WaterFurnace Versatec Base User Manual

Installation Information
Water Piping Connections
Electrical
Startup Procedures
Troubleshooting
Preventive Maintenance
Versatec Base Series Installation Manual
IM1201AUB 05/14
Table of Contents
Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
General Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
Installing Horizontal Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Hanger Bracket Locations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Duct System and Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Water Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
System Cleaning and Flushing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Open Loop Ground Water Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Freeze Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
VERSATEC BASE SERIES INSTALLATION MANUAL
Electrical Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-18
Blower Performance Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-22
5-Speed ECM Constant Torque Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Wiring Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24-29
Controls - Aurora Base Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30-33
Controls - UPC (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34-39
Unit Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Operating Parameters and Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
Compressor and Thermistor Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Refrigerant Circuit Guideline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Heat of Extraction/Rejection Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Reference Calculations and Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
Startup/Troubleshooting Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47-48
Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Replacement Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Service Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50-51
Revision Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
VERSATEC BASE SERIES INSTALLATION MANUAL
UB
1-2 3 4-6 7 8 9
10 11 12 14
V 036 T L 0 0 0 C A N13A15N16017A18319020SS
21-22*23

Model Nomenclature

Model Type
UB – Versatec Base
Cabinet Configuration
V – Vertical H - Horizontal
Unit Capacity (MBTUH) 006, 009, 012, 015, 018, 024, 030, 036, 042, 048, 060, 070
Discharge Configuration
T – Top (Vertical) E – End (Horizontal) S – Side (Horizontal)
Return Air Configuration
L – Left R – Right
Voltage
0 – 208-230/60/1 2 – 265-277/60/1 (006-036) 3 – 208-230/60/3 (024-070) 4 – 460/60/3 (024-070) 5 – 575/60/3 (PSC Only 042-070) 9 – 115/60/1 (006-012)
Future Option
0 – None
Blower Options
0 – PSC Blower 1 – Variable Speed ECM Blower (015-070) 4 – 5-Speed ECM Blower (015-070)
Water Coil Option
C – Copper D – Insulated Copper N – CuproNickel P – Insulated CuproNickel
Sound Kit Option
A – None B – Sound Kit (Not Available on UBH006-012)
Vintage
* - Factory Use Only
Non-Standard Options
SS – Standard
Drain Pan Option
0 – Composite, No Secondary Connection 1 – Composite, Secondary Connection 2 – Stainless Steel, No Secondary Connection 3 – Stainless Steel, Secondary Connection
Air Coil Option
3 – All-Aluminum, Uncoated 4 – All-Aluminum, AlumiSeal
Filter Option
A – MERV 4 B – MERV 13
Cabinet Option
0 – Unpainted Cabinet, Filter Rail 2 – Unpainted Cabinet, 4-Sided Filter Rack 1 – Painted Cabinet, Filter Rail 3 – Painted Cabinet, 4-Sided Filter Rack
Phase Guard
N – No Phase Guard, No Disconnect D – No Phase Guard, Disconnect P – Phase Guard, No Disconnect B – Phase Guard, Disconnect
Control Option
A – AuroraTM Base Control (ABC) E – Aurora UPC DDC Controller F – Aurora UPC DDC Controller with LON
Water Control Option
N – None R – Water Flow Regulator (015-070) V – 2-Way Valve (015-070) B – 2-Way Valve w/ Water Flow Regulator (015-070)
Rev.: 24 April 2014D
1
2
TM
Note: 1 - Phase Guard Only Available on 208-230/60/3, 460/60/3, and 575/60/3 2 - 50VA transformer with Aurora Base Control, and 75VA transformer with Aurora UPC control
All Versatec Base Series product is safety listed under UL1995 thru ETL and performance listed with AHRI in accordance with standard 13256-1.
4

General Installation Information

VERSATEC BASE SERIES INSTALLATION MANUAL
Safety Considerations
WARNING: Before performing service or maintenance operations on a system, turn off main power switches to the indoor unit. If applicable, turn off the accessory heater power switch. Electrical shock could cause personal injury.
Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair or service heating and air conditioning equipment. Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning and replacing filters. All other operations should be performed by trained service personnel. When work­ing on heating and air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations and have a fire extinguisher available.
Moving and Storage
Move units in the normal “up” orientation. Horizontal units may be moved and stored per the information on the packaging. Do not stack more than three units in total height. Vertical units may be stored one upon another to a maximum height of two units. Do not attempt to move units while stacked. When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Examine units for shipping damage, removing the units from the packaging if necessary. Units in question should also be internally inspected. If any damage is noted, the carrier should make the proper notation on the delivery receipt, acknowledging the damage.
Unit Location
Locate the unit in an indoor area that allows for easy removal of the filter and access panels. Location should have enough space for service personnel to perform maintenance or repair. Provide sufficient room to make water, electrical and duct connection(s). If the unit is located in a confined space, such as a closet, provisions must be made for return air to freely enter the space by means of a louvered door, etc. Any access panel screws that would be difficult to remove after the unit is installed should be removed prior to setting the unit. On horizontal units, allow adequate room below the unit for a condensate drain trap and do not locate the unit above supply piping. Care should be taken when units are
located in unconditioned spaces to prevent damage from frozen water lines and excessive heat that could damage electrical components.
Installing Vertical Units
Vertical units are available in left or right air return configurations. Top flow vertical units should be mounted level on a vibration absorbing pad slightly larger than the base to provide isolation between the unit and the floor.
Vertical Unit Mounting
2 in. PEX Foam
5
VERSATEC BASE SERIES INSTALLATION MANUAL
Vertical Dimensional Data
Standard filter rails for
open return applications
Field installed duct flange
Deluxe filter rack for
ductable return applications
A
RN
S
Q
AIR COIL SIDE
P
B
A
Air coil
N
Q
ACCESS
PANEL
P
B
AIR COIL SIDE
2' (61 cm) Alternate
F
Service Access
2' (61 cm)
Isometric View - Left Return
FRONT
F
M
M
FRONT
Top View - Right Return Top View - Left Return
Service Access Left Return
(Right Return Opposite Side)
U
T
W
Air coil
Air coil
ACCESS
PANEL
ACCESS
PANEL
C
1.6 in (4.1 cm) Condensate 3/4 in
PVC glue socket
1.6 in (4.1 cm)
5
H
2
E
1
D
Front View - Right Return
Water Connections*
Power supply
1 in (25.4 mm)
knockout
6 8
1/2" (12.7 mm)
J
L
Low voltage
knockout
L
K
Condensate
3/4 in PVC
glue socket
1.6 in (4.1 cm)
8 7
Water
Connections*
Front View - Left Return
NOTE: * Water connections protrude approximately 1.5 in. from cabinet.
V
C
1.6 in (4.1 cm)
5 2
1
H
E
J
D
6
ACCESS
8
PANEL
L
8 7
L
K
Right View - Right Return (J & L)
Left View - Left Return (K & L)
6
Vertical Dimensional Data cont.
VERSATEC BASE SERIES INSTALLATION MANUAL
Overall Cabinet
Vertical
Models
006-012
015-018
024-030
036
042-048
060
070
006-012
015-018
024-030
036
042-048
060
070
Condensate is 3/4 in. PVC female glue socket and is switchable from side to front. * Discharge fl ange is fi eld installed and extends 1 in. (25.4 mm) from top of cabinet.
** Vertical units shipped with standard 2 in. (fi eld adjustable to 1 in.) open application fi lter rail extending 2.2 in. from the unit and is not suitable for duct connection. For ductable return connection applications, order the 2 in. (fi eld adjustable to 1 in.) duct collar/ fi lter rack which extends to 3.25 in. from the unit and is suitable for duct connections.
in. 19.2 19.2 24.2 2.6 5.6 8.8 1/2 in. 7.4 3.4 5.4 2.2
cm. 48.8 48.8 61.5 6.6 14.2 22.4 12.7 mm 18.8 8.6 13.7 5.6
in. 22.5 22.2 30.2 2.6 7.6 10.8 3/4 in. 9.4 5.4 7.4 2.2
cm. 57.2 56.4 76.7 6.6 19.3 27.4 19.1 mm 23.9 13.7 18.8 5.6
in. 22.5 22.2 36.2 2.6 7.6 10.8 3/4 in. 9.4 5.4 7.4 2.2
cm. 57.2 56.4 91.9 6.6 19.3 27.4 19.1 mm 23.9 13.7 18.8 5.6
in. 22.5 26.2 40.2 2.6 7.6 10.8 3/4 in. 10.1 6.1 8.1 2.2
cm. 57.2 66.5 102.1 6.6 19.3 27.4 19.1 mm 25.7 15.5 20.6 5.6
in. 22.5 26.2 44.2 2.6 7.6 10.8 3/4 in. 10.1 6.1 8.1 2.2
cm. 57.2 66.5 112.3 6.6 19.3 27.4 19.1 mm 25.7 15.5 20.6 5.6
in. 25.5 31.2 44.2 2.6 7.6 10.8 1 in. 10.1 6.1 8.1 2.2
cm. 64.8 79.2 112.3 6.6 19.3 27.4 25.4 mm 25.7 15.5 20.6 5.6
in. 25.5 31.2 48.2 2.6 7.6 10.8 1 in. 10.1 6.1 8.1 2.2
cm. 64.8 79.2 122.4 6.6 19.3 27.4 25.4 mm 25.7 15.5 20.6 5.6
Vertical
Models
in. 10.0 10.0 4.6 4.4 7.8 2.4 14.3 10.1 2.0
cm. 25.4 25.4 11.7 11.2 19.8 6.1 36.3 25.7 5.1
in. 14.0 14.0 4.1 4.3 7.7 2.1 18.1 14.0 2.0
cm. 35.6 35.6 10.4 10.9 19.6 5.3 46.0 35.6 5.1
in. 14.0 14.0 4.1 4.3 7.7 2.1 18.1 20.0 2.0
cm. 35.6 35.6 10.4 10.9 19.6 5.3 46.0 50.8 5.1
in. 14.0 14.0 6.1 4.5 7.7 2.1 22.1 22.1 2.0
cm. 35.6 35.6 15.5 11.4 19.6 5.3 56.1 56.1 5.1
in. 18.0 18.0 4.1 3.9 3.9 2.1 22.1 26.1 2.0
cm. 45.7 45.7 10.4 9.9 9.9 5.3 56.1 66.3 5.1
in. 18.0 18.0 6.6 4.6 6.3 1.6 28.1 26.0 2.0
cm. 45.7 45.7 16.8 11.7 16.0 4.1 71.4 66.0 5.1
in. 18.0 18.0 6.6 4.6 6.3 1.6 28.1 30.0 2.0
cm. 45.7 45.7 16.8 11.7 16.0 4.1 71.4 76.2 5.1
A B C D E H 1/2 in. cond 1/2 in. cond 1 in. cond M
Width Depth Height* In Out
Discharge Connection
duct fl ange installed (±0.10 in)
NPQRSTUVW
Supply Width Supply Depth Return Depth Return Height
125
Water Connections
Cond-
ensate
Loop
Water FPT
Electrical Knockouts 678 JKL
Low
Voltage
using deluxe fi lter rack (±0.10 in)
Low
Voltage
**Return Connection
Supply
Power
Filter Rack
Width
09/26/12
Vertical Disconnect
When using disconnect, do not use dimension L from the standard vertical dimensional data. Use dimension LL from the vertical disconnect dimensional data.
Vertical Models LL
015-018
024-030
036
042-048
060 070
Dimensions in inches [cm] * Models 006-012 - Externally Mounted Disconnect
15.8 [40.1]
18.8 [47.8]
15.3 [38.9]
13.8 [35.1]
14.3 [36.3]
14.3 [36.3]
Disconnect Located
on this Side for a
Disconnect
Location
Power Supply
Right Return
Alternative Power Supply
LL
Vertical Shown in Left
Return Configuration
7
VERSATEC BASE SERIES INSTALLATION MANUAL
Horizontal Dimensional Data
Right Return
Condensate "X" PVC size
End Discharge
Deluxe filter rack option shown
2.3
BLOWER
OUTLET
AIR COIL SIDE
FILTER RACK
H
3
2.1
Right Return
End Discharge
N
A
Standard filter rails
1 in knockout
1/2 in knockout
Side Discharge
P
M
C
L
BP
Front
AP
CMP
2' (61 cm)
Service Access
1.7
K
J
Right Return Air Front View
1.7
2
E
1
D
Left Return Air Front View
AP = Alternate Service Panel BP = Blower Service Panel CP = Control Access Panel CMP = Compressor Service Panel
1.7
CP AP
CMP
A
1.7
CP AP
CMP
Legend
E
D
J
Service Access
1/2 in knockout 1 in knockout
K
Standard filter rails
Front
AP
CMP
2' (61 cm)
BP
Side Discharge
Deluxe filter rack option shown P
N
L
C
M
BLOWER
OUTLET
Left Return
End Discharge
A
Left Return
"X" PVC size
End Discharge
2.3 AIR COIL SIDE
FILTER RACK
3
2.1
Condensate
H
P
P
N
L
M
BP
Air Coil
Front Front
Water Connections*
BLOWER
OUTLET
Right Return Side Discharge
C
FILTER RACK CONNECTION FILTER RACK CONNECTION
B
Right Return Side View
AP
CMP
1.5
K
Front
J
SQ
R
1/2 in knockout
1 in knockout
1" knockout
1/2 in knockout
T
Deluxe filter
rack option
(shown)
Front
C
1.5
J
AP
K
T
CMP
Left Return Side Discharge
S
R
Q
B
Left Return Side View
N
BLOWER
OUTLET
Air Coil
Water Connections*
NOTE: * Water connections protrude approximately 1.5 in. from cabinet.
BP
M
L
8
Horizontal Dimensional Data cont.
VERSATEC BASE SERIES INSTALLATION MANUAL
Horizontal
Models
Width Depth Height* In Out Condensate Water FPT Low Voltage Power Supply
006-012**
015-018
024-030
036
042-048
060
070
Horizontal
Models
006-012**
015-018
024-030
036
042-048
060
070
Horizontal units shipped with standard 2 in. (fi eld adjustable to 1 in.) open application fi lter rail extending 2.2 in. from the unit and is not suitable for duct connection. For ductable return connection applications, order the 2 in. (fi eld adjustable to 1 in.) duct collar/ fi lter rack which extends to 3.25 in. from the unit and is suitable for duct connections.
** UBH006-012 offers a lifted drain pan that allows the trap to be installed without additional ceiling height required.
in. 19.2 35.0 12.1 1.8 4.8 3.6 1/2 in. 7.4 7.5
cm. 48.8 88.9 30.7 4.6 12.2 9.1 12.70 mm 18.8 19.1
in. 22.5 35.0 17.2 1.8 6.8 0.8 3/4 in. 7.1 7.1
cm. 57.2 88.9 43.7 4.6 17.3 2.0 19.05 mm 18.0 18.0
in. 22.5 42.0 17.2 1.8 6.8 0.8 3/4 in. 7.1 7.1
cm. 57.2 106.7 43.7 4.6 17.3 2.0 19.05 mm 18.0 18.0
in. 22.5 42.0 19.2 1.8 6.8 0.8 3/4 in. 9.2 7.1
cm. 57.2 106.7 48.8 4.6 17.3 2.0 19.05 mm 23.4 18.0
in. 22.5 45.0 19.2 1.8 6.8 0.8 3/4 in. 9.2 7.1
cm. 57.2 114.3 48.8 4.6 17.3 2.0 19.05 mm 23.4 18.0
in. 25.5 48.0 21.2 1.8 6.8 0.8 1 in. 9.2 9.1
cm. 64.8 121.9 53.8 4.6 17.3 2.0 25.4 mm 23.4 23.1
in. 25.5 53.0 21.2 1.8 6.8 0.8 1 in. 9.2 9.1
cm. 64.8 134.6 53.8 4.6 17.3 2.0 25.4 mm 23.4 23.1
in. 2.3 8.0 10.0 2.7 22.5 9.4 2.4 1.4 1/2 in.
cm. 5.8 20.3 25.4 6.9 57.2 23.9 6.1 3.6 1.3
in. 5.7 10.5 9.4 4.9 16.4 14.5 2.0 1.4 3/4 in.
cm. 14.5 26.7 23.9 12.4 41.7 36.8 5.1 3.6 1.9
in. 5.7 10.5 9.4 4.9 23.4 14.5 2.0 1.4 3/4 in.
cm. 14.5 26.7 23.9 12.4 59.4 36.8 5.1 3.6 1.9
in. 6.7 10.5 9.4 4.9 27.4 16.5 2.0 1.4 3/4 in.
cm. 17.0 26.7 23.9 12.4 69.6 41.9 5.1 3.6 1.9
in. 4.2 13.6 13.2 2.4 30.4 16.5 2.0 1.5 3/4 in.
cm. 10.7 34.5 33.5 6.1 77.2 41.9 5.1 3.8 1.9
in. 4.8 13.6 13.2 4.6 35.4 18.7 2.3 1.3 3/4 in.
cm. 12.2 34.5 33.5 11.7 89.9 47.5 5.8 3.3 1.9
in. 4.8 13.6 13.2 4.6 40.4 18.5 2.3 1.4 3/4 in.
cm. 12.2 34.5 33.5 11.7 102.6 47.0 5.8 3.6 1.9
Overall Cabinet
A B C D E H 1/2 in. cond 1 in. cond
Discharge Connection
duct fl ange installed (±0.10 in)
LMNPQRS TX
Supply Width Supply Depth Return Depth Return Height
123
Water Connections Electrical Knockouts
Loop
Return Connection
using deluxe fi lter rack option (±0.10 in)
JK
PVC Size
09/26/12
Horizontal Disconnect
When using disconnect, do not use dimension K from the standard horizontal dimensional data. Use dimension KK from the horizontal disconnect dimensional data.
Horizontal Models KK
015-018
024-030
036
042-048
060 070
Dimensions in inches [cm] * Models 006-012 - Externally Mounted Disconnect
8.2 [20.8]
8.2 [20.8]
9.2 [23.4]
9.2 [23.4]
11.2 [28.4]
10.2 [25.9]
Disconnect Located on this Side for a Left Return
Disconnect Location
KK
Power Supply
Horizontal Shown
In Right Return
Configuration
9
VERSATEC BASE SERIES INSTALLATION MANUAL

Installing Horizontal Units

Installing Horizontal Units
Horizontal units are available with side or end discharge and may be easily field converted by flipping the blower discharge panel. Horizontal units are normally suspended from a ceiling by four 3/8 in. diameter threaded rods. The rods are usually attached to the unit by hanger bracket kits furnished with each unit. Lay out the threaded rods per the dimensions below. Assemble the hangers to the unit as shown. Securely tighten the brackets to the unit using the weld nuts located on the underside of the bottom panel. When attaching the hanger rods to the bracket, a double nut is required since vibration could loosen a single nut.
NOTE: The unit should be pitched approximately 1/4 in. towards the drain in both directions to facilitate the removal of condensate.
Horizontal Unit Mounting
Use only the bolts provided in the kit to attach hanger brackets. The use of longer bolts could damage internal parts. Some applications require the installation of horizontal units on an attic floor. In this case, the unit should be set in a full size secondary drain pan on top of a vibration absorbing pad. The secondary drain pan prevents possible condensate overflow or water leakage damage to the ceiling. The secondary drain pan is usually placed on a plywood base isolated from the ceiling joists by additional layers of vibration absorbing material. Insulate supply plenum and use at least one 90° elbow and flexible duct collar to reduce noise.
CAUTION: Do not use rods smaller than 3/8 in. diameter since they may not be strong enough to support the unit. The rods must be securely anchored to the ceiling.
10

