The information and descriptions contained herein are the property of WALCHEM Corporation. Such
information and descriptions may not be copied or reproduced by any means, or disseminated or
distributed without the express prior written permission of WALCHEM Corporation, 5 Boynton Road,
Holliston, MA 01746.
This document is for information purposes only and is subject to change without notice.
Statement of Limited Warranty
WALCHEM Corporation warrants equipment of its manufacture, and bearing its identification to be free
from defects in workmanship and material for a period of 24 months for electronics and 12 months for
mechanical parts and electrodes from date of delivery from the factory or authorized distributor under
normal use and service and otherwise when such equipment is used in accordance with instructions
furnished by WALCHEM Corporation and for the purposes disclosed in writing at the time of purcha se, if
any. WALCHEM Corporation's liability under this warranty shall be limited to replacement or repair,
F.O.B. Holliston, MA U.S.A. of any defective equipment or part which, having been returned to
WALCHEM Corporation, transportation charges prepaid, has been inspected and determined by
WALCHEM Corporation to be defective. Replaceable elastomeric parts and glass components are
expendable and are not covered by any warranty.
THIS WARRANTY IS IN LIEU OF ANY OTHER WARRANTY, EITHER EXPRESS OR IMPLIED, AS TO
DESCRIPTION, QUALITY, MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE OR
USE, OR ANY OTHER MATTER.
7.2 Conductivity Readout Does Not Change................................................................................36
7.3 Procedure for Evaluation of Conductivity Electrode...............................................................37
8.0 SERVICE POLICY .....................................................................................................................37
1.0 INTRODUCTION
The Walchem WBL Series controllers offer conductivity control of boiler water and control of chemical
feed. The WBL400 series controller has one feed/auxiliary relay available. The WBL410 series
controller has four feed/auxiliary relays. The chemical feed pump may be selected to operate in one of
the following modes:
Feed and Blowdown
Feed and Blowdown with Lockout
Feed as a percent of Blowdown
Feed as a percent of Time
Feed based on a Water Contactor input
Feed based on a Paddlewheel Water meter input
The WBL series boiler controller is supplied with a temperature compensated stainless steel electrode
with a cell constant of 1.0. The controller is a microprocessor driven industrial type with on/off control
outputs. Timed sample or continuous modes may be selected. An optional isolated 4-20 mA output that
is proportional to the conductivity reading is available for all models.
Any set point may be viewed without interrupting control. Each set point change will take effect as soon
as it is entered. An access code is available to protect set point parameters, while still allowing settings to
be viewed.
Our unique USB feature provides the ability to upgrade the software in the controller to the latest
version.
An advanced USB capability option is available. The Config file feature allows you to save all the set
points from a controller onto a USB flash disk, and then import them into another controller, making the
programming of multiple controllers fast and easy. The data logging feature allows you to save the last
months readings and events to a USB flash disk.
1
2.0 SPECIFICATIONS
2.1 Measurement Performance
Conductivity Range 0 - 10,000 µS/cm (microSiemens/centimeter)
Conductivity Resolution 1 µS/cm
Conductivity Accuracy 10 - 10,000 µS/cm ±1% of reading
Mechanical Relays Pre-powered on circuit board switching line voltage
4 - 20 mA (optional) Internally powered
Agency Approvals
UL ANSI/UL 61010-1:2004, 2
CAN/CSA C22,2 No.61010-1:2004 2
CE Safety EN 61010-1 2
CE EMC EN 61326 :1998 Annex A*
Note: For EN61000-4-6,-3 the controller met performance criteria B.
*Class A equipment: Equipment suitable for use in establishments other than domestic, and those directly
connected to a low voltage (100-240 VAC) power supply network which supplies buildings used for
domestic purposes.
0 - 10 µS/cm ±20% of reading
100-240 VAC, 50/60 Hz, 8A
Fuse: 1.0 ampere, 5 x 20 mm
6 A (resistive), 1/8 HP
All relays are fused together as one group, total current for this
group must not exceed 6A.
Two relays for WBL400 models, six relays for WBL410 models.
