with hard water (greater than 10 grains or 170 total hardness).
Water Tank Preparation
To install a unit with a hot water generator, follow these installation guidelines.
1. Turn off the power to the water heater.
2. Attach a water hose to the water tank drain connection and run the other end of the hose to an open drain or outdoors.
3. Close the cold water inlet valve to the water heater tank.
4. Drain the tank by opening the valve on the bottom of the tank, then open the pressure relief valve or hot water faucet.
5. Flush the tank by opening the cold water inlet valve to the water heater to free the tank of sediments. Close when draining water is clear.
6. Disconnect the garden hose and remove the drain valve from the water heater.
7. Refer to Plumbing Installation and Hot Water Generator Startup.
Typical Hot Water Generator Installation
3/4 in. x 3/4 in. x 1/2 in. Tee
Ball Valve
Vent
HWG
Water Out
Field Installed
HWG Pump
HWG
Water In
Cold
Water In
Drain Valve
P/T Relief
Valve
Water Out
In
Hot
Hot Water Generator Installation In Preheat Tank
Cold
3/4 in. x 3/4 in. x 1/2 in. Tee
Ball Valve
Vent
Water Out
Field Installed
HWG
Water In
HWG
HWG Pump
Water In
P/T Relief
Valve
In
Drain Valve
NOTE: This configuration maximizes hot water generator capability.
Hot
Water Out
P/T Relief
Valve
Plumbing Installation
1. Inspect the dip tube in the water heater cold inlet
for a check valve. If a check valve is present it must be removed or damage to the hot water generator circulator will occur.
2. Remove drain valve and fitting.
3. Thread the 3/4-inch NPT x 3-1/2-inch brass nipple into
the water heater drain port.
4. Attach the center port of the 3/4-inch FPT tee to the
opposite end of the brass nipple.
5. Attach the 1/2-inch copper to 3/4-inch NPT adaptor to
the side of the tee closest to the unit.
6. Install the drain valve on the tee opposite the adaptor.
7. Run interconnecting tubing from the tee to HWG
water out.
CAUTION: Elements will burn out if energized dry.
8. Cut the cold water “IN” line going to the water heater.
9. Insert the reducing solder tee in line with cold water “IN” line as shown.
10. Run interconnecting copper tubing between the unit DHW water “IN” and the tee (1/2-inch nominal). The recommended maximum distance is 50 feet.
11.
To prevent air entrapment in the system, install a vent coupling at the highest point of the interconnecting lines.
12. Insulate all exposed surfaces of both connecting water lines with 3/8-inch wall closed cell insulation.
NOTE: All plumbing and piping connections must comply with local plumbing codes.
16
VERSATEC ULTRA SERIES INSTALLATION MANUAL
Hot Water Generator Connections cont.
Hot Water Generator Startup
1. Make sure the power is off to the heat pump. Connect the wire from the hot water generator pump to T1 on the contactor.
2. Close the drain valve to the water heater.
3. Open the cold water supply to the tank.
4. Open a hot water faucet in the building to bleed air from the system. Close when full.
5. Open the pressure relief valve to bleed any remaining air from the tank, then close.
6. If so equipped, turn the venting (burping) screw in the center of the pump two (2) turns open (water will drip out), wait until all air is purged from the pump, then tighten the plug. Use vent couplings to bleed air from the lines.
7. Carefully inspect all plumbing for water leaks and correct as required.
8. Before restoring electrical supply to the water heater, adjust the temperature setting on the tank.
• On tanks with both upper and lower elements, the lower element should be turned down to the lowest setting, approximately 100°F. The upper element should be adjusted to 120°F to 130°F. Depending upon the specific needs of the customer, you may want to adjust the upper element differently.
• On tanks with a single element, lower the thermostat setting to 120°F.
9. After the thermostat(s) is adjusted, replace the access cover and restore electrical supply to the water heater.
10. Make sure that any valves in the hot water generator circuit are open.
11. Turn on the unit to heating.
12. The HWG pump should be running. When the pump is first started, turn the venting (burping) screw (if equipped) in the center of the pump two (2) turns open until water dribbles out, then replace. Allow the pump to run for at least five minutes to ensure that water has filled the circulator properly.
13. The temperature difference between the water entering and leaving the hot water generator should be 5°F to 15°F. The water flow should be approximately 0.4 gpm per ton of nominal cooling.
14. Allow the unit to heat water for 15 to 20 minutes to be sure operation is normal.
CAUTION: Never operate the HWG circulating pump while dry. If the unit is placed in operation before the hot water generator piping is connected, be sure that the pump wires are disconnected from the contactor.
17
VERSATEC ULTRA SERIES INSTALLATION MANUAL

Freeze Detection

For Aurora Base Control, set SW2-1, FP1, on the printed circuit board for applications using a closed loop antifreeze solution to 15°F [-9.4°C]. On applications using an open loop/ground water system (or closed loop no antifreeze), set this dip switch to 30°F [-1.1°C], the factory default setting. (Refer to the Dip Switch Field Selection table).

Electrical Connections

General
Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable.
Power Connection
Connect the incoming line voltage wires to L1 and L2 of the contactor for single-phase unit. Consult the Electrical Data tables for correct fuse sizes.
Aurora Base Control Box
208 Volt Operation
All Versatec Ultra Series 208/230 units are factory wired for 230 volt operation. For 208 volt operation, the red and blue transformer wires must be switched on terminal strip PS.
CAUTION: When installing a unit with an ECM blower motor in 460/60/3 voltage, a neutral wire is required to allow proper unit operation.
18
Loading...
+ 42 hidden pages