Hanger Bracket Locations

VERSATEC BASE SERIES INSTALLATION MANUAL
D
Compressor
Section
B
E
Hanger Dimensions
Model
006-012
015-018
024-030
036
042-048
060
070
Hanger Kit
Part Number
in.
99S500A04
cm. 90.9 55.4 46.0
in.
99S500A04
cm. 90.9 63.8 54.4
in.
99S500A04
cm. 108.6 63.8 54.4
in.
99S500A04
cm. 108.7 63.8 54.4
in.
99S500A04
cm. 116.3 63.8 54.4
in.
99S500A04
cm. 124.0 71.4 62.0
in.
99S500A04
cm. 136.7 71.4 62.0
Right
F
C
Air Handler
Section
G
A
3/8”
Threaded Rod
(not supplied)
Bolt and Lockwasher
Unit Hanger Dimensions
ABC
35.8 21.8 18.1
35.8 25.1 21.4
42.8 25.1 21.4
42.8 25.1 21.4
45.8 25.1 21.4
48.8 28.1 24.4
53.8 28.1 24.4
09/26/12
E
Compressor
Section
D
Vibration Isolator
Washer
Hex Nuts (not supplied)
Weight Distribution
Model
006-
012
015-
018
024
030
036
042
048
060
070
Vertical
Shipping
Weight
lb. 111 112 44 21 19 28
kg 50 51 20 10 9 12
lb. 171 176 67 32 32 45
kg 78 80 30 15 15 20
lb. 245 242 85 47 45 65
kg 111 110 39 21 20 29
lb. 245 242 85 47 45 65
kg 111 110 39 21 20 29
lb. 267 265 95 60 50 60
kg 121 120 43 27 23 27
lb. 305 310 105 68 60 77
kg 138 141 48 31 27 35
lb. 305 310 105 68 60 77
kg 138 141 48 31 27 35
lb. 344 350 115 77 68 90
kg 156 159 52 35 31 41
lb. 357 378 130 80 73 95
kg 162 171 59 36 33 43
Horizontal
Shipping
Weight
Left
G
Air Handler
Section
F
Horizontal Weight Distribution
Front Back
DEFG
10/03/12
11
VERSATEC BASE SERIES INSTALLATION MANUAL

Duct System

An air outlet collar is provided on vertical top flow units and all horizontal units to facilitate a duct connection. A flexible connector is recommended for discharge and return air duct connections on metal duct systems. Uninsulated duct should be insulated with a minimum of 1-inch duct insulation. Application of the unit to uninsulated ductwork in an unconditioned space is not recommended as the unit’s performance will be adversely affected.
If the unit is connected to existing ductwork, check the duct system to ensure that it has the capacity to accommodate the air required for the unit application. If the duct is too small, as in the replacement of heating only systems, larger

Water Piping

The proper water flow must be provided to each unit whenever the unit operates. To assure proper flow, use pressure/temperature ports to determine the flow rate. These ports should be located at the supply and return water connections on the unit. The proper flow rate cannot be accurately set without measuring the water pressure drop through the refrigerant-to-water heat exchanger.
ductwork should be installed. All existing ductwork should be checked for leaks and repaired if necessary.
The duct system should be sized to handle the design airflow quietly and efficiently. To maximize sound attenuation of the unit blower, the supply and return plenums should include an internal duct liner of fiberglass or constructed of ductboard for the first few feet. On systems employing a sheet metal duct system, canvas connectors should be used between the unit and the ductwork. If air noise or excessive airflow is a problem, the blower speed can be changed.
All source water connections on commercial units are fittings that accept a male pipe thread (MPT). Insert the connectors by hand, then tighten the fitting with a wrench to provide a leakproof joint. When connecting to an open loop (groundwater) system, thread any copper MPT fitting into the connector and tighten in the same manner as described above.
12

Water Quality

VERSATEC BASE SERIES INSTALLATION MANUAL
In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period
with extremely hard water, the owner should be informed that the heat exchanger may require occasional flushing. Failure to adhere to the guidelines in the water quality table
could result in loss of warranty. of time, lose heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualified service mechanic, as special solutions and pumping equipment are required. Hot water generator coils can likewise become scaled and possibly plugged. In areas
Material Copper 90/10 Cupronickel 316 Stainless Steel
pH Acidity/Alkalinity
Scaling
Corrosion
Iron Fouling
(Biological Growth)
Erosion
NOTES: Grains = ppm divided by 17
mg/L is equivalent to ppm
Calcium and
Magnesium Carbonate
Hydrogen Sulfide
Chlorine Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Chlorides Less than 20 ppm Less than 125 ppm Less than 300 ppm
Carbon Dioxide Less than 50 ppm 10 - 50 ppm 10 - 50 ppm
Ammonia Less than 2 ppm Less than 2 ppm Less than 20 ppm
Ammonia Chloride Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Nitrate Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Hydroxide Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Sulfate Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Total Dissolved Solids (TDS) Less than 1000 ppm 1000 - 1500 ppm 1000 - 1500 ppm
LSI Index +0.5 to -0.5 +0.5 to -0.5 +0.5 to -0.5
Iron, FE
Bacterial Iron Potential
Iron Oxide
Suspended Solids
Threshold Velocity
(Fresh Water)
Less than 0.5 ppm (rotten egg
Sulfates Less than 125 ppm Less than 125 ppm Less than 200 ppm
2
+ (Ferrous)
smell appears at 0.5 ppm)
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 mic
7 - 9 7 - 9 7 - 9
(Total Hardness)
less than 350 ppm
< 0.2 ppm < 0.2 ppm < 0.2 ppm
< 6 ft/sec < 6 ft/sec < 6 ft/sec
Units with cupronickel heat exchangers are recommended
for open loop applications due to the increased resistance
to build-up and corrosion, along with reduced wear caused
by acid cleaning.
ron size
(Total Hardness)
less than 350 ppm
10 - 50 ppm Less than 1 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
(Total Hardness)
less than 350 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
2/22/12

Condensate Drain

On vertical units, the internal condensate drain assembly consists of a drain tube which is connected to the drain pan, a 3/4 in. PVC female adapter and a flexible connecting hose. The female adapter may exit either the front or the side of the cabinet. The adapter should be glued to the field-installed PVC condensate piping. On vertical units, a condensate hose is inside all cabinets as a trapping loop; therefore, an external trap is not necessary.
Vent (if needed)
PVC tube stub 1/8 in. per foot
PVC tube stub
NOTE: UBH006-012 offers a lifted drain pan that allows the trap to be installed without additional ceiling height required.
PVC coupling
1.5 in.
1.5 in.
On horizontal units, a PVC stub or stainless steel tube is provided for condensate drain piping connection. An external trap is required (see below). If a vent is necessary, an open stand pipe may be applied to a tee in the field­installed condensate piping.
NOTE: All units equipped with electronic condensate overflow protection.
Unit Pitch for DrainHorizontal Drain Connection (Composite Drain Pan)
1/2'' Pitch
Drain
13
VERSATEC BASE SERIES INSTALLATION MANUAL

System Cleaning and Flushing

Cleaning and Flushing
Prior to start up of any heat pump, the water circulating system must be cleaned and flushed of all dirt and debris.
If the system is equipped with water shutoff valves, the supply and return runouts must be connected together at each unit location (This will prevent the introduction of dirt into the unit, see Flushing with Water Shutoff Valve Equipped Systems illustration). The system should be filled at the water make-up connection with all air vents open. After filling, vents should be closed.
Flushing with Water Shutoff Valve Equipped Systems
Return Runout
Supply Runout
Mains
Rubber Hose
Runouts Initially Connected Together
The contractor should start the main circulator with the pressure reducing valve makeup open. Vents should be checked in sequence to bleed off any trapped air and to verify circulation through all components of the system.
As water circulates through the system, the contractor should check and repair any leaks found in the piping system. Drain(s) at the lowest point(s) in the system should be opened for initial flush and blowdown, making sure water fill valves are set at the same rate. Check the pressure gauge at the pump suction and manually adjust the make­up water valve to hold the same positive pressure both before and after opening the drain valves. Flushing should continue for at least two hours, or longer if required, until drain water is clean and clear.
The supplemental heater and/or circulator pump, if used, should be shut off. All drains and vents should be opened to completely drain the system. Short-circuited supply and return runouts should now be connected to the unit supply and return connections.
Refill the system with clean water. Test the system water for acidity and treat as required to leave the water slightly alkaline (pH 7.5 to 8.5). The specified percentage of antifreeze may also be added at this time. Use commercial grade antifreeze designed for HVAC systems only. Environol™ brand antifreeze is recommended.
Once the system has been filled with clean water and antifreeze (if used), precautions should be taken to protect the system from dirty water conditions. Dirty water will result in system-wide degradation of performance, and solids may clog valves, strainers, flow regulators, etc. Additionally, the heat exchanger may become clogged which reduces compressor service life and can cause premature unit failure.
In boiler/tower application, set the loop control panel set points to desired temperatures. Supply power to all motors and start the circulating pumps. After full flow has been established through all components including the heat rejector (regardless of season), air vented and loop temperatures stabilized, each of the units will be ready for check, test and start up and for air and water balancing.

Ground Source Loop System Checkout

Once piping is completed between the unit pumping system and ground loop, final purging and charging of the loop is needed. A high pressure pump is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from the loop itself. Antifreeze solution is used in most areas to prevent freezing. Flush the system adequately to remove as much air as possible; then pressurize the loop to a static pressure of 40-50 PSI (summer) or 50-75 PSI (winter). This is normally adequate for good system operation. Loop static pressure may decrease soon after initial installation, due to pipe expansion and loop temperature change. Running the unit for at least 30 minutes after the system has been completely purged of air will allow for the “break-in” period. It may be necessary to adjust static loop pressure (by adding water) after the unit has run for the first time. Loop static pressure will also fluctuate with the seasons. Pressures will be higher in the winter months than during the cooling season. This fluctuation is normal and should be considered when charging the system initially.
Ensure the pump provides adequate flow through the unit by checking pressure drop across the heat exchanger. Usually 2.25-3.0 gpm of flow per ton of cooling capacity is recommended in earth loop applications.
14

Open Loop Ground Water Systems

VERSATEC BASE SERIES INSTALLATION MANUAL
Typical open loop piping is shown below. Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit to prevent mineral precipitation. Use a closed, bladder-type expansion tank to minimize mineral formation due to air exposure. Insure proper water flow through the unit by checking pressure drop across the heat exchanger and comparing it to the figures in unit capacity data tables in the specification catalog. 1.5-2 gpm of flow per ton of cooling capacity is recommended in open loop applications. Due to only minor differences in flow rate from low to high, only one solenoid valve should be used. The valve should be sized for full flow.
Open System - Groundwater Application
Unit Supply
Aux. Heat Supply
Flexible Duct Collar
Rubber Bladder Expansion Tank
Solenoid
Valve
Drain
Disconnects
(IfApplicable)
Compressor Line Voltage
Low Voltage
to Thermostat
and Valve
P/T Plugs
Vibration
Absorbing Pad
Strainer
Boiler Drains
For HX Flushing
Shut Off Valves
(to isolate solenoid
valve while acid flushing)
Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways, depending on local codes, i.e. recharge well, storm sewer, drain field, adjacent stream or pond, etc. Most local codes forbid the use of sanitary sewer for disposal. Consult your local building and zoning departments to assure compliance in your area.
Flow Control
Valve
(on outlet of
Solenoid Valve)
Water Out
Water In
Shut Off Valves
15
VERSATEC BASE SERIES INSTALLATION MANUAL

Freeze Detection

For Aurora Base Control, set SW2-1, FP1, on the printed circuit board for applications using a closed loop antifreeze solution to 15°F [-9.4°C]. On applications using an open loop/ground water system (or closed loop no antifreeze), set this dip switch to 30°F [-1.1°C], the factory default setting. (Refer to the Dip Switch Field Selection table).

Electrical Connections

General
Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable.
Power Connection
Connect the incoming line voltage wires to L1 and L2 of the contactor for single-phase unit. Consult the Electrical Data tables for correct fuse sizes.
Aurora Base Control Box
208 Volt Operation
All Versatec Base Series 208/230 units are factory wired for 230 volt operation. For 208 volt operation, the red and blue transformer wires must be switched on terminal strip PS.
CAUTION: When installing a unit with a variable speed ECM blower motor in 460/60/3 voltage, a neutral wire is required to allow proper unit operation.
16

Electrical Data

PSC Motor
Model
006
009
012
015
018
024
030
036
042
048
060
070
HACR circuit breaker in USA only
Rated
Voltage
115/60/1 104/127 9.5 6.1 29.0 1.5 7.6 9.1 15
208-230/60/1 198/253 4.7 3.0 15.0 0.6 3.6 4.4 10/15
265/60/1 238/292 4.2 2.7 11.0 0.6 3.3 4.0 10/15
115/60/1 104/127 12.5 8.0 50.0 1.5 9.5 11.5 15
208-230/60/1 198/253 6.4 4.1 21.0 0.6 4.7 5.7 10/15
265/60/1 238/292 6.7 4.3 22.0 0.6 4.9 6.0 10/15
115/60/1 104/127 14.8 9.5 50.0 1.5 11.0 13.4 20
208-230/60/1 198/253 7.7 4.9 25.0 0.6 5.5 6.7 10/15
265/60/1 238/292 70 4.5 22.0 0.6 5.1 6.2 10/15
208-230/60/1 198/253 9.2 5.9 29.0 1.1 7.8 9.5 15
265/60/1 238/292 7.8 5.0 28.0 1.0 6.6 8.0 10/15
208-230/60/1 198/253 10.4 6.7 33.5 1.1 7.8 9.5 15
265/60/1 238/292 8.7 5.6 28.0 1.0 6.6 8.0 10/15
208-230/60/1 198/253 13.0 7.4 43.0 1.2 8.6 10.5 15
265/60/1 238/292 12.6 6.7 46.0 1.1 7.8 9.5 15
208-230/60/3 187/253 13.0 5.9 63.0 1.2 7.1 8.6 10/15
460/60/3 414/506 6.0 2.9 30.0 0.6 3.5 4.2 10/15
208-230/60/1 198/253 17.5 9.4 54.0 1.5 10.9 13.3 20
265/60/1 238/292 14.0 8.0 46.0 1.5 9.5 11.5 15
208-230/60/3 187/253 13.5 6.6 63.0 1.5 8.1 9.8 15
460/60/3 414/506 6.4 3.2 30.0 1.0 4.2 5.0 10/15
208-230/60/1 198/253 20.5 11.6 74.0 2.2 13.8 16.7 25
265/60/1 238/292 17.7 9.9 67.0 1.1 11.0 13.5 20
208-230/60/3 187/253 13.5 7.4 68.0 2.2 9.6 11.5 15
460/60/3 414/506 7.1 3.8 34.0 1.1 4.9 5.9 10/15
208-230/60/1 198/253 25.0 13.0 88.0 3.5 16.5 19.8 30
208-230/60/3 187/253 14.5 8.6 68.0 3.5 12.1 14.3 20
460/60/3 342/506 7.7 4.2 34.0 1.8 6.0 7.1 10/15
575/60/3 517/633 6.0 3.5 28.0 1.4 4.9 5.8 10/15
208-230/60/1 198/253 24.5 15.7 84.0 3.5 19.2 23.1 35
208-230/60/3 187/253 17.5 11.0 88.0 3.5 14.5 17.3 25
460/60/3 342/506 8.0 5.6 44.0 1.8 7.4 8.8 10/15
575/60/3 517/633 7.0 4.4 36.0 1.9 5.8 6.9 10/15
208-230/60/1 198/253 33.0 21.1 105.0 5.9 27.0 32.3 50
208-230/60/3 187/253 22.0 12.9 88.0 5.9 18.8 22.0 30
460/60/3 342/506 12.0 6.7 55.0 3.0 9.7 11.4 15
575/60/3 517/633 7.5 5.1 36.0 1.9 7.0 8.3 10/15
208-230/60/1 198/253 36.0 23.0 130.0 5.9 28.9 34.7 50
208-230/60/3 187/253 24.6 14.3 110.0 5.9 20.2 23.8 35
460/60/3 342/506 11.5 7.1 55.0 3.0 10.1 11.9 15
575/60/3 517/633 8.7 5.6 43.0 1.9 7.5 8.9 10/15
Voltage
Min/Max
VERSATEC BASE SERIES INSTALLATION MANUAL
Compressor
MCC RLA LRA
Blower
Motor
FLA
Total
Unit
FLA
Min Circ
Amp
Max
Fuse/
HACR
10/03/12
17
VERSATEC BASE SERIES INSTALLATION MANUAL
Electrical Data cont.
5-Speed ECM Motor
Model
015
018
024
030
036
042
048
060
070
HACR circuit breaker in USA only
Rated
Voltage
208-230/60/1 198/253 9.2 5.9 29.0 4.1 10.0 11.5 15
265/60/1 238/292 7.8 5.0 28.0 3.6 8.6 9.8 10/15
208-230/60/1 198/253 10.4 6.7 33.5 4.1 10.8 12.5 15
265/60/1 238/292 8.7 5.6 28.0 3.6 9.2 10.6 10/15
208-230/60/1 198/253 13.0 7.4 43.0 4.1 11.5 13.4 20
265/60/1 238/292 12.6 6.7 46.0 3.6 10.3 12.0 15
208-230/60/3 187/253 13.0 5.9 63.0 4.1 10.0 11.5 15
460/60/3 414/506 6.0 2.9 30.0 2.1 5.0 5.7 10/15
208-230/60/1 198/253 17.5 9.4 54.0 4.1 13.5 15.9 25
265/60/1 238/292 14.0 8.0 46.0 3.6 11.6 13.6 20
208-230/60/3 187/253 13.5 6.6 63.0 4.1 10.7 12.4 15
460/60/3 414/506 6.4 3.2 30.0 2.1 5.3 6.1 10/15
208-230/60/1 198/253 20.5 11.6 74.0 4.1 15.7 18.6 30
265/60/1 238/292 17.7 9.9 67.0 3.6 13.5 16.0 25
208-230/60/3 187/253 13.5 7.4 68.0 4.1 11.5 13.4 20
460/60/3 414/506 7.1 3.8 34.0 2.1 5.9 6.9 10/15
208-230/60/1 198/253 25.0 13.0 88.0 7.6 20.6 23.9 35
208-230/60/3 187/253 14.5 8.6 68.0 7.6 16.2 18.4 25
460/60/3 414/506 7.7 4.2 34.0 4.0 8.2 9.3 10/15
208-230/60/1 198/253 24.5 15.7 84.0 7.6 23.3 27.2 40
208-230/60/3 187/253 17.5 11.0 88.0 7.6 18.6 21.4 30
460/60/3 414/506 8.0 5.6 44.0 4.0 9.6 11.0 15
208-230/60/1 198/253 33.0 21.1 105.0 7.6 28.7 34.0 50
208-230/60/3 187/253 22.0 12.9 88.0 7.6 20.5 23.7 35
460/60/3 414/506 12.0 6.7 55.0 4.0 10.7 12.4 15
208-230/60/1 198/253 36.0 23.0 130.0 7.6 30.6 36.4 50
208-230/60/3 187/253 24.6 14.3 110.0 7.6 21.9 25.5 35
460/60/3 414/506 11.5 7.1 55.0 4.0 11.1 12.9 20
Voltage
Min/Max
MCC RLA LRA
Compressor
Blower
Motor
FLA
Total
Unit FLA
Min
Circ
Amp
Max Fuse/ HACR
10/03/12
18
Electrical Data cont.
Variable Speed ECM Motor
Model
015
018
024
030
036
042
048
060
070
HACR circuit breaker in USA only
Rated
Voltage
208-230/60/1 198/253 9.2 5.9 29.0 4.0 9.9 11.4 15
265/60/1 238/292 7.8 5.0 28.0 4.1 9.1 10.3 15
208-230/60/1 198/253 10.4 6.7 33.5 4.0 10.7 12.4 15
265/60/1 238/292 8.7 5.6 28.0 4.1 9.7 11.1 15
208-230/60/1 198/253 13.0 7.4 43.0 4.0 11.4 13.3 20
265/60/1 238/292 12.6 6.7 46.0 4.1 10.8 12.5 20
208-230/60/3 187/253 13.0 5.9 63.0 4.0 9.9 11.4 15
460/60/3 414/506 6.0 2.9 30.0 4.1 7.0 7.7 10/15
208-230/60/1 198/253 17.5 9.4 54.0 4.0 13.4 15.8 25
265/60/1 238/292 14.0 8.0 46.0 4.1 12.1 14.1 20
208-230/60/3 187/253 13.5 6.6 63.0 4.0 10.6 12.3 20
460/60/3 414/506 6.4 3.2 30.0 4.1 7.3 8.1 10/15
208-230/60/1 198/253 20.5 11.6 74.0 4.0 15.6 18.5 30
265/60/1 238/292 17.7 9.9 67.0 4.1 14.0 16.5 25
208-230/60/3 187/253 13.5 7.4 68.0 4.0 11.4 13.3 20
460/60/3 414/506 7.1 3.8 34.0 4.1 7.9 8.9 15
208-230/60/1 198/253 25.0 13.0 88.0 4.0 17.0 20.3 35
208-230/60/3 187/253 14.5 8.6 68.0 4.0 12.6 14.8 25
460/60/3 414/506 7.7 4.2 34.0 4.1 8.3 9.4 15
208-230/60/1 198/253 24.5 15.7 84.0 4.0 19.7 23.6 40
208-230/60/3 187/253 17.5 11.0 88.0 4.0 15.0 17.8 30
460/60/3 414/506 8.0 5.6 44.0 4.1 9.7 11.1 15
208-230/60/1 198/253 33.0 21.1 105.0 7.0 28.1 33.4 55
208-230/60/3 187/253 22.0 12.9 88.0 7.0 19.9 23.1 35
460/60/3 414/506 12.0 6.7 55.0 6.9 13.6 15.3 25
208-230/60/1 198/253 36.0 23.0 130.0 7.0 30.0 35.8 60
208-230/60/3 187/253 24.6 14.3 110.0 7.0 21.3 24.9 40
460/60/3 414/506 11.5 7.1 55.0 6.9 14.0 15.8 25
Voltage
Min/Max
VERSATEC BASE SERIES INSTALLATION MANUAL
Compressor Blower
MCC RLA LRA
Motor
FLA
Total
Unit FLA
Min Circ
Amp
Max Fuse/ HACR
10/03/12
CAUTION: When installing a unit with an variable speed ECM blower motor in 460/60/3 voltage, a neutral wire is required to allow proper unit operation.
19
VERSATEC BASE SERIES INSTALLATION MANUAL

