Warner Electric MCS2000-PSDRV2 User Manual

MCS2000-PSDRV2 Power Supply/Dual
Voltage/Dual Channel Driver
819-0525 P-2010-7
Installation & Operating Instructions
Contents
Installation
Mounting . . . . . . . . . . . . . . . . . . . . . . . . .4
System Wiring
Interfacing to MCS2000 Tension
Controls . . . . . . . . . . . . . . . . . . . . . . . . . .5
24 volt Brake Systems . . . . . . . . . . . . . . 8
48 volt Brake Systems . . . . . . . . . . . . .10
System Start-Up . . . . . . . . . . . . . . . . . . . . . . . 11
System Troubleshooting . . . . . . . . . . . . . . . . . 17
Listing of figures and illustrations . . . . . . . . . . .21
Warranty Information . . . . . . . . . . . . . . . . . . . BC
Introduction
The MCS2000-PSDRV2 Power Supply/Dual Channel/Dual Voltage driver is a replacement for the MCS2000-PSDRV and MCS2000-PSDRVH Drivers in a single unit. The Power Supply section will operate from 100 – 260 VAC and provide a 24 VDC output for operating either the driver section of the unit or the MCS2000-ECA and other sensors. The Dual Channel/Dual Voltage driver section will operate from either 24 volts DC input or 48 volts DC input and provide output voltage and current for operation of any of the 24 volt DC tension brakes available from Warner Electric.
The universal design replaces two separate power supply/drivers in one package and provides for dual brake operation, for either single brake when only one brake is required or dual brake operation on splicer systems where two brakes are required.
reduced input terminals on the front of the unit for the driver section that are pluggable which will make installation and wiring much easier than the previous versions. By using a pluggable terminal block, if replacement is required then only the controller has to be disconnected and removed and a new controller installed without having to rewire the entire system.
Footprint for the PSDRV2 is identical to that of the MCS2000-PSDRV and MCS2000-PSDRVH power supply/drivers. The MCS2000-PSDRV and MCS2000-PSDRVH can be replaced with the MCS2000-PSDRV2 without having to make any mechanical changes in the mounting footprint.
Additionally, LED indicators on the face of the control make troubleshooting and monitoring operation much simpler than previous versions. A combination red and green LED for each channel determines operation during normal run conditions as well as during faults.
Each driver channel has its own individual anti-residual adjustment to make brake adjustment in the “off” state optimum. Anti-residual provides a reverse current to the brakes in the off state to minimize residual magnetism build up. This allows for reducing the drag torque in the brake during initial start up.
The driver can be controlled by any of the MCS2000 controllers offered as either a single channel system or dual channel system. The MCS2000-ECA, MCS2000-CTDA, or MCS2000-CTLC controllers can provide the operating signals. The MCS2000-PSDRV2 has
Warner Electric • 800-825-9050 P-2010-7 • 819-0525
2
Specifications
Model: MCS2000-PSDRV2 Dual Channel/Dual
Voltage Driver
Part Number: 6910-448-110
Power Supply Section:
Input: 100 – 260 VAC, 50/60 Hz., single phase
Ouput: 24 VDC, 3.1 Amps DC
Wiring: 3 Position pluggable terminal block for
AC Input 4 Position pluggable terminal block for DC Output Power
Reset Mode: Requires power off and then power on to reset driver
Driver Section:
Input Voltage: 24 Volts DC or 48 Volts DC, + / -10%
Status and Diagnostic Indicators: 2 LED’s on each channel indicate normal operation and fault conditions during operation. One Green and one Red LED.
Protection Input: Polarity protected to prevent damage in the event of inversion of DC power supply voltages.
Protection Output: Short circuit protected during operation and power up. Output is also protected from overload conditions. Once short circuit is detected, drive locks out for 10 msec and resets. After 4 cycles, drive trips out and requires reset.
Wiring: Via 10 position pluggable terminal block
Operating Temperature: + 104 ° F (40 ° C)
Storage Temperature: -13 ° F to + 131° F
(-25° C to + 55° C)
Enclosure: NEMA 1 (IP 20)
Output Voltage: 24 VDC or 48 VDC depending on power supply input voltage. In Overvoltage mode, output voltage is limited to 48 volts DC for 30 seconds before reducing back to 24 VDC
Output Current: Maximum of 4.5 amps DC per channel. Overload capacity to 6 amps maximum per channel for 30 seconds to be followed by maximum 3 amps for a minimum period of 120 seconds.
Anti-Residual Output: 10% of input power supply voltage. Adjustable for each channel.
-2.4 volts DC with 24 VDC power supply input
-4.8 volts DC with 48 VDC power supply input
Analog Input Voltage: 0 to 10 Volts DC on Input A, or Input B. When operating with 48 volt DC power, input of 0 to 5 volts corresponds to 24 Volt DC output, and from 5 to 10 volts input overvoltage mode from 24 to 48 volts DC with timed limitation.
Certifications: CE
Warner Electric • 800-825-9050 P-2010-7 • 819-0525
3
Installation
Mounting
Select a location that will allow for sufficient air movement around the control.
Overall Dimensions: 6.85 x 2.95 x 7.28 inches (174 x 75 x 185 mm).