Fully isolated
600 Ohm max resistive load
Resolution .001% of span
Accuracy ± 1% of reading
nd
Edition (2001)*
nd
Edition*
nd
Edition*
2.3 Mechanical
Enclosure Material Polycarbonate
Operating Ambient Temp 32 – 122°F (0 – 50°C)
Storage Temperature -20 – 180°F (-29 – 80°C)
Electrode mounting ¾" NPTF
Electrode rating 250 psi at 392°F (17.2 bars at 200°C)
Electrode material 316 SS and PEEK
NEMA Rating NEMA 4X
Dimensions 8.5" x 6.5" x 5.5"
Display 2 x 16 character backlit liquid crystal
2
2.4 WBL Variables and their Limits
Low Limit High Limit
Conductivity menu
Temperature Menu
BlowdownMenu
Set Point 0 µS/cm 10,000 µS/cm
Dead Band 5 µS/cm 500 µS/cm
Blowdown Limit Time (set in hours/minutes) 1 minute 8 hrs: 20 min
Feed Menu
Feed Lockout Timer (Mode A) 1 second 99 min: 59 sec
Percent of Blowdown (Mode B) 5 % 99 %
Feed Time Limit (Mode B) 1 minute 99 min: 59 sec
Percent of Time (Mode C) 0.1 %99 %
Feed Cycle Time (Mode C) 10 minutes 59 min: 59 sec
Time per Contact (Mode D) 1 second 59 min: 59 sec
÷ Contacts by (Mode D) 1 contact 100 contacts
Time Limit (Mode D & E) 1 minute 99 min: 59 sec
Time/Vol (Mode E) 1 second 59 min: 59 sec
Vol to Initiate Feed (Mode E) 1 9,999
K Factor (Mode E) 1 pulse/vol 20,000 pulses/vol
4-20 mA Menu 4 & 20 mA Settings 0 µS/cm 10,000 µS/cm
Access Code Menu New Value 0 9999
Alarm Menu* High & Low (set to zero to disable) 1% 50%
Datalog Menu (Optional)
Config Menu (Optional)
Upgrade Menu
*Note: The Alarm relay is non-programmable. Refer to the Main Menu diagram on page 16 for the list of error
conditions that trigger the alarm relay.
Inspect the contents of the carton. Please notify the carrier immediately if there are any signs of damage
to the controller or its parts. Contact your distributor if any of the parts are missing. The carton should
contain: a WBL series controller and instruction manual. Any options or accessories will be incorporated
as ordered.
3.2 Mounting the electronic enclosure
The WBL series controller is supplied with mounting holes on the enclosure. It should be wall mounted
with the display at eye level, on a vibration-free surface, utilizing all four mounting holes for maximum
stability. Use M6 (1/4" diameter) fasteners that are appropriate for the substrate material of the wall. The
enclosure is NEMA 4X rated. The maximum operating ambient temperature is 122°F (50°C); this should
be considered if installation is in a high temperature location. The enclosure requires the following
clearances:
Top: 2" (50 mm)
Left: 8" (203 mm)
Right: 4" (102 mm)
Bottom: 7" (178 mm)
3.3 Installation
Once the WBL series controller is mounted, the metering pumps may be located at any distance from the
controller. The conductivity electrode should be placed as close to the controller as possible, to a
maximum distance of 250 ft. Less than 25 ft is recommended. The cable MUST be shielded from
background electrical noise. (The standard cable length is 10 feet. Should you require longer cable,
consult factory.)
Important Installation Notes: (see figure 1)
1. Make sure the minimum water level in the boiler is at least 4-6 inches above the skimmer
blowdown line. If the skimmer line is closer to the surface, it is likely that steam will be drawn
into the line instead of boiler water. The skimmer line must also be installed above the highest
tube.
2. Maintain a 3/4 inch minimum pipe ID with no flow restrictions from the tap for the boiler
skimmer blowdown line to the electrode. If the ID is reduced below 3/4 inch, then flashing will
occur beyond that point and the conductivity reading will be low and erratic. Minimize the
usage of tees, valves, elbows or unions between the boiler and the electrode.
3. A manual shut off valve should be installed so that the electrode can be removed and cleaned.
This valve must be a full port valve in order to avoid a flow restriction.
4. Keep the distance between the tap for the boiler skimmer line to the electrode as short as
possible, to a maximum of 10 feet.
5. Mount the electrode in the side branch of a cross in a horizontal run of pipe. This will minimize
entrapment of steam around the electrode and will allow any solids to pass through.
4
6. There MUST be a flow restriction after the electrode and/or control valve in order to provide
back pressure. This flow restriction will be either a flow control valve or an orifice union. The
amount of the flow restriction will affect the blowdown rate as well, and should be sized
accordingly.
7. Install the motorized ball valve or solenoid valve per the manufacturer’s instructions.
8. For best results, align the hole in the conductivity electrode such that the direction of water flow
is through the hole.
Guide to Sizing Blowdown Valves and Orifice Plates
1. Determine the Rate of Steam Production in Pounds per Hour:
Either read off the boiler name plate (water-tube boilers) or
Calculate from horsepower rating (fire-tube boilers):
HP x 34.5 = lbs/hr. Example: 100 HP = 3450 lbs/hr.
2. Determine the Concentration Ratio (BASED ON FEEDWATER)
A water treatment chemical specialist should determine the desired number of cycles of concentration.
This is the ratio of TDS in the boiler water to TDS in the feedwater. Note that feedwater means the water
that is fed to the boiler from the deaerator and includes makeup water plus condensate return.