Blower Performance Data

Standard PSC Motor
Blower
Model
006
009
012
015
018
024
030
036
042
048
060
070
Factory settings are in Bold
Airfl ow values are with dry coil and standard fi lter For wet coil performance fi rst calculate the face velocity of the air coil (Face Velocity [fpm] = Airfl ow [cfm] / Face Area [sq ft]). Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by 0.12 in. wg. and 500 fpm by 0.16 in. wg. * Setting for 265V operation.
Blower
Spd
H
MH
ML* 365355345335315300280270255240230195----
L 320 305 295 280 260 250 235 225 210 195 180 150 135 - - ­H
MH
ML* 365353345335315300280270255240230195----
L 320 305 295 280 260 250 235 225 210 195 180 150 135 - - ­H
MH
ML* 365353345335315300280270255240230195----
L 320 305 295 280 260 250 235 225 210 195 180 150 135 - - ­H
M
L 620610600590575550525490455395340290---­H
M
L 620610600590575550525490455395340290---­H
M
L 810790775755740725705675650620595510---­H
M
L 825820815810805795790775765735705655----
H
M 1180 1155 1140 1125 1100 1075 1055 1020 990 955 920 840 725 590 - -
L 1045 1035 1025 1015 1005 985 970 945 920 890 865 795 690 - - ­H
M
L 1160 1140 1130 1120 1100 1070 1050 1020 990 950 910 831 632 590 - -
H
M 1655 1620 1585 1555 1535 1500 1465 1415 1370 1330 1290 1170 970 - - -
L 1325 1315 1310 1285 1265 1245 1220 1180 1140 1115 1090 990 ---­H
M
L 2045 2030 2020 1995 1980 1950 1925 1890 1855 1825 1800 1750 1640 1535 1395 -
H
M 2290 2265 2250 2230 2200 2170 2150 2135 2125 2105 2085 2015 1950 1865 1785 1680
L 2115 2100 2085 2060 2040 2020 2005 1990 1975 1950 1930 1875 1805 1720 1655 1510
Motor
Size
6 x 8 1/10
6 x 8 1/10
6 x 8 1/10
9 x 7 1/6
9 x 7 1/6
9 x 7 1/5
9 x 7 1/3
9 x 7 1/2
10x10 1/2
10 x 10 1/2
11 x 10 1
11 x 10 1
HP
0 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.80 0.90 1.00
435425415405390365340325305290275245----
400 390 380 370 355 335 310 295 280 265 255 210 195 - - -
435423415405390370340325305290275245----
400 388 380 370 355 335 310 295 280 265 255 210 195 - - -
435423415405390370340325305290275245----
400 388 380 370 355 335 310 295 280 265 255 210 195 - - -
795775755735715690670600530490455395---­725710695675660640620560495465435375----
795775755735715690670600530490455395---­725710695675660640620560495465435375----
1035 1015 995 970 950 925 900 865 835 795 760 685 560 - - -
880 860 845 820 805 785 765 740 720 690 665 590 530 - - -
1170 1145 1130 1110 1080 1050 1030 995 965 925 890 815 700 - - -
1040 1030 1020 1005 990 965 945 915 890 860 830 760 650 - - -
1320 1295 1275 1240 1210 1185 1155 1120 1085 1045 1005 915 805 655 - -
1530 1500 1475 1445 1425 1380 1340 1290 1240 1185 1130 810 715 630 - ­1435 1415 1395 1370 1350 1325 1300 1265 1235 1180 1130 1040 755 640 - -
1845 1810 1775 1740 1705 1660 1615 1560 1510 1455 1405 1275 1080 - - -
2345 2320 2305 2285 2250 2205 2180 2135 2090 2060 2030 1945 1850 1740 1600 1465
2195 2170 2150 2125 2105 2075 2045 2005 1970 1940 1915 1845 1770 1630 1500 -
2505 2475 2450 2410 2385 2365 2340 2305 2275 2250 2230 2170 2070 1975 1880 1765
Airfl ow (cfm) at External Static Pressure (in. wg)
10/03/12
Setting Blower Speed - PSC
CAUTION: Disconnect all power before performing this operation.
20
HIGH
E
R
I
W
D
E
E
P
S
N
A
F
PSC BLOWER MOTOR BODY
LOWMEDIUM
Blower Performance Data cont.
5-Speed ECM Motor
Motor
Motor
Model
030
036
042
048
060
070
Factory settings are in Bold
Airfl ow values are with dry coil and standard 1 in. fi lter
Spd
High 5
Med High
015
Med 3 725 715 700 680 660 635 615 600 585 560 535 485 - - - -
Med Low
Low 1 655600550530508490475435395350------
High 5
Med High
018
Med 3 725 715 700 680 660 635 615 600 585 560 535 485 - - - -
Med Low
Low 1 655600550530508490475435395350------
High 5
Med High
024
Med 3 855 838 820 800 780 773 765 745 725 715 705 670 580 - - -
Med Low
Low 1 615600585565545523500468435408380-----
High 5
Med High
Med 3 1020 1008 995 978 960 950 940 923 905 895 885 850 795 735 - -
Med Low
Low 1 795 778 760 738 715 705 695 678 660 650 640 575 530 - - -
High 5
Med High
Med 3 1180 1163 1145 1135 1125 1110 1095 1085 1075 1060 1045 975 865 750 - -
Med Low
Low 1 835 823 810 793 775 758 740 723 705 690 675 640 570 - - -
High 5
Med High
Med 3
Med Low
Low 1 1340 1323 1305 1283 1260 1245 1230 1213 1195 1175 1155 1040 915 875 - -
High 5
Med High
Med 3
Med Low
Low 1 1430 1413 1395 1385 1375 1358 1340 1320 1300 1275 1250 1170 1060 995 930 875
High 5
Med High
Med 3
Med Low
Low 1 1815 1803 1790 1775 1760 1743 1725 1705 1685 1665 1645 1600 1565 1515 1470 1410
High 5
Med High
Med 3
Med Low
Low 1 1850 1833 1815 1800 1785 1765 1745 1728 1710 1683 1655 1615 1580 1530 1475 1300
Blower
Ta p
4
2 695675650630610590575550525490455-----
4
2 695675650630610590575550525490455-----
4
2 790 773 755 743 730 710 690 675 660 643 625 570 - - - -
4
2 980 963 945 935 925 908 890 878 865 848 830 805 780 720 - -
4
2 1125 1115 1105 1090 1075 1065 1055 1040 1025 1008 990 950 855 730 - -
4 1695 1688 1680 1660 1640 1623 1605 1593 1580 1573 1565 1535 1505 1460 1395 1300
2 1510 1495 1480 1465 1450 1435 1420 1403 1385 1373 1360 1310 1250 1135 1055 1010
4 1840 1833 1825 1810 1795 1785 1775 1770 1765 1755 1745 1715 1670 1620 1540 1360
2 1645 1630 1615 1605 1595 1583 1570 1560 1550 1530 1510 1475 1420 1350 1265 1180
4 2260 2250 2240 2223 2205 2195 2185 2168 2150 2133 2115 2085 2045 2005 1975 1930
2 2010 1995 1980 1963 1945 1935 1925 1908 1890 1873 1855 1825 1780 1745 1690 1645
4 2300 2295 2290 2270 2250 2233 2215 2200 2185 2168 2150 2115 2080 2040 1990 1915
2 2040 2028 2015 2000 1985 1965 1945 1930 1915 1898 1880 1850 1805 1760 1725 1685
Motor
Size
9 x 7 1/2
9 x 7 1/2
9 x 7 1/2
9 x 7 1/2
9 x 7 1/2
11 x 10 1
11 x 10 1
11 x 10 1
11 x 10 1
HP
0 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.80 0.90 1.00
915 895 880 865 850 830 815 805 795 775 750 730 695 640 - -
805 785 765 750 740 725 705 685 665 655 635 605 535 - - -
915 895 880 865 850 830 815 805 795 775 750 730 695 640 - -
805 785 765 750 740 725 705 685 665 655 635 605 535 - - -
1000 983 965 950 935 923 910 900 890 873 855 800 825 - -
905 888 870 860 850 833 815 805 795 775 755 740 705 - - -
1315 1293 1270 1243 1215 1183 1150 1120 1090 1055 1020 930 845 - - ­1145 1130 1115 1105 1095 1080 1065 1053 1040 1013 985 905 820 - - -
1405 1380 1355 1333 1310 1275 1240 1208 1175 1135 1095 1015 895 775 - -
1275 1265 1255 1245 1235 1215 1195 1168 1140 1105 1070 985 875 770 - -
1805 1793 1780 1770 1760 1740 1720 1710 1700 1688 1675 1655 1635 1590 1550 1475
1605 1593 1580 1560 1540 1523 1505 1493 1480 1470 1460 1420 1380 1305 1205 1135
2000 1990 1980 1968 1955 1940 1925 1920 1915 1910 1905 1880 1845 1790 1655 1505
1755 1743 1730 1718 1705 1698 1690 1683 1675 1655 1635 1600 1555 1495 1435 1300
2455 2440 2425 2413 2400 2390 2380 2365 2350 2335 2320 2295 2245 2175 2085 2015
2140 2123 2105 2095 2085 2065 2045 2033 2020 2005 1990 1960 1915 1870 1835 1790
2500 2495 2490 2473 2455 2438 2420 2405 2390 2363 2335 2325 2280 2215 2120 1995
2175 2163 2150 2138 2125 2100 2075 2060 2045 2030 2015 1980 1945 1905 1860 1820
VERSATEC BASE SERIES INSTALLATION MANUAL
Airfl ow (cfm) at External Static Pressure (in. wg)
5-Speed ECM Motor Connections
High Voltage Connections
3/16 in.
C
GN
C - Black L - Orange
G - Green
L
N - Brown
09/26/12
21
G - Blue Y1 - Red
345
12
Low Voltage
Connections 1/4 in.
AUX - Gray
VERSATEC BASE SERIES INSTALLATION MANUAL
5-Speed ECM Constant Torque Motors
The 5-speed ECM is a ‘Constant Torque’ ECM motor and delivers air flow similar to a PSC but operates as efficiently as an variable speed ECM Motor. Because it’s an ECM Motor, the 5-speed ECM can ramp slowly up or down like the variable speed ECM Motor. There are 5 possible speed taps available on the 5-speed ECM motor with #1 being the lowest airflow and #5 being the highest airflow. These speed selections are preset at the time of manufacture and are easily changed in the field if necessary.
5-Speed ECM Benefits:
- High efficiency
- Soft start
- 5 speeds with up to 4 speeds on-line
- Built in logic allows air flow to change with G, Y1, Y2 and W signals
- Super efficient low airflow continuous blower setting (G)
If more than one tap are energized at the same time, built in logic gives precedence to the highest tap number and allows air flow to change with G, Y1, Y2 and W signals. Each of those 5 speeds has a specific ‘Torque’ value programmed into the motor for each speed selection. As static pressure increases, airflow decreases resulting in less torque on the rotor. The motor responds only to changes in torque and adjusts its speed accordingly.
The 5-speed ECM motor is powered by line voltage but the motor speed is energized by 24VAC.
Power Connection - 3/16 in. quick connects - Line 1 (orange wire) to L, Ground (green wire) to G, Line 2 (for 208V-230V units) to N (brown wire).
Signal Connection - 1/4 in. quick connects - Common to C, 24VAC to Taps #1-5.
Applying 24VAC power between any of the motor taps 1-5 (1/4 in. quick connects) and common will signal the motor to run and regulate torque at the programmed level. The tap input voltage must be in the range 12-33VAC. The 5-speed ECM will have less variation over the operating static pressure range versus a PSC motor as well as a significant watts reduction due to the high motor efficiency.
Thermal Protection - Motor is electronically protected.
Locked Rotor Amps - If motor speed decreases below a
programmed stall speed, the motor will shut down and after a delay period, the control will attempt to restart the motor.
The 5-speed ECM speed tap selections are as follows: The blue wire should be placed on the speed tap desired for the (G) continuous blower setting – factory wired to Tap 1.
The red wire should be placed on the speed tap desired during compressor operation (Y1 signal) – factory wired to Tap 3 or 4.
The gray wire is not factory wired to the motor and is tied to the wire harness. It is field connected and can be used with 3ht/2cl thermostats or IntelliZone to deliver the required air flow for the Y2 signal.
The tan wire should be placed on the speed tap desired for auxiliary heat (W signal) – factory wired to Tap 5.
22
VERSATEC BASE SERIES INSTALLATION MANUAL
Blower Performance Data cont.
Variable Speed ECM Motor
Max
Model
015
018
024
030
036
042
048
060
070
Factory settings are at recommended L-M-H DIP switch locations. Shaded regions are recommended for best performance. It is acceptable to operate outside of this area as long as the WSHP operates within the guidelines of the Operating Limits table and Correction Factor tables. Lowest and Highest DIP switch settings are assumed to be L and H respectively. CFM is controlled within ±5% up to the maximum esp. Max esp includes allowance for wet coil and standard fi lter
Blower
ESP
0.50 9 x 7 1/2
0.50 9 x 7 1/2
0.50 9 x 7 1/2
0.50 9 x 7 1/2
0.50 9 x 7 1/2
0.50 11 x 10 1/2
0.50 11 x 10 1/2
0.75 11 x 10 1
0.75 11 x 10 1
Size
Motor
hp
123456789101112
300 400
300 400
400 500 600
400 500 600
400 500 600 700
500 600 700 875
500 600 700 875 1050 1150
600 800 1000 1300
600 800 1000 1300
500 600M700H800
L
500 600 700 800
L
LM
L
L
L
L
MH
L
L
Air Flow Dip Switch Settings
700 800 900 1000 1100
H
700 800 900 1000 1100
MH
800 900 1000 1100 1200
M H
1050 1150 1250 1325 1375 1475 1550
MH
1250 1325 1375 1475 1550 1600
MH
1500 1750 1950 2100 2200 2300
MH
1500 1750 1950 2100 2200 2300
MH
09/26/12
Setting Blower Speed - Variable Speed ECM
Variable speed ECM blower motors have 12 selectable speeds and are factory set for optimum performance. When applicable, the speed settings may also be adjusted through the Building Automation System (BAS).
CAUTION: Disconnect all power before performing this operation.
23
VERSATEC BASE SERIES INSTALLATION MANUAL
Blower Performance Data cont.
Setting Blower Speed - Variable Speed ECM
The ABC board’s Yellow Confi g LED will fl ash the current variable speed ECM blower speed selections for low, med, and high continuously with a short pause in between. The speeds can also be confi rmed with the AID Tool under the Setup/ECM Setup screen. The variable speed ECM blower motor speeds can be fi eld adjusted with or without using an AID Tool.
Variable Speed ECM Setup without an AID Tool
The blower speeds for Low (G only), Med (Y1), and High (Y2/Aux) can be adjusted directly at the Aurora ABC board which utilizes the push button (SW1) on the ABC board. This procedure is outlined in the Variable Speed ECM Confi guration Mode portion of the Aurora ‘Base’ Control System section.
Variable Speed ECM Setup with an AID Tool
A much easier method utilizes the AID Tool to change the airfl ow using the procedure below. First navigate to the Setup screen and then select ECM Setup. This screen displays the current variable speed ECM settings. It allows the technician to enter the setup screens to change the variable speed ECM settings. Change the highlighted item using the and buttons and then press the button to select the item.
Variable Speed ECM Setup with an AID Tool cont.
ECM SPEED INFO
Selecting YES will enter variable speed ECM speed
LOW SPEED: 3 MED SPEED: 5 HIGH SPEED: 7
WANT TO CHANGE?
YES
OPTION ◀▶NOENTER
setup, while selecting NO will return to the previous screen.
Variable Speed ECM Speed Setup - These screens allow the technician to select the low, medium, and high blower speed for the variable speed ECM blower motor. Change the highlighted item using the and buttons. Press the button to select the speed.
ECM SPEED INFO
1 2 <– LOW 3 4 5 6 7 8 9 10 11 12
OPTION ◀▶ ENTER
ECM SPEED INFO
1 2 LOW 3 4 5 <– MED 6 7 8 9 10 11 12
OPTION ◀▶ ENTER
ECM SPEED INFO
1 2 LOW 3 4 5 MED 6 7 8 9 10 11 12 <– HIGH
OPTION ◀▶ ENTER
After the high speed setting is selected the AID Tool will automatically transfer back to the ECM Setup screen.
24

