WaterFurnace Versatec Base User Manual

Installation Information
Water Piping Connections
Electrical
Startup Procedures
Troubleshooting
Preventive Maintenance
Versatec Base Series Installation Manual
IM1201AUB 05/14
Table of Contents
Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
General Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
Installing Horizontal Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Hanger Bracket Locations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Duct System and Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Water Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
System Cleaning and Flushing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Open Loop Ground Water Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Freeze Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
VERSATEC BASE SERIES INSTALLATION MANUAL
Electrical Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-18
Blower Performance Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-22
5-Speed ECM Constant Torque Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Wiring Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24-29
Controls - Aurora Base Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30-33
Controls - UPC (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34-39
Unit Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Operating Parameters and Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
Compressor and Thermistor Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Refrigerant Circuit Guideline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Heat of Extraction/Rejection Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Reference Calculations and Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
Startup/Troubleshooting Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47-48
Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Replacement Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Service Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50-51
Revision Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
VERSATEC BASE SERIES INSTALLATION MANUAL
UB
1-2 3 4-6 7 8 9
10 11 12 14
V 036 T L 0 0 0 C A N13A15N16017A18319020SS
21-22*23

Model Nomenclature

Model Type
UB – Versatec Base
Cabinet Configuration
V – Vertical H - Horizontal
Unit Capacity (MBTUH) 006, 009, 012, 015, 018, 024, 030, 036, 042, 048, 060, 070
Discharge Configuration
T – Top (Vertical) E – End (Horizontal) S – Side (Horizontal)
Return Air Configuration
L – Left R – Right
Voltage
0 – 208-230/60/1 2 – 265-277/60/1 (006-036) 3 – 208-230/60/3 (024-070) 4 – 460/60/3 (024-070) 5 – 575/60/3 (PSC Only 042-070) 9 – 115/60/1 (006-012)
Future Option
0 – None
Blower Options
0 – PSC Blower 1 – Variable Speed ECM Blower (015-070) 4 – 5-Speed ECM Blower (015-070)
Water Coil Option
C – Copper D – Insulated Copper N – CuproNickel P – Insulated CuproNickel
Sound Kit Option
A – None B – Sound Kit (Not Available on UBH006-012)
Vintage
* - Factory Use Only
Non-Standard Options
SS – Standard
Drain Pan Option
0 – Composite, No Secondary Connection 1 – Composite, Secondary Connection 2 – Stainless Steel, No Secondary Connection 3 – Stainless Steel, Secondary Connection
Air Coil Option
3 – All-Aluminum, Uncoated 4 – All-Aluminum, AlumiSeal
Filter Option
A – MERV 4 B – MERV 13
Cabinet Option
0 – Unpainted Cabinet, Filter Rail 2 – Unpainted Cabinet, 4-Sided Filter Rack 1 – Painted Cabinet, Filter Rail 3 – Painted Cabinet, 4-Sided Filter Rack
Phase Guard
N – No Phase Guard, No Disconnect D – No Phase Guard, Disconnect P – Phase Guard, No Disconnect B – Phase Guard, Disconnect
Control Option
A – AuroraTM Base Control (ABC) E – Aurora UPC DDC Controller F – Aurora UPC DDC Controller with LON
Water Control Option
N – None R – Water Flow Regulator (015-070) V – 2-Way Valve (015-070) B – 2-Way Valve w/ Water Flow Regulator (015-070)
Rev.: 24 April 2014D
1
2
TM
Note: 1 - Phase Guard Only Available on 208-230/60/3, 460/60/3, and 575/60/3 2 - 50VA transformer with Aurora Base Control, and 75VA transformer with Aurora UPC control
All Versatec Base Series product is safety listed under UL1995 thru ETL and performance listed with AHRI in accordance with standard 13256-1.
4