Example: 10 cycles of concentration has been recommended
3. Determine the Required Blowdown Rate in Pounds Per Hour
Blowdown Rate = Steam Production / (Concentration Ratio –1)
Example: 3450/(10-1) = 383.33 lbs./hr
4. Determine if Continuous or Intermittent Sampling is Required
Use intermittent sampling when the boiler operation or loading is intermittent, or on boilers where the
required blowdown rate is less than 25% of the smallest available flow control valve or less than the flow
through the smallest orifice. See the graphs on the next page.
Use continuous sampling when the boiler is operating 24 hours per day and the required blowdown rate
is more than 25% of the smallest applicable flow control valve or orifice. See the graphs on the next
page.
Use of a flow control valve will give you the best control of the process, since the flow rate can be easily
adjusted. The dial on the valve also gives you a visual indication if the flow rate has been changed. If the
valve clogs, it can be opened to clear the obstruction, and closed to the previous position.
If an orifice plate is used, you must install a valve downstream from the orifice in order to fine tune the
flow rate and provide additional back pressure in many applications.
Example: An 80 psi boiler has a Required Blowdown Rate of 383.33 lbs./hr. The maximum flow rate of
the smallest flow control valve is 3250 lbs./hr. 3250 x 0.25 = 812.5 which is too high for continuous
sampling. Using an orifice, the flow rate through the smallest diameter plate is 1275 lbs./hr. This is too
high for continuous sampling.
5
5. Determine the Orifice or Flow Control Valve Size for this Blowdown Rate
Use the following graphs to select a flow control device:
18000
16000
14000
12000
10000
Lbs/hr
8000
6000
4000
2000
Flow Rate in Lbs/hr for Various Orifices
1/8 inch dia
3/16 inch dia
1/4 inch dia
5/16 inch dia
Install accessories
either vertically or
horizontally, per
manufacturer's
instructions.
Skimmer Blowdown Lin e
3/4" Min. up to Electrode
Full Port Block
Manual Blowdown
(Normally Closed)
Valve
Motorized
Ball
or
Solenoid
Valve
CONDUCTIVITY
ELECTRODE
¾"
Cross
To Drain
Flow
Control
Valve
or Orifice
Union
Manual Clean-Out
(Normally Closed)
RECOMMENDED INSTALLATION
CONTINUOUS SAMPLING
Figure 1 Typical Installation
Flow
Control
Valve or
Orifice Union
To Drain
To Drain
7
3.4 Icon Definitions
Symbol Publication Description
IEC 417, No.5019 Protective Conductor Terminal
IEC 417, No. 5008 Off (Supply)
3.5 Electrical Installation
The various standard wiring options are shown in figure 2. Your WBL series controller will arrive from
the factory prewired or ready for hardwiring. Depending on your configuration of controller options, you
may be required to hardwire some or all of the input/output devices. Refer to figures 3 and 4 for circuit
board layout and wiring.
Notes:
1. When wiring the conductivity electrode, it is critical to use shielded 24 AWG cable. DO NOT
route the cable in the same conduit as any AC wiring. The shield must be terminated at the
controller earth ground only. Make sure to cut off the shield wire at the electrode and to ensure
that it does not touch the grounded junction box.
2. When wiring the optional flow meter contactor input, the 4-20 mA output or a remote flow switch,
it is advisable to use stranded, shielded, twisted pair wire between 22-26 AWG. Shield should be
terminated at the controller ground stud (see figures 3 and 4).
3. Always route low voltage (sensor) signals with at least 6” separation from AC voltage wiring.
IEC 417, No. 5007 On (Supply)
ISO 3864, No. B.3.6 Caution, risk of electric shock
ISO 3864, No. B.3.1 Caution
CAUTION
1. There are live circuits inside the controller even when the power switch on the front panel is in
the OFF position! The front panel must never be opened before power to the controller is
REMOVED!
If your controller is prewired, it is supplied with a 8 foot, 18 AWG power cord with USA
style plug. A tool (#1 Phillips driver) is required to open the front panel.
2. When mounting the controller, make sure there is clear access to the disconnecting device!
3. The electrical installation of the controller must be done by trained personnel only and
conform to all applicable National, State and Local codes!
4. Proper grounding of this product is required. Any attempt to bypass the grounding will
compromise the safety of persons and property.
5. Operating this product in a manner not specified by Walchem may impair the protection
provided by the equipment.
8
CONDUCTIVITY
ELECTRODE
FLOW SWITCH
(OPTIONAL)
POWER
POWER
BLOWDOWN
FEED
BLOWDOWN
AUX1
SPARES
PLUG
Figure 2a WBL400 Conduit Wiring
AUX2
PLUG
AUX4/ALARM
SPARES
AUX3
Figure 2b WBL410 Conduit Wiring
4-20mA
(OPTIONAL)
4-20mA
(OPTIONAL)
FLOW METER
(OPTIONAL)
CONDUCTIVITY
ELECTRODE
FLOW SWITCH
(OPTIONAL)
FLOW METER
(OPTIONAL)
9