Warren Controls E024, E026, EO29, E030, EO25 Installation, Operation And Maintenance Instructions

ELECTRIC ACTUATOR
E024, EO25, E026, EO29 & E030
TABLE OF CONTENTS
Electric Actuator Specifications...................................... 2
Overview ................................................................................ 3
Actuator Wiring Diagrams ................................................ 4
VMS-35 Specifications and Wiring Diagram .............. 5
VMS -35 Installation and Testing .................................... 6
VMS -35 Battery Replacement ........................................ 7
Removal of E024 & E025 ................................................... 8
Installation of E024 &E025 ............................................... 9
Removal of E026, E029 & E030......................................10
Installation of E026, E029 & E030 ................................. 11
Set-up ....................................................................................12
Control Action ....................................................................13
HVAC/BAC ELECTRIC IOM
Power Failure Direction E025 & E026 .........................14
Indicator Lights ..................................................................15
Installation Drawings ................................................ 16-17
Addendum A ................................................................ 18-20
Addendum B ................................................................ 21-25
HVAC_BAC_ELECTRIC_IOM_RevCa_0219
92500115 RevD
ELECTRIC ACTUATOR SPECIFICATIONS*
Valve Usage: E024, E025 [Valve sizes 1/2 to 4 Inch] E026 [Valve sizes 1 to 6 Inch] E029, E030 [Valve sizes 1-1/4 to 10 Inch]
______________________________________________________________________________________________
Power supply: 24 VAC ± 20% 50/60 Hz, 24 VDC ± 10% ______________________________________________________________________________________________
Power Requirements E024 E025 E026 E029
Power consumption running 2 W 3 W 5 W 6 W
Power consumption holding 1.5 W 2 W 2 W 1.5 W
Transformer sizing (24 VAC Class 2) 4 VA 7 VA 9.5 VA 11 VA
Power Requirements E030‡
Power consumption running (Battery charging)
Power consumption running (Battery charged)
Power consumption holding (Battery charging)
Power consumption holding (Battery charged)
Transformer sizing (24 VAC Class 2)
______________________________________________________________________________________________
Timing: 90 seconds full stroke max ______________________________________________________________________________________________
Control Signal: 2-10 Vdc (default), 4-20 mAdc [with KR500 (resistor kit)] ______________________________________________________________________________________________
Feedback Signal: 2-10 Vdc ______________________________________________________________________________________________
Signal Failure Direction: E024, E029, E030 Fail Closed or Lower Port Closed (default), or Fail Open or Upper Port Closed E025, E026 Fail Closed or Lower Port Closed (default), or Fail Open or Upper Port Closed
______________________________________________________________________________________________
Power Failure Mode: E024, E029 Fail-In-Place E030 Fail-Safe to Signal Failure Direction E025, E026 Fail Closed or Lower Port Closed (default), or Fail Open or Upper Port Closed
______________________________________________________________________________________________
Capacitor: E025, E026 Capacitor charge time 5 to 20 seconds ______________________________________________________________________________________________
Manual Override: Yes, with supplied Allen Key (4mm E024, E025 / 5mm, E026, E029, E030) ______________________________________________________________________________________________
Construction: Aluminum die cast Yoke, plastic Housing ______________________________________________________________________________________________
Connections: 3 foot long 4 Conductor 18 gauge wire, pigtail (may include fifth pink colored conductor only used for factory programming. Do Not Use or Connect)
______________________________________________________________________________________________
Enclosure Type: NEMA 2, IP54, UL 2 ______________________________________________________________________________________________
Noise Level: E024, E025 45 dBA E026 60 dBA E029, E030 65 dBA
______________________________________________________________________________________________
Environmental: Operating: Ambient + 32°F to +122°F (0 to +50°C) Humidity: 5 to 95% RH non-condensing Storage: -40°F to +176°F [-40°C to +80°C]
______________________________________________________________________________________________
Orientation: Factory Aligned per drawings ______________________________________________________________________________________________
Mounting: Vertical above centerline of valve ______________________________________________________________________________________________
Safety Agency Listing: CE, cULus
16 W
11 W
11.5 W
6.3 W
21 VA
‡E029 w/VMS-35
* See page 5 for VMS-35 Specifications
2600 Emrick Blvd • Bethlehem, PA 18020 • USA • 800-922-0085 • www.warrencontrols.com
2
OVERVIEW
ADAPTION POWER
The actuators feature a native 2-10 Vdc Control Signal. Installation of the KR500 Resistor Kit converts the Control Signal input to 4-20 mAdc. When using 4-20 mA input, terminate the 500 ohm resistor from the KR500 resistor kit between the White and Black actuator wires. When using the VMS-35, this can be easily done between the NO1 and LN terminals for Actuator 1 and between the NO2 and LN terminals for Actuator 2.
