N – No Phase Guard, No Disconnect
D – No Phase Guard, Disconnect
P – Phase Guard, No Disconnect
B – Phase Guard, Disconnect
Control Option
A – AuroraTM Base Control (ABC)
E – Aurora UPC DDC Controller
F – Aurora UPC DDC Controller with LON
Water Control Option
N – None
R – Water Flow Regulator (015-070)
V – 2-Way Valve (015-070)
B – 2-Way Valve w/ Water Flow Regulator
(015-070)
Rev.: 24 April 2014D
1
2
TM
Note:
1 - Phase Guard Only Available on 208-230/60/3, 460/60/3, and 575/60/3
2 - 50VA transformer with Aurora Base Control, and 75VA transformer with Aurora UPC control
All Versatec Base Series product is safety listed under UL1995 thru ETL and performance
listed with AHRI in accordance with standard 13256-1.
4
General Installation Information
VERSATEC BASE SERIES INSTALLATION MANUAL
Safety Considerations
WARNING: Before performing service or
maintenance operations on a system, turn off main
power switches to the indoor unit. If applicable,
turn off the accessory heater power switch.
Electrical shock could cause personal injury.
Installing and servicing heating and air conditioning
equipment can be hazardous due to system pressure and
electrical components. Only trained and qualified service
personnel should install, repair or service heating and air
conditioning equipment. Untrained personnel can perform
the basic maintenance functions of cleaning coils and
cleaning and replacing filters. All other operations should
be performed by trained service personnel. When working on heating and air conditioning equipment, observe
precautions in the literature, tags and labels attached to the
unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use a quenching cloth for brazing operations and
have a fire extinguisher available.
Moving and Storage
Move units in the normal “up” orientation. Horizontal units
may be moved and stored per the information on the
packaging. Do not stack more than three units in total
height. Vertical units may be stored one upon another to
a maximum height of two units. Do not attempt to move
units while stacked. When the equipment is received, all
items should be carefully checked against the bill of lading
to be sure all crates and cartons have been received.
Examine units for shipping damage, removing the units
from the packaging if necessary. Units in question should
also be internally inspected. If any damage is noted, the
carrier should make the proper notation on the delivery
receipt, acknowledging the damage.
Unit Location
Locate the unit in an indoor area that allows for easy
removal of the filter and access panels. Location should
have enough space for service personnel to perform
maintenance or repair. Provide sufficient room to make
water, electrical and duct connection(s). If the unit is
located in a confined space, such as a closet, provisions
must be made for return air to freely enter the space
by means of a louvered door, etc. Any access panel
screws that would be difficult to remove after the unit
is installed should be removed prior to setting the unit.
On horizontal units, allow adequate room below the unit
for a condensate drain trap and do not locate the unit
above supply piping. Care should be taken when units are
located in unconditioned spaces to prevent damage from
frozen water lines and excessive heat that could damage
electrical components.
Installing Vertical Units
Vertical units are available in left or right air return
configurations. Top flow vertical units should be mounted
level on a vibration absorbing pad slightly larger than the
base to provide isolation between the unit and the floor.
Vertical Unit Mounting
2 in. PEX Foam
5
VERSATEC BASE SERIES INSTALLATION MANUAL
Vertical Dimensional Data
Standard filter rails for
open return applications
Field installed
duct flange
Deluxe filter rack for
ductable return applications
A
RN
S
Q
AIR COIL SIDE
P
B
A
Air coil
N
Q
ACCESS
PANEL
P
B
AIR COIL SIDE
2' (61 cm)
Alternate
F
Service Access
2' (61 cm)
Isometric View - Left Return
FRONT
F
M
M
FRONT
Top View - Right ReturnTop View - Left Return
Service Access Left Return
(Right Return Opposite Side)
U
T
W
Air coil
Air coil
ACCESS
PANEL
ACCESS
PANEL
C
1.6 in (4.1 cm)
Condensate 3/4 in
PVC glue socket
1.6 in (4.1 cm)
5
H
2
E
1
D
Front View - Right Return
Water
Connections*
Power supply
1 in (25.4 mm)
knockout
6
8
1/2" (12.7 mm)
J
L
Low voltage
knockout
L
K
Condensate
3/4 in PVC
glue socket
1.6 in (4.1 cm)
8
7
Water
Connections*
Front View - Left Return
NOTE: * Water connections protrude approximately 1.5 in. from cabinet.
