This manual is the property of the owner of this particular Tube-Ice®
machine.
Model #____________________ Serial #____________________.
It is to be left on the premises with this machine at all times. After startup, it should be stored in a safe place where it can be readily available
when needed for future reference in maintaining troubleshooting or
servicing.
Failure to comply with this notice will result in unnecessary
inconvenience and possible additional expenses.
This manual is intended as an informational tool for the installation,
operation, maintenance, troubleshooting, and servicing of this
equipment. If an existing situation calls for additional information not
found herein, we suggest that you contact your distributor first. If
further assistance or information is needed, please feel free to contact the
factory at 502-635-3000 or FAX at 502-635-3024.
IMPORTANT: The Warranty Registration/Start-Up Report found in the
front of this manual is to be completed and returned to the factory
promptly after the official start-up.
Please return to: VOGT ICE, LLC
1000 W. Ormsby Ave.
Louisville, KY 40210
Page 3
Vogt Order Number: _____________
Vogt Ice LLC
1000 West Ormsby Ave
Louisville, KY 40210
Phone: 502-635-3000
Fax: 502-635-3024
Warranty Registration/Start-Up Form
HES20, HES30, HES40, HE60
Model Number: __________________________ Serial Number: ____________________
This form must be filled out and sent to Vogt in order to activate warranty.
Date of Start-Up: ___________________ Form Completed By: ________________________________
AC Condenser Model Number: ____________________ AC Condenser Serial Number: ________________________
Service Company
Company Name: ____________________________________________ Phone: _______________________
Important Safety Notice............................................................................................................................... 1-2
Special precautions to be observed when charging refrigeration systems ................................................... 1-2
Safety Symbols & What They Mean ........................................................................................................... 1-3
Principle of Operation ................................................................................................................................. 3-1
Air Cooled Piping Diagram, FIGURE 3-1 .................................................................................................. 3-2
Water Cooled Piping Diagram, FIGURE 3-2 .............................................................................................. 3-2
Ice Bin Capacity .......................................................................................................................................... 3-4
When Ice Bin Thermostats Are Not Used ................................................................................................... 3-5
Single Ice .................................................................................................................................................... 3-5
PLC Features & Functions........................................................................................................................... 4-6
Water Distributors, FIGURE 5-1................................................................................................................. 5-4
Water Distributors, Freezer Cover, Gasket Part #'s, TABLE 5-1 ................................................................ 5-4
Water Tank .................................................................................................................................................. 5-5
Drip Pan .................................................................................................................................................... 5-5
Water Cooled Condensers ........................................................................................................................... 5-5
Draining the Condenser ............................................................................................................................... 5-6
Chemical Cleaning the Condenser ............................................................................................................... 5-6
10/16/13
Page 9
HES Series Service Manual
TABLE OF CONTENTS
Page No.
5. MAINTENANCE (Cont.)
Mechanical Cleaning the Condenser ........................................................................................................... 5-6
Part I. .................................................................................................................................................... 5-6
Part II ................................................................................................................................................... 5-7
PLC Inputs and Outputs, TABLE 6-2 ......................................................................................................... 6-3
Machine Will Not Run ................................................................................................................................ 6-4
Water Tank.................................................................................................................................................. 7-6
Cutter-Water Tank Assembly, FIGURE 7-6................................................................................................ 7-6
Head Pressure.............................................................................................................................................. 7-17
Air-Cooled Units ......................................................................................................................................... 7-17
Condenser Fan Switch, FIGURE 7-15 ........................................................................................................ 7-17
5/24/11
Air Cooled Condenser Cleaning.................................................................................................................. 7-17
Water Cooled Units ..................................................................................................................................... 7-19
Water Regulating Valve, FIGURE 7-18...................................................................................................... 7-19
Page 11
HES Series Service Manual
7. SERVICE OPERATIONS (Cont.)
Water Regulating Valve Part #'s, TABLE 7-8............................................................................................. 7-19
Water Cooled Condenser Service................................................................................................................ 7-20
Compressor Motor Rotation ........................................................................................................................ 7-20
Short Circuit Protection, FIGURE 7-22 ...................................................................................................... 7-24
Control Circuit Protection ........................................................................................................................... 7-24
Motor Short Circuit Protection .................................................................................................................... 7-25
Motor Over Current Protection ................................................................................................................... 7-25
Pumping Down Freezer ............................................................................................................................... 7-29
Pumping Down Entire System..................................................................................................................... 7-29
Removal of Refrigerant From the Machine ................................................................................................. 7-29
Single to Dual Ice Conversion ..................................................................................................................... 7-31
10. TECHNICAL SERVICE BULLETINS ................................................................................................ 10-1
11. INDEX .................................................................................................................................................... 11-1
5/24/11
Page 13
HES Series Service Manual
INTRODUCTION
1. Introduction
Henry Vogt Machine Co.
A Brief History Of Our Company. Henry Vogt Machine Co. was founded as a small machine
shop in Louisville, Kentucky in 1880. In 1938, Vogt built the first Tube-Ice® machine and
revolutionized the ice-making industry. Our first “sized-ice” machine quickly replaced the old canice plants, which required much hard labor and large amounts of floor space for freezing, cutting,
and crushing ice by hand.
Today, Vogt Ice, LLC carries on the tradition as one of the world's leading producers of ice-making
equipment.
Vogt Energy-Saving Tube-Ice Machines Are Cost Effective. Today, Vogt Tube-Ice® machines
enjoy a well-earned reputation as the most energy efficient, dependable ice-making equipment in the
world.
Using as little as one-half to one-third the energy required by competitors’ ice makers, Tube-Ice®
machines produce the same amount of ice--in restaurants, sports arenas, packing plants, and
wholesale operations around the globe--at great savings.
In addition, Tube-Ice® machines are renowned for their long life, giving many customers more than
35 years of dependable service. Ask someone who owns one.
Preview. All the skill in engineering and fabrication that we’ve learned in over a century of
experience is reflected in the HES model Tube-Ice® machines. Since Vogt introduced Tube-Ice®
machines in 1938, the process of making Tube-Ice® ice has been widely recognized as the most
economical means of production. The machine’s economic and reliable operation have been proven
over and over again, in a network of varied types of installations throughout the world.
Furnished with your machine is the Certificate Of Test--the report of operating data which is a
record of the unit’s satisfactory operation at our factory test floor. It is evidence of our desire to
deliver to you “the finest ice-making unit ever made.”
This manual is designed to assist you in the operation and maintenance of your unit. Your Tube-Ice®
machine will give you a lifetime of service when you install it, maintain it, and service it properly.
Please read your manual carefully before attempting installation, operation, or servicing of this
professionally-designed piece of equipment. Also, make sure the Warranty Registration/Start-up
Report is completed and returned.
If you have additional questions, please call your distributor. Also, feel free to phone the factory
direct at (502) 635-3000or 1-800-853-8648.
1-1
10/15/13
Page 14
1-2
INTRODUCTION
Important Safety Notice. This information is intended for use by individuals possessing adequate
backgrounds of electrical, refrigeration and mechanical experience. Any attempt to repair major
equipment may result in personal injury and property damage. The manufacturer or seller cannot be
responsible for the interpretation of this information, nor can it assume any liability in connection
with its use.
Special Precautions To Be Observed When Charging Refrigeration Systems. Only technicallyqualified persons, experienced and knowledgeable in the handling of refrigerant and operation of
refrigeration systems, should perform the operations described in this manual. All local, federal, and
EPA regulations must be strictly adhered to when handling refrigerants.
If a refrigeration system is being charged from refrigerant cylinders, disconnect each cylinder when
empty or when the system is fully charged. A gage should be installed in the charging line to
indicate refrigerant cylinder pressure. The cylinder may be considered empty of liquid refrigerant
when the gauge pressure is 25 pounds or less, and there is no frost on the cylinder. Close the
refrigerant charging valve and cylinder valve before disconnecting the cylinder. Loosen the union in
the refrigerant charging line--carefully to avoid unnecessary and illegal release of refrigerant into the
atmosphere.
Immediately close system charging valve at commencement of defrost or thawing cycle if
refrigerant cylinder is connected. Never leave a refrigerant cylinder connected to system
except during charging operation. Failure to observe either of these precautions can result in
transferring refrigerant from the system to the refrigerant cylinder, over-filling it, and
possibly causing the cylinder to rupture because of pressure from expansion of the liquid
refrigerant brought on by an increase in temperature.
Always store cylinders containing refrigerant in a cool place. They should never be exposed to
temperatures higher than 120°F (R-22) or 108°F (R-404A) and should be stored in a manner to
prevent abnormal mechanical shocks.
Also, transferring refrigerant from a refrigeration system into a cylinder can be very dangerous and
is not recommended.
It is not recommended that refrigerant be transferred from a refrigeration system directly into
a cylinder. If such a transfer is made, the refrigerant cylinder must be an approved, CLEAN
cylinder--free of any contaminants or foreign materials--and must be connected to an
approved recovery mechanism with a safety shutoff sensor to assure contents do not exceed net
weight specified by cylinder manufacturer or any applicable code requirements.
HES Series Service Manual
! CAUTION !
! CAUTION !
! CAUTION !
! CAUTION !
10/15/13
Page 15
HES Series Service Manual
INTRODUCTION
1-3
Safety Symbols & What They Mean. Prior to installation or operation of the Tube-Ice® machine,
please read this manual. Are you familiar with the installation, start-up, and operation of a Tube-
®
Ice
machine? Before you operate, adjust or service this machine, you should read this manual,
understand the operation of this machine, and be aware of possible dangers.
These safety symbols will alert you
when special care is needed.
Please heed.
! DANGER !
Indicates an immediate hazard and that special precautions
are necessary to avoid severe personal injury or death.
