VULCAN-HART CORPORATION, 3600 NORTH POINT BOULEVARD, BALTIMORE, MARYLAND 21222
OPERATING, INSTALLATION AND SERVICE PERSONNEL
Operating information for this equipment has been prepared for use by qualified and/or authorized operating
personnel.
All installation and service on this equipment is to be performed by qualified, certified, licensed and/or
authorized installation or service personnel, with the exception of any marked with a ? in front of the part
number.
Service may be obtained by contacting the Factory Service Department, Factory Representative or Local
Service Agency.
DEFINITIONS
QUALIFIED AND/OR AUTHORIZED OPERATING PERSONNEL
Qualified or authorized operating personnel are those who have carefully read the information in this manual
and are familiar with the equipment's functions or have had previous experience with the operation of the
equipment covered in this manual.
QUALIFIED INSTALLATION PERSONNEL
Qualified installation personnel are individuals, a firm, corporation or company which either in person or
through a representative are engaged in, and are responsible for:
1. The installation of gas piping from the outlet side of the gas meter, or the service regulator when the meter
is not provided, and the connection and installation of the gas appliance. Qualified installation personnel
must be experienced in such work, be familiar with all precautions required, and have complied with all
requirements of state or local authorities having jurisdiction. Reference in the United States of America National Fuel Gas code ANSI Z223.1 (Latest Edition). In Canada-Canadian Standard CAN1-B149.1 NAT.
GAS (Latest Edition) or CAN1-B149.2 PROPANE (Latest Edition).
2. The installation of electrical wiring from the electric meter, main control box or service outlet to the electric
appliance. Qualified installation personnel must be experienced in such work, be familiar with all
precautions required, and have complied with all requirements of state or local authorities having
jurisdiction. Reference: In the United States of America-National Electrical Code ANSI NFPA No. 70
(Latest Edition). In Canada-Canadian Electrical Code Part 1 CSA-C22.1 (Latest Edition).
QUALIFIED SERVICE PERSONNEL
Qualified service personnel are those who are familiar with Vulcan equipment who have been endorsed by
the Vulcan-Hart Corporation. All authorized service personnel are required to be equipped with a complete set
of service parts manuals and stock a minimum amount of parts for Vulcan equipment.
SHIPPING DAMAGE CLAIM PROCEDURE
For your protection, please note that equipment in this shipment was carefully inspected and packed by
skilled personnel before leaving the factory. The transportation company assumes full responsibility for safe
delivery upon acceptance of this shipment.
If shipment arrives damaged:
1. VISIBLE LOSS OR DAMAGE — Be certain this is noted on freight bill or express receipt and signed by
person making delivery.
2. FILE CLAIM FOR DAMAGES IMMEDIATELY — Regardless of extent of damage.
3. CONCEALED LOSS OR DAMAGE — If damage is unnoticed until merchandise is unpacked, notify
transportation company or carrier immediately, and file "concealed damage" claim with them. This should
be done within (15) days of date of delivery is made to you. Be sure to retain container for inspection.
We cannot assume responsibility for damage or loss incurred in transit. We will, however, be glad to furnish
you with necessary documents to support your claim.
PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE
IMPORTANT NOTES FOR ALL VULCAN APPLIANCES
1. These units are produced with the best possible workmanship and material. Proper installation is vital if best performance and
appearance are to be achieved. Installer must follow the installation instructions carefully.
2. Information on the construction and installation of ventilating hoods may be obtained from the "Standard for the installation of
equipment for the removal of smoke and grease laden vapors from commercial cooking equipment," NFPA No. 96 (latest
edition) available from the National Fire Protection Association, Battery March Park, Quincy MA 02269.
3. For an appliance equipped with a flexible electric supply cord, the cord is equipped with a three prong (grounding) plug. This
grounding plug is for your protection against shock hazard and should be plugged directly into a properly grounded three prong
receptacle. Do not cut or remove the grounding prong from this plug. If the appliance is not equipped with a grounding plug, and
electric supply is needed, ground the appliance by using the ground lug provided (refer to the wiring diagram).
(FOR GAS APPLIANCES ONLY)
4. Do not obstruct the air flow into and around the appliance. This air flow is necessary for proper combustion of gases and for
ventilation of the appliance. Provisions for ventilation of incoming air supply for the equipment in the room must be in accordance
with National Fuel Gas Code ANSI Z223.1 (latest edition).
5. Do not obstruct the flow of flue gases from the flue duct (when so equipped) located on the rear (or sides) of the appliance. It is
recommended that the flue gases be ventilated to the outside of the building through a ventilation system installed by qualified
personnel.