V
C
1.6 in
(4.1 cm)
5
2
1
H
E
J
D
6
ACCESS
8
PANEL
L
8
7
L
K
Right View - Right Return (J & L)
Left View - Left Return (K & L)
6
Vertical Dimensional Data cont.
VERSATEC BASE SERIES INSTALLATION MANUAL
Overall Cabinet
Vertical
Models
006-012
015-018
024-030
036
042-048
060
070
006-012
015-018
024-030
036
042-048
060
070
Condensate is 3/4 in. PVC female glue socket and is switchable from side to front.
* Discharge fl ange is fi eld installed and extends 1 in. (25.4 mm) from top of cabinet.
** Vertical units shipped with standard 2 in. (fi eld adjustable to 1 in.) open application fi lter rail extending 2.2 in. from the unit and
is not suitable for duct connection. For ductable return connection applications, order the 2 in. (fi eld adjustable to 1 in.) duct collar/
fi lter rack which extends to 3.25 in. from the unit and is suitable for duct connections.
When using disconnect, do not use dimension L from the
standard vertical dimensional data. Use dimension LL from
the vertical disconnect dimensional data.
AP = Alternate Service Panel
BP = Blower Service Panel
CP = Control Access Panel
CMP = Compressor Service Panel
1.7
CP
AP
CMP
A
1.7
CP
AP
CMP
Legend
E
D
J
Service Access
1/2 in knockout
1 in knockout
K
Standard filter rails
Front
AP
CMP
2' (61 cm)
BP
Side Discharge
Deluxe filter rack option shown
P
N
L
C
M
BLOWER
OUTLET
Left Return
End Discharge
A
Left Return
"X" PVC size
End Discharge
2.3
AIR COIL SIDE
FILTER RACK
3
2.1
Condensate
H
P
P
N
L
M
BP
Air Coil
FrontFront
Water Connections*
BLOWER
OUTLET
Right Return Side Discharge
C
FILTER RACK CONNECTIONFILTER RACK CONNECTION
B
Right Return Side View
AP
CMP
1.5
K
Front
J
SQ
R
1/2 in knockout
1 in knockout
1" knockout
1/2 in knockout
T
Deluxe filter
rack option
(shown)
Front
C
1.5
J
AP
K
T
CMP
Left Return Side Discharge
S
R
Q
B
Left Return Side View
N
BLOWER
OUTLET
Air Coil
Water Connections*
NOTE: * Water connections protrude approximately 1.5 in. from cabinet.
BP
M
L
8
Horizontal Dimensional Data cont.
VERSATEC BASE SERIES INSTALLATION MANUAL
Horizontal
Models
WidthDepthHeight*InOutCondensateWater FPT Low Voltage Power Supply
006-012**
015-018
024-030
036
042-048
060
070
Horizontal
Models
006-012**
015-018
024-030
036
042-048
060
070
Horizontal units shipped with standard 2 in. (fi eld adjustable to 1 in.) open application fi lter rail extending 2.2 in. from the unit and
is not suitable for duct connection. For ductable return connection applications, order the 2 in. (fi eld adjustable to 1 in.) duct collar/
fi lter rack which extends to 3.25 in. from the unit and is suitable for duct connections.
** UBH006-012 offers a lifted drain pan that allows the trap to be installed without additional ceiling height required.
When using disconnect, do not use dimension K from the
standard horizontal dimensional data. Use dimension KK
from the horizontal disconnect dimensional data.
Horizontal units are available with side or end discharge
and may be easily field converted by flipping the blower
discharge panel. Horizontal units are normally suspended
from a ceiling by four 3/8 in. diameter threaded rods. The
rods are usually attached to the unit by hanger bracket kits
furnished with each unit. Lay out the threaded rods per
the dimensions below. Assemble the hangers to the unit as
shown. Securely tighten the brackets to the unit using the
weld nuts located on the underside of the bottom panel.
When attaching the hanger rods to the bracket, a double
nut is required since vibration could loosen a single nut.