! DANGER !
! WARNING !
Indicates a strong possibility of a hazard and that an
unsafe practice could result in severe personal injury.
! WARNING !
! CAUTION !
Means hazards or unsafe practices could result
in personal injury or product or property damage.
! CAUTION !
3/25/08
Page 16
3/25/08
Page 17
HES Series Service Manual
Only service personnel experienced and certified in refrigeration and qualified to work
Inspection. As soon as you receive your machine, inspect it for any damage. If damage is suspected,
note it on the shipper’s papers (i.e., the trucker’s Bill of Lading). Immediately make a separate written
request for inspection by the freight line’s agent. Any repair work or alteration to the machine without
the permission of the Vogt Ice LLC can void the machine’s warranty.
The machine was shipped with a full charge of HCFC-404A stored in the receiver. Visually check all
lines for mechanical damage. If a leak is suspected, check all joints with a Halogen Leak Detector. All
leaks should be reported to the Vogt Ice LLC to obtain authorization for repair.
2-1
RECEIPT OF YOUR TUBE-ICE MACHINE
2. Receipt Of Your Tube-Ice Machine
! WARNING !
with high voltage electrical equipment should be allowed to install or work
on this Tube-Ice® machine.
! WARNING !
10/16/13
Page 18
Important Notice.
2-2
HES Series Service Manual
RECEIPT OF YOUR TUBE-ICE MACHINE
Safety Valves. Two safety pressure relief valves are an integral part of the packaged Tube-Ice
machine. One is located in the low side of the system in the suction line between the freezer and the
suction stop valve and one is in the high side of the system on the receiver. You must vent each of the
pressure relief valves to the atmosphere in such a manner as to comply with local and national codes.
Machine Room. The machine must be located inside a suitable building and must not be subjected to
ambient temperatures below 50°F (10°C) or above 110°F (43.3°C). Heat radiation from other sources
(sunlight, furnaces, condenser, etc.) and unusual air current may affect the operation of the machine and
should be avoided. The electrical components of the Tube-Ice® machine are rated NEMA 1.
Therefore, the machine should not be located in a hazardous area.
Storage (prior to installation or start-up). The machine must not be stored or installed in an area that
is subject to reach temperatures at or above 115°F (46.1°C).
The Warranty/Registration Start-Up Report must be completed and
returned to the Vogt Ice LLC to initiate and assure a full warranty.
®
10/16/13
Page 19
HES Series Service Manual
HOW YOUR TUBE-ICE MACHINE WORKS
3.
How Your Tube-Ice Machine Works
Principle Of Operation. The selector switch located on the switch plate of the freezing unit
controls the manual operation of the machine. With the selector switch in the “Ice” position, the
machine is controlled by the PLC and ice bin controls, which will automatically stop and start the
freezing unit by the level of the ice in the storage bin. With Dual Ice machines, the type ice produced
(cylinder or crushed) is determined by the position of the selector switch located in the switch plate.
For Single Type Ice machines, a jumper in the control panel determines the type of ice produced.
(See Electrical Controls for details)
The control wiring is arranged so that the unit will stop only upon the completion of a thawing
period and partial pump down cycle whether by putting the selector switch in the “Off” position or
the ice bin controls.
The selector switch should be put in the “Clean” position only when the equipment is to be cleaned
or pumped down as outlined in the “Cleaning Procedure,” and “Total Pump-Down Procedure”,
Section 7, and instructions attached to the machine.
If it should become necessary to instantly stop the machine, the external disconnect switch (supplied
by customer) must be turned off.
FIGURE 3-1 and 3-2 illustrates the piping diagram of the refrigerant and water circuits of the Tube-
®
machines with numbers for easy reference. Throughout this manual the numbers you see in
Ice
parentheses refer to the numbers in this piping schematic.
The freezer (2) is a shell and tube-type vessel. During the freezing period, water is constantly
recirculated through the vertical tubes of the freezer by a centrifugal pump (6). Make-up water is
maintained by a float valve (12) in the water tank (7). Solenoid valve (20), sometimes referred to as
the “A” valve, is open and solenoid valve (18), sometimes referred to as the “D” valve, is closed.
Refrigerant gas from the top of the freezer (2) passes through the N.O. suction Stop Valve (49), the
accumulator (88), and to the compressor (3), which discharges it into the condenser (15).
Condensed liquid refrigerant from the condenser flows through the boil out coil of the accumulator
(88) and into the receiver (15R). Liquid refrigerant from the receiver flows through the filter/drier
(46), the thawing chamber (16) of the freezer, the strainer (43), “A” valve (20), expansion valve
(17), and into the freezer, thereby completing the freezing circuit.
At the completion of the freezing period, thawing is started by action of the freezer pressure switch
(56) in the control panel. The water pump is stopped and solenoid valve “A” (20) is closed. After a
time lapse of seven seconds, solenoid valve “D” (18) is opened, The Suction Stop Valve (49) closed,
the cutter motor (5M) is started and the harvest (thaw) timer (FIGURE 9-6) is activated. Warm gas
from the receiver is discharged into the freezer through valve (18), thereby slightly thawing the ice,
which drops on the rotating cutter for sizing. Cylinder ice will be discharged through the right halfsection of the ice discharge chute when viewing the Tube-Ice
®
machine from the front. Crushed ice
will be discharged through the left half-section of the ice discharge chute.
Air-cooled machines have a solenoid valve (53), sometimes referred as the “X” valve, in the
compressor discharge line, and a check valve (101) in the liquid return line to the receiver. These
valves prevent the migration of refrigerant to the condenser when the machine is not operating.
18. Thaw Gas Solenoid Valve “D” 70. Stop Valve (ball)
20. Liquid Line Solenoid Valve “A” 88. Accumulator
23. Condenser Water Inlet Connection 90A. Thaw Gas Stop Valve
23A. Make-Up Water Inlet Connection 90B. Thaw Gas / FPS Stop Valve
24. Condenser Water Out Connection 91. Liquid Return Stop
3/25/08
25. Water Tank Drain Connection 101. Check Valve
28. Refrigerant Charging Valve
30. Gage Glass
32. AC Condenser Service Connection
Page 22
HES Series Service Manual
3-4
HOW YOUR TUBE-ICE MACHINE WORKS
Storing Ice. When storing ice in a bin, make sure the bin control sensors are mounted in the bin
properly. Dual ice machines require a storage bin with a divider and must have two bin controls.
A machine making one type of ice will not have a bin divider and will require only one bin control.
If the machine is making cylinder ice, the sensor should be mounted on the right side of the bin. If
making crushed ice, the sensor should be mounted on the left side of the bin.
FIGURE 3-3
Bin Control Sensor Installation
Ice Bin Capacity. Crushed or cylinder ice weighs approximately 35 pounds per cubic ft. (35 lb/ft
3
).
As ice drops into a bin, it will pile up and slope naturally at about a 45° angle. This natural slope
should be taken into account when locating the bin thermostat bulb (or other bin level control) and
when calculating the normal bin capacity. If the ice is spread out by hand in the bin for maximum
storage capacity, make sure a hazard is not created by allowing ice to back up into the chute and
jamming the cutter. Always allow enough room below the chute for at least one harvest (cylinder
ice = 42 lbs. / cycle , crushed ice = 31 lbs. / cycle).
If a two-way defector is installed below the ice chute, care should be taken to make sure it is located
directly in the center of the stream of ice as it falls to give even distribution of the ice.
Page 23
HES Series Service Manual
HOW YOUR TUBE-ICE MACHINE WORKS
When ice bin thermostats are NOT used. For Dual ice machines, with the selector switch SS2 set
on either “Auto” or “Cyl” ice, the machine will produce cylinder ice only. If the switch is changed to
“Cru” while the unit is producing cylinder ice, after the first 5 minutes of a cycle, it will complete the
freeze and harvest of cylinder ice before changing to the production of crushed ice. The next cycle
will produce crushed ice.
With the switch set on “Cru” the machine will produce crushed ice. If the switch is changed to “Auto”
or “Cyl” within the first 5 minutes of a cycle, the unit will revert immediately to the production of
cylinder ice.
If an alternate bin level control is used, it must be located in a position to stop the machine prior to ice
backing up into the ice chute and jamming cutter.
Single Ice Type.
No Divider in bin (cylinder or crushed ice). With the selector switch on “Ice”, the machine will
produce either cylinder or crushed ice. The machine will contain only one freezer pressure switch
(FPS2) and one bin Control (BC2), and a 3-position selector switch (SS), the reversing relay (R) is not
included. The machine will also be supplied with an ice chute without an ice deflector door assembly.
Cylinder Ice. The single ice type machine will be factory adjusted to produce cylinder ice.
3-5
Crushed Ice. To convert a single type ice machine from cylinder to crushed ice, do the
following:
• Move jumper in control panel
• Adjust freezer pressure switch (FPS2)
See “Converting from cylinder to crushed ice”, Section 7, “Service Operations” for details.
Dual Ice Type (crushed and cylinder).
Divider in bin (cylinder and crushed ice separately stored). With the selector switch SS2 on
“Auto”, the machine will automatically produce cylinder ice until the cylinder-ice bin is filled. This
action will open the cylinder ice thermostat switch in the cylinder ice bin and will automatically
change the machine over to crushed ice production--PROVIDED THE CRUSHED ICE BIN IS NOT
FULL. When the crushed ice bin is filled, its thermostat switch opens and stops the machine upon
completion of the harvest cycle and partial pump down cycle.
If, when producing cylinder ice, the thermostat switch for cylinder ice should open within the first
five minutes of that cycle, the machine will immediately revert to crushed ice production. The
selection of cylinder or crushed ice can be changed for that cycle only within the first five minutes of
the freezing cycle. Note: The “R” (reversing relay) is not energized when making cylinder ice.