General Installation Information

VERSATEC BASE SERIES INSTALLATION MANUAL
Safety Considerations
WARNING: Before performing service or maintenance operations on a system, turn off main power switches to the indoor unit. If applicable, turn off the accessory heater power switch. Electrical shock could cause personal injury.
Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair or service heating and air conditioning equipment. Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning and replacing filters. All other operations should be performed by trained service personnel. When work­ing on heating and air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations and have a fire extinguisher available.
Moving and Storage
Move units in the normal “up” orientation. Horizontal units may be moved and stored per the information on the packaging. Do not stack more than three units in total height. Vertical units may be stored one upon another to a maximum height of two units. Do not attempt to move units while stacked. When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Examine units for shipping damage, removing the units from the packaging if necessary. Units in question should also be internally inspected. If any damage is noted, the carrier should make the proper notation on the delivery receipt, acknowledging the damage.
Unit Location
Locate the unit in an indoor area that allows for easy removal of the filter and access panels. Location should have enough space for service personnel to perform maintenance or repair. Provide sufficient room to make water, electrical and duct connection(s). If the unit is located in a confined space, such as a closet, provisions must be made for return air to freely enter the space by means of a louvered door, etc. Any access panel screws that would be difficult to remove after the unit is installed should be removed prior to setting the unit. On horizontal units, allow adequate room below the unit for a condensate drain trap and do not locate the unit above supply piping. Care should be taken when units are
located in unconditioned spaces to prevent damage from frozen water lines and excessive heat that could damage electrical components.
Installing Vertical Units
Vertical units are available in left or right air return configurations. Top flow vertical units should be mounted level on a vibration absorbing pad slightly larger than the base to provide isolation between the unit and the floor.
Vertical Unit Mounting
2 in. PEX Foam
5
VERSATEC BASE SERIES INSTALLATION MANUAL
Vertical Dimensional Data
Standard filter rails for
open return applications
Field installed duct flange
Deluxe filter rack for
ductable return applications
A
RN
S
Q
AIR COIL SIDE
P
B
A
Air coil
N
Q
ACCESS
PANEL
P
B
AIR COIL SIDE
2' (61 cm) Alternate
F
Service Access
2' (61 cm)
Isometric View - Left Return
FRONT
F
M
M
FRONT
Top View - Right Return Top View - Left Return
Service Access Left Return
(Right Return Opposite Side)
U
T
W
Air coil
Air coil
ACCESS
PANEL
ACCESS
PANEL
C
1.6 in (4.1 cm) Condensate 3/4 in
PVC glue socket
1.6 in (4.1 cm)
5
H
2
E
1
D
Front View - Right Return
Water Connections*
Power supply
1 in (25.4 mm)
knockout
6 8
1/2" (12.7 mm)
J
L
Low voltage
knockout
L
K
Condensate
3/4 in PVC
glue socket
1.6 in (4.1 cm)
8 7
Water
Connections*
Front View - Left Return
NOTE: * Water connections protrude approximately 1.5 in. from cabinet.
V
C
1.6 in (4.1 cm)
5 2
1
H
E
J
D
6
ACCESS
8
PANEL
L
8 7
L
K
Right View - Right Return (J & L)
Left View - Left Return (K & L)
6
Vertical Dimensional Data cont.
VERSATEC BASE SERIES INSTALLATION MANUAL
Overall Cabinet
Vertical
Models
006-012
015-018
