Vulcan GEF-1M Service Manual

McDONALD'S®
INSTALLATION, SERVICE
& PARTS MANUAL FOR
GEF-M&SM SERIES
GAS FRYERS
VULCAN-HART CORPORATION, 3600 NORTH POINT BOULEVARD, BALTIMORE, MARYLAND 21222
Operating information for this equipment has been prepared for use by qualified and/or authorized operating personnel.
All installation and service on this equipment is to be performed by qualified, certified, licensed and/or authorized installation or service personnel, with the exception of any marked with a ? in front of the part number.
Service may be obtained by contacting the Factory Service Department, Factory Representative or Local Service Agency.
DEFINITIONS
QUALIFIED AND/OR AUTHORIZED OPERATING PERSONNEL
Qualified or authorized operating personnel are those who have carefully read the information in this manual and are familiar with the equipment's functions or have had previous experience with the operation of the equipment covered in this manual.
QUALIFIED INSTALLATION PERSONNEL Qualified installation personnel are individuals, a firm, corporation or company which either in person or
through a representative are engaged in, and are responsible for:
1. The installation of gas piping from the outlet side of the gas meter, or the service regulator when the meter is not provided, and the connection and installation of the gas appliance. Qualified installation personnel must be experienced in such work, be familiar with all precautions required, and have complied with all requirements of state or local authorities having jurisdiction. Reference in the United States of America ­National Fuel Gas code ANSI Z223.1 (Latest Edition). In Canada-Canadian Standard CAN1-B149.1 NAT. GAS (Latest Edition) or CAN1-B149.2 PROPANE (Latest Edition).
2. The installation of electrical wiring from the electric meter, main control box or service outlet to the electric appliance. Qualified installation personnel must be experienced in such work, be familiar with all precautions required, and have complied with all requirements of state or local authorities having jurisdiction. Reference: In the United States of America-National Electrical Code ANSI NFPA No. 70 (Latest Edition). In Canada-Canadian Electrical Code Part 1 CSA-C22.1 (Latest Edition).
QUALIFIED SERVICE PERSONNEL Qualified service personnel are those who are familiar with Vulcan equipment who have been endorsed by
the Vulcan-Hart Corporation. All authorized service personnel are required to be equipped with a complete set of service parts manuals and stock a minimum amount of parts for Vulcan equipment.
SHIPPING DAMAGE CLAIM PROCEDURE
For your protection, please note that equipment in this shipment was carefully inspected and packed by skilled personnel before leaving the factory. The transportation company assumes full responsibility for safe delivery upon acceptance of this shipment.
If shipment arrives damaged:
1. VISIBLE LOSS OR DAMAGE — Be certain this is noted on freight bill or express receipt and signed by
person making delivery.
2. FILE CLAIM FOR DAMAGES IMMEDIATELY — Regardless of extent of damage.
3. CONCEALED LOSS OR DAMAGE — If damage is unnoticed until merchandise is unpacked, notify
transportation company or carrier immediately, and file "concealed damage" claim with them. This should be done within (15) days of date of delivery is made to you. Be sure to retain container for inspection.
We cannot assume responsibility for damage or loss incurred in transit. We will, however, be glad to furnish you with necessary documents to support your claim.
PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE
IMPORTANT NOTES FOR ALL VULCAN APPLIANCES
1. These units are produced with the best possible workmanship and material. Proper installation is vital if best performance and appearance are to be achieved. Installer must follow the installation instructions carefully.
2. Information on the construction and installation of ventilating hoods may be obtained from the "Standard for the installation of equipment for the removal of smoke and grease laden vapors from commercial cooking equipment," NFPA No. 96 (latest edition) available from the National Fire Protection Association, Battery March Park, Quincy MA 02269.
3. For an appliance equipped with a flexible electric supply cord, the cord is equipped with a three prong (grounding) plug. This grounding plug is for your protection against shock hazard and should be plugged directly into a properly grounded three prong receptacle. Do not cut or remove the grounding prong from this plug. If the appliance is not equipped with a grounding plug, and electric supply is needed, ground the appliance by using the ground lug provided (refer to the wiring diagram).
(FOR GAS APPLIANCES ONLY)
4. Do not obstruct the air flow into and around the appliance. This air flow is necessary for proper combustion of gases and for ventilation of the appliance. Provisions for ventilation of incoming air supply for the equipment in the room must be in accordance with National Fuel Gas Code ANSI Z223.1 (latest edition).
5. Do not obstruct the flow of flue gases from the flue duct (when so equipped) located on the rear (or sides) of the appliance. It is recommended that the flue gases be ventilated to the outside of the building through a ventilation system installed by qualified personnel.