With the selector switch set on “Cru”, the machine will produce crushed ice until the bin is filled and
the thermostat switch opens. It will then shut down at the completion of the thawing period and
partial pump down cycle. If the switch is changed to “Auto” or “Cyl” within five minutes of the
machine starting crushed ice freeze, it will switch immediately to the production of cylinder ice.
10/16/13
The machine will never stop by action of the bin thermostat during any freezing operation. It will
always complete the evacuation and discharge of all the ice and completion of a partial pumpdown
cycle regardless of the causes, which open either thermostat switch.
Crushed Ice Preferred. A special customized PLC can be programmed and furnished as an option to
produce crushed ice first when the selector switch is in the to “Auto” position. This option will still
allow the operator to select “Cyl” or “Cru” ice as desired, but will produce crushed ice and satisfy that
thermostat first then revert to making cylinder ice. Contact your distributor for details.
Page 24
Page 25
HES Series Service Manual
ELECTRICAL CONTROLS & THEIR FUNCTIONS
4. Electrical Controls & Their Functions
FIGURE 4-1A
Control Panel (Cover Removed)
Note: Machines manufactured after May 1999 will use Allen-Bradley controls
FIGURE 4-1B
Control Panel with Hoffman Enclosure (Door Open)
4-1
10/16/13
Page 26
4-2 HES Series Service Manual
ELECTRICAL CONTROLS & THEIR FUNCTIONS
Vogt Part #
Reference Cutler-Hammer Allen-Bradley Description
12A2117G09 SAME CRUSHED ICE BIN CONTROL (DUAL ICE ONLY)
BC1
12A2117G09SAME CYLINDER ICE BIN CONTROL
BC2
12A7516E1012A7516E26COMPRESSOR CONTACTOR
C
12A7518E15 12A7518E30COMPRESSOR AUX CONTACT
12A7515E18 SAME PUMP / CUTTER MOTOR CIRCUIT BREAKER (10 AMP)
CB1
12A7515E19SAME * CONDENSER FAN MOTOR CIRCUIT BREAKER (15 AMP)
CB2
CB3 & CB4
CPA
FPS1
FPS2
FU1-FU3
FU10 & FU20
PLC
SS & SS2
TEST
*Note: AIR COOLED ONLY
**Note: 5-position switch no long available. Dual ice machines will use two 3-position selectors switches in place of
the 5-position. Clean/Off/Ice (SS) and Crushed/Auto/Cylinder (SS2)
12A7530E11 12A7516E23CUTTER MOTOR STARTER / CONTACTOR
CU
12A7508H2108 12A7538E01CUTTER OVERLOAD HEATERS (3.38-5.54 A) / OL RELAY (2-7 A)
12A2117E04 SAME FREEZER PRESSURE SWITCH (DUAL ICE ONLY)
12A2117E04 SAME FREEZER PRESSURE SWITCH
N/A 12A7504E13CONDENSER FAN MOTOR FUSES, 6A, 600V (400/460V MACH)
N/A 12A7504E14CONTROL CIRCUIT FUSES, 7A, 600V (400/460V MACH)
12A7530E11 12A7516E23PUMP MOTOR STARTER / CONTACTOR
P
12A7508H2109 12A7538E01PUMP OVERLOAD HEATERS (4.96-8.16 AMPS) / OL RELAY (2-7 A)
12A7500E45 12A7500E56
PB1
12A7500E75
N/A 12A7537S06POWER LINE FILTER (CE MACHINES ONLY)
PLF
SAME 12A7536M01PROGRAMMABLE CONTROLLER
12A7517E18 12A7517E27 REVERSING RELAY (DUAL ICE ONLY)
R
**12A7500E43SAME 5 POSITION SELECTOR SWITCH (DUAL ICE)
12A7500E44 12A7500E61
12A7500E73
N / A N / A TERMINAL BLOCK
TB
N / A N / A TEST BLOCK (ON CUTLER-HAMMER - FACTORY USE ONLY)
3 POSITION SELECTOR
CONTACT BLOCK (FOR ALLEN-BRADLEY ONLY)
TABLE 4-1
10/16/13
Page 27
HES Series Service Manual
ELECTRICAL CONTROLS & THEIR FUNCTIONS
Description of Control Panel Parts.
*BC1 and BC2. Bin Controls. Ice bin thermostats for automatically stopping and starting the
machine based on the ice level in the storage bin. BC1 (Crushed Ice). BC2 (Cylinder Ice).
C. Compressor Motor Contactor. Provides power to the compressor motor. Energized during
freezing and thawing. Normally closed contact provides power to the compressor crankcase heater
when the machine is off.
CB1. Pump / Cutter Motor Circuit Breaker (10 amps). Two pole magnetic circuit breaker used for
short circuit protection in the cutter or pump motor circuit. If breaker trips, power is removed from
control circuit, shutting machine down.
CB2. Condenser Fan Motor Circuit Breaker (15 amps). Two-pole thermal magnetic circuit breaker
used for short circuit protection in the condenser motor circuit. If breaker trips, power is removed from
condenser only. Machine will eventually shut off on high discharge pressure.
CB3 and CB4. Control Circuit Breaker (3 Amps). Current limiting thermal magnetic circuit breaker
used as overload and short circuit protection for crankcase heater, PLC outputs and other control circuit
components.
CPA. Copeland PerformanceAlert. Device that monitors compressor current, phase and temperature
and shuts off machine if a problem is detected.
CU. Cutter Motor Starter.
Cutler-Hammer: A three phase motor starter with adjustable bimetallic heater packs, wired for use with
single-phase motor. Cutter Motor Overload (heater packs) – Class 10 overloads rated 3.38 - 5.54 Amps
set at cutter motors FLA rating. Pull "Reset" button to test overload.
Allen-Bradley: Motor starter made of 3-pole contactor and solid-state overload relay, wired for use
with single-phase motor. Overload - Class 10 rated 2 - 7 Amps set at cutter motors FLA rating. Press
"TEST" button to test overload.
Can be configured to reset automatically (“A”) or manually (“M”). PLC controlled machines will have
the overload reset in the “automatic” position. When an overload condition occurs, an auxiliary contact
signals the PLC of a problem and shuts the machine off (PLC input light # 5 will be “off” when
overload is tripped). Will automatically reset after an overloads cool.
See Section 7, Motor Over Current Protection for details.
*FPS1 and FPS2. Freezer Pressure Switches. For regulating the ice thickness by sensing the freezer
pressure and initiating the thaw period. FPS1 (Crushed Ice). FPS2 (Cylinder Ice).
FU10 & FU20. Transformer Primary Protection Fuses - 400/460V machines only. (7A, 600V,
time delay fuses). Fuses used for transformer primary protection along with control circuit upstream of
CB3/CB4.
FU1, FU2 & FU3. Condenser Fan motor Fuses - 400/460V machines only. (6A, 600V, Time delay
fuses). Fused used for short circuit protection in the condenser motor circuit. If fuse(s) blows, power is
removed from condenser only. Machine will eventually shut off on high discharge pressure.
5/24/11
4-3
Page 28
4-4
HES Series Service Manual
ELECTRICAL CONTROLS & THEIR FUNCTIONS
P.Pump Motor Starter.
Cutler-Hammer: A three phase motor starter with adjustable bimetallic heater packs, wired for use on
single phase. Pump Motor Overload (heater packs) – Class 10 overloads rated 4.96 – 8.16 Amps set at
pump motors FLA rating. Pull "Reset" button to test overload.
Allen-Bradley: Motor starter made of 3-pole contactor and solid-state overload relay, wired for use
with single-phase motor. Overload - Class 10 rated 2 - 7 Amps set at pump motors FLA rating. Press
"TEST" button to test overload.
Can be configured to reset automatically (“A”) or manually (“M”). PLC controlled machines will have
the overload reset in the “automatic” position. When an overload condition occurs, an auxiliary contact
signals the PLC of a problem and shuts the machine off (PLC input light # 5 will be “off” when
overload is tripped). Will automatically reset after an overloads cool.
See Section 7, Motor Over Current Protection for details.
PB1. Start/ Harvest button. For starting the machine in the ice-making mode. Momentary contact or
initiating a harvest cycle if the machine is in the freeze mode. Can be used to bypass the built in 120
minute start-up mode delays as well as terminate a harvest cycle.
PLC. Programmable Logic Controller. For monitoring, sequencing, and controlling various
functions of the Tube-Ice® operation. Also has a built in thaw timer for controlling the time of the
thawing period. Thawing time is adjustable from 1 1/2 to 5 minutes.
PLF. Power Line Filter. Used on “CE” approved machines only. Used to reduce amount of noise on
incoming power lines.
*R. Reversing Relay (Dual Ice Only). Switches machine to crush ice by making or breaking various
circuits concerning crushed ice production. Energized during crushed ice production only.
SS. Selector Switch. Three position switch for the purpose of selecting from three different machine
modes, Clean/Off/Ice.
*SS2. Selector Switch (Dual Ice Only). Three position switch for the purpose of selecting the type of
ice, Crushed/Auto/Cylinder.
1LT. Fault indicator light (24VDC light) flashes a designated number of times. A non-auto restart fault
occurs or a auto-restart fault occurs three consecutive times.
*Note: Components used in dual ice type machines only.
10/16/13
Page 29
HES Series Service Manual
ELECTRICAL CONTROLS & THEIR FUNCTIONS
Wiring And Electrical Connection.