024-030
036
042-048
060
070
006-012
015-018
024-030
036
042-048
060
070
Condensate is 3/4 in. PVC female glue socket and is switchable from side to front. * Discharge fl ange is fi eld installed and extends 1 in. (25.4 mm) from top of cabinet.
** Vertical units shipped with standard 2 in. (fi eld adjustable to 1 in.) open application fi lter rail extending 2.2 in. from the unit and is not suitable for duct connection. For ductable return connection applications, order the 2 in. (fi eld adjustable to 1 in.) duct collar/ fi lter rack which extends to 3.25 in. from the unit and is suitable for duct connections.
in. 19.2 19.2 24.2 2.6 5.6 8.8 1/2 in. 7.4 3.4 5.4 2.2
cm. 48.8 48.8 61.5 6.6 14.2 22.4 12.7 mm 18.8 8.6 13.7 5.6
in. 22.5 22.2 30.2 2.6 7.6 10.8 3/4 in. 9.4 5.4 7.4 2.2
cm. 57.2 56.4 76.7 6.6 19.3 27.4 19.1 mm 23.9 13.7 18.8 5.6
in. 22.5 22.2 36.2 2.6 7.6 10.8 3/4 in. 9.4 5.4 7.4 2.2
cm. 57.2 56.4 91.9 6.6 19.3 27.4 19.1 mm 23.9 13.7 18.8 5.6
in. 22.5 26.2 40.2 2.6 7.6 10.8 3/4 in. 10.1 6.1 8.1 2.2
cm. 57.2 66.5 102.1 6.6 19.3 27.4 19.1 mm 25.7 15.5 20.6 5.6
in. 22.5 26.2 44.2 2.6 7.6 10.8 3/4 in. 10.1 6.1 8.1 2.2
cm. 57.2 66.5 112.3 6.6 19.3 27.4 19.1 mm 25.7 15.5 20.6 5.6
in. 25.5 31.2 44.2 2.6 7.6 10.8 1 in. 10.1 6.1 8.1 2.2
cm. 64.8 79.2 112.3 6.6 19.3 27.4 25.4 mm 25.7 15.5 20.6 5.6
in. 25.5 31.2 48.2 2.6 7.6 10.8 1 in. 10.1 6.1 8.1 2.2
cm. 64.8 79.2 122.4 6.6 19.3 27.4 25.4 mm 25.7 15.5 20.6 5.6
Vertical
Models
in. 10.0 10.0 4.6 4.4 7.8 2.4 14.3 10.1 2.0
cm. 25.4 25.4 11.7 11.2 19.8 6.1 36.3 25.7 5.1
in. 14.0 14.0 4.1 4.3 7.7 2.1 18.1 14.0 2.0
cm. 35.6 35.6 10.4 10.9 19.6 5.3 46.0 35.6 5.1
in. 14.0 14.0 4.1 4.3 7.7 2.1 18.1 20.0 2.0
cm. 35.6 35.6 10.4 10.9 19.6 5.3 46.0 50.8 5.1
in. 14.0 14.0 6.1 4.5 7.7 2.1 22.1 22.1 2.0
cm. 35.6 35.6 15.5 11.4 19.6 5.3 56.1 56.1 5.1
in. 18.0 18.0 4.1 3.9 3.9 2.1 22.1 26.1 2.0
cm. 45.7 45.7 10.4 9.9 9.9 5.3 56.1 66.3 5.1
in. 18.0 18.0 6.6 4.6 6.3 1.6 28.1 26.0 2.0
cm. 45.7 45.7 16.8 11.7 16.0 4.1 71.4 66.0 5.1
in. 18.0 18.0 6.6 4.6 6.3 1.6 28.1 30.0 2.0
cm. 45.7 45.7 16.8 11.7 16.0 4.1 71.4 76.2 5.1
A B C D E H 1/2 in. cond 1/2 in. cond 1 in. cond M
Width Depth Height* In Out
Discharge Connection
duct fl ange installed (±0.10 in)
NPQRSTUVW
Supply Width Supply Depth Return Depth Return Height
125
Water Connections
Cond-
ensate
Loop
Water FPT
Electrical Knockouts 678 JKL
Low
Voltage
using deluxe fi lter rack (±0.10 in)
Low
Voltage
**Return Connection
Supply
Power
Filter Rack
Width
09/26/12
Vertical Disconnect
When using disconnect, do not use dimension L from the standard vertical dimensional data. Use dimension LL from the vertical disconnect dimensional data.
Vertical Models LL
015-018
024-030
036
042-048
060 070
Dimensions in inches [cm] * Models 006-012 - Externally Mounted Disconnect
15.8 [40.1]
18.8 [47.8]
15.3 [38.9]
13.8 [35.1]
14.3 [36.3]
14.3 [36.3]
Disconnect Located
on this Side for a
Disconnect
Location
Power Supply
Right Return
Alternative Power Supply
LL
Vertical Shown in Left
Return Configuration
7
VERSATEC BASE SERIES INSTALLATION MANUAL
Horizontal Dimensional Data
Right Return
Condensate "X" PVC size
End Discharge
Deluxe filter rack option shown
2.3
BLOWER
OUTLET
AIR COIL SIDE
FILTER RACK
H
3
2.1
Right Return
End Discharge
N
A
Standard filter rails
1 in knockout
1/2 in knockout
Side Discharge
P
M
C
L
BP
Front
AP
CMP
2' (61 cm)
Service Access
1.7
K
J
Right Return Air Front View
1.7
2
E
1
D
Left Return Air Front View
AP = Alternate Service Panel BP = Blower Service Panel CP = Control Access Panel CMP = Compressor Service Panel
1.7
CP AP
CMP
A
1.7
CP AP
CMP
Legend
E
D
J
Service Access
1/2 in knockout 1 in knockout
K
Standard filter rails
Front