6. For an appliance equipped with casters, (1) the installation shall be made with a connector that complies with the Standard for Connectors for Movable Gas Appliances, ANSI Z21.69 (latest edition), and Addenda, Z21.69a (latest edition), and a quick­disconnect device that complies with the Standard for Quick-Disconnect Devices for Use With Gas Fuel, ANSI Z21.41 (latest edition), and Addenda, Z21.41a (latest edition) and Z21.41b (latest edition), and (2) adequate means must be provided to limit the movement of the appliance without depending on the connector and the quick-disconnect device or its associated piping to limit the appliance movement. If disconnection of the restraint is necessary, reconnect this restraint after the appliance has been returned to its originally installed position.
7. The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.45 k Pa).
8. The appliance must be isolated from the gas supply system by closing its individual manual shutoff valve during any pressure testing of the gas supply system at test pressures equal to or less than 1/2 psig (3.45 k Pa).
CAUTIONS
FOR YOUR SAFETY
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS
IN THE VICINITY OF THIS EQUIPMENT OR ANY OTHER APPLIANCE.
1. KEEP THE APPLIANCE FREE AND CLEAR FROM ALL COMBUSTIBLE SUBSTANCES.
2. IN THE EVENT A GAS ODOR IS DETECTED, SHUT UNIT(S) DOWN AT THE MAIN SHUTOFF VALVE AND CONTACT THE LOCAL GAS COMPANY OR GAS SUPPLIER FOR SERVICE.
3. POST IN A PROMINENT LOCATION, INSTRUCTIONS TO BE FOLLOWED IN THE EVENT THE SMELL OF GAS IS DETECTED. THIS INFORMATION MAY BE OBTAINED FROM A LOCAL GAS SUPPLIER.
GEF INSTALLATION, SERVICE & PARTS MANUAL INDEX
DESCRIPTION PAGE
DEFINITIONS (Inside Front Cover) CAUTIONS IMPORTANT NOTES 1 INDEX 2
SECTION I INSTALLATION
UNCRATING INSTRUCTIONS 3 ELECTRIC CONNECTIONS 3 GAS SUPPLY CONNECTIONS 4 POSITIONING FRYER UNDER HOOD 4
SECTION II SERVICING
CONTROLS 5 AIR ADJUSTMENT 6 HIGH LIMIT TEST & PROCEDURES 6 CLEANING BLOWER INLET SCREEN & WHEEL 6 CALIBRATION PROCEDURES 7 TROUBLE SHOOTING 8-9
SECTION III PARTS
PARTS LIST 10-24 REVISION SHEET (Inside Back Cover)
NOTES
A Rating Plate is located on the inside fryer door panel stating the Model Number, Serial Number, Type of Gas, Voltage and Amperage.
A complete set of Wiring Diagrams are included in the back of this manual. A Wiring Decal may also be found on the inside lower front panel.
GEF-SM units all require an isolation relay to isolate each tank vat section of the fryer. The isolation relay is located behind the front control panel.
This appliance is to be installed with a six inch clearance at the sides and rear to combustible construction.
Fryer must be installed at least 16 in. away from open top flame units. Motors in GEF fryers are permanently lubricated and require no additional maintenance.
The vent of this appliance should be checked every 6 months for restrictions.
2
GEF UNCRATING
INSTRUCTIONS
ELECTRIC CONNECTION
The following procedure should be followed when uncrating all GEF Fryers.
1. Pry right and left hand crate sides off of crate back
and front.
2. Pry crate back and front off of crate bottom.
3. Remove cardboard box containing component parts
from the 2x4 wood packaging braces.
4. Using caution, cut (2) straps and remove (2) 2 x 4
wood braces.
5. Remove protective plastic liner from unit.
6. Remove packaging material from unit.
7. Assemble legs and remove unit from crate bottom
as near to final resting place as possible.
8. Open cardboard box containing component parts
and unwrap parts. Care should be taken when checking unit quantities. See chart below for correct contents of parts.
UNIT
PART DESCRIPTION
Basket Hanger 1 2 3 1 2 3 Quick Disconnect 1 1 1 1 1 1 Rack Supports 2 4 6 2 4 6 Probe Tubes 1 2 3 2 4 6 Clean Out Rod 1 1 1 1 1 1
1M 2M 3M 2SM 4SM 6SM
QUANTITIES
Position fryer as near to final resting place as possible. Connect 120V AC electric supply to fryer barrier strip. Barrier strip may be connected from rear of unit. To reach barrier, remove electric cover plate "A" from unit. After connecting 120V AC electric supply to fryer barrier strip, verify with a voltmeter that the following condition exists. See Detail "A".
1. Black to White 120V AC.
2. Black to Ground 120V AC.
3. White to Ground 0.00V AC. Make all other necessary electrical connections.
Improper grounding and/or polarity will result in lock out of unit and eventual damage to the ignition systems.