Refer to TABLE 4-1 below to properly size wiring connections. A fused disconnect must be
provided near the Tube-Ice® machine. Connect 3-phase power to terminals L1, L2, L3 for operation
of the Tube-Ice® machine and its controls. If one leg of the 3 phase power is higher or lower
(“Wild”), then it should be connected to terminal #L2. Connect the “Ground” wire to the “Ground”
terminal provided. On dual voltage, 50 Hz machines, the 220V single phase should be connected to
terminals L4 and L5.
Note: When initially starting the machine, the scroll compressor must be phased properly. If the
compressor is run backwards for an extended period of time, the compressor may be damaged. See
Section 7, Compressor Motor Rotation for details.
Air-cooled condenser should be wired to terminals 20,21,22 and 23 (see FIGURES 4-9, 4-10).
460V air cooled condensers should be wired to terminals B1, B2, B3, 22 & 23.
4-5
FIGURE 4-2
Terminal Block Connections
Standard Voltages: Water Cooled Air Cooled
Model Voltage F.L.A. Min. Ampacity Max. Fuse F.L.A. Min. Ampacity Max. Fuse
Explanation. The HES-Series Tube-Ice® machine is controlled by a PLC (Programmable Logic
Controller). The PLC controls the sequence of events and monitors the ice machine functions. The
operational sequences of the HES-Series Tube-Ice® machine can be described best as a series of eight
different modes. Each mode identifies and defines a sequence of events that occur while in that mode
and thereby cause it to move to the next mode. Only one mode is active at a time.
Start-Up Mode. The start-up mode is a function, which prevents the premature automatic starting of
the machine at the time of installation, after a power interruption, or after a safety trip. Its normal time
period is two hours. The start-up mode may be bypassed at any time by pressing the “Harvest/Start”
button to immediately advance to the standby mode.
! CAUTION !
If the power has been turned off to the machine, make sure the compressor crankcase is warm
And there is no liquid refrigerant in with the oil before restarting the unit.
! CAUTION !
5/24/11
Page 31
HES Series Service Manual
ELECTRICAL CONTROLS & THEIR FUNCTIONS
Standby Mode. The standby mode is a decision-making mode. It monitors the position of all the
various switches in the control circuit and at the proper time decides which mode to advance to next.
Freeze Mode (Freeze Cycle). The freeze mode is active during the normal ice making cycle. During
this time, the circulating water pump and compressor are running and the “A” (liquid feed) solenoid
valve and “X” solenoid valve compressor discharge (AC units only) is open.
Harvest Mode (Thaw Cycle). The harvest mode is normally initiated at the termination of the freeze
mode. At this time, the circulating water pump stops and the “A” (liquid feed) solenoid valve closes.
After seven seconds, the “D” (thaw gas) solenoid valve opens, the “SS” (suction stop) solenoid valve
closes, the cutter motor starts and the thaw timer is activated.
The harvest mode is terminated by the thaw (harvest) timer at which time the machine will begin
another freeze cycle. The harvest mode can also be terminated manually by pushing in the
“Harvest/Start” button.
NOTE: If the “Selector Switch” switch is in the “Off” position or the bin control is satisfied the
machine will advance to the partial pumpdown mode before shutting off (standby mode).
Partial Pumpdown Mode. The partial pumpdown mode precedes the normal off or standby mode. Its
purpose is to transfer a portion of the liquid from the suction accumulator and freezer into the receiver
prior to shutdown of the machine (standby mode). This will discourage any migration of liquid
refrigerant to the compressor during the off or standby mode. It is also intended to prevent any liquid
refrigerant slugging to the compressor when the machine restarts in a freeze mode.
4-7
When partial pumpdown is initiated, the “A” (liquid feed) solenoid valve is closed and the water pump
and compressor run for a set time. After this set time the compressor stops and the machine is in the
standby mode.
Model HES-20 HES-30 HES-40
Time 7 minutes 5 minutes 3 minutes
TABLE 4-4
Partial Pumpdown Time
NOTE: The PLC uses the cylinder ice pressure switch (FPS2) as a partial pumpdown safety. Do not
remove this pressure switch from the machine.
Total Pumpdown Mode. The function of the total pumpdown mode is to transfer all of the liquid
refrigerant from the freezer (evaporator) into the receiver. Total pumpdown is initiated as the first
phase of and prior to entering the “Clean” mode.
Its main purpose is to clear the freezer of liquid refrigerant and prevent possible refrigerant migration to
the compressor while running the “Clean” cycle. It can also be used to check the units total refrigerant
charge, isolate the refrigerant in the receiver while making repairs, or prepare the machine for
disconnecting and moving.
To restart the machine after a total pumpdown, put the “Selector Switch” switch in the “Ice” position
and press the “Harvest/Start” button. At this time the “A” (liquid feed) solenoid valve will open for
two minutes, allowing refrigerant to feed into the freezer before the machine starts into a freeze cycle.
5/24/11
Page 32
4-8
HES Series Service Manual
ELECTRICAL CONTROLS & THEIR FUNCTIONS
Clean Mode. The “Clean” mode is considered to be maintenance or servicing function of the machine.
During this mode only the water pump will run. The first phase of the “Clean” mode is a total
pumpdown.
! CAUTION !
Do not attempt to bypass the total pumpdown phase of the “Clean” mode. If a clean cycle is
performed without first completing a total pumpdown, the warm water being circulated through
the freezer tubes can force refrigerant to migrate to the suction accumulator and compressor
which can cause compressor damage when returning to the freeze mode.
! CAUTION !
After the total pumpdown, the water pump can be stopped by simply moving the “Selector Switch”
from the “Clean” to the “Off” position. To restart the water pump, move the “Selector Switch” back to
the “Clean” position and press the “Harvest/Start” button. (Note: If the freezer and compressor suction
pressure have come up enough to open the freezer pressure switch FPS2 and close low pressure safety
switch 4PS, the compressor will come on and pump down the freezer again.) Ice machine cleaning
solution can be circulated though the tubes to accomplish the cleaning procedure. If the water pump is
left to run in the clean mode for more than two hours, the PLC will shut the machine off. The clean
mode can be resumed by pushing the “Harvest/Start” button.
NOTE: Running in Clean mode for extended period of time can cause excessive pressure to build up in
the freezer.
At the termination of the clean mode, the machine can be returned to ice making mode by putting the
“Selector Switch” in the “Ice” position and pressing the “Harvest/Start” button. . At this time the “A”
(liquid feed) solenoid valve will open for two minutes, allowing refrigerant to feed into the freezer
before the machine starts into a freeze cycle.
Fault Mode. The HES Series (“S” for Smart) is equipped with a PLC (programmable logic
controller) that controls all aspects of the operation. One of the functions of the PLC is to shut down
the machine when a problem arises and send a signal to the fault indicator light located on the far-left
side of the electrical panel. The red light is visible through the opening in the front casing and will
blink when a problem has caused the machine to shut down (See FIGURE 4-2).
NOTE: The Fault Light will flash the designated number of times ONLY if the fault is a not a autorestart fault or a auto-restart fault that has occurred three consecutive times. For your reference,
TABLE-4-3 contains a list of fault codes.
# Description Restart Off Delay
1 High / Low Press - Freeze No N/A
2 High / Low Press - Harvest No N/A
3 High / Low Press - Partial Pumpdown No N/A
4 High / Low Press - Total Pumpdown No N/A
5 Short Cycle Yes 2 hrs
6 Long Cycle No N/A
7 Pump Motor Overload Yes 30 min
8 Cutter Motor Overload Yes 30 min
N/A Power Failure Yes 2 hrs
NOTE: The machine may be off on a fault and not flashing an error code if the fault is an auto-restart
fault and it is not the third consecutive occurrence of this fault.
TABLE 4-5
PLC Fault Codes
5/24/11
Page 33
If fault 1, 4, 6 or 7 occurs ("LOCKOUT"), fault must be manually reset by cycling power to the Performance Alert.
HES Series Service Manual
ELECTRICAL CONTROLS & THEIR FUNCTIONS
Copeland Performance Alert (CPA). This device is used to monitor the compressor discharge
temperature, compressor current and phase, as well as control voltage to the compressor contactor. If
a problem is detected, the compressor will shut off. The fault light on the CPA will flash a certain
number of times to indicate the fault that occurred. See table below.
NOTE: When this occurs, the ice machine will continue to run but the compressor will not be on.
The ice machine will eventually shut off on a “Long Cycle Fault”.
Some faults, referred to as “lockout” faults, will require cycling power to the Performance Alert to
reset. This can be done by switching CB1 to the “off” position for 5 seconds, then back “on”.
NOTE: If ice machine has a High/Low pressure fault, the Performance Alert can detect low control
voltage at the compressor contactor and flash 9 times. This will clear when the machine is re-start.
FIGURE 4-4
Copeland Performance Alert Wiring
Alert Codes System Conditions Description
1 High Discharge Temperature
4 Lock Rotor
6 Missing Phase
7 Reverse Phase (Scroll only)
8 Welded Contactor No demand signal but current has been detected in one
or both phases
9 Low Voltage Control voltage dips below 85V for 110V or 170V for
11 DLT Sensor Failure Discharge Temperature Sensor short or open circuit
Discharge Temperature above set point
(default 230 Deg F) adjustable 170 to 281
4 Consecutive Compressor trips after run time of 1 to
15 seconds indicating compressor won't start
Demand signal is present but current is missing in
one phase
Demand signal is present but current is not detected in
the correct sequence
220V
Note:
Faults 1, 4, 6, 7, 9 will shut off compressor with a off time of 20 minutes (adjustable from 10 to 40 minutes).