AP
CMP
2' (61 cm)
BP
Side Discharge
Deluxe filter rack option shown P
N
L
C
M
BLOWER
OUTLET
Left Return
End Discharge
A
Left Return
"X" PVC size
End Discharge
2.3 AIR COIL SIDE
FILTER RACK
3
2.1
Condensate
H
P
P
N
L
M
BP
Air Coil
Front Front
Water Connections*
BLOWER
OUTLET
Right Return Side Discharge
C
FILTER RACK CONNECTION FILTER RACK CONNECTION
B
Right Return Side View
AP
CMP
1.5
K
Front
J
SQ
R
1/2 in knockout
1 in knockout
1" knockout
1/2 in knockout
T
Deluxe filter
rack option
(shown)
Front
C
1.5
J
AP
K
T
CMP
Left Return Side Discharge
S
R
Q
B
Left Return Side View
N
BLOWER
OUTLET
Air Coil
Water Connections*
NOTE: * Water connections protrude approximately 1.5 in. from cabinet.
BP
M
L
8
Horizontal Dimensional Data cont.
VERSATEC BASE SERIES INSTALLATION MANUAL
Horizontal
Models
Width Depth Height* In Out Condensate Water FPT Low Voltage Power Supply
006-012**
015-018
024-030
036
042-048
060
070
Horizontal
Models
006-012**
015-018
024-030
036
042-048
060
070
Horizontal units shipped with standard 2 in. (fi eld adjustable to 1 in.) open application fi lter rail extending 2.2 in. from the unit and is not suitable for duct connection. For ductable return connection applications, order the 2 in. (fi eld adjustable to 1 in.) duct collar/ fi lter rack which extends to 3.25 in. from the unit and is suitable for duct connections.
** UBH006-012 offers a lifted drain pan that allows the trap to be installed without additional ceiling height required.
in. 19.2 35.0 12.1 1.8 4.8 3.6 1/2 in. 7.4 7.5
cm. 48.8 88.9 30.7 4.6 12.2 9.1 12.70 mm 18.8 19.1
in. 22.5 35.0 17.2 1.8 6.8 0.8 3/4 in. 7.1 7.1
cm. 57.2 88.9 43.7 4.6 17.3 2.0 19.05 mm 18.0 18.0
in. 22.5 42.0 17.2 1.8 6.8 0.8 3/4 in. 7.1 7.1
cm. 57.2 106.7 43.7 4.6 17.3 2.0 19.05 mm 18.0 18.0
in. 22.5 42.0 19.2 1.8 6.8 0.8 3/4 in. 9.2 7.1
cm. 57.2 106.7 48.8 4.6 17.3 2.0 19.05 mm 23.4 18.0
in. 22.5 45.0 19.2 1.8 6.8 0.8 3/4 in. 9.2 7.1
cm. 57.2 114.3 48.8 4.6 17.3 2.0 19.05 mm 23.4 18.0
in. 25.5 48.0 21.2 1.8 6.8 0.8 1 in. 9.2 9.1
cm. 64.8 121.9 53.8 4.6 17.3 2.0 25.4 mm 23.4 23.1
in. 25.5 53.0 21.2 1.8 6.8 0.8 1 in. 9.2 9.1
cm. 64.8 134.6 53.8 4.6 17.3 2.0 25.4 mm 23.4 23.1
in. 2.3 8.0 10.0 2.7 22.5 9.4 2.4 1.4 1/2 in.
cm. 5.8 20.3 25.4 6.9 57.2 23.9 6.1 3.6 1.3
in. 5.7 10.5 9.4 4.9 16.4 14.5 2.0 1.4 3/4 in.
cm. 14.5 26.7 23.9 12.4 41.7 36.8 5.1 3.6 1.9
in. 5.7 10.5 9.4 4.9 23.4 14.5 2.0 1.4 3/4 in.
cm. 14.5 26.7 23.9 12.4 59.4 36.8 5.1 3.6 1.9
in. 6.7 10.5 9.4 4.9 27.4 16.5 2.0 1.4 3/4 in.
cm. 17.0 26.7 23.9 12.4 69.6 41.9 5.1 3.6 1.9
in. 4.2 13.6 13.2 2.4 30.4 16.5 2.0 1.5 3/4 in.
cm. 10.7 34.5 33.5 6.1 77.2 41.9 5.1 3.8 1.9
in. 4.8 13.6 13.2 4.6 35.4 18.7 2.3 1.3 3/4 in.
cm. 12.2 34.5 33.5 11.7 89.9 47.5 5.8 3.3 1.9
in. 4.8 13.6 13.2 4.6 40.4 18.5 2.3 1.4 3/4 in.
cm. 12.2 34.5 33.5 11.7 102.6 47.0 5.8 3.6 1.9
Overall Cabinet
A B C D E H 1/2 in. cond 1 in. cond
Discharge Connection
duct fl ange installed (±0.10 in)
LMNPQRS TX
Supply Width Supply Depth Return Depth Return Height
123
Water Connections Electrical Knockouts
Loop
Return Connection
using deluxe fi lter rack option (±0.10 in)
JK
PVC Size
09/26/12
Horizontal Disconnect
When using disconnect, do not use dimension K from the standard horizontal dimensional data. Use dimension KK from the horizontal disconnect dimensional data.
Horizontal Models KK
015-018
024-030
036
042-048
060 070
Dimensions in inches [cm] * Models 006-012 - Externally Mounted Disconnect
8.2 [20.8]
8.2 [20.8]
9.2 [23.4]
9.2 [23.4]
11.2 [28.4]
10.2 [25.9]
Disconnect Located on this Side for a Left Return
Disconnect Location
KK
Power Supply
Horizontal Shown
In Right Return
Configuration
9
VERSATEC BASE SERIES INSTALLATION MANUAL

