Wachendorff DA9602R User guide

Universal panel meter DA9602R
Wachendorff Prozesstechnik GmbH & Co. KG
Industriestrasse 7 D-65366 Geisenheim Tel.: +49 (0) 67 22 / 99 65 - 20 Fax: +49 (0) 67 22 / 99 65 - 78 www.wachendorff.de
l Universal panel meter in 96 x 48 mm DIN format l Extremly short mounting depth of 32 mm l Universal input for process signals, thermocouples and RTD l 16 mm high red LED display l 2 alarm outputs as relay l Protection IP65 from the front l Programming via buttons or software (USB-Port)
DA9602R
DA9602 the majority of the variables and sensors encountered in industrial processes. It contains two alarms (six functions), sensor offset, configuration of parameters protected by password, USB communication, indication in degrees Celsius (°C) or Fahrenheit (°F), among others.
Display: LED display, 5-digits, red with 16 mm high digits. Display range input signal: -1.999 to 30.000 Display range totalizer: 0 to 999.999.999 (alternating display)
Indicators: Ten red indicators for alarm status, communication, totalizer function, Min- and MAX-value. °C,°F ON, depending on temperature range TX, RX, USB ON, during communication via USB A1, A2 ON, when alarm is active TOT ON, when displaying totalizer value HIGH ON, when most significat digit of totalizer is displayed LOW ON, when last
significat digit of totalizer is displayed
Input impedance: Thermocouples, RTD, 0 to 50 mV: >10 MOhm; 0 to 5/10 V: >500 kOhm; 0/4 to 20 mA: 100 Ohm
Excitation: 24 VDC +/-15 % @ 50 mA
Relay outputs: 2x Relay SPST, 1,5 A at 240 VAC / 30 VDC.
Serial communication: Mini-USB (virtual COM port).
Supply: 100 to 240 VAC +/-10 %, 50/60Hz, 6 VA
Connections:
8
7
6
5
4
3
SUPPLY
100-240 VAC/VDC
50/60 Hz - 9 VA
ALM1
RELAIS
ALM2
RELAIS
P/N: XXXXXXXX S/N: XXXXXXXXXXXX
wp-direkt.de
24 VDC
++
13
OUT
12
V
++
11
mA
INPUT
10
9
Protection: IP65 from the front (with rubber sealing), back side IP20.
Housing: Plastic case Polycarbonat (PC) L94-V2. Back panel ABS +
PC Ul94 V-0.
Diemensions: W 96 mm x H 48 mm x D 35 mm. Panel cut out: 93,0 x 45,5 mm. Mounting with plastic clamps.
Connection: Plug-in terminal blocks, 5 mm pitch.
Environmental conditions: Operating temeprature: 0 °C to +50 °C;
relative humidity 80 % rF @ 30 °C, for temperature above 30 ºC, reduction by 3 % rF for ºC.
Package content: Panel meter, mounting material, rubber sealing, manual.
Buttons: 4 buttons for programming and setup of set points.
Input range: Setup of input signal via buttons.
Thermocouples: Type J, K,T, N, R, S, B, E; internal cold junction RTD: Pt100 in 3-wire connection (alpha = 0,00385) Linear inputs: 0 V to 5/10 V, 0/4 mA to 20 mA, 0 mV to 50 mV
Sensor type Measurement range
TC type J -110 ºC to 950 ºC (-166 ºF to 1742 ºF) TC type
K -150 ºC to 1370 ºC (-238 ºF to 2498 ºF)
TC type
T -160 ºC to 400 ºC (-256 ºF to 752 ºF)
TC type
N -270 ºC to 1300 ºC (-454 ºF to 2372 ºF)
TC type
R -50 ºC to 1760 ºC (-58 ºF to 3200 ºF)
TC type
S -50 ºC to 1760 ºC (-58 ºF to 3200 ºF)
TC type
B 400 ºC to 1800 ºC (752 ºF to 3272 ºF)
TC type
E -90 ºC to 730 ºC (-130 ºF to 1346 ºF)
RTD -200 ºC to 850 ºC (-328 ºF to 1562 ºF)
Accuracy:
Thermocouples type J, K, T, E: 0,25 % of the span +/-1 °C Thermocouples type of the span
N, R, S, B: 0,25 % +/-3 °C RTD: 0,2 % of the span Linear analogue input: 0,2 % of the span
Resolution: Internal resolution with 65.535 steps (16 bits), Display resolution 32.000 steps.
Measurement rate: 55 Hz with programmable digital filter.
Copyright by Wachendorff Prozesstechnik GmbH & Co. KG, Industriestraße 7, D-65366 Geisenheim, Tel.: 06722/9965-20, Fax: -78, Stand: 20.08.2012. Alle Angaben ohne Gewähr, Irrtümer und Änderungen vorbehalten.
Order details
Typ Order-No.
Universal panel meter, 2 relay, 240 VAC DA9602R0
Accessories
USB programming cable. KABUSB20 Softwaredownload under:
http://www.wachendorff.de/wp/dpc_dow_epg_sof.html
Loading...