* The Cutter or Pump overload is tripped (PLC input light 5 is “off”)
High / Low Pressure Fault during Freeze
High / Low Pressure Fault during Harvest
High / Low Pressure Fault during Partial Pumpdown
High / Low Pressure Fault during Total Pumpdown
Short Cycle Faults (3 Consecutive)
Long Cycle Fault
Water Pump Motor Overload Fault (3 Consecutive)
Cutter Motor Overload Fault (3 Consecutive)
While in the Fault Mode, if Harvest / Start Button is pressed twice and the machine does not start, one of the following is true:
* Bin control is not calling for ice or Selector switch is in the “off” position (PLC input lights 0 & 1 are “off”)
* The high / low pressure switch is tripped (PLC input light 6 is “off”)
Press Harvest / Start
Button twice to
Press Harvest / Start
Button twice to
2 Minute
Run water
pump for
Harvest
2 Minute
FIGURE 4-5
Machine Fault Startup Sequence
Freeze
Harvest
Freeze
5/24/11
FIGURE 4-6
Fault Indicator / Selector Switch Location
Page 35
HES Series Service Manual
ELECTRICAL CONTROLS & THEIR FUNCTIONS
4-11
10/16/13
NOTE:
USE COPPER CONDUCTORS
RATED 60 °C OR HIGHER
FIGURE 4-7
Dual Ice Type (200/208/230V)
Page 36
4-12
HES Series Service Manual
ELECTRICAL CONTROLS & THEIR FUNCTIONS
10/16/13
NOTE:
USE COPPER CONDUCTORS
RATED 60 °C OR HIGHER
FIGURE 4-8
Single Ice Type (200/208/230V)
Page 37
HES Series Service Manual
ELECTRICAL CONTROLS & THEIR FUNCTIONS
4-13
10/16/13
NOTE:
USE COPPER CONDUCTORS
RATED 60 °C OR HIGHER
FIGURE 4-9
Dual Ice Type (400/460V)
Page 38
4-14
HES Series Service Manual
ELECTRICAL CONTROLS & THEIR FUNCTIONS
10/16/13
NOTE:
USE COPPER CONDUCTORS
RATED 60 °C OR HIGHER
FIGURE 4-10
Single Ice Type(400/460V)
Page 39
HES Series Service Manual
ELECTRICAL CONTROLS & THEIR FUNCTIONS
Wiring Connections to Air-Cooled Condenser.
FIGURE 4-11
Wiring For BOHN DVT005 with Cold Weather Valve and Single Fan,
50/50 Condenser Split
5/24/11
4-15
Page 40
4-16
HES Series Service Manual
ELECTRICAL CONTROLS & THEIR FUNCTIONS
Wiring For BOHN DVT008 with Cold Weather Valve and Single Fan,
FIGURE 4-12
50/25/25 Condenser Split
5/24/11
Page 41
HES Series Service Manual
ELECTRICAL CONTROLS & THEIR FUNCTIONS
FIGURE 4-13
Wiring For BOHN DVT012 /DVT016 with Cold Weather Valve and Two Fan,
50/50 Condenser Split
5/24/11
4-17
Page 42
Blank page
5/24/11
Page 43
Page 44
Page 45
Page 46
Page 47
Page 48
Page 49
HES Series Service Manual
Part II.
The inside of the water end plates and the outer tube sheet surfaces should be cleaned only with clear
water and a rag or a soft bristle brush. A worn paintbrush is excellent. These surfaces have been
coated with a special material, which will give years of protection against corrosion unless damaged.
Never use a wire brush or a strong caustic on these surfaces.
Flush condenser tubes clear with air, water, or a piece of rag on a stick or wire. In many cases this is
all that is required. If the inside surfaces are smooth, even though discolored, further cleaning is not
necessary. It is useless to try and get a bright copper surface on the inside of the tubes. They will
discolor almost immediately in service and the condenser has been designed with an adequate
reserve for moderate fouling on these surfaces.
If, however, a rough coating remains inside the tubes after flushing and wiping, further cleaning is
desirable. The color of this coating varies with water conditions, but roughness indicates cleaning
tools should be used.
Any type tool to be considered should be tried first on a piece of copper tubing held in a vise or flare
block. Nylon, brass, or copper brushes are recommended. If any flakes of copper appear or if score
marks are made inside the tube, the tool should not be used. Never use anything with sharp or rigid
edges, which could cut into the copper tubing.
A cleaning tool is available from Vogt
through your distributor. Part #12A 2055B01.
5-7
MAINTENANCE
When using a cleaning tool, keep the inside of the tube wet and move the tool slowly from one end
to the other while rotating it at a moderate speed. A hand drill brace is recommended. If an electric
drill is used, a low speed attachment on a 1/4” size drill is preferred. Larger units are powerful
enough to damage a tube, if for any reason, the cleaning tool should stick. After one or two passes
in each tube, they should be flushed and inspected. Often this is enough, although some deposits
require more. In any case, stop when a few places begin to show a copper color.
After cleaning, wipe all foreign matter from the tube sheets and studs. Reassemble as outlined on
gasket installation instructions.
If the gasket seal ridge was damaged and a replacement is not immediately available, water leaks can
be stopped by removing the gasket, drying it, and apply a thin film of a non-hardening gasket sealer,
such as Permatex #2, around the seal ridge. This film should be no thicker than the height of the
ridge itself and about 3/16” wide. Then re-assemble.
If a new gasket is put on later, be sure to remove any grit or particles that stick to the sealer film on
the tube sheet. It is not necessary to remove all traces of the sealer before installing a new gasket, as
long as no particles that cut into the new gasket remain on the surface.
Water Cooled Condenser Gasket
Machine Manufacture Model # Vogt Part # Vogt Part #
HES-20 KH-2X 12A2115S040112A2600S01
HES-30 KH-3X or C-3X 12A2115S030112A2600S01
HES-40 KH-5X or C-5X 12A2115S020112A2600S03
10/16/2013
TABLE 5-2
Water Cooled Condenser Gasket
Page 50
5-8
MAINTENANCE
Air-Cooled Condenser Cleaning. Visual inspection will indicate if dirt is accumulating and
clogging the fin face of the condenser. A vacuum cleaner, compressed air, or a brush may be used to
remove any accumulation of loose dirt from the fin section of the condenser.
For the removal of more severe accumulations of dirt or foreign materials, a detergent-type cleaner
can be used. Your local refrigeration supply house can supply this cleaning agent. Follow the
manufacturer’s instructions when using a liquid cleaner.
If fins have been damaged, they should be straightened with the proper fin comb.
Compressor Oil. In starting and charging the unit, the oil sight glass (33) in the crankcase of the
compressor should be watched carefully for the first hour to make certain the proper lubrication is
being maintained. The oil may become low in the crankcase on an initial start-up if the electrical
current has been interrupted to the machine, thus de-energizing the compressor crankcase heater.
Before starting the machine again, the heater should be energized for a time period of at least two
hours to evaporate refrigerant that may have condensed in the crankcase during the shutdown period.
If level is low after start-up, it should begin to return after a short period of operation.
The oil level should be checked frequently, particularly during the start-up operation, to see that a
sufficient amount of oil remains in the crankcase. While it is important to observe the oil splash
during operation, the true level can be obtained only when the compressor is stopped. With the
compressor idle, the oil level should be between 1/2 to 3/4 of the sight glass, but not above the top of
the sightglass.
HES Series Service Manual
Although the machine was shipped with the oil charge, which was originally added for the test
operation, it may be necessary to add some oil when or if new refrigerant is added to the system.
An oil pump should be used to force any oil that may be required into the system. Oil may be added
to the compressor of all units through the compressor oil charging port. Air should be purged from
the oil pump discharge line by forcing some oil through the line before tightening the charging port.
R22 – use “Dual Inhibited Sunisco 3GS” (Viscosity 150) or equal.
R404A – use Polyolester (POE) Oil (Viscosity 150).
10/16/2013
FIGURE 5-2
Scroll Compressor
Cutter Gear Reducer Oil. The oil level for the gear reducer should be checked if there is evidence
of a leak. It should be level with the plugged opening in the side of the gear housing. Use Mobile
600W cylinder oil or equal.
Page 51
Page 52
Page 53
HES Series Service Manual
The HES Series is equipped with a PLC (programmable logic controller) that controls all aspects of the
machines operation. One function of the PLC is to shut down the machine when a machine fault occurs.
By continuously monitoring the High / Low pressure safety switch, the Freeze cycle time, and the cutter
and pump motor overloads, the PLC can determine if a problem exist.
There are two types of faults, which can occur: an "auto-restart fault" and a "major fault". For your
reference, TABLE 6-1 contains a list of fault codes.
"Auto-Restart Fault" - if the machine shuts off due to a "short cycle" fault, a pump motor overload or
a cutter motor overload, the machine will automatically restart itself after a predetermined amount of
time (Off Delay). If an auto-restart fault occurs three consecutive times, it will be considered a "major"
fault and not automatically restart.
"Major Fault" - if the machine shuts off due to a High / Low Pressure fault or a "long cycle" fault, the
machine will not automatically restart. This is considered a "major" fault.
Note: A major fault is also an auto-restart fault that has occurred three consecutive times.
When a "major fault" occurs, the PLC sends a signal to the fault indicator light located on the far-left
side of the electrical panel. The red light is visible through the opening in the front casing and will
display the appropriate error code (See FIGURE 6-2).
NOTE: The Fault Light will flash the designated number of times ONLY if the fault is a "major fault".
The machine may be off on a fault and not flashing an error code if the fault is an auto-restart fault and it
is not the third consecutive occurrence of this fault.