Installing Horizontal Units

Installing Horizontal Units
Horizontal units are available with side or end discharge and may be easily field converted by flipping the blower discharge panel. Horizontal units are normally suspended from a ceiling by four 3/8 in. diameter threaded rods. The rods are usually attached to the unit by hanger bracket kits furnished with each unit. Lay out the threaded rods per the dimensions below. Assemble the hangers to the unit as shown. Securely tighten the brackets to the unit using the weld nuts located on the underside of the bottom panel. When attaching the hanger rods to the bracket, a double nut is required since vibration could loosen a single nut.
NOTE: The unit should be pitched approximately 1/4 in. towards the drain in both directions to facilitate the removal of condensate.
Horizontal Unit Mounting
Use only the bolts provided in the kit to attach hanger brackets. The use of longer bolts could damage internal parts. Some applications require the installation of horizontal units on an attic floor. In this case, the unit should be set in a full size secondary drain pan on top of a vibration absorbing pad. The secondary drain pan prevents possible condensate overflow or water leakage damage to the ceiling. The secondary drain pan is usually placed on a plywood base isolated from the ceiling joists by additional layers of vibration absorbing material. Insulate supply plenum and use at least one 90° elbow and flexible duct collar to reduce noise.
CAUTION: Do not use rods smaller than 3/8 in. diameter since they may not be strong enough to support the unit. The rods must be securely anchored to the ceiling.
10

Hanger Bracket Locations

VERSATEC BASE SERIES INSTALLATION MANUAL
D
Compressor
Section
B
E
Hanger Dimensions
Model
006-012
015-018
024-030
036
042-048
060
070
Hanger Kit
Part Number
in.
99S500A04
cm. 90.9 55.4 46.0
in.
99S500A04
cm. 90.9 63.8 54.4
in.
99S500A04
cm. 108.6 63.8 54.4
in.
99S500A04
cm. 108.7 63.8 54.4
in.
99S500A04
cm. 116.3 63.8 54.4
in.
99S500A04
cm. 124.0 71.4 62.0
in.
99S500A04
cm. 136.7 71.4 62.0
Right
F
C
Air Handler
Section
G
A
3/8”
Threaded Rod
(not supplied)
Bolt and Lockwasher
Unit Hanger Dimensions
ABC
35.8 21.8 18.1
35.8 25.1 21.4
42.8 25.1 21.4
42.8 25.1 21.4
45.8 25.1 21.4
48.8 28.1 24.4
53.8 28.1 24.4
09/26/12
E
Compressor
Section
D
Vibration Isolator
Washer
Hex Nuts (not supplied)
Weight Distribution
Model
006-
012
015-
018
024
030
036
042
048
060
070
Vertical
Shipping
Weight
lb. 111 112 44 21 19 28
kg 50 51 20 10 9 12
lb. 171 176 67 32 32 45
kg 78 80 30 15 15 20
lb. 245 242 85 47 45 65
kg 111 110 39 21 20 29
lb. 245 242 85 47 45 65
kg 111 110 39 21 20 29
lb. 267 265 95 60 50 60
kg 121 120 43 27 23 27
lb. 305 310 105 68 60 77
kg 138 141 48 31 27 35
lb. 305 310 105 68 60 77
kg 138 141 48 31 27 35
lb. 344 350 115 77 68 90
kg 156 159 52 35 31 41
lb. 357 378 130 80 73 95
kg 162 171 59 36 33 43
Horizontal
Shipping
Weight
Left
G
Air Handler
Section
F
Horizontal Weight Distribution
Front Back
DEFG
10/03/12
11
VERSATEC BASE SERIES INSTALLATION MANUAL

Duct System

An air outlet collar is provided on vertical top flow units and all horizontal units to facilitate a duct connection. A flexible connector is recommended for discharge and return air duct connections on metal duct systems. Uninsulated duct should be insulated with a minimum of 1-inch duct insulation. Application of the unit to uninsulated ductwork in an unconditioned space is not recommended as the unit’s performance will be adversely affected.
If the unit is connected to existing ductwork, check the duct system to ensure that it has the capacity to accommodate the air required for the unit application. If the duct is too small, as in the replacement of heating only systems, larger