A single wire brings a 2-10 Vdc Feedback Signal. The Feedback Signal is not available using 4-20 mAdc.
(E024, E029, E030) (E025, E026)
Manual Override is possible by turning off the power, pressing the Manual Override button
and rotating the supplied Allen key in the Hex Override Socket.
To raise the actuator stem turn the Allen key counter-clockwise.
E024
Engage the manual override:
The override button can lock in place for NON­CAPACITOR E024, E029 and E030 actuators. Press the button down and into the actuator to lock. The OVERRIDE BUTTON will remain down and will need to be pressed to return to its original position.
The button must be continuously pressed completely down throughout travel for E025 AND E026 actuators with CAPACITORS.
E029 E030
E025 E026
E024 E029 E030
E025 E026
WARNING: Do not force or turn the HEX OVERRIDE SOCKET when the OVERRIDE BUTTON is not pressed. Doing so may cause damage to the actuator gears.
DANGER
PRESS THE MANUAL OVERRIDE BUTTON IN FIRMLY WHILE OPERATING THE MANUAL OVERRIDE. FAILURE TO DO SO WHILE THE ACTUATOR IS POWERED OR BEING DRIVEN TO THE POWER FAILURE DIRECTION CAN CAUSE SERIOUS PERSONAL INJURY AND DAMAGE THE ACTUATOR.
The Rotation Switch can be adjusted to set the direction the Control Signal opens and closes the valve (and Loss of Signal direction in some actuators) in the field without actuator removal.
Adaption (Auto-Calibration
- green LED), a combined Adaption/ Power button to reset and relearn the valve stroke as well as indicate the actuator is powered. When the Button is pressed, the actuator will drive one full cycle to its mechanical end stops OR the valves mechanical seats. Upon completion of this cycle the actuators working range (Control Signal, Feedback Signal and running time) will be adjusted to the actual stroke of the actuator.
Status (yellow LED) to confirm communication.
!
HVAC_BAC_ELECTRIC_IOM_RevCa_0219
3
2-10 VDC
Line
Volts
24 VAC
CLASS 2
TRANSFORMER
2-10 VDC
CONTROL SIGNAL
2-10 VDC
FEED- BACK
ACTUATOR
BK #1 ( )
RD #2 ( )
WH #3 (Y)
OR #5 (U)
Common
Hot
Input, 2 to 10 VDC
Output, 2 to 10 VDC
4-20 MADC
Line
Volts
24 VAC
CLASS 2
TRANSFORMER
4-20 MADC
CONTROL SIGNAL
2-10 VDC
FEED- BACK
ACTUATOR
BK #1 ( )
RD #2 ( )
WH #3 (Y)
OR #5 (U)
Common
Hot
Input, 2 to 10 VDC
Output, 2 to 10 VDC
KR500
RESISTOR
ACTUATOR WIRING DIAGRAMS - PROPORTIONAL CONTROL
2600 Emrick Blvd • Bethlehem, PA 18020 • USA • 800-922-0085 • www.warrencontrols.com
4
For On-O control see Addendum B on pages 21-25.
VMS-35 BCM
Power 24 VAC
HOT
Existing Jumper
L LN RC LN TG BT AC LNNC1 C1 NO1
NC2 C2
NO2
CONTROL SIGNAL (S)
(RECOMMENDED)
(RECOMMENDED)
OUTPUT TO
ACTUATOR A
OUTPUT TO
ACTUATOR B
(IF USED)
Actuator BActuator A
1. The VMS-35 can power one (1) or two (2) actuators.
2. Energize 24 VAC before connecting red lead to battery.
3. Also read actuator wiring and setup instructions.
4. To prevent signal interference proper signal wire cable
shielding is recommended.
5. When using long wire runs and a 2 – 10 Vdc signal, signal and power cables should be run in separate conduits to avoid interference.