Note: Unit must be mounted vertically to have
best possible cooling effect.
o 1. Using the dimensional data from Figure 1,
drill and tap 4 mounting holes for either
4.5 mm screws or #10 screws on the panel
or mounting surface the drive will be
mounted to.
o 2. Using either 4.5 mm or #10 screws, mount
the unit to the panel or mounting surface.
Tighten screws sufficiently so that unit will
not come loose during normal machine operation or vibration.
Note: 0 Volt terminals in control are tied to
control housing. A good ground is required between the control and the panel or mounting surface.
o 3. After unit is mounted and secured, make
sure that spacing is sufficient around the housing and that at least a clearance of at least 2.00 inches (50.8 mm) for the front panel wiring plug to facilitate wiring unit and plugging connector to control.
o 4. Double check all mounting before
proceeding to the wiring section.
Driver Outline and Mounting Dimensions
Figure 1 Mounting Dimensions
Warner Electric • 800-825-9050 P-2010-7 • 819-0525
4
System Wiring
Controllers
The MCS2000-PSDRV2 will operate with any of the MCS2000 series Controllers. It will provide interface between the brakes and the MCS2000­ECA, MCS2000-CTDA or MCS2000-CTLC Tension Controls. Additionally when the MCS2000-ECA is used, the MCS2000-PSDRV2 can supply the 24 VDC power for operating the controller as well.
Wiring between the various controls will vary somewhat, but for all practical purposes are pretty similar.
The MCS2000-PSDRV2 will operate with any of the 24 volt Warner Electric Tension Brakes or Clutches as long as the maximum current rating per channel is not exceeded.
Wiring to the MCS2000-ECA Control
Refer to Figure 2 for wiring hook-ups.
CAUTION: It is recommended that shielded cable or twisted wire pairs be used to minimize the possibly of noise affecting either the controller or driver circuitry. Additionally, lead lengths should be kept as short as possible.
If only a single brake is to be used on the MCS2000-PSDRV2, then skip to either the 24 volt brake wiring section, page 8 or the 48 Volt brake wiring section, page 10.
o 3. Connect a wire from terminal Out 2 (V) on
the MCS2000-ECA to terminal number 3 InB 0-10 V on the MCS2000-PSDRV2. Insure that both terminals are tightened securely.
o 4. Connect a wire from terminal Out 1 (0V) on
the MCS2000-ECA to terminal number 4 0V on the MCS2000-PSDRV2. Insure that both terminals are tightened securely.
o 5. This completes the wiring between the
MCS2000-ECA and the MCS2000­PSDRV2. Double check all wiring before proceeding to the next section.
o 6. Proceed to either the 24 volt brake wiring
section, page 8 or the 48 volt brake wiring section, page 10 of the manual.
Note: Also refer to MCS2000-ECA Manual for
exact terminal strip locations and designations.
o 1. Connect a wire from terminal Out 1 (V) on
the MCS2000-ECA to terminal number 1 InA 0-10 V on the MCS2000-PSDRV2. Insure that both terminals are tightened securely.
o 2. Connect a wire from terminal Out 1 (0V) on
the MCS2000-ECA to terminal number 2 0V on the MCS2000-PSDRV2. Insure that both terminals are tightened securely.
If a dual brake system is to be used, then proceed to step 3.
Warner Electric • 800-825-9050 P-2010-7 • 819-0525
5
(green)
(red)
MSC2000-PSDRV2
“A” Antiresidual
Channel A
“B” Antiresidual
Channel B
1 2 3 4 5 6 7 8 9
10
InA 0-10V
0-V
InB 0-10V
0V
Brk A+ Brk A­Brk B+ Brk B-
-DC Pwr
+24-48V
+24V
+24V
0V
0V
MCS2000-ECA Controller
MCS2000-PSDRV2 Driver
Note: Wiring is shown for both channels. If only one channel is required, then follow wiring for channel “A”.
Figure 2 MCS2000-ECA to MCS2000-PSDRV2
Wiring to the MCS2000-CT’S Controllers
Note: Since the MCS2000-CTDA and
MCS2000-CTLC controllers have
25 pin DB connectors with cables
wiring is made via the cable.
Care must be taken to insure the correct wires are connected and none of the other wires contact or short out. It is recommended that unused wires be cut off and taped so that shorting and grounding out does not occur.
Note: Refer to the MCS2000-CTDA or
MCS2000-CTLC Manual for exact wire
functions and designations.
Refer to Figure 3 for wiring hook-ups.
Warner Electric • 800-825-9050 P-2010-7 • 819-0525
6
o 1. Connect the brown wire [Channel 1 Out
(V)] from the connector cable on the MCS2000-CT controller to terminal 1 In A 0 – 10 V on the MCS2000-PSDRV2. Insure that the terminal on the MCS2000-PSDRV2 is tightened securely.
o 3. Connect the red wire [Channel 2 Out (V)]
from the connector cable on the MCS2000-CT controller to terminal 3 In B 0-10 V on the MCS2000-PSDRV2. Insure that the terminal on the MCS2000-PSDRV2 is tightened securely.
o 2. Connect the green wire [Channel 1 Out
(0V)] from the connector cable on the MCS2000-CT controller to terminal 2, 0 V on the MCS2000-PSDRV2. Insure that the terminal on the MCS2000-PSDRV2 is tightened securely.