Water Piping

The proper water flow must be provided to each unit whenever the unit operates. To assure proper flow, use pressure/temperature ports to determine the flow rate. These ports should be located at the supply and return water connections on the unit. The proper flow rate cannot be accurately set without measuring the water pressure drop through the refrigerant-to-water heat exchanger.
ductwork should be installed. All existing ductwork should be checked for leaks and repaired if necessary.
The duct system should be sized to handle the design airflow quietly and efficiently. To maximize sound attenuation of the unit blower, the supply and return plenums should include an internal duct liner of fiberglass or constructed of ductboard for the first few feet. On systems employing a sheet metal duct system, canvas connectors should be used between the unit and the ductwork. If air noise or excessive airflow is a problem, the blower speed can be changed.
All source water connections on commercial units are fittings that accept a male pipe thread (MPT). Insert the connectors by hand, then tighten the fitting with a wrench to provide a leakproof joint. When connecting to an open loop (groundwater) system, thread any copper MPT fitting into the connector and tighten in the same manner as described above.
12

Water Quality

VERSATEC BASE SERIES INSTALLATION MANUAL
In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period
with extremely hard water, the owner should be informed that the heat exchanger may require occasional flushing. Failure to adhere to the guidelines in the water quality table
could result in loss of warranty. of time, lose heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualified service mechanic, as special solutions and pumping equipment are required. Hot water generator coils can likewise become scaled and possibly plugged. In areas
Material Copper 90/10 Cupronickel 316 Stainless Steel
pH Acidity/Alkalinity
Scaling
Corrosion
Iron Fouling
(Biological Growth)
Erosion
NOTES: Grains = ppm divided by 17
mg/L is equivalent to ppm
Calcium and
Magnesium Carbonate
Hydrogen Sulfide
Chlorine Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Chlorides Less than 20 ppm Less than 125 ppm Less than 300 ppm
Carbon Dioxide Less than 50 ppm 10 - 50 ppm 10 - 50 ppm
Ammonia Less than 2 ppm Less than 2 ppm Less than 20 ppm
Ammonia Chloride Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Nitrate Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Hydroxide Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Sulfate Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Total Dissolved Solids (TDS) Less than 1000 ppm 1000 - 1500 ppm 1000 - 1500 ppm
LSI Index +0.5 to -0.5 +0.5 to -0.5 +0.5 to -0.5
Iron, FE
Bacterial Iron Potential
Iron Oxide
Suspended Solids
Threshold Velocity
(Fresh Water)
Less than 0.5 ppm (rotten egg
Sulfates Less than 125 ppm Less than 125 ppm Less than 200 ppm
2
+ (Ferrous)
smell appears at 0.5 ppm)
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 mic
7 - 9 7 - 9 7 - 9
(Total Hardness)
less than 350 ppm
< 0.2 ppm < 0.2 ppm < 0.2 ppm
< 6 ft/sec < 6 ft/sec < 6 ft/sec
Units with cupronickel heat exchangers are recommended
for open loop applications due to the increased resistance
to build-up and corrosion, along with reduced wear caused
by acid cleaning.
ron size
(Total Hardness)
less than 350 ppm
10 - 50 ppm Less than 1 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
(Total Hardness)
less than 350 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
2/22/12

Condensate Drain

On vertical units, the internal condensate drain assembly consists of a drain tube which is connected to the drain pan, a 3/4 in. PVC female adapter and a flexible connecting hose. The female adapter may exit either the front or the side of the cabinet. The adapter should be glued to the field-installed PVC condensate piping. On vertical units, a condensate hose is inside all cabinets as a trapping loop; therefore, an external trap is not necessary.
Vent (if needed)
PVC tube stub 1/8 in. per foot
PVC tube stub
NOTE: UBH006-012 offers a lifted drain pan that allows the trap to be installed without additional ceiling height required.
PVC coupling
1.5 in.
1.5 in.
On horizontal units, a PVC stub or stainless steel tube is provided for condensate drain piping connection. An external trap is required (see below). If a vent is necessary, an open stand pipe may be applied to a tee in the field­installed condensate piping.
NOTE: All units equipped with electronic condensate overflow protection.
Unit Pitch for DrainHorizontal Drain Connection (Composite Drain Pan)
1/2'' Pitch
Drain
13
VERSATEC BASE SERIES INSTALLATION MANUAL