Wiring Schematics

y
y
g
g
g
g
)
)
)
g
g
g
g
y
y
g
y
y
A
y
Aurora Base Control 208-230/60/1 PSC
Grn
P3
H M L
PSC
Blower
Motor
Black
Cap
3 Airflow Settings
WhtBrn
Compressor
Cap
White
RB
13
Note 2
Blue
Red
208V
S
Tan
Black
C
R
Black
Red
T1T2
CC
L1L2
Blue
Black
230V 265V
Transformer
24V
Yellow Black/White
Green (93)
Black (95)
Red (97)
Note 1
Ground Neutral
Disconnect
L1 L1
L2 L2
L3 L3
Unit Power Supply 208-230-265/60/1
G
VERSATEC BASE SERIES INSTALLATION MANUAL
Note 3
Isolation
Valve
213
Red (51)
Green
(50)
White
(52)
P2
Red (53)
Note 3
P1
Accessory Relay
Operation
Cycle with Blower C
cle with Compressor Water Valve Slow Open Outdoor Air Damper
Event
Random Start Delay Compressor On Delay Compressor Minimum On Time Compressor Short Cycle Delay Blower Off Delay Fault Recognition Delay – High Pressure Start-Up Bypass – Low Pressure Fault Recognition Delay – Low Pressure
pass – Low Water/Air Coil Limit
Start-Up B
nition Delay – Low Water/Air Coil Limit
Fault Reco Fault Recognition Delay – Condensate Overflow Thermostat Call Recognition Time Auxiliary Heat Staging Dela Emergency Heat Staging Dela Water Valve Slow Open Dela Reheat Delay
SW2-5
SW2-4
On Off On Off On
urora Timing Events
On Off Off
RB
White (12)
JW2
DH W Y2 Y1 G O/B C R LO R F FG CC CCG
ES LS ALM
K5
ALG ACC COM ACC NO ACC NC
LO R C O/B G Y1 Y2 W DH
K6
P9
K4
F1
R
Normal Mode
5 to 80 seconds 1 second
Less than 1 second
RS485 NET
C
G r
ee n
Test Mode
5 seconds < 1 second 2 minutes 5 seconds 4 minutes 15 seconds
30 seconds 2 seconds
Less than 1 second
2 minutes
30 seconds 30 seconds
2 minutes 30 seconds 30 seconds
2 seconds 2 seconds
5 minutes
2 minutes 90 seconds 90 seconds 30 seconds 30 seconds
30 seconds
30 seconds 30 seconds 30 seconds
20 seconds
7.5 seconds
RS485 NET
RA-B+
P8 P7
Slow Flash Fast Flash Flash Code
Status LED (LED1, Green Configuration LED (LED2, Yellow Fault LED (LED3, Red
Status LED (LED1, Green)
Normal Mode Control is Non-Functional Test Mode Lockout Active Dehumidification Mode Reserved Reserved Load Shed ESD Reserved
Resistor
RV
CC
Black (
Violet (14)
Black (15)
1
3)
CC
CC2HICC2LOCC2
24V
P5
G
K3
K2
Aurora Base Control
(ABC)
LED4LED5
RS485 EXP
C
RA-B+C
N/A
P6
Brown (23)
Condensate
1 second on and 1 second off 100 milliseconds on and 100 milliseconds off 100 milliseconds on and 400 milliseconds off with a 2 second pause before repeatin
Random Start Delay
ON
OFF Slow Flash Fast Flash
Flash Code 2 Flash Code 3 Flash Code 4 Flash Code 5 Flash Code 6 Flash Code 7
Aurora LED Flash Codes
Fast Flash Fast Flash Fast Flash
Configuration LED (LED2, Yellow)
No Software Overide Flash ECM Setting DIP Switch Overide Slow Flash ECM Configure Mode Fast Flash
ure Mode Off
Reset Confi
FD
RV
T
O
O
Yellow
Yellow
r
r
ange (01)
a
nge (02)
REVREV FP1 FP1 FP2 FP2 LPSLPSHPSHPS
P12
K1
SW1
Status
EH2CEH1CCO
P3
470
47
HPLP
0
Blue
Blue (08)
Black (09)
B lack (10)
(07 )
G
Fault
R
FP1 – 15°F/30°F FP2 – 15°F/30°F
RV – B/O Acc – Dip 1 Acc – Dip 2
CC – Dual/Single
L – Pulse/Continuous
Reheat/Normal
Config
Y
CCGY1
Fault LED (LED3, Red)
Normal Mode Input Fault Lockout High Pressure Lockout Low Pressure Lockout Low Air Coil Limit Lockout - FP2 Low Water Coil Limit Lockout - FP1 Reserved Condensate Overflow Lockout
e Shutdown
Over/Under Volta Reserved Reserved Air/Water Coil Limit Sensor Error
P4
C
Black/White
R
Yellow
F
PWM
CFM
C P13
On
Off
1 2 3 4 5 6 7 8
SW2
1 – Optional, factory installed unit mounted disconnect. 2 – Swap blue and red leads for 208V operation. 3 – Optional, factory installed internal isolation valve.
Notes:
Legend
Factor
OFF Flash Code 1 Flash Code 2 Flash Code 3 Flash Code 4 Flash Code 5 Flash Code 6 Flash Code 7 Flash Code 8 Flash Code 9
Flash Code 10 Flash Code 11
Low Voltage Wirin Factory Line Voltage Wirin Field Low Voltage Wiring Field Line Voltage Wiring Optional Block
e PCB Traces
DC Volta Field Zone Sensor Wirin Internal Junction Quick Connect Terminal
Field Wiring Lug
L1
Ground Relay Contacts – N.O., N.C.
Capacitor
Fuse
CC – Compressor Contactor CO – Condensate Overflow Sensor ES – Emergency Shutdown HP – High Pressure Switch LP – Low Pressure Switch FD – Freeze Detection Sensor F1 – Fuse
Thermistor
T
Coil
Rela
Switch - Condensate Overflow Switch - High pressure
Switch - Low pressure
123
Polarized connector
ht Emitting Diode - Green
Li
G
Light Emitting Diode - Yellow
Y
Light Emitting Diode - Red
R
SW1 – Push button SW2 – DIP package 8 position RB – Blower Relay RV – Reversing Valve Coil
97P817-01 11/08/10
25
VERSATEC BASE SERIES INSTALLATION MANUAL
g
A
A
A
A
g
A
(
A
)
)
)
)
)
)
(
(
(
( )
)
)
)
)
y
)
)
)
)
)
)
)
)
)
)
( )
g ( )
)
( )
g
g
g
g
g
g
)
)
)
g
y
y
y
y
A
y
Wiring Schematics cont.
Aurora Base Control 460/60/3 Variable Speed ECM
Note 4
PGM
Y-OU T
Y
C
Black/White (92
Yellow (91
Note 2
Isolation
Valve
213
Red
51) Green
50) White
52)
Red
Note 2
53
Accessory Relay
Operation
Cycle with Blower Cycle with Compressor Water Valve Slow Open Outdoor Air Damper
Event
Random Start Dela Compressor On Dela Compressor Minimum On Time Compressor Short Cycle Dela Blower Off Dela Fault Recognition Delay – High Pressure Start-Up Bypass – Low Pressure Fault Recognition Delay – Low Pressure Start-Up Bypass – Low Water/Air Coil Limit Fault Recognition Delay – Low Water/Air Coil Limit Fault Recognition Delay – Condensate Overflow Thermostat Call Recognition Time Auxiliary Heat Staging Delay Emergency Heat Staging Delay Water Valve Slow Open Delay Reheat Dela
DH W Y2 Y1 G O/B C R LO R F FG CC CCG
P2
ES LS ALM
LG ACC COM ACC NO ACC NC
LO R C O/B G Y1 Y2 W DH
P1
F1
R
SW2-5
SW2-4
On
On
Off
Off
Off
On Off On
urora Timing Events
Compressor
T3
YellowRed Black
T2T3
CC
L2L3
Blue 460V
Transformer
Yellow
K5
K6
RS485 NET
C
Green
Normal Mode
5 to 80 seconds 1 second
30 seconds 2 seconds
Less than 1 second
30 seconds 30 seconds
30 seconds 30 seconds
90 seconds 90 seconds 30 seconds 30 seconds
Test Mode
5 seconds < 1 second 2 minutes 5 seconds 4 minutes 15 seconds
Less than 1 second
2 minutes
30 seconds
30 seconds
2 minutes
30 seconds
30 seconds 2 seconds 2 seconds 5 minutes
20 seconds 2 minutes
7.5 seconds
24V
T1
T2
T1
L1
Black
Black/White
P9
P8
Note 3
Phase Guard Monitor (PGM)
L1 L2 L3
Black (7 White (8 Red (9
Black (54 Blue (55 Red (56
CC
Violet (14)
Black
15
JW2
RS485 NET
RA-B+
Slow Flash Fast Flash Flash Code
Status LED (LED1, Green Configuration LED (LED2, Yellow Fault LED (LED3, Red
Normal Mode Control is Non-Functional Test Mode Lockout Active Dehumidification Mode Reserved Reserved Load Shed ESD Reserved
CC2HICC2LOCC2
P5
G
K3
K4
K2
urora Base Control
ABC)
LED4LED5
RS485 EXP
C
B+C
R
N/
P7
1 second on and 1 second off 100 milliseconds on and 100 milliseconds off 100 milliseconds on and 400 milliseconds off with a 2 second pause before repeating
Random Start Delay
Status LED (LED1, Green)
-
P6
Brown (23
Condensate
Fast Flash Fast Flash Fast Flash
Configuration LED (LED2, Yellow)
No Software Overide Flash ECM Settin
ON
DIP Switch Overide Slow Flash
OFF
ECM Configure Mode Fast Flash
Slow Flash
Reset Configure Mode Off
Fast Flash Flash Code 2 Flash Code 3 Flash Code 4 Flash Code 5 Flash Code 6 Flash Code 7
Orange
Brown
Black (54
Blue (55
Red (56
RV
FD
RV
T
Oran
Orange (02)
Yellow
e 01
CC
24V
REVREV FP1 FP1 FP2 FP2LPSLPS HPSHPS
P12
K1
SW1
EH2CEH1CCO
P3
Aurora LED Flash Codes
PB3
N
L1
L2
L3

Resistor

Blue (07)
Blue (08)
Yellow
Status
G
FP1 – 15°F/30°F FP2 – 15°F/30°F
CC – Dual/Sin
L – Pulse/Continuous
Reheat/Normal
CCGY1
Normal Mode Input Fault Lockout High Pressure Lockout Low Pressure Lockout Low Air Coil Limit Lockout - FP2 Low Water Coil Limit Lockout - FP1 Reserved Condensate Overflow Lockout Over/Under Voltage Shutdown Reserved Reserved Air/Water Coil Limit Sensor Error
HPLP
Black (09)
RV – B/O cc – Dip 1 cc – Dip 2
Confi
Fault LED (LED3, Red)
Unit Power Suppl 460/60/3 w/Neutral
G
Note 1
Green (93 Gray (94
Black (95
Yellow (96
Red (97
Black
10
P4
PWM
CFM
C
P13
Fault
R
Off
le
SW2
Y
C
R
F
On
1 2 3 4 5 6 7 8
Ground Neutral
Disconnect
L1 L1
L2 L2
L3 L3
Orange
Brown
Variable Speed
ECM Blower Motor
R
G
CFM
PWM
16
P112 3 4 51
C1
C2
1 312 15 10
P12
Black/White
Yellow Violet (42
Blue (24 Yellow (25
Green/Yellow (28
Green
Notes:
1 – Optional, factory installed unit mounted disconnect. 2 – Optional, factory installed internal isolation valve. 3 – Optional, factory installed phase guard. 4 – Optional, factory installed phase guard. The yellow transformer
wire shall be connected directly to the CPU board, if this option is not installed.
Legend
OFF Flash Code 1 Flash Code 2 Flash Code 3 Flash Code 4 Flash Code 5 Flash Code 6 Flash Code 7 Flash Code 8 Flash Code 9
Flash Code 10 Flash Code 11
Factory Low Voltage Wiring Factory Line Voltage Wiring Field Low Volta Field Line Voltage Wirin Optional Block DC Voltage PCB Traces Field Zone Sensor Wiring Internal Junction Quick Connect Terminal
Field Wirin
L1
CC – Compressor Contactor CO – Condensate Overflow Sensor ES – Emergency Shutdown HP – High Pressure Switch LP – Low Pressure Switch FD – Freeze Detection Sensor F1 – Fuse
Lu
Ground Relay Contacts – N.O., N.C.
Capacitor
Fuse
e Wirin
Thermistor
T
Relay Coil
Switch - Condensate Overflow Switch - Hi
h pressure
Switch - Low pressure
123
Polarized connector
Light Emitting Diode - Green
G
Light Emitting Diode - Yellow
Y
Light Emitting Diode - Red
R
SW1 – Push button SW2 – DIP package 8 position RB – Blower Relay RV – Reversing Valve Coil
PGM – Phase Guard Monitor RH – Reheat Valve Coil
97P818-07 12/08/10
26
Wiring Schematics cont.
g
A
A
/
f
A
A
(
(
(
( )
)
( )
y
y
g
g
g
g
g
g
)
)
)
)
)
)
)
)
g
)
)
g
g
g
A
g
f
y
f
f
y
y
y
g
y
y
Aurora Base Control 460/60/3 5-Speed ECM
T1
T3
Note 4
Phase Guard Monitor (PGM)
L1 L2 L3
Black (7) White (8) Red (9)
Note 5
PGM
Y-OU T
Y
C
Black/White (92
Yellow (91
Note 2
Isolation
Valve
213
Red
51) Green
50) White
52)
Note 2
Accessory Relay
Operation
cle with Blower
C Cycle with Compressor Water Valve Slow Open Outdoor Air Damper
Event
Random Start Delay Compressor On Dela Compressor Minimum On Time Compressor Short Cycle Dela Blower Off Dela Fault Recognition Delay – High Pressure Start-Up Bypass – Low Pressure Fault Recognition Delay – Low Pressure Start-Up Bypass – Low Water/Air Coil Limit Fault Reco
nition Delay – Low Water/Air Coil Limit Fault Recognition Delay – Condensate Overflow Thermostat Call Recognition Time Auxiliary Heat Staging Dela Emergency Heat Staging Delay Water Valve Slow Open Delay Reheat Dela
DH W Y2 Y1 G O/B C R LO R F FG CC CCG
P2
ES
LS ALM ALG ACC COM ACC NO ACC NC
LO R
Red
C
O/B
53
G Y1
Y2
W
DH
P1
R
SW2-5
SW2-4
On
On
Of
Off
Of
On Off On
Aurora Timing Events
Yellow
F1
T2
Red
Yellow
T2T3
CC
L2L3
L1
Blue
Blue 460V
460V
Transformer
24V
K5
K6
LED4
G
RS485 NET
C
Green
Normal Mode
5 to 80 seconds 1 second
30 seconds 2 seconds
Less than 1 second
30 seconds 30 seconds
30 seconds 30 seconds
90 seconds 90 seconds 30 seconds 30 seconds
Test Mode
5 seconds < 1 second 2 minutes 5 seconds 4 minutes 15 seconds
Less than 1 second
2 minutes
30 seconds
2 minutes
30 seconds 30 seconds
30 seconds 2 seconds 2 seconds 5 minutes
20 seconds 2 minutes
7.5 seconds
Black
T1
Black
Black
Black/White
P9
P8
JW2
LED5
G
RS485 NET
RA-B+
Slow Flash Fast Flash Flash Code
Status LED (LED1, Green) Confi
uration LED (LED2, Yellow
Fault LED (LED3, Red
Normal Mode Control is Non-Functional Test Mode Lockout Active Dehumidification Mode Reserved Reserved Load Shed ESD Reserved
Note 1
Green (93
Black (95)
Yellow (96
Red (97)
Ground Neutral
Disconnect
L1 L1
L2 L2
L3 L3
RV
CC
Violet (14)
Black (15)
CC2HICC2LOCC2
P5
G
K3
K4
K2
urora Base Control
(ABC)
RS485 EXP
C
RA-B+C
P7
1 second on and 1 second off 100 milliseconds on and 100 milliseconds off 100 milliseconds on and 400 milliseconds off with a 2 second pause before repeatin
Random Start Delay
Status LED (LED1, Green)
N/
P6
Brown (23
Condensate
Fast Flash Fast Flash Fast Flash
Configuration LED (LED2, Yellow)
No Software Overide Flash ECM Settin
ON
DIP Switch Overide Slow Flash
OFF
ECM Configure Mode Fast Flash
Slow Flash
Reset Confi
Fast Flash Flash Code 2 Flash Code 3 Flash Code 4 Flash Code 5 Flash Code 6 Flash Code 7
RV
Orange (01)
Orange (02)
REVREV FP1 FP1 FP2 FP2LPSLPS HPSHPS
K1
SW1
CO
C
Aurora LED Flash Codes
ure Mode Of

Resistor
FD
T
Yellow
Yellow
Status
EH2CEH1
P3
VERSATEC BASE SERIES INSTALLATION MANUAL
Unit Power Supply
460/60/3
G
Brown
Orange
HPLP