NOTES
VMS-35
OR#5(U)
WH#3(Y) RD#2(+) BK#1(-)
OR#5(U)
WH#3(Y) RD#2(+) BK#1(-)
BACKUP CONTROL MODULE
SPECIFICATIONS
Actuator Usage: E030 (E030 includes a VMS-35 BCM), E029, E024 Power supply: 24 VAC ± 20% 50/60 Hz Power Requirement: 40 VA MAX Power Output: 24 VAC 25VA 25W Total Number Actuators: One or Two Construction: Battery w/Circuit Board, Charger and Transformer Enclosure Type: NEMA 4X, IP66, UL 4X, CSA 4X Flame Retardant: UL 50 Construction: UV Stabilized Fiberglass Reinforced Polyester,
Polycarbonate Hinge and Closed Cell Neoprene Gasket
Connections: Two 1/2 IN conduit with one plug Number Batteries: One Initial Charge: 2-4 hours Output Cycle Time:
6.5 Minutes from loss of power until circuit board times out Battery Life: Up to 5 years … Replacement battery model UB1213 / 12V, 1.3 Ah
Mounting: Feet for Wall Mount (4.91” x 8.75” centers) Environmental: Operating/ Storage: Ambient +32°F to +104°F
(0 to +40°C) – due to battery
Weight: 4.25 lbs (2 kg) Safety Agency Listing: Not listed
VMS-35 WIRING DIAGRAM - PROPORTIONAL CONTROL
For On-O control see Addendum B on pages 21-25.
TERMINALS
L System Power 24 VAC (+) LN System Neutral (-) RC Remote Control BT Battery Test (+) TG Test Ground (-) C1 Control Signal 1st Actuator (+) C2 Control Signal 2nd Actuator (+) NC1 Not Used NC2 Not Used NO1 Relay Normally Open 1st Actuator NO2 Relay Normally Open 2nd Actuator AC 24 VAC Out (+)
Operation:
Proportional Normal: Terminal L is connected to 24 VAC building power. Terminal LN completes the circuit to BK. Actuator responds to modulating input signal.
Power Failure: Terminal AC changes to 24 V square wave from battery/ inverter. A relay breaks the connection between Terminals C1 and NO1 forcing the actuator to return to the rotation switch position (See page 13 for explanation of rotation switch position).
Loss of Signal: Terminal AC uses 24VAC building power. The control signal is broken forcing the actuator to return to the rotation switch position (See page 13 for explanation of rotation switch position).
HVAC_BAC_ELECTRIC_IOM_RevCa_0219
5
INSTALLATION - PROPORTIONAL CONTROL
1. Disengage the 24 VAC building power circuit before wiring. Verify that the battery inside the VMS-35 has its wires disconnected and leave them that way for now. Disconnect them if they are connected.
2. Connect the VMS-35 to the actuator(s) as shown on wiring diagram. The VMS-35 can power one or two actuators.
Actuator A: Connect terminal N01 to white wire from actuator to drive the valve stem to the rotation switch position. Connect terminal AC to red wire from actuator to provide power. Connect grounded reference – negative/black wire from actuator to terminal LN. Also connect the control signal (-) to the black wire from the actuator. Connect terminal C1 to the control signal positive (+). If the control signal is 4-20mADC a KR500 500 ohm resistor is required. Terminate the resistor between terminals N01 an LN.
Actuator B: Connect terminal N02 to white wire from actuator to drive the valve stem to the rotation switch position. Connect terminal AC to red wire from actuator to provide power. Connect grounded reference – negative/black wire from actuator to terminal LN. Also connect the control signal (-) to the black wire from the actuator. Connect terminal C2 to the control signal positive (+). If the control signal is 4-20mADC a KR500 500 ohm resistor is required. Terminate the resistor between terminals N02 an LN.
3. While still disconnected, wire the VMS-35 to 24 volts AC power. Connect the hot to terminal L then neutral to terminal LN.
4. Engage the 24 VAC building power.
5. Verify that building power is live then connect the loose red wire inside the VMS-35 enclosure to the positive (+) battery terminal and the black wire to the negative (-) battery terminal.
NOTE: Engage the 24 VAC power to the VMS-35 before connecting the battery. Connecting the battery first causes the VMS-35 to go into the power failure mode. If there are conditions other than power failure during which the actuator should be driven to the rotation switch position (See page 13 for explanation of rotation switch position), replace the jumper between RC & LN with a contact that opens on demand.
For On-O control see Addendum B on pages 21-25.