System Cleaning and Flushing

Cleaning and Flushing
Prior to start up of any heat pump, the water circulating system must be cleaned and flushed of all dirt and debris.
If the system is equipped with water shutoff valves, the supply and return runouts must be connected together at each unit location (This will prevent the introduction of dirt into the unit, see Flushing with Water Shutoff Valve Equipped Systems illustration). The system should be filled at the water make-up connection with all air vents open. After filling, vents should be closed.
Flushing with Water Shutoff Valve Equipped Systems
Return Runout
Supply Runout
Mains
Rubber Hose
Runouts Initially Connected Together
The contractor should start the main circulator with the pressure reducing valve makeup open. Vents should be checked in sequence to bleed off any trapped air and to verify circulation through all components of the system.
As water circulates through the system, the contractor should check and repair any leaks found in the piping system. Drain(s) at the lowest point(s) in the system should be opened for initial flush and blowdown, making sure water fill valves are set at the same rate. Check the pressure gauge at the pump suction and manually adjust the make­up water valve to hold the same positive pressure both before and after opening the drain valves. Flushing should continue for at least two hours, or longer if required, until drain water is clean and clear.
The supplemental heater and/or circulator pump, if used, should be shut off. All drains and vents should be opened to completely drain the system. Short-circuited supply and return runouts should now be connected to the unit supply and return connections.
Refill the system with clean water. Test the system water for acidity and treat as required to leave the water slightly alkaline (pH 7.5 to 8.5). The specified percentage of antifreeze may also be added at this time. Use commercial grade antifreeze designed for HVAC systems only. Environol™ brand antifreeze is recommended.
Once the system has been filled with clean water and antifreeze (if used), precautions should be taken to protect the system from dirty water conditions. Dirty water will result in system-wide degradation of performance, and solids may clog valves, strainers, flow regulators, etc. Additionally, the heat exchanger may become clogged which reduces compressor service life and can cause premature unit failure.
In boiler/tower application, set the loop control panel set points to desired temperatures. Supply power to all motors and start the circulating pumps. After full flow has been established through all components including the heat rejector (regardless of season), air vented and loop temperatures stabilized, each of the units will be ready for check, test and start up and for air and water balancing.

Ground Source Loop System Checkout

Once piping is completed between the unit pumping system and ground loop, final purging and charging of the loop is needed. A high pressure pump is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from the loop itself. Antifreeze solution is used in most areas to prevent freezing. Flush the system adequately to remove as much air as possible; then pressurize the loop to a static pressure of 40-50 PSI (summer) or 50-75 PSI (winter). This is normally adequate for good system operation. Loop static pressure may decrease soon after initial installation, due to pipe expansion and loop temperature change. Running the unit for at least 30 minutes after the system has been completely purged of air will allow for the “break-in” period. It may be necessary to adjust static loop pressure (by adding water) after the unit has run for the first time. Loop static pressure will also fluctuate with the seasons. Pressures will be higher in the winter months than during the cooling season. This fluctuation is normal and should be considered when charging the system initially.
Ensure the pump provides adequate flow through the unit by checking pressure drop across the heat exchanger. Usually 2.25-3.0 gpm of flow per ton of cooling capacity is recommended in earth loop applications.
14

Open Loop Ground Water Systems

VERSATEC BASE SERIES INSTALLATION MANUAL
Typical open loop piping is shown below. Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit to prevent mineral precipitation. Use a closed, bladder-type expansion tank to minimize mineral formation due to air exposure. Insure proper water flow through the unit by checking pressure drop across the heat exchanger and comparing it to the figures in unit capacity data tables in the specification catalog. 1.5-2 gpm of flow per ton of cooling capacity is recommended in open loop applications. Due to only minor differences in flow rate from low to high, only one solenoid valve should be used. The valve should be sized for full flow.
Open System - Groundwater Application
Unit Supply
Aux. Heat Supply
Flexible Duct Collar
Rubber Bladder Expansion Tank
Solenoid
Valve
Drain
Disconnects
(IfApplicable)
Compressor Line Voltage
Low Voltage
to Thermostat
and Valve
P/T Plugs
Vibration
Absorbing Pad
Strainer
Boiler Drains
For HX Flushing
Shut Off Valves
(to isolate solenoid
valve while acid flushing)
Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways, depending on local codes, i.e. recharge well, storm sewer, drain field, adjacent stream or pond, etc. Most local codes forbid the use of sanitary sewer for disposal. Consult your local building and zoning departments to assure compliance in your area.
Flow Control
Valve
(on outlet of
Solenoid Valve)
Water Out
Water In
Shut Off Valves
15
VERSATEC BASE SERIES INSTALLATION MANUAL

Freeze Detection

For Aurora Base Control, set SW2-1, FP1, on the printed circuit board for applications using a closed loop antifreeze solution to 15°F [-9.4°C]. On applications using an open loop/ground water system (or closed loop no antifreeze), set this dip switch to 30°F [-1.1°C], the factory default setting. (Refer to the Dip Switch Field Selection table).