If a dual brake system is to be used, then proceed to step 3.
If only a single brake is to be used on the MCS2000-DRV2, then skip to either the 24 volt brake wiring section, page 8 or the 48 volt brake wiring section, page 10.
o 4. Connect the black wire [Channel 2 Out
(0V)] from the connector cable on the MCS2000-CT controller to terminal 4 on the MCS2000-PSDRV2. Insure that the terminal on the MCS2000-PSDRV2 is tightened securely.
o 5. This completes the wiring between the
MCS2000-CT and the MCS2000-PSDRV2. Double check all wiring before proceeding to the next section C.
o 6. Proceed to either the 24 volt brake wiring
section, page 8 of the manual or the 48 volt brake wiring section, page 10 of the manual.
Note: Wiring is shown for both channels. If only
one channel is required, then follow wiring using only the brown and green wires as shown.
MCS2000-CT Cable and Connector MCS2000-PSDRV2 Driver
Figure 3 MCS2000-CTDA or MCS2000-CTLC to MCS2000-PSDRV2
Warner Electric • 800-825-9050 P-2010-7 • 819-0525
7
Power and Brake Wiring
24 Volt Systems Using The Internal 24V Power Supply
Brake Wiring (Optional AC Power Wiring)
o 1. Wire the positive (+) side of the 24 volt DC
power supply to terminal 10 of the
MCS2000-PSDRV2. Make sure that the
terminal is securely tightened on the
MCS2000-PSDRV2.
o 2. Wire the negative side (-) or DC common
of the 24 volt DC power supply to terminal
9 of the MCS2000-PSDRV2. Make sure
the terminal is securely tightened on the
MCS2000-PSDRV2.
Using External 24 VDC Power Source
o 1. Connect the positive side of the 24 VDC
power source to the positive (+) input,
terminal 10. Tighten terminal securely.
o 2. Connect the negative side of the 24 VDC
power source to the negative (-) input,
terminal 9. Tighten terminal securely.
o 1. Wire the brake for Channel “A” on
terminals 5 and 6 of the MCS2000­PSDRV2. Make sure the terminals are securely tightened.
o 2. If a brake is to be used on Channel “B”
wire the brake to the Channel “B” terminals 7 and 8 on the MCS2000­PSDRV2. Make sure the terminals are securely tightened.
o 3. Wire AC power; hot neutral, and ground to
the power input terminals on the right side of the MCS2000-PSDRV2. Make sure terminals are securely tightened.
Note: Warner Electric Tension brakes are not
polarity sensitive, so wiring between terminals on the MCS2000-DRV2 and brake are not sensitive to the + and ­designations.
Note: Make sure the current capacity is sufficient
to handle the brake load and driver
circuitry. If any other external power
requirements are required, then the power
supply capacity must be sized to handle
these currents as well.
TB Series ATT Series MTB Series Magnetic Particle
TB-170 TB-260 TB-425 TB-500 TB-825
ATTB/ATTC-25 ATTB/ATTC-55
ATTB/ATTC-115
All MTB’s up to 12
*Up to 16 magnets if
outputs paralleled and
inputs paralleled TB-1000 TB-1225 TB-1525
The following 24 volt tension brakes can be used with the MCS2000-DRV2 Driver for 24 volt operation.
MPB/MPC2
magnets
MPB/MPC15 MPB/MPC70
MPB/MPC120
MPB240
POB/POC-0.3 to 20’s
PRB-H’s 1.2 to 20’s
PTB’s 2.5 to 20’s
PMC-A’s 10 to 40’s
PHC-R 0.6 to 40’s
*POB/POC-40 & 80 if output
and inputs paralleled
* When 16 magnet MTB Brakes and POB/POC-40 and 80 Magnetic Particle Brakes are used, inputs and outputs must be wired parallel to obtain sufficient output current for proper brake.
Warner Electric • 800-825-9050 P-2010-7 • 819-0525
8
Brake
Brake
“A”
“B”
24 Volt Power
Supply
- DC
+DC
MSC2000-DRV2
“A” Antiresidual
Channel A
“B” Antiresidual
Channel B
1. In A 0-10V
2. 0V
3. In B 0-10V
4. 0V
5. Brk A+
6. Brk A-
7. Brk B+
8. Brk B-
9. -DC Power
10. + 24 - 48 VDC
Wiring with 24 volt DC External Power Supply
Figure 4 24 Volt System Power Supply and Brake Wiring
Wiring using internal 24 volt DC Power
MCS2000-PSDRV2 Power Supply /Driver
Note: If the internal power supply is used, the maximum current available is 3.1 amps. If higher current is required, then either a second MCS2000-PS power supply is required or an external 24 VDC source is needed in place of the internal supply.