# Description
1 High / Low Press - Freeze No N/A
2 High / Low Press - Harvest No N/A
3 High / Low Press - Partial Pump down No N/A
4 High / Low Press - Total Pump down No N/A
5 Short Cycle Yes 2 hrs
6 Long Cycle No N/A
7 Pump Motor Overload Yes 30 min
8 Cutter Motor Overload Yes 30 min
N/A Power Failure Yes 2 hrs
6-1
TROUBLESHOOTING
6. Troubleshooting
Auto-
Restart
Off Delay
3/25/08
TABLE 6-1
PLC Fault Codes
NOTE: If Auto-Restart = No, fault is considered a "major fault"
* The Cutter or Pump overl oa d is tripped (PLC input l i g ht 5 is “off”)
High / Low Pressure Fault during Freeze
High / Low Pressure Fault during Harvest
High / Low Pressure Fault during Partial Pumpdown
High / Low Pressure Fault during Total Pumpdown
Short Cycle Faults (3 Consecutiv e)
Long Cycle Fault
Water Pump Motor Overload Fault (3 Consecutive)
Cutter Motor Overload Fault (3 Consecutive)
While in the Fault Mode, if Harvest / Start Button is pressed twice and the machine does not start, one of the following is true:
* Bin control is not calling for ice or Selector s wi tch is in the “off” pos ition (PLC i npu t lights 0 & 1 are “off”)
* The high / low pressure switch is tripped (PLC input light 6 is “off”)
Press Harvest / Start
Button twice to
restart machine
Press Harvest / Start
Button twice to
restart machine
If the machine is not running and the fault indicator is not flashing, the best tool for troubleshooting is the PLC
light. Remove the control panel cover and observe lights on the PLC.
Note: In order for the machine to run, PLC inputs # 0 (or 1 for dual ice machines), #5 and #6 must be "on"
No lights on PLC "on"
No PLC input lights "on"
Input #0 (or #1dual ice machine) NOT "on"
but #5 and #6 are "on"
Inputs # 0, # 5 and # 6 are "on" and
Outputs # 1, # 2 and # 4 are "on" but
nothing Is running
Inputs # 0 and # 6 are "on" but # 5 is "off"
* If overloads are set on Manual "M" reset, press the Reset button
If the machine starts up in the "Clean" mode, it was off on Cutter
If inputs # 0, # 5 and # 6 are "on" but the
machine is not running, it is in the Startup
mode.
Checking PLC
If the machine is not running, the first thing that should be done is checking the lights on the PLC.
Check the "Power", "Run" and "Prog-E/CPU-E" lights on the PLC. The PLC Input and Output
lights should also be used to help determine what mode the machine is in or why it will not run.
Note: The PLC is a very reliable device, which has a failure rate of less that 0.1%.
No lights on PLC "on”
PLC "Run" light not "on"
PLC "Error light "on"
No PLC Input lights "on"
PLC output energized (light "on") when
it is supposed to be "off"
(Example - pump runs during harvest cycle)
HES Series Service Manual
See "Checking PLC" below
See "Checking PLC" below
Selector switch is in the "off" position
Ice Bin Control is not calling for ice. Bin Con trol LCD will display
"S1" if calling for ice. See Section 7, page 7-25 for bin control info.
Selector switch in the "on" position and bin control displaying "S1",
but input # 0 not on. Check for bad selector switch.
Note: Bin control and selector switch are in series.
Control Circuit breaker tripped (CB3 or CB4)
* Shorted crankcase heater
* Shorted solenoid valve coil, starter, relay or contactor coil
Note: Machine will eventually shut off on "Long Cycle" fault
Cutter or pump motor overload is tripped. See Section 7, page 7-23.
* If overloads are set on Automatic "A" reset, the motor has
recently tripped. Wait until heaters have cooled and Input # 5
comes "on", then restart machine.
the motor starter to reset.
overload. If the machine starts in the "Freeze" mode, it was off on
pump motor overload.
The machine has shut off on one of the following:
* Power failure
* Cutter motor overload
* Pump motor overload
* Short cycle
Check main disconnect to the machine
Check pump / cutter circuit breaker
Check power to PLC - if line voltage supplied, check the following
* PLC power supply is shorted - to check, remove the wires from
PLC power supply (OUT - 24V and 0V)
* Internal 3A fuse blown
Check "Run/Stop" switch - should be in "Run" position
Flashing Program must be reloaded
Continuous Turn power "off" then back "on" to PLC - if continues, replace PLC
Check PLC power supply labeled "OUT"- 0V and 24V terminal
Note: This is 24VDC - MUST use a DC meter to read
Kill power to PLC using pump/cutter circuit breaker - after power is
restored, all outputs should be "off". If any output comes on, PLC
should be replaced
3/25/08
Page 57
HES Series Service Manual
Low Ice Capacity
If the machine is operating but appears low on capacity, check the following:
Determine the machines actual capacity by obtaining the following information: makeup water
temperature, freeze cycle times, harvest time, and amount of ice per cycle.
Capacity (lbs/day) = 1440 (min/day) / Total cycle (min) * Ice (lbs).
See Section 9 for machines rated capacity and operating vitals.
Intermittent power interruptions or
power failure.
Cutter or pump motor overload trips
(PLC input # 5 light "off")
Electronic Bin Control not positioned
correctly or properly set, shutting
machine off prematurely
Extended Freeze times
* Hot water being supplied to the machine for making ice
* High Compressor discharge pressure
* Faulty D-valve (not closing properly)
Machine Short Cycles
6-5
TROUBLESHOOTING
If there is a power failure or a power interruption, the machine will
advance to a start-up mode when power is restored. After a twohour period, the machine will restart automatically if there is no
other problem.
If the cutter or pump motor overloads trip, the machine will shut off
and go to the start-up mode. Because the overload resets are set on
automatic, "A", when the overload heater packs cool, they will reset.
After a 30 minute delay the machine will restart.
If you suspect this is a problem, set the overloads resets on manual,
"M". See Section 7, page 7-23.
See that bin control is positioned correctly and set properly.
Certain mechanical problems can cause the machine to run extended
freeze cycles. These long freeze cycles may not be long enough to
cause the machine to shut off on "long cycle" fault, but long enough
to reduce capacity substantially.
* Improperly set or defective water float valve
* Leaking or open water tank drain valve
If machine is "short cycling" due to a mechanical or electrical
problem, the machine will shut off and advance to a start-up mode.
After a two-hour period, the machine will restart automatically. (See
Fault # 5 for possible causes)
3/25/08
Page 58
6-6
TROUBLESHOOTING
Major Fault - Below is a list of the Major Faults and possible causes.
This fault can be caused by either high compressor discharge pressure or low compressor suction pressure.
This fault is sensed by the compressor's High/Low Pressure safety switch (PLC input - X6). During normal
machine operation, this safety switch is closed and PLC input X6 is "ON". When this fault occurs, the safety
switch opens and X6 turns "OFF".
- With a Low pressure fault, the safety switch will automatically reset (input # 6 will come "on") when
compressor suction pressure comes up to the set-point (40 PSI).
- With High-pressure fault, the safety switch must be manually reset.
Note: Discharge pressure must be 50 psig below the set point of the switch. This switch is sometimes very hard to reset.
Low Suction Pressure
High Discharge Pressure
Other Problems
(Not High or Low Pressure)
HES Series Service Manual
Broken or leaking capillary tube going from freezer to harvest
pressure switches
Rota-lock valve on bottom of freezer is backseated, shutting off
freezer pressure switch
Faulty or improperly adjusted cylinder ice harvest pressure switch
Note: If crushed ice harvest pressure switch is bad or improperly
adjusted, cylinder ice harvest pressure switch would eventually
close causing machine to harvest. If this occurs, ice would be
thick and could possibly cause the cutter overload to trip.
Faulty PLC input - X2 (will not sense voltage)
Suction stop valve stuck closed (valve is normally on)
Closed compressor suction valve
Dirty condenser restricting air or water flow
Restriction in condenser return line
Closed compressor discharge valve
Water cooled only
* Faulty or improperly adjusted condenser water regulator valve
* No condenser water
Air cooled only
* Faulty X-Valve or X-Valve coil
* Faulty condenser fan motor
* Faulty condenser fan contact
* Faulty condenser fan control pressure switch
Faulty PLC input - X6 (will not sense input voltage)
Broken or leaking capillary tube going from compressor to low side of
High / Low Pressure safety switch
Faulty or improperly adjusted High / Low Pressure safety switch
This fault can be caused by either high compressor discharge pressure or low compressor suction pressure.
This fault is sensed by the compressor's High/Low Pressure safety switch (PLC input - X6). During normal
machine operation, this safety switch is closed and PLC input X6 is "ON". When this fault occurs, the
safety switch opens and X6 turns "OFF".
- With a Low pressure fault, the safety switch will automatically reset (input # 6 will come "on") when
compressor suction pressure comes up to the set-point (40 PSI).
- With High-pressure fault, the safety switch must be manually reset.
Note: Discharge pressure must be 50 psig below the set point of the switch. This switch is sometimes very hard to reset.
Low Suction Pressure
High Discharge Pressure
Other Problems
(Not High or Low Pressure)
Fault # 3 - High / Low Compressor Pressure - Partial Pump down Mode
(Fault Indicator Light Flashing 3 Times)
This fault can be caused by either high compressor discharge pressure or low compressor suction pressure.
This fault is sensed by the compressor's High/Low Pressure safety switch (PLC input - X6). During normal
machine operation, this safety switch is closed and PLC input X6 is "ON". When this fault occurs, the safety
switch opens and X6 turns "OFF".
- With a Low-pressure fault, the safety switch will automatically reset (input # 6 will come "on") when
compressor suction pressure comes up to the set-point (40 PSI).
- With High-pressure fault, the safety switch must be manually reset.
Note: Discharge pressure must be 50 psig below the set point of the switch. This switch is sometimes very hard to reset.