Electrical Connections

General
Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable.
Power Connection
Connect the incoming line voltage wires to L1 and L2 of the contactor for single-phase unit. Consult the Electrical Data tables for correct fuse sizes.
Aurora Base Control Box
208 Volt Operation
All Versatec Base Series 208/230 units are factory wired for 230 volt operation. For 208 volt operation, the red and blue transformer wires must be switched on terminal strip PS.
CAUTION: When installing a unit with a variable speed ECM blower motor in 460/60/3 voltage, a neutral wire is required to allow proper unit operation.
16

Electrical Data

PSC Motor
Model
006
009
012
015
018
024
030
036
042
048
060
070
HACR circuit breaker in USA only
Rated
Voltage
115/60/1 104/127 9.5 6.1 29.0 1.5 7.6 9.1 15
208-230/60/1 198/253 4.7 3.0 15.0 0.6 3.6 4.4 10/15
265/60/1 238/292 4.2 2.7 11.0 0.6 3.3 4.0 10/15
115/60/1 104/127 12.5 8.0 50.0 1.5 9.5 11.5 15
208-230/60/1 198/253 6.4 4.1 21.0 0.6 4.7 5.7 10/15
265/60/1 238/292 6.7 4.3 22.0 0.6 4.9 6.0 10/15
115/60/1 104/127 14.8 9.5 50.0 1.5 11.0 13.4 20
208-230/60/1 198/253 7.7 4.9 25.0 0.6 5.5 6.7 10/15
265/60/1 238/292 70 4.5 22.0 0.6 5.1 6.2 10/15
208-230/60/1 198/253 9.2 5.9 29.0 1.1 7.8 9.5 15
265/60/1 238/292 7.8 5.0 28.0 1.0 6.6 8.0 10/15
208-230/60/1 198/253 10.4 6.7 33.5 1.1 7.8 9.5 15
265/60/1 238/292 8.7 5.6 28.0 1.0 6.6 8.0 10/15
208-230/60/1 198/253 13.0 7.4 43.0 1.2 8.6 10.5 15
265/60/1 238/292 12.6 6.7 46.0 1.1 7.8 9.5 15
208-230/60/3 187/253 13.0 5.9 63.0 1.2 7.1 8.6 10/15
460/60/3 414/506 6.0 2.9 30.0 0.6 3.5 4.2 10/15
208-230/60/1 198/253 17.5 9.4 54.0 1.5 10.9 13.3 20
265/60/1 238/292 14.0 8.0 46.0 1.5 9.5 11.5 15
208-230/60/3 187/253 13.5 6.6 63.0 1.5 8.1 9.8 15
460/60/3 414/506 6.4 3.2 30.0 1.0 4.2 5.0 10/15
208-230/60/1 198/253 20.5 11.6 74.0 2.2 13.8 16.7 25
265/60/1 238/292 17.7 9.9 67.0 1.1 11.0 13.5 20
208-230/60/3 187/253 13.5 7.4 68.0 2.2 9.6 11.5 15
460/60/3 414/506 7.1 3.8 34.0 1.1 4.9 5.9 10/15
208-230/60/1 198/253 25.0 13.0 88.0 3.5 16.5 19.8 30
208-230/60/3 187/253 14.5 8.6 68.0 3.5 12.1 14.3 20
460/60/3 342/506 7.7 4.2 34.0 1.8 6.0 7.1 10/15
575/60/3 517/633 6.0 3.5 28.0 1.4 4.9 5.8 10/15
208-230/60/1 198/253 24.5 15.7 84.0 3.5 19.2 23.1 35
208-230/60/3 187/253 17.5 11.0 88.0 3.5 14.5 17.3 25
460/60/3 342/506 8.0 5.6 44.0 1.8 7.4 8.8 10/15
575/60/3 517/633 7.0 4.4 36.0 1.9 5.8 6.9 10/15
208-230/60/1 198/253 33.0 21.1 105.0 5.9 27.0 32.3 50
208-230/60/3 187/253 22.0 12.9 88.0 5.9 18.8 22.0 30
460/60/3 342/506 12.0 6.7 55.0 3.0 9.7 11.4 15
575/60/3 517/633 7.5 5.1 36.0 1.9 7.0 8.3 10/15
208-230/60/1 198/253 36.0 23.0 130.0 5.9 28.9 34.7 50
208-230/60/3 187/253 24.6 14.3 110.0 5.9 20.2 23.8 35
460/60/3 342/506 11.5 7.1 55.0 3.0 10.1 11.9 15
575/60/3 517/633 8.7 5.6 43.0 1.9 7.5 8.9 10/15
Voltage
Min/Max
VERSATEC BASE SERIES INSTALLATION MANUAL
Compressor
MCC RLA LRA
Blower
Motor
FLA
Total
Unit
FLA
Min Circ
Amp
Max
Fuse/
HACR
10/03/12
17
Loading...
+ 39 hidden pages