48 Volt Systems
Note: Make sure the current capacity is
sufficient to handle the brake load and driver circuitry. If any other external power requirements are required, then the power supply capacity must be sized to handle these currents as well.
o 3. Wire the brake for Channel “A” on
terminals 5 and 6 of the MCS2000-
o 1. Wire the positive (+) side of the 48 volt DC
power supply to terminal 10 of the MCS2000-PSDRV2. Make sure that the terminal is securely tightened on the MCS2000-PSDRV2.
o 2. Wire the negative side (-) or DC common
of the 48 volt DC power supply to terminal 9 of the MCS2000-PSDRV2. Make sure the terminal is securely tightened on the
Warner Electric • 800-825-9050 P-2010-7 • 819-0525
MCS2000-PSDRV2.
o 4. If a brake is to be used on Channel “B”
PSDRV2. Make sure the terminals are securely tightened.
wire the brake to Channel “B” terminals 7 and 8 on the MCS2000-PSDRV2. Make sure the terminals are securely tightened.
9
Note: Warner Electric Tension brakes are not
polarity sensitive, so wiring between terminals on the MCS2000-DRV2 and brake are not sensitive to the + and
ATT Series MTB Series Magnetic Particle
- designations.
The following 24 volt tension brakes can be used with the MCS2000-DRV2 Driver for 48 volt operation with overcurrent feature.
ATTB/ATTC-25 ATTB/ATTC-55
ATTB/ATTC-115
All MTB’s up to 12
magnets
* Up to 16 magnets if
outputs paralleled
MPB/MPC2 MPB/MPC15 MPB/MPC70
MPB/MPC120
MPB240
POB/POC-0.3 to 20’s
PRB-H’s 1.2 to 20’s
PTB’s 2.5 to 20’s
PMC-A’s 10 to 40’s
PHC-R 0.6 to 40’s
*POB/POC-40 & 80 if output
and inputs paralleled
* When 16 magnet MTB Brakes and POB/POC-40 and 80 Magnetic Particle Brakes are used, inputs and outputs must be wired parallel to obtain sufficient output current for proper brake operation.
48 Volt DC Power Supply
MCS2000-PSDRV2 Driver
Figure 5 48 Volt System Power Supply and Brake Wiring
Warner Electric • 800-825-9050 P-2010-7 • 819-0525
10
System Start-Up
AR “A”
Channel “A”
The Channel “A” is operating in the anti-residual mode with the following indication.
Flashing “ON” 1.5 sec, “OFF” 0.5 sec
RED LED is “OFF”
- (Green)
- (Green LED)
- (Red LED)
24 Volt System
o 1. Prior to applying power, double check all
wiring between Tension Control and Driver, Driver and Brake or Brakes, and 24 Volt Power Source and Driver.
o 2. Once connections are checked and
confirmed that all wiring is correct, turn power on to the Power Supply and Controller and observe “RED” and “GREEN” LED Indicators on the Driver.
o 3. If everything is normal, then the “GREEN”
LED will be on and “RED” LED’s will be off. Any other indication of the “RED” and “GREEN” LED’s refer to the troubleshooting section, page 17 of the manual for troubleshooting and diagnostics.
o 4. If drive is functional and no problems are
noted, then the Anti-residual output to the brake or brakes needs to be adjusted accordingly. Adjust the anti-residual output for Channel “A” as follows:
o 4a. Using a digital DC Voltmeter,
connect the positive lead to terminal 1 and the negative lead to terminal 2 of the MCS2000­PSDRV2 for Channel “A” input.
o 4b. Adjust the Tension controller being
used to give a 0 VDC reading on the Channel “A” input.
o 4c. Using a small screwdriver, rotate
the anti-residual potentiometer “A” fully counter-clockwise so the output voltage to the brake is zero level. Voltage can be measured to the Channel “A” brake on terminals 5 and 6 of the MCS2000-PSDRV2. Terminal 5 is positive, and terminal 6 is negative. Note that the “GREEN” LED for Channel “A” is flashing at this time.
o 4d. Now slowly adjust the anti-residual
potentiometer “A” clockwise while feeling the reaction on the brake. When the optimum anti-residual output is obtained, the brake will be very free to rotate or the armatures, in the case of the TB’s, will feel like they are floating away from the magnet assembly.
Note: Using a meter across the brake “A”
terminals 5 and 6 as noted in 4c above, the voltage observed should be negative at this time.
o 4e. Once this point is found, do not
adjust this potentiometer further or the brake can re-engage.
o 4f. If a second brake is used on
Channel “B”, then proceed to step 5 otherwise this completes the anti-residual adjustment for the “A” Channel. Continue to step 6.
The following LED indications will be present
Warner Electric • 800-825-9050 P-2010-7 • 819-0525
11
when anti-residual current is applied to the brake.
AR “B”
Channel “B”
The Channel “B” is operating in the anti-residual mode with the following indication.
Flashing “ON” 1.5 sec, “OFF” 0.5 sec
RED LED is “OFF”
- (Green)
- (Green)
- (Red)
flashing at this time.
o 5. Adjust the anti-residual output for Channel
“B” as follows if a brake is used on this output. If no brake is used, then disregard this portion of the start-up. Proceed to step 6.
o 5a. Using a digital DC Voltmeter,
connect the positive lead to terminal 3 and the negative lead to terminal 4 of the MCS2000­PSDRV2 for Channel “B” input.
o 5b. Adjust the Tension controller being
used to give a 0 VDC reading on the Channel “B” input.
o 5c. Using a small screwdriver, rotate
the anti-residual potentiometer “B” fully counter-clockwise so the output voltage to the brake is zero level. Voltage can be measured to the Channel “B” brake on terminals 7 and 8 of the MCS2000-PSDRV2. Terminal 7 is positive, and terminal 8 is negative. Note that the “GREEN” LED for Channel “B” is
o 5d. Now slowly adjust the anti-residual
potentiometer “B” clockwise while
feeling the reaction on the brake.