Blue
Blue (08)
Black (09)
07
G
FP1 – 15°F FP2 – 15°F/30°F
RV – B/O cc – Dip 1 cc – Dip 2
CC – Dual/Sin
L – Pulse/Continuous
Reheat/Normal
Config
CCGY1
Fault LED (LED3, Red)
Normal Mode Input Fault Lockout High Pressure Lockout Low Pressure Lockout Low Air Coil Limit Lockout - FP2 Low Water Coil Limit Lockout - FP1 Reserved Condensate Overflow Lockout Over/Under Volta Reserved Reserved
ir/Water Coil Limit Sensor Error
Black (10)
Fault
R
30°F
Y
e Shutdown
Gray (30
Tan (31
Red (32
Blue (33) Black (35
P4
C
R
F
PWM CFM
C P13
On
Of
1 2 3 4 5
le
6 7 8
SW2
Flash Code 1 Flash Code 2 Flash Code 3 Flash Code 4 Flash Code 5 Flash Code 6 Flash Code 7 Flash Code 8
Flash Code 9 Flash Code 10 Flash Code 11
Green
Note 6
Black/White
Yellow
5-Speed ECM
LNG
Blower
Motor
123
C45
Note 5
5-Speed ECM Low Voltage Connections
Model TAP-1 TAP-2 TAP-3 TAP-4 TAP-5
015 Blue Red Gray 018 Blue Red Gray 023 Blue Red Gray 024 Blue Red Gray 030 Blue Red Gray 036 Blue Red Gray 041 Blue Red Gray 042 Blue Red Gray 048 Blue Red Gray 060 Blue Red Gray 070 Blue Red Gray
Notes:
1 - Optional, factory installed unit mounted disconnect. 2 - Optional, factory installed internal isolation valve. 3 - Optional, factory installed phase guard. 4 - Optional, factory installed phase guard. The yellow transformer wire shall be connected directly to the CPU board, if this option is not installed. 5 - Refer to the 5-Speed ECM Low Voltage Connection Table. 6 - Wire is provided with the unit but not connected to the 5-Speed ECM.
Legend
Factor
Low Voltage Wirin Factory Line Voltage Wiring Field Low Volta
e Wirin Field Line Voltage Wiring Optional Block DC Volta
e PCB Traces Field Zone Sensor Wiring Internal Junction Quick Connect Terminal
Field Wirin
L1
OFF
CC – Compressor Contactor CO – Condensate Overflow Sensor ES – Emergency Shutdown HP – High Pressure Switch LP – Low Pressure Switch FD – Freeze Detection Sensor F1 – Fuse
Lu
Ground Relay Contacts – N.O., N.C.
Capacitor
Fuse
SW1 – Push button SW2 – DIP package 8 position RB – Blower Relay RV – Reversing Valve Coil PGM – Phase Guard Monitor RH – Reheat Valve Coil
T
123
G
Y
R
97P819-07 3/8/12
Thermistor
Rela
Coil
Switch - Condensate Overflow Switch - High pressure
Switch - Low pressure
Polarized connector
Light Emitting Diode - Green
Light Emitting Diode - Yellow
Light Emitting Diode - Red
27
VERSATEC BASE SERIES INSTALLATION MANUAL
A
A
N
/
CN/
C
S
ignal
Wiring Schematics cont.
Aurora Control with UPC
To ABC - P8
12345678
LON Network
Connections
Devices Must
Be Wired in
Daisy Chain
Configuration
12
Service
LED1
LED2
Tx
LED3
Rx
LED4
Net
12
Optional LON
Add-On Module
LON OC
ECHELON
BACnet or N2
Network
Connections
Devices Must Be Wired in
Daisy Chain Configuration
NET+
COM
NET-
NET+
NET-
COM
Orange
Red
White Black
NET+ NET­COM
NET+ NET­N/C N/C
Signal
GND RNET+ RNET­+12V
RNET LOCAL ACCESS
GND
LN+
2W
4W
LN­+12
LED1
LED2
ADAPTER
/S
LED6
LED7
PORT
Blue
Green
Brown Yellow
POWER
GND
24 VAC
LED3
TX
RX
LON
POWER
FORMAT BATT
Communication
Options
NOTE 1
TX
RX
LED4
LED5
RUN
ERR
12345678 ON
TEN’S
0
149
238
7
6
5 0
149
238
7
6
5
ONE’S
MAC Address Setting
GND
RNET+
RNET-
+12V
GND
RNET+
RNET-
+12V
12
ZS Sensor 2
Addr: 1
ZS Sensor 3
Addr: 2
ZS Sensor 1
Addr: 0
GND
RNET+
RNET-
+12V
ZS Sensor Information
Zone Sensors can be wired in daisy chain as show or in a star or hybrid configuration. Maximum of 5 sensors per UPC. Maximum allowable load 210mA. See the UPC install manual for possible sensor combinations.
DIP
Switch
Value
1 2 4
8
1234
Each ZS sensor must have a unique address, but the addresses do not need to be sequential. Use the DIP switches on the back of the ZS sensor to
ON
set an address from 0 to 4. (0 is the factory default.) Each DIP switch has the value shown in the figure to the left. Turn on as many DIP switches as you need so that their total value equals the address.
28
Notes
1. Use DIP Switches 5 – 8 to change communication protocol and DIP switches 1 – 2 to change BACnet baud rate
Legend
Factory Low Voltage Wiring Field Low Voltage Wiring
RJ45 Connector
12345678
S

Controls - Aurora Base Control

VERSATEC BASE SERIES INSTALLATION MANUAL
Aurora ‘Base’ Control
Field Selectable Options via Hardware
DIP Switch (SW1) – Test/Configuration Button (See SW1
Operation Table)
Test Mode
The control is placed in the test mode by holding the push button switch SW1 for 2 - 5 seconds. In test mode most of the control timings will be shortened by a factor of sixteen (16). LED3 (green) will flash at 1 second on and 1 second off. Additionally, when entering test mode LED1 (red) will
NOTE: Refer to the Aurora Base Control Application and Troubleshooting Guide and the Instruction Guide: Aurora Interface and Diagnostics (AID) Tool for additional information.
flash the last lockout one time. Test mode will automatically time out after 30 minutes. Test mode can be exited by pressing and holding the SW1 button for 2 to 5 seconds or by cycling the power. NOTE: Test mode will automatically be exited after 30 minutes.
Control Features
oftware ABC Standard Version 2.0
Single or Dual Capacity Compressors
Either single or dual capacity compressors can be operated.
Variable Speed ECM Blower Motor Option
A Variable Speed ECM blower motor can be driven directly using the onboard PWM output. Four blower speeds are available based upon the G, Y1, Y2, and W input signals to the board. The blower speeds can be changed either by the ECM manual configurations mode method or by using the Aurora AID Tool directly. All four blower speeds can be set to the same speed if desired.
5-Speed ECM Blower Motor Option
A 5-Speed ECM blower motor will be driven directly using the thermostat connections. Any of the G, Y1, or Y2/W signals can drive any of the 5 available pre-programmed blower speeds on the motor. All 5 Series "G" vintage units will be wired this way at the factory.
Other Control Features
• Random start at power up
• Anti-short cycle protection
• High and low pressure cutouts
• Loss of charge
• Water coil freeze detection
• Air coil freeze detection
• Over/under voltage protection
• Condensate overflow sensor
• Load shed
• Dehumidification (where applicable)
• Emergency shutdown
• Hot gas reheat operation (where applicable)
• Diagnostic LED
• Test mode push button switch
• Two auxiliary electric heat outputs
• Alarm output
• Accessory output with N.O. and N.C.
• Modbus communication (master)
• Modbus communication (slave)
ECM Configuration Mode
The control is placed in the ECM configuration mode by holding the pushbutton switch SW1 for 5 to 10 seconds, the high, low, and “G” ECM speeds can be selected by following the LED display lights. LED2 (yellow) will fast flash when entering the ECM configuration. When setting “G” speed LED3 (green) will be continuously lit, for low speed LED1 (red) will be continuously lit, and for high speed both LED3 (green) and LED1 (red) will be continuously lit. During the ECM configuration mode LED2 (yellow) will flash each of the 12 possible blower speeds 3 times. When the desired speed is flashed press SW1, LED2 will fast flash until SW1 is released. “G” speed has now been selected. Next select low speed, and high speed blower selections following the same process above. After third selection has been made, the control will exit the ECM configuration mode. Aux fan speed will remain at default or current setting and requires the AID Tool for adjustment.
Reset Configuration Mode
The control is placed in reset configuration mode by holding the push button switch SW1 for 50 to 60 seconds. This will reset all configuration settings and the EEPROM back to the factory default settings. LED3 (green) will turn off when entering reset configuration mode. Once LED3 (green) turns off, release SW1 and the control will reset.
DIP Switch (SW2)
SW2-1 FP1 Selection – Low water coil temperature limit
setting for freeze detection. On = 30°F; Off = 15°F.
SW2-2 FP2 Selection – On = 30°F; Off = N/A SW2-3 RV – O/B - thermostat type. Heat pump
thermostats with “O” output in cooling or “B” output in Heating can be selected. On = O; Off = B.
SW2-4 Access Relay Operation (P2) and 2-5
Access Relay Operation SW2-4 SW2-5
Cycle with Blower ON ON
Cycle with Compressor OFF OFF
Water Valve Slow Opening ON OFF
Cycle with Comm. T-stat Hum Cmd OFF ON
29
VERSATEC BASE SERIES INSTALLATION MANUAL
A
Controls - Aurora Base Control cont.
Cycle with Blower - The accessory relay will cycle with the blower output.
Cycle with Compressor - The accessory relay will cycle with the compressor output.
Water Valve Slow Opening - The accessory relay will cycle and delay both the blower and compressor output for 90 seconds.
SW2-6 CC Operation – selection of single or dual capacity
compressor. On = Single Stage; Off = Dual Capacity
SW2-7 Lockout and Alarm Outputs (P2) – selection of a
continuous or pulsed output for both the LO and ALM Outputs. On = Continuous; Off = Pulsed
SW2-8 Future Use
Alarm Jumper Clip Selection
From the factory, ALM is connected to 24 VAC via JW2. By cutting JW2, ALM becomes a dry contact connected to ALG.
ECM Blower Speeds
The blower speeds can be changed either by using the ECM manual configurations mode method or by using the Aurora AID Tool directly (see Instruction Guide: Aurora Interface and Diagnostics (AID) Tool topic).
Field Selectable Options via Software
(Selectable via the Aurora AID Tool)
ECM Blower Speeds
An ECM blower motor can be driven directly using the onboard PWM output. Four blower speeds are available, based upon the “G”, Y1 (low), Y2 (high), and Aux input signals to the board. The blower speeds can be changed either by the ECM manual configurations mode method (see ECM Configuration Mode topic) or by using the Aurora AID Tool directly. All four blower speeds can be set to the same speed if desired. Aux blower speed will remain at default or current setting and requires the AID Tool for adjustment.
Lockout – when locked out, the blower will operate continuously in “G” speed, and PSC blower motor output will remain on. The Alarm output (ALM) and Lockout output (L) will be turned on. The fault type identification display LED1 (Red) shall flash the fault code. To reset lockout conditions with SW2-8 On, thermostat inputs “Y1”, “Y2”, and “W” must be removed for at least 3 seconds. To reset lockout conditions with SW2-8 Off, thermostat inputs “Y1”, “Y2”, “W”, and “DH” must be removed for at least 3 seconds. Lockout may also be reset by turning power off for at least 30 seconds or by enabling the emergency shutdown input for at least 3 seconds.
Lockout With Emergency Heat - if the control is locked out in the heating mode, and a Y2 or W input is received, the control will operate in the emergency heat mode while the compressor is locked out. The first emergency heat output will be energized 10 seconds after the W input is received, and the blower will shift to high speed. If the control remains locked out, and the W input is present, additional stage of emergency heat will stage on after 2 minutes. When the W input is removed, all of the emergency heat outputs will turn off, and the ECM blower will shift to “G” speed and PSC blower motor output will remain on.
High Pressure – fault is recognized when the Normally Closed High Pressure Switch, P4-9/10 opens, no matter how momentarily. The High Pressure Switch is electrically in series with the Compressor Contactor and serves as a hard­wired limit switch if an overpressure condition should occur.
Low Pressure - fault is recognized when the Normally Closed Low Pressure Switch, P4-7/8 is continuously open for 30 seconds. Closure of the LPS any time during the 30 second recognition time restarts the 30 second continuous open requirement. A continuously open LPS shall not be recognized during the 2 minute startup bypass time.
Loss of Charge – fault is recognized when the Normally Closed Low Pressure Switch, P4-7/8 is open prior to the compressor starting.
Safety Features
The following safety features are provided to protect the compressor, heat exchangers, wiring and other components from damage caused by operation outside of design conditions.
Fuse – a 3 amp automotive type plug-in fuse provides protection against short circuit or overload conditions.
nti-Short Cycle Protection – 4 minute anti-short cycle
protection for the compressor.
Random Start – 5 to 80 second random start upon power up.
Fault Retry – in the fault condition, the control will stage off
the outputs and then “try again” to satisfy the thermostat Y input call. Once the thermostat input calls are satisfied, the control will continue on as if no fault occurred. If 3 consecutive faults occur without satisfying the thermostat Y input call, then the control will go to Lockout mode.
Condensate Overflow - fault is recognized when the impedance between this line and 24 VAC common or chassis ground drops below 100K ohms for 30 seconds continuously.
Freeze Detection (Coax) - set points shall be either 30°F or 15°F. When the thermistor temperature drops below the selected set point, the control shall begin counting down the 30 seconds delay. If the thermistor value rises above the selected set point, then the count should reset. The resistance value must remain below the selected set point for the entire length of the appropriate delay to be recognized as a fault. This fault will be ignored for the initial 2 minutes of the compressor run time.
Freeze Detection (Air Coil) - uses the FP2 input to protect against ice formation on the air coil. The FP2 input will operate exactly like FP1 except that the set point is 30 degrees and is not field adjustable.
30
S
Controls - Aurora Base Control cont.
VERSATEC BASE SERIES INSTALLATION MANUAL
Over/Under Voltage Shutdown - An over/under voltage condition exists when the control voltage is outside the range of 18 VAC to 30 VAC. If the over/under voltage shutdown lasts for 15 minutes, the lockout and alarm relay will be energized. Over/under voltage shutdown is self­resetting in that if the voltage comes back within range of 18 VAC to 30 VAC for at least 0.5 seconds, then normal operation is restored.
Operation Description
Power Up - The unit will not operate until all the inputs and safety controls are checked for normal conditions. The unit has a 5 to 80 second random start delay at power up. Then the compressor has a 4 minute anti-short cycle delay after the random start delay.
tandby In standby mode, Y1, Y2, W, DH, and G are not active. Input O may be active. The blower and compressor will be off.
Heating Operation
Heating, 1st Stage (Y1) - The blower is started on “G” speed immediately and the compressor is energized 10 seconds after the Y1 input is received. The ECM blower motor is switched to low speed 15 seconds after the Y1 input.
Heating, 2nd Stage (Y1, Y2) - The compressor will be staged to full capacity 20 seconds after Y2 input is received. The ECM blower will shift to high speed 15 seconds after the Y2 input is received.
Heating, 3rd Stage (Y1, Y2, W) - The hot water pump is de­energized and the first stage of electric heat is energized 10 seconds after the W command is received. If the demand continues the second stage of electric heat will be energized after 5 minutes.
Emergency Heat (W) - The blower will be started on “G” speed, 10 seconds later the first stage of electric heat will be turned on. 5 seconds after the first stage of electric heat is energized the blower will shift to Aux speed. If the emergency heat demand is not satisfied after 2 minutes the second electric heat stage will be energized.
Blower (G) - The blower will start immediately upon receiving a thermostat G command. If there are no other commands from the thermostat the ECM will run on “G” speed until the G command is removed. Regardless of blower input (G) from the thermostat, the blower will remain on for 30 seconds at the end of each heating cycle.
Cooling Operation
In all cooling operations, the reversing valve directly tracks the O input. Thus, anytime the O input is present, the reversing valve will be energized.
Cooling, 1st Stage (Y1, O) - The blower is started on “G” speed immediately and the compressor is energized 10 seconds after the Y1 input is received. The ECM blower motor is switched to low speed 15 seconds after the Y1 input.
Cooling, 2nd Stage (Y1, Y2, O) - The compressor will be staged to full capacity 20 seconds after Y2 input is received. The ECM blower will shift to high speed 15 seconds after the Y2 input is received.
Blower (G) - The blower will start immediately upon receiving a thermostat G command. If there are no other commands from the thermostat the ECM will run on “G” speed until the G command is removed. Regardless of blower input (G) from the thermostat, the blower will remain on for 30 seconds at the end of each heating, cooling, and emergency heat cycle.
Dehumidification (Y1, O, DH or Y1, Y2, O, DH) - When a DH command is received from the thermostat during a compressor call for cooling the ECM blower speed will be reduced by 15% to increase dehumidification.
Emergency Shutdown - Four (4) seconds after a valid ES input, P2-7 is present, all control outputs will be turned off and remain off until the emergency shutdown input is no longer present. The first time that the compressor is started after the control exits the emergency shutdown mode, there will be an anti-short cycle delay followed by a random start delay. Input must be tied to common to activate.
Continuous Blower Operation - The blower output will be energized any time the control has a G input present, unless the control has an emergency shutdown input present. The blower output will be turned off when G input is removed.
Load Shed - The LS input disables all outputs with the exception of the blower output. When the LS input has been cleared, the anti-short cycle timer and random start timer will be initiated. Input must be tied to common to activate.
31
VERSATEC BASE SERIES INSTALLATION MANUAL
1
2
Controls - Aurora Base Control cont.
Aurora ‘Base’ Control LED Displays
These three LEDs display the status, configuration, and fault codes for the control. These can also be read in plain English via the Aurora AID Tool.
Status LED (LED3, Green)
Description of Operation Fault LED, Green
Normal Mode ON Control is Non-functional OFF Test Mode Slow Flash Lockout Active Fast Flash Dehumidification Mode Flash Code 2 (Future Use) Flash Code 3 (Future Use) Flash Code 4 Load Shed Flash Code 5 ESD Flash Code 6 (Future Use) Flash Code 7
Configuration LED (LED2, Yellow)
Description of Operation Configuration LED, Yellow
No Software Overwritten Flashing ECM Setting DIP Switch was Overwritten Slow Flash ECM Configuration Mode Fast Flash
Fault LED (LED1, Red)
Red Fault LED
LED Flash
Code*
Lockout
Normal - No Faults OFF – Fault - Input 1 No Auto Fault - High Pressure 2 Yes Hard or Soft Fault - Low Pressure 3 Yes Hard or Soft Fault - Freeze Detection FP2 4 Yes Hard or Soft Fault - Freeze Detection FP1 5 Yes Hard or Soft Fault - Condensate Overflow 7 Yes Hard or Soft
ABC Basic Faults
Fault - Over/Under Voltage 8 No Auto Fault - FP1 & FP2 Sensor Error 11 Yes Hard or Soft
NOTE: All codes >11 use long flash for tens digit and short flash for the ones digit. 20, 30, 40, 50, etc. are skipped.
Reset/
Remove
Aurora Interface and Diagnostics (AID) Tool
The Aurora Interface and Diagnostics (AID) Tool is a device that is a member of the Aurora network. The AID Tool is used to troubleshoot equipment which uses the Aurora control via Modbus RTU communication. The AID Tool provides diagnostics, fault management, ECM setup, and system configuration capabilities to the Aurora family of controls. An AID Tool is recommended, although not required, for ECM airflow settings. The AID Tool simply plugs into the exterior of the cabinet in the AID Tool port.
ABC Control Board Layout
5.0 in.
On
o
F/30
FP1 – 15
o
F/30oF
FP2 – 15
RV – B/O ACC – Dip ACC – Dip
Reheat/Normal
Control
C
G
O/B
Field ConnectionsField Connections
C
G
O/B
Off
LED 2
o
1
F
2
YR
3
Config
4 5 6 7 8
SW2
Com1
Com2
W
Y1
Y2
DH
W
Y1
Y2
DH
LED 5
LED 4
3A-Fuse
G
G
RR
P3
P6
RS485
P7
P8
EH1
EH2
C
EH1
C
Factory
CO
N/A
(+)
(-) R
Exp
C
(+)
(-) R
RS 485
C
RS485 NET
CC C
6.25 in.
C
CFM
PWM
HP HP LP
LP FP2 FP2 FP1 FP1
REV REV
CC2
G
LO
CC2
HI
CCG
CC
FG
F R
F
CC
G
Y1
P4
Factory
P5
Factory
JW2 - Alarm
P2
ES
ECM PWM
P13
SW1 Test
RV – K1
CC – K2
CC Hi – K3
Fan – K4
Alarm – K5
Acc – K6
LS
ALG
ALM
ACC c
ACC no
LED 3
ACC nc
LED 1
Fault
CC – Dual/Single
G
L – Pulse/Continuous
Status
AuroraTM Base
Factory Use
P11
P9
Factory Fan Connection
R
LO
P1
R
LO
5.75 in.
5.5 in.
32
VERSATEC BASE SERIES INSTALLATION MANUAL

Controls - UPC DDC Control (optional)