Low Suction Pressure
High Discharge Pressure
Water cooled only
* Faulty or improperly adjusted condenser water regulator valve
* No condenser water
Air cooled only
* Faulty X-Valve or X-Valve coil
* Faulty condenser fan motor
* Faulty condenser pressure switch (CPS)
Other Problems
(Not High or Low Pressure)
6-7
TROUBLESHOOTING
Faulty D-Valve or D-Valve coil (not opening properly)
Note: A faulty D-Valve or D-Valve coil may also cause the machine
to stay in a continuos harvest, causing a short cycle fault.
Faulty X-Valve or X-Valve coil (Air cooled only)
Dirty condenser restricting air or water flow
Restriction in condenser return line
Faulty PLC input - X6 (will not sense input voltage)
Broken or leaking capillary tube going from compressor to low side
of High / Low Pressure safety switch
Faulty or improperly adjusted High / Low Pressure safety switch
Low refrigerant charge which allows the compressor to pull freezer
pressure down
Faulty A-Valve or A-Valve coil (not opening properly)
Dirty condenser restricting air or water flow
Restriction in condenser return line
Closed compressor discharge valve
* Faulty condenser fan control pressure switch
Faulty PLC input - X6 (will not sense input voltage)
Broken or leaking capillary tube going from compressor to low side
of High / Low Pressure safety switch
Faulty or improperly adjusted High / Low Pressure safety switch
3/25/08
Page 60
6-8
TROUBLESHOOTING
Fault # 4 - High / Low Compressor Pressure - Total Pumpdown Mode
(Fault Indicator Light Flashing 4 Times)
This fault can be caused by either high compressor discharge pressure or low compressor suction pressure.
This fault is sensed by the compressor's High/Low Pressure safety switch (PLC input - X6). During normal
machine operation, this safety switch is closed and PLC input X6 is "ON". In this mode the Low Pressure
safety switch is used to indicate that the freezer is pumped down and for the machine to leave the Total Pump
down Mode. At this time input X6 will be "OFF". Because of this, the controller will not determine a lowpressure fault until the machine attempts to go to the Freeze Mode. (This will actually occur while machine is
in the Standby Mode). If the machine is unable to reset the High / Low Pressure safety switch by raising the
freezer pressure, or unable to raise the freezer pressure itself, the controller will sense a problem and set the
fault. With High pressure fault, the safety switch must be manually reset.
Low Suction Pressure
High Discharge Pressure
Water cooled only
* Faulty or improperly adjusted condenser water regulator valve
* No condenser water
Air cooled only
* Faulty X-Valve or X-Valve coil
* Faulty condenser fan motor
* Faulty condenser fan contact
Other Problems
(Not High or Low Pressure)
HES Series Service Manual
Faulty A-Valve or A-Valve coil (not opening properly)
Note: If this occurs, the machine may be unable to raise the freezer
pressure above the set-point (35 PSI) to reset the High / Low
Pressure safety switch.
Dirty condenser restricting air or water flow
Restriction in condenser return line
Closed compressor discharge valve
* Faulty condenser fan control pressure switch
Faulty PLC input - X6 (will not sense input voltage)
Broken or leaking capillary tube going from compressor to low side
of High / Low Pressure safety switch.
Faulty or improperly adjusted High / Low Pressure safety switch
Faulty or improperly adjusted cylinder ice harvest pressure switch.
Note: If harvest pressure switch is not closed when High / Low
Pressure safety switch opens, the controller will think there is a
problem with the compressor operating pressure and set the fault.
* Make sure the differential on the cylinder ice harvest pressure
switch is set correctly (10 PSI) as well as the low pressure cut-in
differential on the High / Low Pressure Safety Switch (20 PSI).
3/25/08
Page 61
HES Series Service Manual
Fault # 5 - Short Cycle Fault
(Fault Indicator Light Flashing 5 Times)
A "short cycle" is defined as a Freeze cycle which is less than a predetermined amount of time: HES-20 = 10 minutes
HES-30 = 5 minutes
HES-40 = 5 minutes
If machine runs three consecutive short cycles, it will shut down on Short cycle fault. After a 2 hour
delay, the machine will restart in the Harvest mode before going to a Freeze cycle. If the machine does
not finish a full freeze (short cycle timer times out) the machine will shut off on a Short cycle fault again.
If this occurs again, the machine will shut off and not restart itself.
This fault occurs when the machine encounters three (3) short cycle faults in a row.
Reduced heat load on the Freezer
* Clogged or partially obstructed water distributors
* Pump not supplying adequate water flow (dirty or defective)
* Improper or No makeup water flow
Low refrigerant level in freezer
* Low refrigerant charge in machine
* Harvest cycle too short
* Not enough heat to get ice out during harvest
- Condenser fan motor (s) running continuously
- Sub cooled liquid return from condenser
- Restriction in condenser liquid return line
Non-Condensables in system
Fault # 6 - Long Cycle Fault
(Fault Indicator Light Flashing 6 Times)
A "long cycle" occurs when the machine is in the Freeze Mode for a predetermined amount of
time and has not made a batch of ice. Long Freeze cycle times are defined as:
HES-20 = 120 minutes
HES-30 = 80 minutes
HES-40 = 60 minutes
6-9
TROUBLESHOOTING
* Faulty A-Valve or A-Valve coil (not opening properly)
* Clogged filter drier
* Restriction in the liquid line (TXV strainer)
* Improperly adjusted or defective TXV
Faulty or improperly adjusted harvest pressure switch
Freezer full of ice (refreeze-not all ice getting out during harvest)
* Low compressor discharge pressure
* Faulty D-Valve or D-Valve coil (not opening properly)
Leaking or open water tank drain valve
Improperly set or defective water float valve (on continually)
Faulty D-Valve (not closing properly)
Damaged compressor
Compressor not running
* Compressor Thermal overload
* Faulty compressor contactor
Control Circuit breaker tripped (CB3 or CB4)
* Shorted crankcase heater
* Shorted solenoid valve coil, starter, relay or contactor coil
3/25/08
Page 62
6-10
TROUBLESHOOTING
Fault # 7 - Pump Motor Overload Fault
(Fault Indicator Light Flashing 7 Times)
A three phase motor starter with adjustable bimettalic heater packs, wired for use on single phase,
controls the water pump motor. The overloads are configured to reset automatically (“A”) after a
overload condition occurs. When this occurs auxiliary contact signals the PLC of a problem and shuts the
machine off (PLC input light # 5 will be “off” when overload is tripped).
Will automatically reset after an overloads cool. Pull the reset button to test the overload.
This fault occurs when the water pump overload has tripped 3 consecutive cycles.
Defective pump motor
Fault # 8 - Cutter Motor Overload Fault
(Fault Indicator Light Flashing 8 Times)
A three phase motor starter with adjustable bimettalic heater packs, wired for use on single phase,
controls the cutter motor. The overloads are configured to reset automatically (“A”) after a overload
condition occurs. When this occurs auxiliary contact signals the PLC of a problem and shuts the machine
off (PLC input light # 5 will be “off” when overload is tripped).
Will automatically reset after an overloads cool. Pull the reset button to test the overload.
This fault occurs when the cutter motor overload has tripped 3 consecutive cycles.
Defective cutter motor
Defective gear reducer
HES Series Service Manual
Low voltage being supplied to pump motor
*Low voltage supplied to machine
*Loose wire on the motor starter
* Voltage drop across motor starter contacts
Overloads heaters set too low - See Section 7, Table 7-11
Start switch on pump motor sticking
Running water pump dry
Low voltage being supplied to cutter motor
*Low voltage supplied to machine
*Loose wire on the cutter motor starter
* Voltage drop across motor starter contacts
Overloads set too low - See Section 7, Table 7-11
Ice backing up into ice chute
* Bin stat mounted incorrectly / set incorrectly / defective
* Deflector door not switching properly
(Dual ice machines only)
Making solid ice / freezer full of ice
(Refreeze-not all ice getting out during harvest)
* Faulty or improperly adjusted harvest pressure switch
* Low compressor discharge pressure
* Faulty D-Valve or D-Valve coil (not opening properly)
* Harvest cycle too short
3/25/08
Page 63
HES Series Service Manual
7. Service Operations
SERVICE OPERATIONS
7-1
FIGURE 7-1A
Front View
FIGURE 7-1B
Side View
3/25/08
Page 64
7-2
SERVICE OPERATIONS
HES Series Service Manual
FIGURE 7-1C
Rear View (Water Cooled)
FIGURE 7-1D
Rear View (Air Cooled)
3/25/08
Page 65
HES Series Service Manual
Adjustable Blowdown (for clearer ice). A petcock is installed on the overflow from water pump to
provide means for obtaining blowdown from the water tank during the freezing period. This
supplements the blowdown that is discharged during the thawing period through the bypass piping
connected to the drain of the water tank. (See “Automatic Blowdown” below).
The petcock was set at the factory to discharge enough water during the freeze cycle to produce
clear ice. After installation it should be adjusted to the minimum rate required to maintain
production of clear ice and checked after a few days of ice making.
Automatic Blowdown (harvest cycle). A patented feature of this machine is the automatic
blowdown (40), which is provided to eliminate or reduce the necessity for frequent flushing or
cleaning of the water tank (7) to remove accumulated salts or solids in the water as a result of the
freezing action.
A principle feature of the blowdown arrangement is a drain by-pass effect which is initiated during
each thawing period when the water pump is stopped and the water in the freezer tubes returns to the
water tank thereby raising the water level higher than the by-pass piping (40) and causing a portion
of the water to drain from the bottom of the tank (approximately 1 gal/cycle).
SERVICE OPERATIONS
7-3
The water level, controlled by the float valve (12), regulates the quantity of blowdown during the
thawing period. An optional solenoid valve can be furnished in place of the drain valve to permit
additional if required.