6. For an appliance equipped with casters, (1) the installation shall be made with a connector that complies with the Standard for
Connectors for Movable Gas Appliances, ANSI Z21.69 (latest edition), and Addenda, Z21.69a (latest edition), and a quickdisconnect device that complies with the Standard for Quick-Disconnect Devices for Use With Gas Fuel, ANSI Z21.41 (latest
edition), and Addenda, Z21.41a (latest edition) and Z21.41b (latest edition), and (2) adequate means must be provided to limit
the movement of the appliance without depending on the connector and the quick-disconnect device or its associated piping to
limit the appliance movement. If disconnection of the restraint is necessary, reconnect this restraint after the appliance has been
returned to its originally installed position.
7. The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure
testing of that system at test pressures in excess of 1/2 psig (3.45 k Pa).
8. The appliance must be isolated from the gas supply system by closing its individual manual shutoff valve during any pressure
testing of the gas supply system at test pressures equal to or less than 1/2 psig (3.45 k Pa).
CAUTIONS
FOR YOUR SAFETY
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS
IN THE VICINITY OF THIS EQUIPMENT OR ANY OTHER APPLIANCE.
1. KEEP THE APPLIANCE FREE AND CLEAR FROM ALL COMBUSTIBLE SUBSTANCES.
2. IN THE EVENT A GAS ODOR IS DETECTED, SHUT UNIT(S) DOWN AT THE MAIN
SHUTOFF VALVE AND CONTACT THE LOCAL GAS COMPANY OR GAS SUPPLIER
FOR SERVICE.
3. POST IN A PROMINENT LOCATION, INSTRUCTIONS TO BE FOLLOWED IN THE EVENT
THE SMELL OF GAS IS DETECTED. THIS INFORMATION MAY BE OBTAINED FROM A
LOCAL GAS SUPPLIER.
GEF INSTALLATION, SERVICE & PARTS MANUAL INDEX
DESCRIPTION PAGE
DEFINITIONS(Inside Front Cover)
CAUTIONS
IMPORTANT NOTES1
INDEX2
SECTION I INSTALLATION
UNCRATING INSTRUCTIONS3
ELECTRIC CONNECTIONS3
GAS SUPPLY CONNECTIONS4
POSITIONING FRYER UNDER HOOD4
SECTION II SERVICING
CONTROLS5
AIR ADJUSTMENT6
HIGH LIMIT TEST & PROCEDURES6
CLEANING BLOWER INLET SCREEN & WHEEL6
CALIBRATION PROCEDURES7
TROUBLE SHOOTING8-9
SECTION III PARTS
PARTS LIST10-24
REVISION SHEET(Inside Back Cover)
NOTES
A Rating Plate is located on the inside fryer door panel stating the Model Number, Serial Number,
Type of Gas, Voltage and Amperage.
A complete set of Wiring Diagrams are included in the back of this manual. A Wiring Decal may
also be found on the inside lower front panel.
GEF-SM units all require an isolation relay to isolate each tank vat section of the fryer. The
isolation relay is located behind the front control panel.
This appliance is to be installed with a six inch clearance at the sides and rear to combustible
construction.
Fryer must be installed at least 16 in. away from open top flame units.
Motors in GEF fryers are permanently lubricated and require no additional maintenance.
The vent of this appliance should be checked every 6 months for restrictions.
2
GEF UNCRATING
INSTRUCTIONS
ELECTRIC CONNECTION
The following procedure should be followed when
uncrating all GEF Fryers.
1. Pry right and left hand crate sides off of crate back
and front.
2. Pry crate back and front off of crate bottom.
3. Remove cardboard box containing component parts
from the 2x4 wood packaging braces.
4. Using caution, cut (2) straps and remove (2) 2 x 4
wood braces.
5. Remove protective plastic liner from unit.
6. Remove packaging material from unit.
7. Assemble legs and remove unit from crate bottom
as near to final resting place as possible.
8. Open cardboard box containing component parts
and unwrap parts. Care should be taken when
checking unit quantities. See chart below for correct
contents of parts.
Position fryer as near to final resting place as possible.
Connect 120V AC electric supply to fryer barrier strip.
Barrier strip may be connected from rear of unit. To
reach barrier, remove electric cover plate "A" from unit.
After connecting 120V AC electric supply to fryer
barrier strip, verify with a voltmeter that the following
condition exists. See Detail "A".
1. Black to White 120V AC.
2. Black to Ground 120V AC.
3. White to Ground 0.00V AC.
Make all other necessary electrical connections.
Improper grounding and/or polarity will result in lock
out of unit and eventual damage to the ignition
systems.