Aurora UPC Controller ZS Series Sensors
The Aurora Unitary Protocol Converter (UPC) is designed to add-on to any Aurora based heat pump control. The Aurora Unitary Protocol Convertor (UPC) is designed to allow water source heat pumps to be integrated into Building Automation Systems (BAS) with ease. The Aurora UPC is an integrated solution and communicates directly with the Aurora Heat Pump Controls and allows access/control of a variety of internal Aurora heat pump operations such as sensors, relay operation, faults and other information. In turn, the UPC then converts internal Aurora Modbus protocol to BACnet MS/TP, LON, or N2 protocols and communicates to the BAS system. This provides the great benefit of complete control integration and a myriad of information available to the BAS from the heat pump control. Plus it also allows individual unit configuration such as ECM fan speeds or freeze protection setting directly over the BAS without the need for access to the actual heat pump. The Aurora UPC is programmed using the powerful Eikon object oriented.
The Aurora UPC is implemented with the Aurora Base Controller (ABC) heat pump control into our latest water source heat pumps. This will allow for a BAS to integrate
and communicate to the heat pump thru a choice of 3 different communication protocols. The Aurora UPC has the ability to communicate BACnet MS/TP, N2 open, or LonWorks (requires LON Plugin card). This flexibility is possible due to the onboard dipswitches which allow for the desired protocol and baud rate to be selected in the field. All zone temperatures and zone sensors are connected to the UPC on an RNet bus, simplifying hook up at the unit. RNet sensors can include a combination of zone temperature and humidity, CO2, and VOC sensors. The UPC includes built-in support for a custom configurable keypad/display unit - BACview6 (4-line by 40 character per line display) or BACview5 (2-line by 16 character per line display). Up to 2 Keypad/display units can be mounted remotely for configuration and troubleshooting.
There are an extensive number of points that the UPC has available over the network for integration into the BAS. Control programmers need to carefully determine which points they want to add into the BAS database. A list of the BACnet points, N2 points, and LON SNVTs are available along with their individual point descriptions by contacting the Commercial Solutions Group at 1-877-677-4420.
33
VERSATEC BASE SERIES INSTALLATION MANUAL
Controls - UPC DDC Control (optional) cont.
N2
BAS
BACnet
LonWorks
Aurora UPC Features
• Rugged enclosure made of GE C2950 Cycoloy plastic
• Built-in surge transient protection circuitry
• Operating range of -20° to 140°F; 10 to 95% relative hu­midity, non-condensing
• Onboard CR123A battery has a life of 10 years with 720 hours of cumulative power outage
• Multi-Protocol field selectable communication port that supports:
• EIA-485 BACnet MS/TP @ 9600, 19.2k, 38.4k, 76.8k baud
• Metasys N2 Open
• LonWorks TP/FT-10 (Requires optional LON plug-in
communication card)
• Status of all unit operating conditions and fault lockouts
• Visual LED’s for status of power, network communication, processor operation, and errors
• Provides gateway into Aurora heat pump controls for unsurpassed control flexibility
• Network point for commanding unit into load shed
• Network point for commanding unit into
emergency shutdown
• Network points to assist in fan speed selection
• Network points for freeze protection settings
• Heating and cooling control from a remotely located zone sensor
• Rnet communication port which allows for multiple Rnet zone sensors (5) to be connected for space temperature averaging if desired.
• Local laptop or BACview connection for field service
• FCC, UL and CE listed. BTL Certification is pending
Modbus
Rnet
Aurora UPC Optional Features
• BACview handheld display, needed for field configuration of fan speeds, set points, etc.
• AID Tool for Aurora ABC configuration and troubleshooting.
• Aurora Advanced Control adds the Aurora AXB expansion board and provides added I/O and standard features
• Optional Sensor Kits (requires Aurora Advanced Control with AXB - Future Availability on Select Models/Configurations)
• Refrigeration Monitoring – provides Suction and
discharge pressure, Suction, liquid line temps and superheat and subcooling.
• Performance Monitoring – provides entering and
leaving loop water temperatures, loop flow rate as well as heat of extraction or rejection rate into the loop.
• Energy Monitoring – provides real-time power
measurement (Watt) of compressor, fan, auxiliary heat and zone pump.
• Graphics packages available in the future
34
VERSATEC BASE SERIES INSTALLATION MANUAL
Controls - UPC DDC Control (optional) cont.
Port 1a is used to
communicate to the
Building Automation
System (BAS). This
port’s settings are
configured through
the onboard dip
switches.
Port 2 is used to com-
municate to the Au­rora Base Controller
(ABC).
Port 1b is used for the
LonWorks plugin.
24Vac
Dip switches for configuring the communication port protocol and baud rate for the BAS port.
Rnet port is used
for communicating
zone sensors.
BACview or local
laptop connection.
Aurora Touch Interface
Utilizing a touch-screen interface, the UPC provides a technician the ability to configure and diagnose equipment at the unit or from any room sensor for added accessibility and simpler troubleshooting. The technician will have full access to equipment status, parameter values, temperature, and humidity sensing as well as access to alarm and trend history. With website-like navigation, the Auora Touch Interface is easy to use and provides important insight into the system so your building can operate as efficiently as possible.
Mac address is set by 2 rotary dials.
35
VERSATEC BASE SERIES INSTALLATION MANUAL
Controls - UPC DDC Control (optional) cont.
1. Leaving Air Temperature (LAT) Sensor – This 10 kOhm NTC sensor is factory installed on all UPC equipped heat pumps. It typically is attached to wiring inside the blower cabinet on the suction side of the blower. This sensor is attached on ABC FP2 pins available as LAT AU-30.
1. Compressor Proving Sensors – This optional factory installed current sensor is connected to confirm compressor operation via the power wires. The sensor is attached at ABC Y1 and available at point BV-65.
1. Valve End Switch – This optional input is setup for a field installed flow valve end switch. This end switch input is attached at ABC Y2 and available at point BV-67.
1. Fan Proving Sensors – This optional factory installed current sensor is connected to confirm fan operation via the power wires. The sensor is attached at ABC G and available at point BV-33.
1. Occupancy Sensor - This standard feature includes a field installed and wired room sensor with occupancy sensor typically found in DDC systems. The RNet room sensors can be found thru your commercial representative. The occupancy Sensors are attached at ABC 0 and can be found at point BV-49.
1. Dirty Filter Switch –
This optional field installed switch is connected to confirm dirty filter operation. The dirty filter switch can be found thru your commercial representative. The sensor is attached at ABC W and available at point BV-63.
2. Fault, Configuration, and Status Codes – The codes can be visible to the BAS if desired
Aurora Base Fault Codes (ABC Only)
Fault LED (LED1, Red)
Red Fault LED
Normal - No Faults OFF – Fault - Input 1 No Auto Fault - High Pressure 2 Yes Hard or Soft Fault - Low Pressure 3 Yes Hard or Soft Fault - Freeze Detection FP2 4 Yes Hard or Soft Fault - Freeze Detection FP1 5 Yes Hard or Soft Fault - Condensate Overflow 7 Yes Hard or Soft
ABC Basic Faults
Fault - Over/Under Voltage 8 No Auto Fault - FP1 & FP2 Sensor Error 11 Yes Hard or Soft
NOTE: All codes >11 use long flash for tens digit and short flash for the ones digit. 20, 30, 40, 50, etc. are skipped.
LED Flash
Code*
Lockout
Reset/
Remove
Aurora Advanced Fault Codes (ABC + AXB Expansion Board)
Fault LED (LED1, Red)
Red Fault LED
Normal - No Faults Off ­Fault-Input 1 No Auto Tstat input error. Autoreset upon condition removal. Fault-High Pressure 2 Yes Hard or Soft HP switch has tripped (>600 psi) Fault-Low Pressure 3 Yes Hard or Soft Low Pressure Switch has tripped (<40 psi for 30 continuous sec.) Fault-Freeze Detection FP2 4 Yes Hard or Soft Freeze protection sensor has tripped (<15 or 30 degF for 30 continuous sec.) Fault-Freeze Detection FP1 5 Yes Hard or Soft Freeze protection sensor has tripped (<15 or 30 degF for 30 continuous sec.) Fault-Condensate Overflow 7 Yes Hard or Soft Condensate switch has shown continuity for 30 continuous sec.
ABC Basic Faults
Fault-Over/Under Voltage 8 No Auto Instantaneous voltage is out of range. **Controls shut down until resolved. Fault-FP1 & 2 Snsr Error 11 Yes Hard or Soft If FP1 or 2 Sensor Error Fault-Compressor Monitor 10 Yes Hard or Soft Open Crkt, Run, Start or welded cont Non-CriticAXBSnsrErr 13 No Auto Any Other Sensor Error CriticAXBSnsrErr 14 Yes Hard or Soft Sensor Error for EEV or HW Alert-HotWtr 15 No Auto HW over limit or logic lockout. HW pump deactivated. Fault-VarSpdPump 16 No Auto Alert is read from PWM feedback. Not Used 17 No Auto IZ2 Com Fault. Autoreset upon condition removal. Non-CritComErr 18 No Auto Any non-critical com error Fault-CritComErr 19 No Auto Any critical com error. Auto reset upon condition removal Alarm - Low Loop Pressure 21 No Auto Loop pressure is below 3 psi for more than 3 minutes Alarm - Home Automation 1 23 No Auto Closed contact input is present on Dig 2 input - Text is configurable
ABC & AXB Advanced Faults
Alarm - Home Automation 2 24 No Auto Closed contact input is present on Dig 3 input - Text is configurable
NOTES: *All codes >11 use long flash for tens digit and short flash for the ones digit. 20, 30, 40, 50 etc. are skipped! Alert’ is a noncritical sensor or function that has failed. Normal operation of the heat pump is maintained but service is desired at some point.
LED Flash
Code *
Lockout
Reset/
Remove
Fault Condition Summary
36
VERSATEC BASE SERIES INSTALLATION MANUAL
Controls - UPC DDC Control (optional) cont.
Aurora Base or Advanced Control Configuration and Status Codes
Status LED (LED3, Green)
Description of Operation Fault LED, Green
Normal Mode ON Control is Non-functional OFF Test Mode Slow Flash Lockout Active Fast Flash Dehumidification Mode Flash Code 2 Load Shed Flash Code 5 Emergency Shutdown Flash Code 6 On Peak Mode Flash Code 7 (Future Use) Flash Code 8 (Future Use) Flach Code 9
Configuration LED (LED2, Yellow)
Description of Operation Configuration LED, Yellow
No Software Overwritten ECM Setting DIP Switch Overwritten Slow Flash ECM Configuration Mode Fast Flash Reset Configuration Mode OFF
9. Alarm Relay – The Alarm relay (ALM) is factory connected to 24 VAC via jumper JW2. By cutting JW2, ABC ALM becomes a dry contact connected to ABC ALG. The Relay is field switchable between Factory setting as an Alarm output or available for other uses.
10. Accessory Relay1 –
A configurable, accessory relay on the ABC is provided that can be cycled with the compressor, blower, or the Dehumidifier (DH) input. A third (factory) setting cycles the relay with the compressor but delays the compressor and blower output for 90 sec. Source pump or slow opening solenoid valves in well systems or variable speed primary pumping systems would be a prime use of this feature.
Access Relay Operation SW2-4 SW2-5
Cycle with Blower ON ON
Cycle with Compressor OFF OFF
Water Valve Slow Opening ON OFF
Cycle with Comm. T-stat Hum Cmd OFF ON
11.
Electric Heat EH1 – A digital 24VDC output is provided
for electric heat powering. UPC’s Default programming has EH1 set for AUX/ELEC Heat operation and will be controlled using the UPC’s internal P.I.D. logic. However it can be changed by the BAS to be network controlled.
12. Electric Heat EH2 – A digital VDC output is provided for field options converted from the original EH2 output. Default UPC program has the EH2 output set for Network Control but can be changed by the BAS to be controlled by the UPC’s internal P.I.D. logic.
37
VERSATEC BASE SERIES INSTALLATION MANUAL
2
3
Controls - UPC DDC Control (optional) cont.
Aurora Advanced Control Configuration and Options (Future Availability on Select Models/Configurations)
1. Accessory Relay2 – A second, configurable, accessory relay on the AXB is provided that can be cycled with the compressor 1 or 2 , blower, or the Dehumidifier (DH) input. This is to complement the Accessory 1 Relay on the ABC board.
Position DIP 4 DIP 5 Description
1 ON ON Cycles with Fan or ECM (or G)
2 OFF ON
3 ON OFF
4 OFF OFF Cycles with DH input from ABC board
. Analog Out – A standard 0-10VDC analog output is
provided. This output can be used to drive modulat­ing dampers etc.
. Variable Speed Pump or Modulating Water Valve
- This input and output are provided to drive and
monitor a variable speed pump. The VS pump output is a PWM signal to drive the variable speed pump. The minimum and maximum level are set using the AID Tool. 75% and 100% are the default settings respec­tively. The VS data input allows a separate PWM signal to return from the pump giving fault and performance information. Fault received from the variable speed pump will be displayed as E16. Modulating Water Valve - This Variable speed PWM output is provided to optionally drive a modulating water valve. Through ad­vanced design a 0-10VDC valve can be driven directly from the VS pump output. The minimum and maxi­mum level are set in the same way as the VS pump using the AID Tool. 75% and 100% are the default set­tings respectively.
4. Loop Pump Slaving - This input and output are pro­vided so that two units can be slaved together with a common flow center. When either unit has a call for loop pump, both unit’s loop pump relays and variable speed pumps are energized. The flow center then can simply be wired to either unit. The output from one unit should be routed to the input of the other. If daisy chained up to 16 heat pumps can be wired and slaved together in this fashion.
Cycles with CC1 first stage of compressor
or compressor spd 1-12
Cycles with CC2 second stage of
compressor or compressor spd 7-12
38
VERSATEC BASE SERIES INSTALLATION MANUAL
2
Controls - UPC DDC Control (optional) cont.
Aurora Advanced Control Optional Sensor Kits (Future Availability on Select Models/Configurations)
1. Energy Monitoring (Standard Sensor Kit on
‘Advanced’ models) - The Energy Monitoring Kit
includes two current transducers (blower and electric heat) added to the existing two compressor sensors so that the complete power usage of the heat pump can be measured. The BACview Tool provides configuration detail for the type of blower motor and a line voltage calibration procedure to improve the accuracy. This real time power usage information can be displayed on the AID Tool and is available thru network points when using BACnet or N2 Open.
Compressor Current 1
Compressor Current 2
• Fan Current
Aux Heat Current
• Pump Selection
• Voltage
• Compressor Watts
• Fan Watts
Aux Heat Watts
Pump Watts (VS Only)
. Refrigerant Monitoring (optional sensor kit) - The
optional Refrigerant Monitoring Kit includes two pressure transducers, and three temperature sensors, heating liquid line, suction temperature and existing cooling liquid line (FP1). These sensors allow the measurement of discharge and suction pressures, suction and liquid line temperatures as well as superheat and subcooling. This information can be displayed on the BACview Tool, or the network when using BACnet and N2.
Htg Liquid Line
Clg Liquid Line
• Discharge pressure
• Suction Pressure
Discharge Saturated Temp
Suction Saturated Temperature
• Superheat
• SubCooling
3. Performance Monitoring (optional sensor kit) - The optional Performance Monitoring Kit includes: three temperature sensors, entering and leaving water, leaving air temperature and a water flow rate sensor. With this kit, heat of extraction and rejection will be calculated. This requires configuration using the BACview
Leaving Air Temperature (supply)
Alt Leaving Air Temperature (Supply)
Entering Water Temperature
Leaving Water Temperature
Water Flow Meter
Entering Air Temperature (from zone sensor)
Brine Selection (water/antifreeze)
Heat of Extraction/Rejection
Tool for selection of water or antifreeze.
39
VERSATEC BASE SERIES INSTALLATION MANUAL
Controls - UPC DDC Control (optional) cont.
ZS Series RNet Sensor Overview
The ZS Series line of intelligent zone sensors provides the function and flexibility you need to manage the conditions important to the comfort and productivity of the zone occupants. The ZS sensors are available in a variety of zone sensing combinations to address your application needs. These combinations include temperature, relative humidity, and indoor air quality (carbon dioxide or VOCs (Volatile Organic Compounds)). They are built to be flexible allowing for easy customization of what the user/ technician sees. Designed to work with the Aurora UPC controllers the ZS sensor line includes the ZS Base, ZS Plus, ZS Pro and ZS Pro-F.
The UPC uses a proprietary communication called Rnet to receive the space temperature from the zone sensor.
ZS Base
ZS Plus ZS Pro
This is done using (2) 18 AWG twisted pair unshielded cables for a total of 4 wires connected to the Rnet port. The sensor gets its power from the UPC controller and connecting multiple sensors to one UPC will allow for space temperature averaging. The UPC can support one ZS Pro or ZS Pro F with up to four ZS standard sensors wired to the Rnet port on the UPC for a total of 5 zone sensors. The sensors use a precise 10k ohm thermistor with less than 0.18°F drift over a ten year span, this allows for less maintenance or re-calibration after installation. The sensors also have a hidden communication port for connecting a BACview or local laptop that provides access to the equipment for commissioning and maintenance. The table below shows the features of each of the four sensors that are currently available.
ZS Pro-F
Features ZS Base ZS Plus ZS Pro ZS Pro-F
2
Temp, CO
Neutral Color
Addressable/supports daisy chaining
Hidden communication port
Mounts on a standard 2” by 4” electrical box
Occupancy Status indicator LED
Push button occupancy override
Setpoint adjust
Large, easy to read LCD
Alarm indicator
°F to °C conversion button
Options Part Number Part Number Part Number Part Number
Temperature Only ZSU ZSUPL ZSUP ZSUPF
Temp with CO
Temp with Humidity ZSU-H ZSUPL-H ZSUP-H ZSUPF-H
Temp with Humidity, CO
Temp, Humidity, VOC ZSU-HV ZSUPL-HV ZSUP-HV ZSUPF-HV
Temp with VOC ZSU-V ZSUPL-V ZSUP-V ZSUPF-V
, Humidity, and VOC Options
2
2
√√√√
√√√√
√√√√
√√√√
√√√√
√√√
√√√
√√√
√√
√√
ZSU-C ZSUPL-C ZSUP-C ZSUPF-C
ZSU-HC ZSUPL-HC ZSUP-HC ZSUPF-HC
40
VERSATEC BASE SERIES INSTALLATION MANUAL
Controls - UPC DDC Control (optional) cont.
RNet Sensor Physical and Electrical Data
Sensing Element Range Accuracy
Temperature (on non-Humidity models) -4° to 122° F (-20° C to 50° C) ±0.35° F (0.2° C)
Temperature (on Humidity models) 50° F to 104° F (10° C to 40° C) ±0.5° F (0.3° C)
Humidity 10% to 90% ±1.8% typical
CO2
VOC 0 to 2,000 PPM ±100 PPM
Power Requirements Sensor Type Power Required
Temperature Only All Models 12 Vdc @ 8 mA
Temperature with Humidity All Models
Temp with VOC, or Temp/VOC/Humidity All Models 12 Vdc @ 60 mA
Temp with CO2 , or Temp/ CO2/Humidity All Models
Power Supply
Communication
Local Access Port
Environmental Operating Range
Mounting Dimensions
400 to 1250 PPM
1250 to 2000 PPM
A controller supplies the Rnet sensor network with 12 Vdc @ 210 mA. Additional
power may be required for your application. See sensor ZS Installation Guide
115 kbps Rnet connection between sensor(s) and controller
15 sensors max per Rnet network; 5 sensors max per control program
For connecting a laptop computer to the local equipment for maintenance and commissioning
32° to 122° F (0° - 50° C), 10% to 90% relative humidity, non-condensing
Standard 4”x 2” electrical box using provided 6/32” x 1/2” mounting screws
±30PPM or +/-3% of reading (greater of two)
±5% of reading plus 30 PPM
12 Vdc @ 15 mA (idle) to 190 mA
(CO2 measurement cycle)
12 Vdc @ 15 mA (idle) to 190 mA
(CO2 measurement cycle)
41
VERSATEC BASE SERIES INSTALLATION MANUAL