When the optimum anti-residual
output is obtained, the brake will be
very free to rotate or the armatures,
in the case of the TB’s, will feel like
they are floating away from the
magnet assembly.
Note: Using a meter across the brake “B”
terminals 7 and 8 as noted in 5c above, the voltage observed should be negative at this time.
o 5e. Once this point is found, do not
adjust this potentiometer further or
the brake can re-engage.
o 5f. This completes the adjustment for
the Channel “B” anti-residual.
Proceed to step 6.
Warner Electric • 800-825-9050 P-2010-7 • 819-0525
12
The following LED indications will be present when anti-residual current is applied to the brake.
o 6. Adjust the input voltage from the tension
controller to the Channel “A” input observing the “RED” and “GREEN” LED’s. If a 24 volt system is being commissioned, then only the “GREEN” LED should be functional unless there is a problem with the controller, brake, or wiring.
proceed to the troubleshooting section on page 17 to determine cause and appropriate action to take.
48 Volt System
o 1. Prior to applying power double check all
wiring between Tension Control and Driver, Driver and Brake or Brakes, and 48 Volt Power Source and Driver.
o 7. If no other indications are present on the
LED’s then the system is functioning properly. The intensity of the “GREEN” LED does not change with the amount of output current being supplied to the brake.
o 8. If other LED indications are present,
proceed to the troubleshooting section on page 17 to determine cause and appropriate action to take.
o 9 Adjust the input voltage from the tension
controller to the Channel “B” input if a brake is connected to the Channel “B” output observing the “RED” and “GREEN” LED’s. If a 24 volt system is being commissioned, then only the “GREEN” LED should be functional unless there is a problem with the controller, brake, or wiring.
o 10. If no other indications are present on the
LED’s then the system is functioning properly. The intensity of the “GREEN” LED will not change with the amount of output current being supplied to the brake.
o 11. If other LED indications are present,
o 2. Once connections are checked and
confirmed that all wiring is correct, turn power on to the Power Supply and Controller and observe “RED” and “GREEN” LED Indicators on the Driver.
o 3. If everything is normal, then the
“GREEN” LED will be on and “RED” LED’s will be off. Any other indication of the “RED” and “GREEN” LED’s, refer to the troubleshooting section, page 17 of the manual for troubleshooting and diagnostics
o 4. If drive is functional and no problems are
noted, then the anti-residual output to the brake or brakes needs to be adjusted according. Adjust the anti-residual output for Channel “A” as follows.
o 4a. Using a digital DC Voltmeter,
connect the positive lead to terminal 1 and the negative lead to terminal 2 of the MCS2000­PSDRV2 for Channel “A” input.
o 4b. Adjust the Tension controller being
used to give a 0 VDC reading on the Channel “A” input.
o 4c. Using a small screwdriver, rotate
the anti-residual potentiometer “A” fully counter-clockwise so the output voltage to the brake is zero level. Voltage can be measured to the Channel “A” brake on terminals 5 and 6 of the MCS2000-PSDRV2.
Warner Electric • 800-825-9050 P-2010-7 • 819-0525
13
o 4d. Now slowly adjust the anti-residual
AR “B”
Channel “B”
- (Green)
- (Red)
The Channel “B” is operating in the anti-residual mode with the following indication.
Flashing “ON” 1.5 sec, “OFF” 0.5 sec
RED LED is “OFF”
- (Green)
potentiometer “A” clockwise while feeling the reaction on the brake. When the optimum anti-residual output is obtained, the brake will be very free to rotate without much resistance. This is best if done at core diameter.
Note: Using a meter across the brake “A”
terminals 5 and 6 as noted in 4c above, the voltage observed should be negative at this time.
o 4e. Once this point is found, do not
adjust this potentiometer further or the brake can re-engage.
o 4f. If a second brake is used on
Channel “B”, then proceed to step 5 otherwise this completes the anti-residual adjustment for the “A” Channel. Continue to step 6.
The following LED indications will be present when anti-residual current is applied to the brake.
This is anti-residual mode only.
o 5. Adjust the anti-residual output for Channel
“B” as follows if a brake is used on this output. If no brake is used, then disregard this portion of the start-up. Proceed to step 6.
o 5c. Using a small screwdriver, rotate the
anti-residual potentiometer “B” fully counter-clockwise so the output voltage to the brake is zero level. Voltage can be measured to the Channel “B” brake on terminals 7
o 5a. Using a digital DC Voltmeter,
connect the positive lead to terminal 3 and the negative lead to terminal 4 of the MCS2000-PSDRV2 for Channel “B” input.
o 5b. Adjust the Tension controller being
o 5d. Now slowly adjust the anti-residual
used to give a 0 VDC reading on the
Warner Electric • 800-825-9050 P-2010-7 • 819-0525
14
Channel “B” input.
and 8 of the MCS2000-PSDRV2. Terminal 7 is positive, and terminal 8 is negative. Note that the “GREEN” LED for channel “B” is flashing at this time.
potentiometer “B” clockwise while feeling the reaction on the brake. When the optimum anti-residual
output is obtained, the brake will be
AR “B”
Channel “B”
- (Green)
- (Red)
The Channel “B” is operating in the anti-residual mode with the following indication.