This unit is supplied with a 6 1/2 foot long 3 wire supply
cord. This appliance is equipped with a 3 prong
(grounding) plug for your protection against shock
hazard and should be plugged directly into a properly
grounded three prong receptacle. DO NOT cut or
remove the grounding prong from this plug.
3
POSITIONING FRYER
GAS SUPPLY CONNECTION UNDER HOOD
SIDE ARM
See Detail "C"
All GEF Fryers are equipped with a 3.7"W.C. 3/4" reg-
ulator for natural gas and a 10" W.C. 3/4" regulator for
propane gas.
To connect unit to gas supply, attack quick disconnect
supplied with unit to male fitting as follows:
1. Pull disconnect collar #1 back.
2. Snap disconnect #2 on to male disconnect fitting "C"
supplied on unit.
3. Release disconnect collar when fitting #3 and disconnect #2 snap into place.
4. Connect union #4 to gas supply.
5. Turn main gas supply on and test for gas leakage at all
connecting points.
Fryer is supplied with four adjustable height legs. Legs
should be adjusted so that the fryer is level and at its
proper height in the hood. See Detail — C1.
Position fryer so that it may be pushed straight back
under the hood. Place main top onto fryer by tilting main
top while pushing fryer under hood. After the main top
has cleared the hood, position main top so that it rests
evenly on the unit.
4
CONTROLS
SWITCH PANEL CONTROLS
(Refer to Detail "D")
1. MASTER SWITCH— Controls electric supply to unit
2. POWER "ON" LIGHT— Light indicates when electrical supply is on.
3. TEMPERATURE CONTROL— Maintain frying temperature by controlling power supply.
4. HEATING LIGHT— When "ON" indicates temperature control is calling for gas to burners.
5. HIGH LIMIT TEST SWITCH— Bypasses temperature control for testing of high limit thermostats.
6. FIRST HIGH LIMIT LIGHT— When "ON" indicates first high limit thermostat has shut down unit.
7. SECOND HIGH LIMIT LIGHT— When "ON" indicates second high limit thermostat has shut down unit. (Reset required*)
8. TROUBLE LIGHT— Indicates solid state ignition device has "locked out". (Reset required*)
9. IGNITOR RESET BUTTON
*NOTE: To reset, turn main power switch off, then on.
— See Detail "D" — When up indicates excessive heat or current in control board, allow to cool push
down to reset. If tripping continues, contact service agency.
OPERATIONAL LIGHTING INSTRUCTIONS:
To turn on, push power switch to "ON" position; turn
thermostat dial to temperature desired.
To turn off, push power switch to "OFF" position.
NOTE: Service valve must be in "ON" position and
power cord connected to power source for unit operation.
For service or extended shut down, turn service valve to
"OFF" and disconnect power cord.
The above information may also be found on the inside of
fryer door panel.
5
AIR ADJUSTMENT
HIGH LIMIT TEST
A blue flame seen out of the viewing port indicates
insufficient air. To correct this condition, remove plug
button from air adjustment plunger opening. Using a 1/8"
allen wrench, remove two set screws 1/4-28 NF X 3/8"
Long (one from each opening).
Replace allen wrench back into each opening and rotate
wrench counterclockwise to reduce flame in viewing port
and clockwise to increase flame. The air adjustment has
been properly made when flame is not seen out of the
viewing port and a maximum red glow is achieved on the
burners. (See Detail "B")
CLEANING BLOWER INLET
SCREEN AND WHEEL
For preventative maintenance and maximum performance
of the blower motor, the inlet screen and blower wheel
should be cleaned once a month as follows:
1. Turn power switch "OFF".
2. Remove two (2) wing nuts from side of blower motor.
3. Remove blower inlet screen.
4. Remove blower wheel.
5. Soak blower inlet screen and wheel in mild soap and
water solution. Dry thoroughly before replacing parts.
6. Reassemble screen and wheel to unit, and tighten wing
nuts.
7. Turn power switch to "ON" position and resume unit
operation.
PROCEDURE
A test to determine if the protection devices are properly
functioning. (See steps 1 thru 5)
1. Turn master switch on and set temperature knob to frying
temperature.
2. Heat shortening until heating light goes off.
3. Depress top of high limit test switch and hold until first high
limit comes on, then release switch. (Light will come on at
390 degrees F.-420 degrees F.)
4. Depress bottom of high limit test switch and hold until
second high limit light comes on, then release switch. (Light
will come on at 420 degrees F.-445 degrees F.)
5. Once unit cools down, reset by turning main power switch off
and then on, normal frying operation will then automatically
be resumed.
The above instructions may also be found on the inside fryer
door.
(Refer to Detail "F" for high limit location and viewing ports
location).
6
Loading...
+ 18 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.