Unit Startup

Before Powering Unit, Check The Following:
NOTE: Remove and discard the compressor shipping bolts. The bolts can then be discarded.
• High voltage is correct and matches nameplate.
• Fuses, breakers and wire size correct.
• Low voltage wiring complete.
• Piping completed and water system cleaned and flushed.
• Air is purged from closed loop system.
• Isolation valves are open, water control valves or loop pumps wired.
• Condensate line open and correctly pitched.
• Transformer switched to 208V if applicable.
• Dip switches are set correctly.
• Blower rotates freely – foam shipping support has been removed.
• Blower speed correct.
• Air filter/cleaner is clean and in position.
• Service/access panels are in place.
• Return air temperature is between 50-80°F heating and 60-95°F cooling.
• Check air coil cleanliness to insure optimum performance. Clean as needed according to maintenance guidelines. To obtain maximum performance the air coil should be cleaned before startup. A 10-percent solution of dishwasher detergent and water is recommended for both sides of coil, a thorough water rinse should follow.
Startup Steps
NOTE: Complete the Equipment Start-Up/Commissioning Check Sheet during this procedure. Refer to thermostat
operating instructions and complete the startup procedure.
1. Initiate a control signal to energize the blower motor. Check blower operation.
2. Initiate a control signal to place the unit in the cooling mode. Cooling setpoint must be set below room temperature.
3. Cooling will energize after a time delay. Check for correct rotation of scroll compressors in 3 phase applications. Incorrect rotation will cause low refrigerant pressures and possibly unusual noise. Switch any two power leads at the compressor or contactor to reverse rotation.
4. Be sure that the compressor and water control valve or loop pump(s) are activated.
5. Verify that the water flow rate is correct by measuring the pressure drop through the heat exchanger using the P/T plugs and comparing to the pressure drop table.
6. Check the temperature of both the supply and discharge water (Refer to Operating Parameters tables).
7. Check for an air temperature drop of 15°F to 25°F across the air coil, depending on the blower speed and entering water temperature.
8. Decrease the cooling set point several degrees and verify high-speed blower operation (variable speed ECM only).
9. Adjust the cooling setpoint above the room temperature and verify that the compressor and water valve or loop pumps deactivate.
10. Initiate a control signal to place the unit in the heating mode. Heating set point must be set above room temperature.
11. Heating will energize after a time delay.
12. Check the temperature of both the supply and discharge water (Refer to Unit Operating Parameters tables).
13. Check for an air temperature rise of 20°F to 35°F across the air coil, depending on the blower speed and entering water temperature.
14. If auxiliary electric heaters are installed, increase the heating setpoint until the electric heat banks are sequenced on. All stages of the auxiliary heater should be sequenced on when the thermostat is in the Emergency Heat mode. Check amperage of each element.
15. Adjust the heating setpoint below room temperature and verify that the compressor and water valve or loop pumps deactivate.
16. During all testing, check for excessive vibration, noise or water leaks. Correct or repair as required.
17. Set system to desired normal operating mode and set temperature to maintain desired comfort level.
18. Instruct the owner/operator in the proper operation of the thermostat and system maintenance.
NOTE: Be certain to fill out and forward all warranty registration papers.
42

Operating Parameters

VERSATEC BASE SERIES INSTALLATION MANUAL
Entering Water
Temp °F
30
50
70
90
110
Entering Water
Temp °F
30
50
70
90
110
NOTES: Cooling performance based on entering air temperatures of 80°F DB, 67°F WB.
Heating performance based on entering air temperature of 70°F DB.
Water Flow
gpm/ton
1.5 100-115 170-190 17 - 26 10 - 14 18 - 22 18 - 22
3.0 95-110 150-170 20 - 29 7 - 11 8 - 10 18 - 22
1.5 133 - 148 205 - 225 17 - 26 10 - 14 18 - 22 18 - 22
3.0 129 - 144 185 - 205 20 - 29 7 - 11 8 - 10 18 - 22
1.5 139 - 154 280 - 300 8 - 11 8 -12 18 - 22 18 - 22
3.0 137 - 152 250 - 270 9 - 12 7 - 11 8 - 10 18 - 22
1.5 143 - 158 360 - 380 8 - 11 9 - 13 18 - 22 16 - 20
3.0 141 - 156 330 - 350 9 - 12 8 - 12 8 - 10 16 - 20
2.3 143 - 158 360 - 380 8 - 11 9 - 13 18 - 22 16 - 20
3.0 141 - 156 440-460 9 - 12 8 - 12 8 - 10 16 - 20
Water Flow
gpm/ton
1.5 73 - 79 279 - 304 7 - 13 2 - 6 7 -10 18 - 24
3.0 79 - 85 285 - 310 8 - 14 2 - 6 3 - 6 20 - 26
1.5 103 - 109 308 - 333 8 - 12 4 - 8 8 - 11 20 - 26
3.0 110 - 116 315 - 340 9 - 13 4 - 8 4 - 7 22 - 28
1.5 140 - 146 330 - 365 10 - 14 7 - 11 11 - 14 26 - 32
3.0 146 - 153 340 - 375 10 - 14 7 - 11 7 - 10 28 - 34
1.5 170-177 425-460 14-18 12-16 8-11 42-50
3.0 174-181 435-470 14-18 12-16 8-11 42-50
2.3
3.0
Suction
Pressure psig
Suction
Pressure psig
Discharge
Pressure psig
Discharge
Pressure psig
Superheat Subcooling
Superheat Subcooling
Cooling
Heating
Water Temp
Rise °F
Water Temp
Drop °F
Air Temp Drop
°F DB
Air Temp Rise
°F DB
5/1/11

Operating Limits

Operating Limits
Air Limits
Min. Ambient Air 45 7.2 45 7.2 Rated Ambient Air 80 26.7 70 21.1 Max. Ambient Air 100 37.8 85 29.4 Min. Entering Air 50 10.0 40 4.4 Rated Entering Air db/wb 80.6/66.2 27/19 68 20.0 Max. Entering Air db/wb 110/83 43/28.3 80 26.7
Water Limits
Min. Entering Water 30 -1.1 20 -6.7 Normal Entering Water 50-110 10-43.3 30-70 -1.1 Max. Entering Water 120 48.9 90 32.2
Cooling Heating
(°F) (°C) (°F) (°C)
NOTE: Minimum/maximum limits are only for start-up conditions, and
are meant for bringing the space up to occupancy temperature. Units are not designed to operate at the minimum/maximum conditions on a regular basis. The operating limits are dependent upon three primary factors: 1) water temperature, 2) return air temperature, and 3) ambient temperature. When any of the factors are at the minimum or maximum levels, the other two factors must be at the normal level for proper and reliable unit operation.
43
VERSATEC BASE SERIES INSTALLATION MANUAL

Pressure Drop

Model GPM
1.0 1.2 1.2 1.1 1.0 1.0
006
009
012
015
018
024
030
036
042
048
060
070
1.5 2.2 2.0 1.9 1.8 1.7
2.0 3.3 3.1 2.9 2.7 2.5
2.5 4.1 3.8 3.4 3.1 2.9
1.5 1.9 1.7 1.5 1.3 1.1
2.0 3.0 2.8 2.6 2.4 2.2
3.0 6.3 6.3 6.1 5.9 5.7
4.0 8.1 7.9 7.4 6.8 6.1
1.5 1.1 1.1 1.0 0.9 0.9
2.5 2.4 2.3 2.2 2.0 1.9
3.5 4.2 4.0 3.7 3.4 3.2
4.5 6.1 5.9 5.2 4.7 4.1
2.0 1.8 1.7 1.6 1.4 1.2
3.0 3.3 3.1 2.9 2.6 2.3 4.0 10.1 0.16
4.0 5.0 4.9 4.8 4.7 4.6 5.0 10.4 0.23
5.0 7.1 6.7 5.9 5.4 5.1 6.0 10.6 0.32
3.0 3.3 3.2 3.0 2.8 2.6
4.0 4.7 4.2 3.9 3.6 3.1 4.0 10.1 0.16
5.0 6.2 5.2 4.7 4.1 3.5 5.0 10.4 0.23
6.0 7.7 6.2 5.4 4.6 3.8 6.0 10.6 0.32
3.0 3.2 3.1 2.9 2.7 2.5
4.5 6.1 5.5 4.9 4.5 4.2 4.5 10.2 0.19
6.0 9.0 7.9 6.9 6.3 5.8 6.0 10.6 0.32
8.0 12.9 10.9 9.5 8.8 7.9 8.0 11.0 0.53
4.0 2.4 2.3 2.2 2.0 1.8
6.0 5.1 4.9 4.7 4.5 4.3 6.0 10.6 0.32
8.0 7.8 7.5 7.1 6.9 6.7 8.0 11.0 0.53
10.0 10.5 10.1 9.6 9.3 8.9 10.0 11.5 0.76
5.0 2.0 1.9 1.7 1.5 1.4
7.0 3.6 3.5 3.3 3.1 2.9 7.0 10.8 0.42
9.0 5.2 5.1 4.8 4.6 4.4 9.0 11.2 0.64
12.0 7.5 7.4 7.1 6.9 6.7 12.0 11.9 1.02
5.0 2.1 2.0 1.8 1.6 1.4
8.0 4.8 4.7 4.5 4.4 4.2 8.0 11.0 0.53
11.0 7.5 7.4 7.0 6.6 6.1 11.0 11.7 0.89
14.0 10.1 9.9 9.6 8.8 8.1 14.0 12.3 1.29
6.0 2.7 2.6 2.4 2.2 2.0
9.0 6.0 5.9 5.4 5.2 5.1 9.0 11.2 0.64
12.0 9.5 9.3 8.5 8.3 8.1 12.0 11.9 1.02
16.0 14.2 13.9 12.7 12.3 12.1 16.0 12.8 1.57
9.0 4.5 4.4 4.2 4.0 3.8
12.0 6.5 6.3 6.1 5.9 5.7 12.0 17.4 0.47
15.0 8.6 8.1 7.9 7.7 7.5 15.0 18.1 0.69
20.0 12.1 11.2 10.8 10.6 10.4 20.0 19.2 1.09
12.0 5.7 5.6 5.4 5.2 5.0
15.0 8.9 8.6 8.2 7.7 6.7 15.0 18.1 0.69
18.0 12.0 11.5 11.0 10.1 8.4 18.0 18.7 0.92
24.0 17.4 16.9 16.5 15.1 11.8 24.0 20.1 1.43
Pressure Drop (psi)
30°F 50°F 70°F 90°F 110°F
9/5/12 9/5/12
Valve GPM Cv
Internally mounted 2-position solenoid water
valves are not available on models 006-012
3.0 9.9 0.09
1/2”
3.0 9.9 0.09
1/2”
3.0 9.9 0.09
3/4”
4.0 10.1 0.16
3/4”
5.0 10.4 0.23
3/4”
5.0 10.4 0.23
3/4”
6.0 10.6 0.32
3/4”
9.0 16.8 0.29
1”
12.0 17.4 0.47
1”
Pressure
Drop (psi)
44
VERSATEC BASE SERIES INSTALLATION MANUAL

Compressor and Thermistor Resistance

Compressor Resistance
Model
006 009
012 015 018
024 030 036 042 048
060
070
Thermistor Resistance
Thermistor
Temperature (°F)
5 72,950 14 55,330 23 42,330 32 32,650 41 25,390
50 19,900
59 15,710 68 12,490 77 10,000 86 8,057 95 6,530
104 5,327
113 4,370 122 3,603
131 2,986 140 2,488 149 2,083
115/60/1 208-230/60/1 265/60/1
Run Start Run Start Run Start
1.25-1.43 2.70-3.10 5.30-6.09 5.12-5.89 8.33-9.59 4.25-4.89
0.77-0.89 1.79-2.05 3.65-4.19 3.75-4.31 3.73-4.27 4.45-5.13
Not Available at Time of Publication
Microprocessor
Resistance (Ohms)
3.35-3.85 2.80-3.22 3.73-4.27 4.45-5.13
2.74-3.16 2.60-3.00 3.03-3.49 2.39-2.75
2.24-2.58 2.84-3.26 3.03-3.49 2.39-2.75
1.36-1.50 2.26-2.50 1.33-1.47 2.34-2.58 1.29-1.43 5.06-5.6
0.93-1.03 1.64-1.82 1.33-1.47 2.34-2.58 1.29-1.43 5.06-5.6
0.60-0.66 1.20-1.32 0.76-0.84 1.67-1.85 1.09-1.21 4.38-4.84
0.49-0.55 1.56-1.73 1.09-1.21 4.38-4.84 6.88-7.60
0.51-0.57 1.58-1.74 0.88-0.97 3.41-3.77 5.39-5.96
0.43-0.48 1.33-1.47 0.88-0.97 2.78-3.07 5.39-5.96
0.35-0.40 1.34-1.54 0.71-081 2.72-3.13 4.27-4.92
5/1/11
208-230/60/3
460/60/3 575/60/4
09/26/12

Refrigerant Circuit Guideline

Symptom
Under Charged System (Possible Leak) Low Low Low High Low Low Low Over Charged System High High High Normal High Normal/Low Normal Low Air Flow Heating High High High High/Normal Low High Low Low Air Flow Cooling Low Low Low Low/Normal High High Low Low Water Flow Heating Low/Normal Low/Normal Low Low High Low High Low Water Flow Cooling High High High High Low Low High High Air Flow Heating Low Low Low Low High Low Low High Air Flow Cooling Low High Normal High Low Low Normal High Water Flow Heating Normal Low Normal High Normal Normal Low High Water Flow Cooling Low Low Low Low High Normal Low Low Indoor Air Temperature Heating Low Low Low Normal High Normal Normal/High Low Indoor Air Temperature Cooling Low Low Low Normal/Low High Low Low High Indoor Air Temperature Heating High High High Normal/High Normal/Low Low Normal High Indoor Air Temperature Cooling High High High High Low Low High Restricted TXV (Check Service Advisory) High Low Normal/Low High High Low Low Insufficient Compressor (Possible Bad Valves) Low High Low High Normal/High Low Low TXV - Bulb Loss of Charge Low Low Low High High Low Low Scaled Coaxial Heat Exchanger Heating Low Low Low Normal/Low High Low Low Scaled Coaxial Heat Exchanger Cooling High High High Normal/Low Low Low Low Restricted Filter Drier Check temperature difference (delta T) across filter drier.
Head
Pressure
Suction
Pressure
Compressor
Amp Draw
45
Superheat Subcooling
Air Temp.
Differential
Water Temp.
Differential
7/ 6/ 1 0
VERSATEC BASE SERIES INSTALLATION MANUAL

Heat of Extraction/Rejection Data

Model gpm
1.0 4.6 6.0 7.5 10.2 9.2 13.5
006
009
012
015
018
024
030
036
042
048
060
070
Values displayed in MBtu/h 09/26/12
1.5 3.6 4.7 6.1 7.7 9.8 10.1 9.3 13.3 8.2
2.0 3.1 4.8 6.2 7.8 9.8 10.1 9.3 13.2 8.3
1.5 6.2 7.7 10.0 11.9 11.1 10.1
2.0 5.0 6.3 7.9 10.2 11.8 11.9 11.0 10.1 9.3
3.0 4.8 6.5 8.2 10.4 11.9 12.0 10.9 10.2 9.4
1.5 8.0 9.9 13.3 15.2 14.6 13.6
2.5 6.6 8.4 10.4 13.5 14.6 15.1 14.7 13.6 11.6
3.5 6.4 8.7 10.9 13.7 14.7 15.0 14.8 13.6 11.7
2.0 9.2 11.5 13.4 18.9 18.0 17.0
3.0 7.7 9.5 11.8 13.6 19.2 19.0 18.1 17.1 15.5
4.0 7.2 9.9 12.1 13.8 19.3 19.1 18.2 17.2 15.6
3.0 11.4 14.6 16.2 25.4 24.0 22.7
4.0 9.2 11.7 14.7 16.5 25.2 25.1 23.6 22.7 21.7
5.0 8.9 11.9 14.8 16.8 25.3 24.9 23.3 22.9 21.8
3.0 15.9 20.2 22.5 32.6 30.8 28.8
4.5 13.2 16.5 20.5 22.9 33.1 33.0 31.3 28.8 26.1
6.0 11.9 17.2 20.8 23.3 33.3 33.4 31.7 29.1 26.3
4.0 19.9 25.4 31.0 39.9 37.4 34.8
6.0 16.1 20.7 26.5 31.5 39.0 40.3 37.7 34.8 31.4
8.0 14.5 21.6 27.6 32.0 39.2 40.7 38.1 35.2 31.6
5.0 24.8 32.3 38.1 48.6 46.4 43.0
7.0 20.0 25.9 33.4 38.7 46.7 48.7 46.8 43.1 39.3
9.0 18.4 27.0 34.6 39.3 46.9 48.8 47.1 43.5 39.6
5.0 28.1 37.3 47.4 57.0 52.9 68.6
8.0 22.8 29.9 39.0 48.2 54.7 57.6 53.4 68.7 44.9
11.0 22.1 31.6 40.7 49.0 55.0 58.1 54.0 69.2 45.3
6.0 33.7 44.8 58.0 69.2 64.8 59.5
9.0 26.3 35.4 47.3 58.9 63.9 69.5 65.4 59.6 53.5
12.0 25.9 37.1 49.8 59.9 64.2 69.7 66.0 60.1 53.9
9.0 36.7 47.2 60.6 78.1 73.7 68.6
12.0 28.8 38.0 49.9 61.6 74.0 78.4 74.1 68.7 62.2
15.0 28.6 39.3 52.6 62.6 74.3 78.6 74.4 69.2 62.6
12.0 47.7 63.7 78.4 88.8 86.1 79.5
15.0 36.0 48.7 65.4 79.7 76.1 87.9 86.3 79.6 72.1
18.0 34.5 49.6 67.1 81.0 76.4 87.1 86.5 80.3 72.6
30°F 50°F 70°F 90°F 30°F 50°F 70°F 90°F 110°F
Heat Of Extraction (HE) Heat of Rejection (HR)
46
VERSATEC BASE SERIES INSTALLATION MANUAL

Reference Calculations

Heating Calculations:
LWT = EWT -
LAT = EAT +
TH = HC + HWC
HE
gpm x 500
HC
cfm x 1.08
Cooling Calculations:
LWT = EWT +
LAT(DB) = EAT(DB) -
LC = TC - SC
SC
S/T =
TC
HR
gpm x 500
cfm x 1.08
SC

Legend

ABBREVIATIONS AND DEFINITIONS:
cfm = airflow, cubic feet/minute EWT = entering water temperature, Fahrenheit gpm = water flow in gallons/minute WPD = water pressure drop, PSI and feet of water EAT = entering air temperature, Fahrenheit (dry bulb/wet bulb) HC = air heating capacity, MBtu/h TC = total cooling capacity, MBtu/h SC = sensible cooling capacity, MBtu/h KW = total power unit input, kilowatts HR = total heat of rejection, MBtu/h HE = total heat of extraction, MBtu/h HWC = hot water generator capacity, MBtu/h EER = Energy Efficient Ratio = BTU output/Watt input COP = Coefficient of Performance = BTU output/BTU input LWT = leaving water temperature, °F LAT = leaving air temperature, °F TH = total heating capacity, MBtu/h LC = latent cooling capacity, MBtu/h S/T = sensible to total cooling ratio
47
VERSATEC BASE SERIES INSTALLATION MANUAL