NOTE: The unit should be pitched approximately 1/4
in. towards the drain in both directions to facilitate the
removal of condensate.
Horizontal Unit Mounting
Use only the bolts provided in the kit to attach hanger
brackets. The use of longer bolts could damage internal
parts. Some applications require the installation of
horizontal units on an attic floor. In this case, the unit
should be set in a full size secondary drain pan on top of a
vibration absorbing pad. The secondary drain pan prevents
possible condensate overflow or water leakage damage to
the ceiling. The secondary drain pan is usually placed on a
plywood base isolated from the ceiling joists by additional
layers of vibration absorbing material. Insulate supply
plenum and use at least one 90° elbow and flexible duct
collar to reduce noise.
CAUTION: Do not use rods smaller than 3/8 in.
diameter since they may not be strong enough
to support the unit. The rods must be securely
anchored to the ceiling.
10
Hanger Bracket Locations
VERSATEC BASE SERIES INSTALLATION MANUAL
D
Compressor
Section
B
E
Hanger Dimensions
Model
006-012
015-018
024-030
036
042-048
060
070
Hanger Kit
Part Number
in.
99S500A04
cm.90.955.446.0
in.
99S500A04
cm.90.963.854.4
in.
99S500A04
cm.108.663.854.4
in.
99S500A04
cm.108.763.854.4
in.
99S500A04
cm.116.363.854.4
in.
99S500A04
cm.124.071.462.0
in.
99S500A04
cm.136.771.462.0
Right
F
C
Air Handler
Section
G
A
3/8”
Threaded Rod
(not supplied)
Bolt and
Lockwasher
Unit Hanger Dimensions
ABC
35.821.818.1
35.825.121.4
42.825.121.4
42.825.121.4
45.825.121.4
48.828.124.4
53.828.124.4
09/26/12
E
Compressor
Section
D
Vibration Isolator
Washer
Hex Nuts
(not supplied)
Weight Distribution
Model
006-
012
015-
018
024
030
036
042
048
060
070
Vertical
Shipping
Weight
lb.11111244211928
kg50512010912
lb.17117667323245
kg788030151520
lb.24524285474565
kg11111039212029
lb.24524285474565
kg11111039212029
lb.26726595605060
kg12112043272327
lb.305310105686077
kg13814148312735
lb.305310105686077
kg13814148312735
lb.344350115776890
kg15615952353141
lb.357378130807395
kg16217159363343
Horizontal
Shipping
Weight
Left
G
Air Handler
Section
F
Horizontal Weight Distribution
FrontBack
DEFG
10/03/12
11
VERSATEC BASE SERIES INSTALLATION MANUAL
Duct System
An air outlet collar is provided on vertical top flow units
and all horizontal units to facilitate a duct connection.
A flexible connector is recommended for discharge
and return air duct connections on metal duct systems.
Uninsulated duct should be insulated with a minimum of
1-inch duct insulation. Application of the unit to uninsulated
ductwork in an unconditioned space is not recommended
as the unit’s performance will be adversely affected.
If the unit is connected to existing ductwork, check the duct
system to ensure that it has the capacity to accommodate
the air required for the unit application. If the duct is too
small, as in the replacement of heating only systems, larger
Water Piping
The proper water flow must be provided to each unit
whenever the unit operates. To assure proper flow, use
pressure/temperature ports to determine the flow rate.
These ports should be located at the supply and return
water connections on the unit. The proper flow rate cannot
be accurately set without measuring the water pressure
drop through the refrigerant-to-water heat exchanger.
ductwork should be installed. All existing ductwork should
be checked for leaks and repaired if necessary.
The duct system should be sized to handle the design
airflow quietly and efficiently. To maximize sound
attenuation of the unit blower, the supply and return
plenums should include an internal duct liner of fiberglass
or constructed of ductboard for the first few feet. On
systems employing a sheet metal duct system, canvas
connectors should be used between the unit and the
ductwork. If air noise or excessive airflow is a problem, the
blower speed can be changed.
All source water connections on commercial units are
fittings that accept a male pipe thread (MPT). Insert the
connectors by hand, then tighten the fitting with a wrench
to provide a leakproof joint. When connecting to an open
loop (groundwater) system, thread any copper MPT fitting
into the connector and tighten in the same manner as
described above.
