GAS PRESSURE MEASUREMENT…………………………………...
PRESSURE TAP LOCATION…………………………………………..
SEQUENCE OF OPERATION………………………………………….
WIRING DIAGRAMS…………………………………………………….
This manual is prepared for the use of trained service technicians and should only be used by those
who are properly qualified. This manual is not intended to be all encompassing. You should read, in
it's entirety, the repair procedure you wish to perform to determine if you have the necessary tools,
instruments and skills required to perform the procedure. Procedures for which you do not have the
necessary tools, instruments and skills should not be attempted.
Disconnect the electrical power and follow lockout / tagout procedures
Certain procedures in this manual require electrical test or
measurements while power is applied to the machine. Exercise extreme caution at all
times when attempting these procedures. Before testing, disconnect electrical power
and follow lock/out tagout procedures, then attach test equipment and reapply power to
test.
Procedures in this manual will apply to all RRG models unless specified. No procedure in this
manual will require the removal or raising of the griddle plate. Pictures and illustrations can be of any
model unless the picture or illustration needs to be model specific.
INSTALLATION
Generally, installations are made by the dealer or contracted by the dealer or owner. Detailed
installation instructions are included in the Installation and Operation Manual that is sent with each unit.
However, it should be noted that an improperly installed unit, especially an unlevel unit can lead to
premature electrical component failures. A unit that is higher in the front will cause the flue gases to
vent improperly and gather in the front near the electrical components. All RRG models must be
installed with an externally mounted regulator.
OPERATION
Detailed operation instructions are included in the Installation & Operation Manual sent with each
unit and are also available at WWW.VULCANHART.COM
CLEANING
Detailed cleaning procedures are included in the Installation & Operation manual sent with each
unit.
LUBRICATION
No lubrication is required on this equipment.
SPECIFICATIONS
All RRG models operate on 120 volt, 60 hertz, single phase at 1.0 amps. All models are equipped
with electric solid state thermostats, automatic spark igniters and pilot safety circuit. All models are
equipped with 27,500 BTU/HR burners as standard equipment. One burner is used for every 12 inches
of griddle surface. Natural gas models are to operate at 5.0" W.C. manifold pressure and LP models at
10.0" W.C. manifold pressure with all burners on.
.
-
4 -
919
PRESSURE CHECK PLUG
TEMPERATURE
CONTROLLER
498438
SAFETY IGNITION MODULE
498443
DUAL SOLENOID VALVE
713656
COMPONENT LOCATION
GAS MANIFOLD
720122
¼” FLEX TUBE
KNOB
498438-1
3/8” FLEX TUBE
PILOT ADJUSTMENT VALVE
71
4
INDICATOR LIGHT
720017
36RRG CONFIGURATION SHOWN
PILOT SPARK ASSEMBLY
713930
BURNER ORIFICE
POWER SWITCH
810280-1
-
5 -
EXTERIOR PANELS
CONTROL PANEL
BULLNOSE
CONTROL PANEL
BACK PANEL
FLUE
BACK PANEL
IDENTIFICATION PLATE
Disconnect the electrical
power and follow lockout
/ tagout procedures
The Control Panel holds the
thermostats, indicator lights
and power switch.
REMOVAL
1. Remove the four screws
securing the front of the
control panel. There are
two screws at each end
of the panel.
2. Remove the screws that
secure the bottom of the
control panel to the
underside of the chassis.
3. Pull the control panel
forward and lay face
down directly in front of
the unit while servicing.
4. Reverse the procedure to
install.
BULLNOSE
Disconnect the electrical power and
follow lockout / tagout procedures
It will be necessary to remove the back panel when changing a
burner, temperature probe or to remove excessive grease build up
from the flue area.
REMOVAL
1. Disconnect gas supply at griddle.
2. Remove all screws from rear of griddle securing the back panel.
3. Reverse the procedure to install.
IDENTIFICATION PLATE
The identification plate contains the unit’s full model and serial
number along with BTU rating and clearance information. The
identification plate is located on the right side panel towards the
front of the unit.
FLUE
The flue is the outlet for gases left over from combustion and
excess heat. The flue should never be blocked or covered.
-
6 -
Disconnect the electrical
power and follow
lockout / tagout
procedures
The Bullnose acts as a front
rail or shelf during griddle
operation.
1. Remove the Control
Panel.
2. The bullnose assembly is
secured with several
screws, one at each end
of the bottom of the
assembly and several
more (depending on
size) facing the griddle
plate.
3. Reverse the procedure
to install.
REMOVAL
THERMOSTAT
WIRING CONFIGURATION FRONT VIEW
The thermostat is a solid state control. The thermostat supplies power to the burner solenoid valves
and indicator lights when turned on or until the temperature setpoint is reached.
THERMOSTAT TROUBLESHOOTING
SYMPTOM – BURNER WILL NOT COME ON
1. Check for loose or excessively greasy/dirty connections at thermostat terminals
2. Check that thermostat is set higher than griddle plate surface temperature.
A. Check for 120 voltage going to L1 terminal on thermostat
B. If no voltage, check wiring and power switch.
3. Check safety ignition module.
4. Check for resistance (approx. 50 Ω) from L2 wire to ground when safety circuit should be made.
A. If no resistance, check that pilot is lit and check safety ignition module.
SYMPTOM – GRIDDLE SURFACE TEMPERATURE IS MORE THAN ±5°F OF THERMOSTAT SET
POINT
1. Ensure that you are using a high quality, calibrated surface temperature measuring device.
A. Do not use an infrared thermometer – these are highly inaccurate on a griddle plate.
B. Refer to instructions on page 8 for proper placement of probe and method.
2. Check that burners are properly adjusted.
3. Check that burner valves are operating correctly.
4. Check that there are no burner orifice obstructions
5. Check that the high temp. thermostat probe wire insulation is completely covering the wire. If
you have found no problems in steps 1 – 5, proceed page 9 for calibration instructions.
6. If thermostat will not calibrate after all previous steps – replace thermostat.
Disconnect the electrical power and follow lockout / tagout procedures
-
7 -
Loading...
+ 15 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.