This unit is supplied with a 6 1/2 foot long 3 wire supply cord. This appliance is equipped with a 3 prong (grounding) plug for your protection against shock hazard and should be plugged directly into a properly grounded three prong receptacle. DO NOT cut or remove the grounding prong from this plug.
3
POSITIONING FRYER
GAS SUPPLY CONNECTION UNDER HOOD
SIDE ARM
See Detail "C"
All GEF Fryers are equipped with a 3.7"W.C. 3/4" reg- ulator for natural gas and a 10" W.C. 3/4" regulator for propane gas.
To connect unit to gas supply, attack quick disconnect supplied with unit to male fitting as follows:
1. Pull disconnect collar #1 back.
2. Snap disconnect #2 on to male disconnect fitting "C" supplied on unit.
3. Release disconnect collar when fitting #3 and dis­connect #2 snap into place.
4. Connect union #4 to gas supply.
5. Turn main gas supply on and test for gas leakage at all connecting points.
Fryer is supplied with four adjustable height legs. Legs should be adjusted so that the fryer is level and at its proper height in the hood. See Detail — C1.
Position fryer so that it may be pushed straight back under the hood. Place main top onto fryer by tilting main top while pushing fryer under hood. After the main top has cleared the hood, position main top so that it rests evenly on the unit.
4
CONTROLS
SWITCH PANEL CONTROLS
(Refer to Detail "D")
1. MASTER SWITCH — Controls electric supply to unit
2. POWER "ON" LIGHT — Light indicates when electrical supply is on.
3. TEMPERATURE CONTROL — Maintain frying temperature by controlling power supply.
4. HEATING LIGHT — When "ON" indicates temperature control is calling for gas to burners.
5. HIGH LIMIT TEST SWITCH — Bypasses temperature control for testing of high limit thermostats.
6. FIRST HIGH LIMIT LIGHT — When "ON" indicates first high limit thermostat has shut down unit.
7. SECOND HIGH LIMIT LIGHT — When "ON" indicates second high limit thermostat has shut down unit. (Reset required*)
8. TROUBLE LIGHT — Indicates solid state ignition device has "locked out". (Reset required*)
9. IGNITOR RESET BUTTON *NOTE: To reset, turn main power switch off, then on.
— See Detail "D" — When up indicates excessive heat or current in control board, allow to cool push
down to reset. If tripping continues, contact service agency.
OPERATIONAL LIGHTING INSTRUCTIONS:
To turn on, push power switch to "ON" position; turn thermostat dial to temperature desired. To turn off, push power switch to "OFF" position.
NOTE: Service valve must be in "ON" position and
power cord connected to power source for unit operation. For service or extended shut down, turn service valve to
"OFF" and disconnect power cord. The above information may also be found on the inside of
fryer door panel.
5
AIR ADJUSTMENT
HIGH LIMIT TEST
A blue flame seen out of the viewing port indicates insufficient air. To correct this condition, remove plug button from air adjustment plunger opening. Using a 1/8" allen wrench, remove two set screws 1/4-28 NF X 3/8" Long (one from each opening).
Replace allen wrench back into each opening and rotate wrench counterclockwise to reduce flame in viewing port and clockwise to increase flame. The air adjustment has been properly made when flame is not seen out of the viewing port and a maximum red glow is achieved on the burners. (See Detail "B")
CLEANING BLOWER INLET SCREEN AND WHEEL
For preventative maintenance and maximum performance of the blower motor, the inlet screen and blower wheel should be cleaned once a month as follows:
1. Turn power switch "OFF".
2. Remove two (2) wing nuts from side of blower motor.
3. Remove blower inlet screen.
4. Remove blower wheel.
5. Soak blower inlet screen and wheel in mild soap and water solution. Dry thoroughly before replacing parts.
6. Reassemble screen and wheel to unit, and tighten wing nuts.
7. Turn power switch to "ON" position and resume unit operation.
PROCEDURE
A test to determine if the protection devices are properly functioning. (See steps 1 thru 5)
1. Turn master switch on and set temperature knob to frying temperature.
2. Heat shortening until heating light goes off.
3. Depress top of high limit test switch and hold until first high limit comes on, then release switch. (Light will come on at 390 degrees F.-420 degrees F.)
4. Depress bottom of high limit test switch and hold until second high limit light comes on, then release switch. (Light will come on at 420 degrees F.-445 degrees F.)
5. Once unit cools down, reset by turning main power switch off and then on, normal frying operation will then automatically be resumed.
The above instructions may also be found on the inside fryer door.
(Refer to Detail "F" for high limit location and viewing ports location).
6
Loading...
+ 18 hidden pages