12
Water Quality
VERSATEC BASE SERIES INSTALLATION MANUAL
In ground water situations where scaling could be heavy
or where biological growth such as iron bacteria will be
present, a closed loop system is recommended. The heat
exchanger coils in ground water systems may, over a period
with extremely hard water, the owner should be informed
that the heat exchanger may require occasional flushing.
Failure to adhere to the guidelines in the water quality table
could result in loss of warranty.
of time, lose heat exchange capabilities due to a buildup
of mineral deposits inside. These can be cleaned, but only
by a qualified service mechanic, as special solutions and
pumping equipment are required. Hot water generator coils
can likewise become scaled and possibly plugged. In areas
AmmoniaLess than 2 ppmLess than 2 ppmLess than 20 ppm
Ammonia ChlorideLess than 0.5 ppmLess than 0.5 ppmLess than 0.5 ppm
Ammonia NitrateLess than 0.5 ppmLess than 0.5 ppmLess than 0.5 ppm
Ammonia HydroxideLess than 0.5 ppmLess than 0.5 ppmLess than 0.5 ppm
Ammonia SulfateLess than 0.5 ppmLess than 0.5 ppmLess than 0.5 ppm
Total Dissolved Solids (TDS)Less than 1000 ppm1000 - 1500 ppm1000 - 1500 ppm
LSI Index+0.5 to -0.5+0.5 to -0.5+0.5 to -0.5
Iron, FE
Bacterial Iron Potential
Iron Oxide
Suspended Solids
Threshold Velocity
(Fresh Water)
Less than 0.5 ppm (rotten egg
SulfatesLess than 125 ppmLess than 125 ppmLess than 200 ppm
2
+ (Ferrous)
smell appears at 0.5 ppm)
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 mic
7 - 97 - 97 - 9
(Total Hardness)
less than 350 ppm
< 0.2 ppm< 0.2 ppm< 0.2 ppm
< 6 ft/sec< 6 ft/sec< 6 ft/sec
Units with cupronickel heat exchangers are recommended
for open loop applications due to the increased resistance
to build-up and corrosion, along with reduced wear caused
by acid cleaning.
ron size
(Total Hardness)
less than 350 ppm
10 - 50 ppmLess than 1 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
(Total Hardness)
less than 350 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
2/22/12
Condensate Drain
On vertical units, the internal condensate drain assembly
consists of a drain tube which is connected to the drain
pan, a 3/4 in. PVC female adapter and a flexible connecting
hose. The female adapter may exit either the front or the
side of the cabinet. The adapter should be glued to the
field-installed PVC condensate piping. On vertical units, a
condensate hose is inside all cabinets as a trapping loop;
therefore, an external trap is not necessary.
Vent (if needed)
PVC tube stub
1/8 in. per foot
PVC tube stub
NOTE: UBH006-012 offers a lifted
drain pan that allows the trap to
be installed without additional
ceiling height required.
PVC coupling
1.5 in.
1.5 in.
On horizontal units, a PVC stub or stainless steel tube
is provided for condensate drain piping connection. An
external trap is required (see below). If a vent is necessary,
an open stand pipe may be applied to a tee in the fieldinstalled condensate piping.
NOTE: All units equipped with electronic condensate
overflow protection.
Unit Pitch for DrainHorizontal Drain Connection (Composite Drain Pan)
1/2'' Pitch
Drain
13
VERSATEC BASE SERIES INSTALLATION MANUAL
System Cleaning and Flushing
Cleaning and Flushing
Prior to start up of any heat pump, the water circulating
system must be cleaned and flushed of all dirt and debris.
If the system is equipped with water shutoff valves, the
supply and return runouts must be connected together
at each unit location (This will prevent the introduction of
dirt into the unit, see Flushing with Water Shutoff Valve
Equipped Systems illustration). The system should be filled
at the water make-up connection with all air vents open.
After filling, vents should be closed.
Flushing with Water Shutoff Valve Equipped Systems
Return Runout
Supply Runout
Mains
Rubber Hose
Runouts Initially
Connected Together
The contractor should start the main circulator with the
pressure reducing valve makeup open. Vents should be
checked in sequence to bleed off any trapped air and to
verify circulation through all components of the system.