Troubleshooting

Should a major problem develop, refer to the following information for possible causes and corrective steps.
If compressor won’t run:
1. The fuse may be open or the circuit breaker is tripped. Check electrical circuits and motor windings for shorts or grounds. Investigate for possible overloading. Replace fuse or reset circuit breakers after fault is corrected.
2. Supply voltage may be too low. Check it with a volt meter.
3. Control system may be faulty. Check control for correct wiring of thermostat or aquastat and check the 24 volt trans­former for proper voltage.
4. Wires may be loose or broken. Replace or tighten.
5. The low pressure switch may have tripped due to one or more of the following:
a) Heating
1) Plugged heat exchanger on source side
2) Water flow source side - (Low)
3) Water too cold source side
4) Low refrigerant
b) Cooling
1) Plugged heat exchanger on load side
2) Water flow load side - (Low)
3) Water too cold load side
4) Low refrigerant
6. The high pressure switch may have tripped due to one or more of the following:
a) Heating
1) Plugged heat exchanger on load side
2) Low water flow load side
3) Water too warm load side
b) Cooling
1) Plugged heat exchanger on source side
2) Low water flow on source side
3) Water too warm source side
7. The compressor overload protection may be open.
8. The internal winding of the compressor motor may be grounded to the compressor shell. If so, replace the compressor.
9. The compressor winding may be open or shorted. Disconnect power. Check continuity with ohm meter. If the winding is open, replace the compressor.
If sufficient cooling or heating is not obtained:
1. Check control for improper location or setting.
2. Check for restriction in water flow.
3. Check refrigerant subcooling and superheat for proper refrigerant charge and expansion valve operation.
4. The reversing valve may be defective and creating a bypass of refrigerant. If the unit will not heat, check the reversing valve coil.
If the unit operation is noisy:
1. Check compressor for loosened mounting bolts. Make sure compressor is floating free on its isolator mounts. Check for tubing contact with the compressor or other surfaces. Readjust it by bending slightly.
2. Check screws on all panels.
3. Check for chattering or humming in the contactor or relays due to low voltage or a defective holding coil. Replace the component.
4. Check for proper installation of vibration absorbing material under the unit.
5. Check for abnormally high discharge pressures.
6. Compressor rotation incorrect
Refrigerant Systems
To maintain sealed circuit integrity, do not install service gauges unless unit operation appears abnormal. Compare the change in temperature on the air side as well as the water side to the Operating Parameters tables. If the unit’s performance is not within the ranges listed, and the airflow and water flow are known to be correct, gauges should then be installed and superheat and subcooling numbers calculated. If superheat and subcooling are outside recommended ranges, an adjustment to the refrigerant charge may be necessary.
NOTE: Verify that air and water flow rates are at proper levels before servicing the refrigerant circuit.
48
p
p
q
q
(
)

Startup and Troubleshooting Form

VERSATEC BASE SERIES INSTALLATION MANUAL
Company Name: _________________________________ Technician Name: ________________________________ Model No: ______________________________________ Owner’s Name: __________________________________ Installation Address: ______________________________
Company Phone No:______________________________ Date: __________________________________________ Serial No:_______________________________________ Open or Closed Loop: _____________________________ Installation Date: _________________________________
Check One
Start up/Check-out for new installation
1. FLOW RATE IN GPM (COAXIAL HEAT EXCHANGER) Water In Pressure: a.______ PSI
Water Out Pressure: b.______ PSI Pressure Drop = a - b c.______ PSI Convert Pressure Drop to Flow Rate
(refer to Pressure Drop table) d.______ GPM
2. TEMPERATURE RISE OR DROP ACROSS COAXIAL HEAT EXCHANGER
Water In Temperature: e.______ °F e.______ °F Water Out Temperature: f. ______ °F f. ______ °F Temperature Difference: g.______ °F g.______ °F
3. TEMPERATURE RISE OR DROP ACROSS AIR COIL
Air In Temperature: h.______ °F h.______ °F Air Out Temperature: i. ______ °F i. ______ °F Temperature Difference: j. ______ °F j. ______ °F
Troubleshooting Problem:___________________________________
COOLING HEATING
COOLING HEATING
4. HEAT OF REJECTION (HR) / HEAT OF EXTRACTION (HE) CALCULATION HR or HE = Flow Rate x Temperature Difference x Brine Factor*
d. (above) x g. (above) x 485 for Methanol or Environol, 500 for water* Heat of Extraction (Heating Mode) = btu/hr Heat of Rejection (Cooling Mode) = btu/hr Compare results to Capacity Data Tables
Note: Steps 5 through 8 need only be completed if a problem is suspected
5. WATTS Volts: m._____
Total Amps (Comp. + Fan): n. _____ AMPS n. ______ AMPS Watts = m. x n. x 0.85 o. _____ WATTS o. ______ WATTS
6. CAPACITY Cooling Capacity = HR. - (o. x 3.413) Heating Capacity= HE. + (o. x 3.413)
7. EFFICIENCY Cooling EER = p. / o. Heating COP = p. / (o. x 3.413)
8. SUPERHEAT Suction Pressure: r. ______ PSI r. ______ PSI
Suction Saturation Temperature: s. ______ °F s. ______ °F Suction Line Temperature: t. ______ °F t. ______ °F Superheat = t. - s. u. _____ °F u. ______ °F
Head Pressure: v. ______ PSI v. ______ PSI High Pressure Saturation Temp.: w. _____ °F w. _____ °F Liquid Line Temperature*: x. ______ °F x. ______ °F Subcooling = w. - x. y. ______ °F y. ______ °F
* Note: Liquid line is between the coaxial heat exchanger and the expansion valve in the cooling mode; between the air coil and the expansion valve in the heating mode.
S.H.) / SUBCOOLING (S.C.
COOLING HEATING
VOLTS m.______ VOLTS
. _____ btu/hr . _____ btu/hr
. _____ EER . _____ COP
COOLING HEATING
49
VERSATEC BASE SERIES INSTALLATION MANUAL
DEALER: PHONE #: DATE: PROBLEM: MODEL #: SERIAL #:
COOLING CYCLE ANALYSIS
Startup/Troubleshooting Form
Unit Amp Draw:
°F
AIR
°F
Line Voltage:
COIL
COAX
LOAD
°F°F
PSI PSI
BRINE IN
Water to Water Application
BRINE OUT
Heat of Extraction/Rejection = GPM x 500 (485 for water/antifreeze) x ∆T
Note: DO NOT hook up pressure gauges unless there appears to be a performance problem.
HEATING CYCLE ANALYSIS
EXPANSION
VALVE
LIQUID LINE
Loop: Open
°F
PSI PSI
BRINE IN
Closed
COAX
SOURCE
BRINE OUT
PSI
°F
SAT °F=
SUCTION
COMPRESSOR
REVERSING
VALVE
Hot Water
-
Generator
°F°F
°F
°F
DISCHARGE
°
F
PSI = SAT F
Superheat
Subcooling
°
°F
AIR
COIL
Unit Amp Draw:
Line Voltage:
°F
COAX
LOAD
°F°F
PSI PSI
BRINE IN
Water to Water Application
BRINE OUT
LIQUID LINE
EXPANSION
VALVE
°
F
Loop: Open
COAX
SOURCE
PSI PSI
BRINE IN
50
Closed
BRINE OUT
PSI
°F
SAT °F=
SUCTION
COMPRESSOR
REVERSING
VALVE
Hot Water
-
Generator
°F°F
°F
°F
DISCHARGE
°
F
PSI = SAT F
Superheat
Subcooling
°
VERSATEC BASE SERIES INSTALLATION MANUAL

Preventive Maintenance

Water Coil Maintenance
1. Keep all air out of the water. An open loop system should be checked to ensure that the well head is not allowing air to infiltrate the water line. Lines should always be airtight.
2. Keep the system under pressure at all times. It is recommended in open loop systems that the water control valve be placed in the discharge line to prevent loss of pressure during off cycles. Closed loop systems must have positive static pressure.
NOTE: On open loop systems, if the installation is in an area with a known high mineral content (125 PPM or greater) in the water, it is best to establish with the owner a periodic maintenance schedule so the coil can be checked regularly. Should periodic coil cleaning be necessary, use standard coil cleaning procedures which are compatible with either the cupronickel or copper water lines. Generally, the more water flowing through the unit the less chance for scaling.
Other Maintenance
Filters
Filters must be clean to obtain maximum performance. They should be inspected monthly under normal operating conditions and be replaced when necessary. Units should never be operated without a filter.
Condensate Drain
In areas where airborne bacteria produce a slime in the drain pan, it may be necessary to treat chemically to minimize the problem. The condensate drain can pick up lint and dirt, especially with dirty filters. Inspect twice a year to avoid the possibility of overflow.
Blower Motors
Blower motors are equipped with sealed ball bearings and require no periodic oiling.
Air Coil
The air coil must be cleaned to obtain maximum performance. Check once a year under normal operating conditions and, if dirty, brush or vacuum (with a brush attachment) clean. Care must be taken not to damage the aluminum fins while cleaning.
CAUTION: Fin edges are sharp.

Replacement Procedures

Obtaining Parts
When ordering service or replacement parts, refer to the model number and serial number of the unit as stamped on the serial plate attached to the unit. If replacement parts are required, mention the date of installation of the unit and the date of failure, along with an explanation of the malfunctions and a description of the replacement parts required.
In-Warranty Material Return
Material may not be returned except by permission of authorized warranty personnel. Contact your local distributor for warranty return authorization and assistance.
51
VERSATEC BASE SERIES INSTALLATION MANUAL
Service Parts - Vertical
006 009 012 015 018 024 030 036 042 048 060 070
Compressor 208-230/60/1 34P653-01 34P590-01 34P591-01 34P592-01 34P593-01 34P636-01 34P637-01 34P635-01 34P638-01 34P639-01 34P630-01 34P631-01
265/60/1 34P653-02 34P590-02 34P591-02 34P592-02 34P593-02 34P636-02 34P637-02 34P635-02 Not Available
230/60/3 Not Available 34P636-03 34P637-03 34P635-03 34P638-03 34P639-03 34P630-03 34P631-03
460/60/3 Not Available 34P636-04 34P637-04 34P635-04 34P638-04 34P639-04 34P630-04 34P631-04
575/60/3 Not Available 34P638-05 34P639-05 34P630-05 34P631-05
115/60/1 34P653-09 34P590-09 34P591-09 Not Available
Run Capacitor 208-230/60/1 16P002D12 16P002D17 16P002D18 16P002D19 16P002D19 16P002D20 16P002D21 16P002D32 16P002D23
Compressor
Run Capacitor 265/60/1 16P002D27 16P002D30 16P002D29 16P002D30 Not Available
Run Capacitor 115/60/1 16P002D21 16P002D36 Not Available
Sound Jacket 92P504A01 92P523-01 92P524-01
Discharge Muffler Not Available 36P503B02
VS ECM Motor 208-230/60/1 Not Available 14P515B01 14P516B01 14P517B01
VS ECM Motor 265/60/1 Not Available 14P515B03 Not Available
VS ECM Motor 230/60/3 Not Available 14P515B01 14P516B01 14P517B01
VS ECM Motor 460/60/3 Not Available 14P515B03 14P516B03 14P517B03
Motor & Blower
VS ECM Blower Housing Not Available 53P512B01 53P515B01
Variable Speed ECM
PSC Motor 115/60/1 14P506-03 Not Available
PSC Motor 208-230/60/1 14P506-02 14P507B01 14P508B01 14P509B01 14P510B01 14P511B01 14P512B01 14P514B01
PSC Motor 265/60/1 14P506-02 14P507B02 14P508B02 14P509B02 14P510B02 Not Available
PSC Motor 230/60/3 Not Available 14P508B01 14P509B01 14P510B01 14P511B01 14P512B01 14P514B01
PSC Motor 460/60/3 Not Available 14P508B03 14P509B03 14P510B03 14P511B02 14P512B02 14P514B02
PSC Motor 575/60/3 Not Available 14P511B03 14P512B03 14P514B03
PSC Motor & Blower
PSC Blower & Housing 53P512B01 53P517-02 53P515B01
5-Speed ECM Motor 208-230/60/1
5-Speed ECM Motor 277/60/1
5-Speed ECM Motor 230/60/ 3
5-Speed ECM Motor
5-Speed ECM
Motor & Blower
460/60/ 3
5-Speed ECM Blower & Housing
Air Coil 61P723-41 61P704-41 61P713-41 61P705-41 61P711-41 61P706-41 61P715-41
Coax (Copper) 62P587-01 62P591-01 62P586-01 62P586-01 62P586-01 62P586-01 62P572-01 62P566-01 62P568-01 62P573-01 62P574-01
TXV 33P605-19 33P605-16 33P605-02 33P605-10 33P608-10 33P605-13
Reversing Valve 33P502-05 33P502-05 33P502-05 33P505-04 33P506-04 33P503-05 33P526-04
Components
Refrigeration
Filter Drier 36P500B01 36P500B02
Transformer 115/60/1 15P008B02 Not Available
Transformer 208-230/60/1 15P501B01
Transformer 265/60/1 15P507B01 Not Available
Transformer 230/60/3 Not Available 15P501B01
Controls
Transformer 460/60/3 Not Available 15P505B01
Transformer 575/60/3 Not Available 15P506B01
Phase Guard Not Available 19P541A06
High Pressure Switch 35P506B02
Not Available 14S536-18 14S536-01 14S536-02 14S536-03 14S537-01 14S537-02 14S537-03 14S537-03
Not Available 14S536-19 14S536-02 14S536-07 14S536-08 Not Available
Not Available 14P536-01 14S536-02 14S536-03 14S537-01 14S537-02 14S537-03 14S537-03
Not Available 14S536-03 14S536-10 14S536-11 14S537-04 14S537-05 14S537-06 14S537-06
Not Available 53P512B01 53P515B01
Safeties
Low Pressure Switch 35P506B01
Sensors &
Part numbers subject to change 8/19/13
52
VERSATEC BASE SERIES INSTALLATION MANUAL
Service Parts - Horizontal
006 009 012 015 018 024 030 036 042 048 060 070
Compressor 208-230/60/1 34P653-01 34P590-01 34P591-01 34P592-01 34P593-01 34P636-01 34P637-01 34P635-01 34P638-01 34P639-01 34P630-01 34P631-01
265/60/1 34P653-02 34P590-02 34P591-02 34P592-02 34P593-02 34P636-02 34P637-02 34P635-02 Not Available
230/60/3 Not Available 34P636-03 34P637-03 34P635-03 34P638-03 34P639-03 34P630-03 34P631-03
460/60/3 Not Available 34P636-04 34P637-04 34P635-04 34P638-04 34P639-04 34P630-04 34P631-04
575/60/3 Not Available 34P638-05 34P639-05 34P630-05 34P631-05
115/60/1 34P653-09 34P590-09 34P591-09 Not Available
Run Capacitor 208-230/60/1 16P002D12 16P002D17 16P002D18 16P002D19 16P002D19 16P002D20 16P002D21 16P002D32 16P002D23
Compressor
Run Capacitor 265/60/1 16P002D27 16P002D30 16P002D29 16P002D30 Not Available
Run Capacitor 115/60/1 16P002D21 16P002D36 Not Available
Sound Jacket 92P504A01 92P523-01 92P524-01
Discharge Muffler Not Available 36P503B02
VS ECM Motor 208-230/60/1 Not Available 14P515B01 14P516B01 14P517B01
VS ECM Motor 265/60/1 Not Available 14P515B03 Not Available
VS ECM Motor 230/60/3 Not Available 14P515B01 14P516B01 14P517B01
VS ECM Motor 460/60/3 Not Available 14P515B03 14P516B03 14P517B03
Motor & Blower
VS ECM Blower Housing Not Available 53P512B01 53P515B01
Variable Speed ECM
PSC Motor 115/60/1 14P506-03 Not Available
PSC Motor 208-230/60/1 14P506-02 14P507B01 14P508B01 14P509B01 14P510B01 14P511B01 14P512B01 14P514B01
PSC Motor 265/60/1 14P506-02 14P507B02 14P508B02 14P509B02 14P510B02 Not Available
PSC Motor 230/60/3 Not Available 14P508B01 14P509B01 14P510B01 14P511B01 14P512B01 14P514B01
PSC Motor 460/60/3 Not Available 14P508B03 14P509B03 14P510B03 14P511B02 14P512B02 14P514B02
PSC Motor 575/60/3 Not Available 14P511B03 14P512B03 14P514B03
PSC Motor & Blower
PSC Blower & Housing 53P512B01 53P517-02 53P515B01
5-Speed ECM Motor 208-230/60/1
5-Speed ECM Motor 277/60/1
5-Speed ECM Motor 230/60/ 3
5-Speed ECM Motor
5-Speed ECM
Motor & Blower
460/60/ 3
5-Speed ECM Blower & Housing
Air Coil 61P726-41 61P726-41 61P726-41 61P704-41 61P712-41 61P707-41 61P708-41 61P709-41 61P710-41
Coax (Copper) 62P587-01 62P591-01 62P586-01 62P586-01 62P586-01 62P586-01 62P572-01 62P566-01 62P568-01 62P573-01 62P574-01
TXV 33P605-19 33P605-16 33P605-02 33P605-10 33P608-10 33P605-13
ponents
Reversing Valve 33P502-05 33P502-05 33P502-05 33P505-04 33P506-04 33P503-05 33P526-04
Refrigeration Com-
Filter Drier 36P500B01 36P500B02
Transformer 115/60/1 15P008B02 Not Available
Transformer 208-230/60/1 15P501B01
Transformer 265/60/1 15P507B01 Not Available
Transformer 230/60/3 Not Available 15P501B01
Controls
Transformer 460/60/3 Not Available 15P505B01
Transformer 575/60/3 Not Available 15P506B01
Phase Guard Not Available 19P541A06
High Pressure Switch 35P506B02
Not Available 14S536-18 14S536-01 14S536-02 14S536-03 14S537-01 14S537-02 14S537-03 14S537-03
Not Available 14S536-19 14S536-06 14S536-07 14S536-08 Not Available
Not Available 14P536-01 14S536-02 14S536-03 14S537-01 14S537-02 14S537-03 14S537-03
Not Available 14S536-09 14S536-10 14S536-11 14S537-04 14S537-05 14S537-06 14S537-06
Not Available 53P512B01 53P515B01
Safeties
Low Pressure Switch 35P506B01
Sensors &
Part numbers subject to change. 8/19/13
53
VERSATEC BASE SERIES INSTALLATION MANUAL
Notes
54
VERSATEC BASE SERIES INSTALLATION MANUAL
Revision Guide
Pages: Description: Date: By:
All Added CuproNickel Water Coil Option 20 May 2014 DS
All Updated with New Aurora UPC DDC Controls 20 May 2014 DS
4 Corrected Nomenclature Error 23 Oct 2013 DS
All Updated Series with New All-Aluminum Air Coils 09 Oct 2013 DS
16-19 Updated Aurora Controls Description 04 Mar 2013 DS
All Updated Nomenclature to Reflect New Variable Speed ECM Blower 12 Nov 2012 DS
All Added 006 - 015 Models 30 Oct 2012 DS
55 Added Revision Guide 30 Oct 2012 DS
55
Manufactured by WaterFurnace International, Inc. 9000 Conservation Way Fort Wayne, IN 46809 www.waterfurnace.com
Product: Versatec Base Series Type: Geothermal/Water Source Heat Pump Size: Commercial 0.5-6 Ton
IM1201AUB 05/14
©2014 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. WaterFurnace has a policy of continual product research and development and
reserves the right to change design and specifi cations without notice.
Document: Installation Manual
Loading...