TESTING
Disconnecting the jumper between RC & LN, with building power on, will drive the actuator to the rotation switch position (See page 11 for explanation of rotation switch position).
Testing the VMS-35 and the charging system and battery is recommended yearly. To test charging measure the voltage between terminals TG & BT. TG is negative. When the power supply is charging correctly the voltage will be 13 - 14 volts DC. To test the battery disconnect LN or L, wait for the actuator to return to the rotation switch position (See page 13 for explanation of rotation switch position) and then measure the voltage between TG & BT. A good and adequately charged battery will be between 10 - 12 volts DC.
The VMS-35 is a standby power supply.
It is intended to drive an actuator to either open or close a valve during a power failure. The VMS-35 can power one or two actuators.
2600 Emrick Blvd • Bethlehem, PA 18020 • USA • 800-922-0085 • www.warrencontrols.com
6
VMS-35 (UB1213) BATTERY REPLACEMENT
PROCEDURE:
NOTE Normal valve operation under 24 VAC power need not be interrupted
during battery replacement; however, the fail-safe function will not be avail-
able until the new battery is in place, connected and sufficiently charged (typi-
cally 2-4 hours).
1. Refer to the picture (left) to locate and disconnect the Red and Black wires from the battery.
2. Remove the two battery mounting bracket screws and remove the battery and bracket.
3. Place the bracket over the new battery and install the assembly as shown, using the two screws removed in step 2 (above).
4. Connect the Black wire to the black (unmarked) terminal.
5. With 24 VAC power present, connect the Red wire to the red terminal. VMS-35 circuitry will automatically charge the battery. (If 24 VAC is not present, the valve may move to its fail-safe position, depending upon residual charge in the new battery.)
Black Red
6. Recycle or dispose of the old battery properly. Do not incinerate!
HVAC_BAC_ELECTRIC_IOM_RevCa_0219
7
READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING.
REMOVAL OF E024 & E025 ACTUATORS FROM VALVE
SEE DRAWING D3400024 on page 16
THESE INSTRUCTIONS TREAT THE ACTUATOR ITEM 1 AND LINKAGE BASE ITEM 17 AS AN ASSEMBLY. FOR INSTRUCTIONS ON HOW TO REMOVE THE ACTUATOR AND THE LINKAGE BASE AS SEPARATE ITEMS SEE ADDENDUM A ON PAGE 18.
1) Remove line pressure and isolate valve in piping.
2) Operate actuator so plug is off seat(s) or travel stop in valve.
3)
Remove power and signal from actuator. For E025, after power is removed, cycle Fail-Safe Switch from Up Arrow to Down Arrow until actuator stem no longer moves. Adaption/Power (green LED) changes from blinking to off. Return Fail-Safe Switch to original position. If necessary use the manual override to operate actuator so plug is off seat(s) or travel stop in valve.
(See manual override on page 3)
WARNING: DO NOT FORCE OR TURN THE MANUAL OVERRIDE WHEN THE MANUAL OVERRIDE BUTTON IS NOT PRESSED. DOING SO MAY CAUSE DAMAGE TO THE ACTUATOR GEARS.
5) Use actuator manual override to raise the stem connector
until the stem adapter is disengaged (See manual override on page 3).
WARNING: DO NOT FORCE OR TURN THE MANUAL OVERRIDE WHEN THE MANUAL OVERRIDE BUTTON IS NOT PRESSED. DOING SO MAY CAUSE DAMAGE TO THE ACTUATOR GEARS.
WARNING: DO NOT LOOSEN THE FACTORY SET ADJUSTABLE HEIGHT SCREWS ON THE SIDES OF THE ACTUATOR YOKE LINKAGE.
6) Loosen yoke locknut (Item 3) until it is free of bonnet.
7) Remove spacer ring (Item 2).
8) Remove actuator from valve.
WARNING: DO NOT LOOSEN THE FACTORY SET ADJUSTABLE HEIGHT SCREWS ON THE SIDES OF THE ACTUATOR YOKE.
9) Hold jam nut (Item 4) on valve stem and turn the stem adapter
(Item 5) to disengage from valve stem.
4) Unlock stem connector clamp, use fingers on the front and back sides of black lock assembly to evenly raise the lock assembly.
WARNING: WHEN HANDLING THE ACTUATOR TAKE CARE NOT TO DAMAGE THE STEM CONNECTOR CLAMP AND CROSS BAR ASSEMBLY.