As water circulates through the system, the contractor
should check and repair any leaks found in the piping
system. Drain(s) at the lowest point(s) in the system should
be opened for initial flush and blowdown, making sure
water fill valves are set at the same rate. Check the pressure
gauge at the pump suction and manually adjust the makeup water valve to hold the same positive pressure both
before and after opening the drain valves. Flushing should
continue for at least two hours, or longer if required, until
drain water is clean and clear.
The supplemental heater and/or circulator pump, if used,
should be shut off. All drains and vents should be opened
to completely drain the system. Short-circuited supply and
return runouts should now be connected to the unit supply
and return connections.
Refill the system with clean water. Test the system water
for acidity and treat as required to leave the water slightly
alkaline (pH 7.5 to 8.5). The specified percentage of
antifreeze may also be added at this time. Use commercial
grade antifreeze designed for HVAC systems only.
Environol™ brand antifreeze is recommended.
Once the system has been filled with clean water and
antifreeze (if used), precautions should be taken to protect
the system from dirty water conditions. Dirty water will
result in system-wide degradation of performance, and
solids may clog valves, strainers, flow regulators, etc.
Additionally, the heat exchanger may become clogged
which reduces compressor service life and can cause
premature unit failure.
In boiler/tower application, set the loop control panel
set points to desired temperatures. Supply power to all
motors and start the circulating pumps. After full flow has
been established through all components including the
heat rejector (regardless of season), air vented and loop
temperatures stabilized, each of the units will be ready for
check, test and start up and for air and water balancing.
Ground Source Loop System Checkout
Once piping is completed between the unit pumping
system and ground loop, final purging and charging of
the loop is needed. A high pressure pump is needed to
achieve adequate flow velocity in the loop to purge air
and dirt particles from the loop itself. Antifreeze solution
is used in most areas to prevent freezing. Flush the
system adequately to remove as much air as possible;
then pressurize the loop to a static pressure of 40-50
PSI (summer) or 50-75 PSI (winter). This is normally
adequate for good system operation. Loop static pressure
may decrease soon after initial installation, due to pipe
expansion and loop temperature change. Running the
unit for at least 30 minutes after the system has been
completely purged of air will allow for the “break-in”
period. It may be necessary to adjust static loop pressure
(by adding water) after the unit has run for the first time.
Loop static pressure will also fluctuate with the seasons.
Pressures will be higher in the winter months than during
the cooling season. This fluctuation is normal and should be
considered when charging the system initially.
Ensure the pump provides adequate flow through the unit
by checking pressure drop across the heat exchanger.
Usually 2.25-3.0 gpm of flow per ton of cooling capacity is
recommended in earth loop applications.
14
Open Loop Ground Water Systems
VERSATEC BASE SERIES INSTALLATION MANUAL
Typical open loop piping is shown below. Always maintain
water pressure in the heat exchanger by placing water
control valves at the outlet of the unit to prevent mineral
precipitation. Use a closed, bladder-type expansion tank
to minimize mineral formation due to air exposure. Insure
proper water flow through the unit by checking pressure
drop across the heat exchanger and comparing it to the
figures in unit capacity data tables in the specification
catalog. 1.5-2 gpm of flow per ton of cooling capacity is
recommended in open loop applications. Due to only minor
differences in flow rate from low to high, only one solenoid
valve should be used. The valve should be sized for full flow.
Open System - Groundwater Application
Unit Supply
Aux. Heat Supply
Flexible
Duct Collar
Rubber Bladder
Expansion Tank
Solenoid
Valve
Drain
Disconnects
(IfApplicable)
Compressor
Line Voltage
Low Voltage
to Thermostat
and Valve
P/T Plugs
Vibration
Absorbing Pad
Strainer
Boiler Drains
For HX Flushing
Shut Off Valves
(to isolate solenoid
valve while acid flushing)
Discharge water from the unit is not contaminated in any
manner and can be disposed of in various ways, depending
on local codes, i.e. recharge well, storm sewer, drain field,
adjacent stream or pond, etc. Most local codes forbid
the use of sanitary sewer for disposal. Consult your local
building and zoning departments to assure compliance in
your area.