Flashing “ON” 1.5 sec, “OFF” 0.5 sec
RED LED is “OFF”
- (Green)
very free to rotate without much resistance. This is best if done at core diameter.
Note: Using a meter across the brake “B”
terminals 7 and 8 as noted in 5c above, the voltage observed should be negative at this time.
o 5e. Once this point is found, do not
adjust this potentiometer further or the brake can re-engage.
o 5f. This completes the adjustment for
the Channel “B” anti-residual. Proceed to step 6.
The following LED indications will be present when anti-residual current is applied to the brake.
This is anti-residual mode only.
o 6. Adjust the input voltage from the tension
controller to the Channel “A” input observing the “RED” and “GREEN” LED’s. If a 48 volt system is being commissioned, then only the “GREEN” LED should be functional with the input voltage between the 0 to 5 volt level, unless there is a problem with the controller, brake, or wiring.
o 6b. Allow the control to operate in this
mode for 60 seconds or more and observe the LED’s. After the Overexcitation circuit times out, the “RED” LED will be flashing at a frequency of approximately 30 hertz with the LED being “ON” approximately 1 second and “OFF” approximately 1 second. Measuring
o 6a. Adjust the input voltage from the
tension controller to the Channel “A” input above 5 volts while observing
the output to the brake on Terminals 5 and 6 should indicate the brake is
at 24 volts DC. the “GREEN” and “RED” LED’s. The “GREEN” LED should be on steady and the “RED” LED should be flashing at a rate of approximately 30 hertz frequency with the LED on for typically 0.5 second and off for
Warner Electric • 800-825-9050 P-2010-7 • 819-0525
1.5 seconds. This indicates the brake is operating in the overcurrent mode and will be limited to 60 seconds.
o 6c. Reduce the input on Terminals 1 and
2 to less than 5 volts DC and
observe the LED’s at this time. The
“GREEN” LED will be “ON”, and the
“RED” LED will be flashing at a
frequency of approximately 20 hertz,
with the “ON” time of approximately
0.5 second and the “OFF” time of
approximately 2.5 seconds. The
15
operate in the 0 to 24 volt range, but the overexcitation level from 24 volts to 48 volts is not available as the circuit has not reset as yet.
o 6d. Once the overexcitation has reset,
the “GREEN” LED will be “ON” and the “RED” LED will be flashing as in step 6a above when the input voltage goes above 5 volts again at Terminals 1 and 2 of the MCS2000-PSDRV2.
o 7. If no other indications are present on the
LED’s then the system is functioning properly. The intensity of the “GREEN” LED does not change with the amount of output current being supplied to the brake. This completes the checkout of the “A” Channel. Proceed to step 9.
o 8. If LED indications are present other than
those described above, proceed to the troubleshooting section on page 17 to determine cause and appropriate action to take.
o 9. Adjust the input voltage from the tension
controller to the Channel “B” input observing the “RED” and “GREEN” LED’s. If a 48 volt system is being commissioned, then only the “GREEN” LED should be functional with the input voltage between the 0 to 5 volt level, unless there is a problem with the controller, brake, or wiring.
o 9a. Adjust the input voltage from the
tension controller to the Channel “B” input above 5 volts while observing the “GREEN” and “RED” LED’s. The “GREEN” LED should be on steady and the “RED” LED should be flashng at a rate of approximately 30 hertz frequency with the LED on for typically 0.5 second and off for 1.5 seconds. This indicates the brake is operating in the overcurrent mode and will be limited to 60 seconds.
overexcitation circuit times out, the “RED” LED will be flashing at a frequency of approximately 30 hertz with the LED being “ON” approximately 1 second and “OFF” approximately 1 second. Measuring the output to the brake on Terminals 5 and 6 should indicate the brake is at 24 volts DC.
o 9c. Reduce the input on Terminals 3
and 4 to less than 5 volts DC and observe the LED’s at this time. The “GREEN” LED will be “ON”, and the “RED” LED will be flashing at a frequency of approximately 20 hertz, with the “ON” time of approximately 0.5 second and the “OFF” time of approximately 2.5 seconds. The control output to the brake can operate in the 0 to 24 volt range, but the overexcitation level from 24 volts is not available as the circuit has not reset as yet.
o 9d. Once the overexcitation has reset,
the “GREEN” LED will be “ON” and the “RED” LED will be flashing as in step 6a above when the input voltage goes above 5 volts again at Terminals 3 and 4 of the MCS2000-PSDRV2.
o 10. If no other indications are present on
the LED’s then the system is functioning properly. The intensity of the “GREEN” LED does not change with the amount of output current being supplied to the brake. This completes the checkout of the “B” Channel. The system is now ready for set-up of the controller. Proceed to the controller manual to set up the controller properly.
o 11. If LED indications are present other than
those described above, proceed to the troubleshooting section on page 17 to determine cause and appropriate action to take.
o 9b. Allow the control to operate in this
mode for 60 seconds or more and
o 12. This completes the set up of the
MCS2000-DRV2 Driver.
observe the LED’s. After the
Warner Electric • 800-825-9050 P-2010-7 • 819-0525
16
LED’s
Green Green Red Red
ON
ON
ON
ON
OFF
OFF
OFF
OFF
LED Operation Functional Description
MCS2000-PSDRV2 is Powered Off
MCS2000-PSDRV2 is “ON” and ready
MCS2000-PSDRV2 is in anti-residual mode
MCS2000-PSDRV2 Overcurrent enabled Limited to 60 sec maximum at full output.