WARNING: THE VALVE STEM SHOULD NEVER BE TURNED WHILE THE PLUG IS IN CONTACT WITH THE SEAT OTHERWISE THE SEATING SURFACES WILL BE DAMAGED VOIDING THE WARRANTY.
10) Remove stem adapter from valve stem.
11) Remove jam nut from valve stem.
2600 Emrick Blvd • Bethlehem, PA 18020 • USA • 800-922-0085 • www.warrencontrols.com
8
READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING.
INSTALLATION OF E024 & E025 ACTUATORS ON THE VALVE
SEE DRAWING D3400024 on page 16
THESE INSTRUCTIONS TREAT THE ACTUATOR ITEM 1 AND LINKAGE BASE ITEM 17 AS AN ASSEMBLY. FOR INSTRUCTIONS ON HOW TO INSTALL THE ACTUATOR AND THE LINKAGE BASE AS SEPARATE ITEMS SEE ADDENDUM A ON PAGE 19.
THE SILVER SPACER RING THAT COMES WITH THE ACTUATOR MUST BE ASSEMBLED ON TOP SIDE OF YOKE WITH TURNED DOWN (MACHINED) SIDE FACING DOWN AS SHOWN ON DRAWING.
1) Push valve stem down until plug is seated. Note stem location.
2) Unlock stem connector clamp, use fingers on the front and back sides of black lock assembly to evenly raise the lock assembly.
WARNING: WHEN HANDLING THE ACTUATOR TAKE CARE NOT TO DAMAGE THE STEM CONNECTOR CLAMP AND CROSS BAR ASSEMBLY.
3) Install hex jam nut (Item 4) on valve stem. Thread jam nut so that one inch of threads are exposed between jam nut and top of stem.
4) Hold jam nut on valve stem and turn the stem adapter (Item
5) until it bottoms out on the valve stem. Tighten jam nut to the bottom of the stem adapter to secure valve stem to stem adapter.
WARNING: THE VALVE STEM SHOULD NEVER BE TURNED WHILE THE PLUG IS IN CONTACT WITH THE SEAT OTHERWISE THE SEATING SURFACES WILL BE DAMAGED VOIDING THE WARRANTY.
5) Place actuator, spacer ring (Item 2) and yoke locknut (Item
3) over valve stem and onto bonnet. Watch orientation of spacer ring and yoke locknut. Actuator base must rest on bonnet. If necessary, use the manual override to raise the stem connector (See manual override on page 3).
WARNING: DO NOT FORCE OR TURN THE MANUAL OVERRIDE WHEN THE MANUAL OVERRIDE BUTTON IS NOT PRESSED. DOING SO MAY CAUSE DAMAGE TO THE ACTUATOR GEARS.
6) Rotate actuator to desired orientation. For the factory default actuator position the motor electrical wire end of the actuator faces the outlet side of a 2-way valve, common “C” port on a 3-way mixing valve, and lower “L” port on a 3-way diverting valve. Thread yoke locknut onto bonnet and tighten securely. Use blunt chisel and hammer for tightening.
7) Push valve stem down until plug is seated. Refer to position noted in Step 1.
8) Use actuator manual override to lower the stem connector over the stem adapter (See manual override on page 3). Lock stem connector clamp, use fingers on the front and back sides of black lock assembly to evenly lower the lock assembly.
WARNING: DO NOT FORCE OR TURN THE MANUAL OVERRIDE WHEN THE MANUAL OVERRIDE BUTTON IS NOT PRESSED. DOING SO MAY CAUSE DAMAGE TO THE ACTUATOR GEARS.
WARNING: WHEN HANDLING THE ACTUATOR TAKE CARE NOT TO DAMAGE THE STEM CONNECTOR CLAMP AND CROSS BAR ASSEMBLY.
9 ) Push orange travel indicators (Item 8) together against both
sides of stem connector travel indicator.
10) Connect power and signal to actuator.
(See also Set-Up, page 12)
11) Press the Adaption (Auto-Calibration) button on the actuator and wait until the cycle is complete.
12) Stroke valve several times to check operation.
WARNING: DO NOT LOOSEN THE FACTORY SET ADJUSTABLE HEIGHT ADJUSTMENT SCREWS ON THE SIDES OF THE ACTUATOR YOKE LINKAGE.
13) Return line pressure to valve.
HVAC_BAC_ELECTRIC_IOM_RevCa_0219
9
Loading...
+ 19 hidden pages