Flow Control
Valve
(on outlet of
Solenoid Valve)
Water Out
Water In
Shut Off Valves
15
VERSATEC BASE SERIES INSTALLATION MANUAL
Freeze Detection
For Aurora Base Control, set SW2-1, FP1, on the printed
circuit board for applications using a closed loop antifreeze
solution to 15°F [-9.4°C]. On applications using an open
loop/ground water system (or closed loop no antifreeze), set
this dip switch to 30°F [-1.1°C], the factory default setting.
(Refer to the Dip Switch Field Selection table).
Electrical Connections
General
Be sure the available power is the same voltage and phase
as that shown on the unit serial plate. Line and low voltage
wiring must be done in accordance with local codes or the
National Electric Code, whichever is applicable.
Power Connection
Connect the incoming line voltage wires to L1 and L2 of the
contactor for single-phase unit. Consult the Electrical Data
tables for correct fuse sizes.
Aurora Base Control Box
208 Volt Operation
All Versatec Base Series 208/230 units are factory wired
for 230 volt operation. For 208 volt operation, the red and
blue transformer wires must be switched on terminal strip PS.
CAUTION: When installing a unit with a
variable speed ECM blower motor in 460/60/3
voltage, a neutral wire is required to allow
proper unit operation.
16
Electrical Data
PSC Motor
Model
006
009
012
015
018
024
030
036
042
048
060
070
HACR circuit breaker in USA only
Rated
Voltage
115/60/1104/1279.56.129.01.57.69.115
208-230/60/1198/2534.73.015.00.63.64.410/15
265/60/1238/2924.22.711.00.63.34.010/15
115/60/1104/12712.58.050.01.59.511.515
208-230/60/1198/2536.44.121.00.64.75.710/15
265/60/1238/2926.74.322.00.64.96.010/15
115/60/1104/12714.89.550.01.511.013.420
208-230/60/1198/2537.74.925.00.65.56.710/15
265/60/1238/292704.522.00.65.16.210/15
208-230/60/1198/2539.25.929.01.17.89.515
265/60/1238/2927.85.028.01.06.68.010/15
208-230/60/1198/25310.46.733.51.17.89.515
265/60/1238/2928.75.628.01.06.68.010/15
208-230/60/1198/25313.07.443.01.28.610.515
265/60/1238/29212.66.746.01.17.89.515
208-230/60/3187/25313.05.963.01.27.18.610/15
460/60/3414/5066.02.930.00.63.54.210/15
208-230/60/1198/25317.59.454.01.510.913.320
265/60/1238/29214.08.046.01.59.511.515
208-230/60/3187/25313.56.663.01.58.19.815
460/60/3414/5066.43.230.01.04.25.010/15
208-230/60/1198/25320.511.674.02.213.816.725
265/60/1238/29217.79.967.01.111.013.520
208-230/60/3187/25313.57.468.02.29.611.515
460/60/3414/5067.13.834.01.14.95.910/15
208-230/60/1198/25325.013.088.03.516.519.830
208-230/60/3187/25314.58.668.03.512.114.320
460/60/3342/5067.74.234.01.86.07.110/15
575/60/3517/6336.03.528.01.44.95.810/15
208-230/60/1198/25324.515.784.03.519.223.135
208-230/60/3187/25317.511.088.03.514.517.325
460/60/3342/5068.05.644.01.87.48.810/15
575/60/3517/6337.04.436.01.95.86.910/15
208-230/60/1198/25333.021.1105.05.927.032.350
208-230/60/3187/25322.012.988.05.918.822.030
460/60/3342/50612.06.755.03.09.711.415
575/60/3517/6337.55.136.01.97.08.310/15
208-230/60/1198/25336.023.0130.05.928.934.750
208-230/60/3187/25324.614.3110.05.920.223.835
460/60/3342/50611.57.155.03.010.111.915
575/60/3517/6338.75.643.01.97.58.910/15
Voltage
Min/Max
VERSATEC BASE SERIES INSTALLATION MANUAL
Compressor
MCCRLALRA
Blower
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
10/03/12
17
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.