MCS2000-PSDRV2 Overcurrent limit has gone past 60 sec. Output has reduced back to 24 volts.
MCS2000-PSDRV2 Normal operation but overcurrent is not available as it is still in limit mode and will reset on time out.
0.5 Sec ON/2.5 sec OFF
1 Sec ON/1 Sec OFF
0.5 Sec ON/1.5 Sec OFF
1.5 Sec ON/0.5 Sec OFF
System Troubleshooting
Troubleshooting the MCS2000-PSDRV2 Dual Channel/Dual Voltage Driver is fairly straight forward. There are certain basic checks that can be made using a digital meter. All readings taken on the MCS2000-PSDRV2 will be either DC voltages or DC currents, or AC line voltage. A meter sufficient to measure up to 100 VDC and 10 Amps DC and 300 VAC will be suitable for taking any of the measurements deemed necessary.
Additionally, the MCS2000-PSDRV2 offers a certain amount of diagnostics built into the unit via the “GREEN” and “RED” LED’s for troubleshooting purposes.
As with any electronic device, care should be taken when installing, wiring and commissioning the unit. Failure to do so may damage or destroy the driver and void the warranty.
The following diagnostic indications are possible with the two indicator LED’s on the face of the controller.
Figure 6 LED Indicator Operations and Descriptions – Normal Operation
Note: Each Channel “A” and “B” can be operated independently, so one channel can have one set of indications while the second channel can have a completely different set of indications. This will be dependent on how controller is set to operate the MCS2000- PSDRV2 Driver.
Warner Electric • 800-825-9050 P-2010-7 • 819-0525
17
The following chart shows a comparison of the MCS2000-PSDRV, MSC2000-PSDRVH and the
LED’s
Green
Green
Red
Red
LED Operation
OFF
OFF
ON
ON ON
Functional Description
Internal installation error at power up. Fault Error. Output locked “OFF”, Driver has tripped.
Return MCS2000-PSDRV2 for Repair.
0.5 Sec ON/0.5 Sec OFF
1.5 Sec ON/0.5 Sec OFF
Short Circuit or Overload on Output at Power Up. Output Locked “OFF”, Driver has tripped.
Reset by Power Off and then Power On.
Short Circuit or Overload during normal operation. Output Locked “OFF”. Driver has tripped.
Reset by Power Off and then Power On.
Internal auxiliary power supply out of tolerance. Output Locked “OFF”.
Auto Reset when condition clears.
Internal auxiliary power supply failure or drive power supply greater than 48 VDC, +10%. Output Locked “OFF”.
Auto Reset when condition clears.
OR
MCS2000-PSDRV2 terminal connections.
Figure 7 LED Indicator Operations and Descriptions – Fault Conditions
Warner Electric • 800-825-9050 P-2010-7 • 819-0525
18
Other Potential Faults
Symptom Possible Solution
Check LED’s for various conditions.
Check incoming DC power to MCS2000-PSDRV2 either 24 VDC or 48 VDC. Check that power is applied.
No Output to Brake
Brake does not produce sufficient torque
Brake seems to drag when off
If unit has power, check that input signals to Input “A” and Input “B” vary between 0 and 10 VDC.
Check that brake coil is not open by doing a resistance check on the magnet coil. Refer to the Tension
Catalog for proper resistance.
Check that brake is wired to the MCS2000-PSDRV2.
Verify that the brake is the proper size for the application. Contact Warner Electric for assistance.
Check that maximum voltage is being applied to the brake. Also, check that brake coil is drawing rated current at maximum voltage by placing a digital current meter in series with one of the brake leads.
Check the Driver LED’s to insure that the control has not gone into a fault condition.
Check mechanically that the brake armature or magnets are free and not binding and can engage properly.
Check that the input signal to the Channel “A” and Channel “B” inputs goes to full 10 volts on the control inputs. If inputs do not go to 10 volts maximum, check the controller for proper operation and set up. Refer to the particular control manual for proper adjustments.
Check that the anti-residual output is set properly. Too little output and the brake will drag due to possibly high residual.
Check that the anti-residual output is not adjusted too high. Adjusting the anti-residual too high can result in the brake re-engaging.
Refer to the Anti-Residual Adjustment section of this manual for proper adjustment and readjust as necessary.
The MCS2000-PSDRV2 is a universal driver designed as a replacement for the previous MCS2000-PSDRV and MCS2000-PSDRVH in one version.
The MCS2000-DRV2 is different from
Terminal block connections are slightly different on the MCS2000-PSDRV2 since the previous drivers had additional inputs that typically were not used.
my old driver
If the application used some of the previous terminals, then consult the factory for assistance in making the MCS2000-PSDRV2 compatible for the application.
Warner Electric • 800-825-9050 P-2010-7 • 819-0525
19
The following chart shows a comparison of the MCS2000-PSDRV, MSC2000-PSDRVH and the MCS2000-PSDRV2 terminal connections.
These only apply to the Driver portion of the pluggable terminal block. The Power Supply section between the three versions are the same and did not change.
MCS2000-DRV MCS2000-PSDRV2 MCS2000-DRVH MCS2000-PSDRV2
REF 10 V
0 V
In BxV
In B 0 – 10 V
0 V
In AxV
In A 0 – 10 V
0 V
BRK COM
BRK B +
BRK COM
BRK A +
+ 24 V
0 V
Not Available Not Available Not Available
Terminal #3 Terminal #4
Not Available
Terminal #1 Terminal #2 Terminal #8 Terminal #7 Terminal #6 Terminal #5
Terminal #10
Terminal #9
Ref 10 V
0 V
In BxV
In B 0 – 10 V
In B 0 – 20 ma
Out BxV
0 V
In AxV
In A 0 – 10 V
In A 0 – 20 ma
Out AxV
0 V
BRK B +
BRK COM
BRK A +
BRK COM
+ 48 V
0 V
Not Available Not Available Not Available
Terminal #3 Not Available Not Available
Terminal #4 Not Available
Terminal #1 Not Available Not Available
Terminal #2
Terminal #7
Terminal #8
Terminal #5
Terminal #6
Terminal #10
Terminal #9
If problems arise that are not covered in the above troubleshooting section, then either the local Warner Electric Representative or Warner Electric Distributor should be contacted for additional assistance.
This completes the installation of the MCS2000-PSDRV2 Driver. This manual covers only the Driver and does not cover the controller part of the system. Refer to the appropriate manual for set-up and operation of the controller. Failure to do so could result in damage to the controller and/or driver and possibly void the warranty.
Warner Electric • 800-825-9050 P-2010-7 • 819-0525
20
Figure Description
Page Number
Figure 1 Outline and Mounting Dimensions 4
Figure 2
Figure 3
MCS2000-ECA to MCS2000-DRV2 Wiring 6
MCS2000-CTxx to MCS2000-DRV2 Wiring 7
Figure 4 24 Volt Power and Brake Wiring 9
Figure 5 48 Volt Power and Brake Wiring 10
Figure 6
Figure 7
LED Indicator Operations and Descriptions – Normal 17 LED Indicator Operations and Descriptions – Faults 18
Warner Electric • 800-825-9050 P-2010-7 • 819-0525
21
Warranty
Warner Electric LLC warrants that it will repair or replace (whichever it deems advisable) any product manufactured and sold by it which proves to be defective in material or workmanship within a period of one (1) year from the date of original purchase for consumer, commercial or industrial use.
This warranty extends only to the original purchaser and is not transferable or assignable without Warner Electric LLC’s prior consent.
Warranty service can be obtained in the U.S.A. by returning any defective product, transportation charges prepaid, to the appropriate Warner Electric LLC factory. Additional warranty information may be obtained by writing the Customer Satisfaction Department, Warner Electric LLC, 449 Gardner Street, South Beloit, Illinois 61080, or by calling 815-389-3771.
A purchase receipt or other proof of original purchase will be required before warranty service is rendered. If found defective under the terms of this warranty, repair or replacement will be made, without charge, together with a refund for transportation costs. If found not to be defective, you will be notified and, with your consent, the item will be repaired or replaced and returned to you at your expense.
This warranty covers normal use and does not cover damage or defect which results from alteration, accident, neglect, or improper installation, operation, or maintenance.
Some states do not allow limitation on how long an implied warranty lasts, so the above limitation may not apply to you.
Warner Electric LLC’s obligation under this warranty is limited to the repair or replacement of the defective product and in no event shall Warner Electric LLC be liable for consequential, indirect, or incidental damages of any kind incurred by reason of the manufacture, sale or use of any defective product. Warner Electric LLC neither assumes nor authorizes any other person to give any other warranty or to assume any other obligation or liability on its behalf.
WITH RESPECT TO CONSUMER USE OF THE PRODUCT, ANY IMPLIED WARRANTIES WHICH THE CONSUMER MAY HAVE ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL CONSUMER PURCHASE. WITH RESPECT TO COMMERCIAL AND INDUSTRIAL USES OF THE PRODUCT, THE FOREGOING WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER WARRANTIES, WHETHER EXPRESSED OR IMPLIED BY OPERATION OF LAW OR OTHERWISE, INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from state to state.
Changes in Dimensions and Specifications.All dimensions and specifications shown in Warner Electric catalogs are subject to change without notice. Weights do not include weight of boxing for shipment. Certified prints will be furnished without charge on request to Warner Electric.
Warner Electric LLC
31 Industrial Park Road • New Hartford, CT 06057 815-389-3771 • Fax: 815-389-2582 www.warnerelectric.com
P-2010-7 • 819-0525 6/12 Printed in USA
Loading...