3/25/08
FIGURE 7-2
Automatic Blowdown / Petcock
Page 66
7-4
SERVICE OPERATIONS
Float Valve (make-up water). The make-up water float valve (12) maintains the proper pumping
level in the water tank for ice making. The valve should be set to maintain a water level in the water
tank during the freezing period, so that there will be a quantity of by-pass or blowdown only during
the thaw mode. The water level during the freeze mode should always be below the by-pass piping
to prevent excessive waste of cold water, resulting in loss of ice capacity.
If it should become necessary to clean the float valve, close the stop valve in the make-up water line
to the machine and remove the float valve. After the valve has been cleaned and reinstalled, check
to ascertain if the proper water level is being maintained.
It is advisable to install a large area strainer in the water supply line to protect the float valve from
dirt or solids in the water, which would necessitate frequent cleaning. A strainer of 40-mesh screen
is usually satisfactory.
HES Series Service Manual
Vogt Part #: 12A4200H0401
FIGURE 7-3
Water Float Valve
Circulating Water Pump Motor. The motor bearings are pre-lubricated and sealed. They require
no further lubrication. Pump should operate with the water level above the impeller housing.
The pump is equipped with a mechanical seal, which is self-addressing and requires no lubrication.
However, the pump should not be operated unless circulating water. The pump manufacturer
recommends that a mechanical seal be kept as a spare. When ordering replacement parts, specify
pump size, type, serial number, and manufacturer’s name as indicated on the nameplate.
Water Pump
Discharge
Vogt Part #:
12A2450E29
Water Pump
Water Pump
Suction
Suction Elbow
3/25/08
American Products Pump (AP)
FIGURE 7-4
Circulating Water Pumps
Water Pump
Discharge Elbow
Vogt Part #:
12A2450E30
Gorman Rupp Pump (GRI)
Page 67
HES Series Service Manual
Vogt Part #’s
Description Frequency Pump/Motor # Impellor # Seal # “O” Ring #
AP Pump 60hz 12A4020A06 12A4020Y0212A4080S04126628AP
50hz 12A4020A07 12A4020Y0412A4080S04126628AP
GRI Pump 60hz 12A4020GR0112A4080S21
50hz 12A4020GR0212A4080S22
Water Distributors. The water distributors are located in the distributing head (8) at the top of the
freezer. There are 78 distributors used in models having an “S” suffix (i.e., Models HES-10S, HES20S, HES-30S, and HES-40S); 48 distributors are used in models having an “M” suffix (i.e., Models
HES-10M, HES-20M, HES-30M, and HES-40M). These may require occasional or periodical
cleaning to remove suspended solids and foreign particles accumulated from the make-up water.
The frequency of this cleaning operation will depend on the characteristics of the water supply.
The cleaning operation is indicated when the inside diameter of a large proportion of the ice
becomes irregular (due to channeling of the water) or if some of the ice is opaque. Or if there is a
noticeable decrease in ice capacity.
TABLE 7-1
Water Pump Part #’s
SERVICE OPERATIONS
7-5
To clean distributors, stop the unit and remove the freezer cover (8) on top of the freezer. The water
distributors may then be removed with pliers for cleaning by soaking in a solution of ice machine
cleaner or 10% muratic acid and water. Grasp the top of the distributor gently with pliers, twist, and
pull up and out of the tube. After cleaning, reinstall distributors firmly in each tube.
Note: When re-installing distributors on the outside row, make sure holes are away from the gasket
Vogt Part #
Size Ice Number of Tubes Water Distributor Freezer Cover Freezer Cover Gasket
1” 78 12B2185N11
1 1/4” 48 12B2185N21
12A2145C0912A2600G01
TABLE 7-2
Water Distributor / Freezer Cover / Gasket Part #’s
Freezer Cover
Freezer Cover Gasket
Water Distributors
3/25/08
FIGURE 7-5
Freezer Cover / Gasket / Water Distributors
! WARNING !
Acid can cause serious burns or blindness. Always add the acid
to the water for dilution. Wear eye and body protection.
! WARNING !
Page 68
7-6
SERVICE OPERATIONS
Water Tank. The production of opaque ice usually indicates that the water in the water tank
contains a concentrated amount of solids or salts.
Remove cover plate, open drain valve (39) and clean tank thoroughly by flushing out with a hose
and scrubbing with a stiff brush. Close the drain valve and refill tank with fresh water.
When restarting the machine after filling the water tank, be sure that the water pump is circulating
water. It is possible that air may have collected in the pump impeller housing and the unit may have
to be stopped and started several times to expel the air.
HES Series Service Manual
3/25/08
FIGURE 7-6
Cutter/Water Tank Assembly With Water Pump and Cutter Motor
Cutter Gear Reducer. The oil level for the gear reducer should be checked if there is evidence of a
leak. It should be level with the plugged opening in the side of the gear housing. Use Mobile 600W
cylinder oil or equal. (Replacement oil 19T3020C01)
The motor bearings are prelubricated and require no further lubrication.
Page 69
HES Series Service Manual
Gear Reducer Replacement.
1. Stop the machine and lockout its power.
2. Remove four cap screws holding the motor to the reducer housing.
3. Separate the motor from the reducer by pulling the motor and shaft out of the reducer sleeve. Be
sure to catch and save shaft key for later reassembly.
4. Remove bolts holding gearbox-mounting plate to the drive gear enclosure and lift out gear
reducer and plate assembly.
5. Remove drive gear from the reducer output shaft. Two 1/4”-20 x 1 1/2” long (all thread) bolts
can be used for jacking screws in the two threaded holes of the drive gear.
6. Remove the split hub (bushing) from the reducer shaft and remove the gear reducer from the
mounting plate.
7. Reassemble in the reverse order.
8. After assembly of the drive gear on the gear reducer, set the assembly in place in the enclosure,
and check vertical alignment of the drive gear and cutter ring gear. Turn the gears by hand a full
turn to make sure they engage the full width of the teeth. Adjust the hub accordingly.
SERVICE OPERATIONS
7-7
9. Adjust the horizontal engagement of the gear teeth by the four bolts holding the reducer to the
mounting. There should be only a slight amount of tooth clearance at the closest engagement spot.
10. After complete assembly, test operation and check for unusual noise and normal motor amperage.
Cutter Bearing. The cutter bearing is of the sleeve type and is made of UHMW plastic requiring no
lubrication. If necessary to replace this bearing, follow instructions under heading “Cutter and Gear
Drive”.
Cutter and Gear Drive. To remove the ice cutter (21), when and if necessary, proceed as follows:
1. Turn machine off.
2. Close the stop valve in the make-up water line to water pan.
3. Drain the tank, disconnect the make-up water line and drain line from the water tank.
4. Separate motor from the cutter drive reducer by removing four cap screws. Watch for shaft key
when separating unit, which must be installed in motor keyway when unit is reassembled. It is
not necessary to remove the reducer from its mounting plate on the water pan.
5. Remove the water pump, which is attached to the side of the tank by four bolts and nuts.
6. Remove ice discharge chute, which is attached to the water tank by four wing nuts.
7. Remove the water tank assembly which contains the cutter by removing four bolts and nuts
from around the top edge of the tank.
Assembly may then be taken to a workbench for removal of cutter.
3/25/08
Page 70
7-8
SERVICE OPERATIONS
To remove the cutter from the water tank assembly, perform the following:
1. Remove the ice deflector by removing the hinge pin at the hub end.
2. Remove the cutter disc assembly, which is held onto the shaft by a roll pin. The cutter can now
be removed.
3. Remove the cutter bearing bracket which is held in place by three 1/4” cap screws holding cutter
support to side of the water tank.
Cutter Bearing Replacement. If the bearing requires replacement, perform the following:
1. Remove the worn bearing by driving the 3/16” lock pin located in the side of bronze hub
through the bearing wall with a 3/16” punch. Drive or press the bearing from hub.
2. The new bearing may be driven into hub using old bearing as a driver.
3. When bearing is fully seated, drill a 3/16” hole through bearing wall using original hole in hub
as a pilot.
4. Lock new bearing in place with 3/16” lock pin. Insert the pin flush with outside of hub, check
that pin does not extend beyond inner surface of the bearing.
The parts should be reassembled reversing the procedure described for removal.
HES Series Service Manual
3/25/08
NOTE: Deflector door assembly and chute deflector may be removed if there is no divider in the bin.
FIGURE 7-7
Ice Discharge Arrangement
Page 71
HES Series Service Manual
12A3040S01
STAINLESS STEEL SPIROL PIN
1/4” DIA X 1 1/2” LONG
7-9
SERVICE OPERATIONS
12A4030R12
GEAR REDUCER (10:1)
WATER PUMP
WATER PUMP
(GORMAN-RUPP)
HZ- 12A4020A06
60
60HZ – 12A4020GR01
50HZ – 12A4020A07
50HZ – 12A4020GRO2
12A2900M0507
1/2 HP 50/60HZ
CUTTER MOTOR
19T4500S12
GEAR BOX MOUNTING
PLATE ASSEMBLY
(PART OF WATER TANK)
3/25/08
FIGURE 7-8
Cutter/Water Tank Parts
Page 72
7-10
SERVICE OPERATIONS
HES Series Service Manual
12A2240A1108
HEX NUT 5/16” S S
12A4030R12
GEAR REDUCER (10:1)
3/25/08
FIGURE 7-9
Cutter Drive Parts
Page 73
HES Series Service Manual
7-11
SERVICE OPERATIONS
3/25/08
12A3040S01
SS SPIROL PIN
1/4” DIA X 1 1/2” LONG
(FOR CUTTER DISC)
FIGURE 7-10
Cutter Parts
Page 74
7-12
SERVICE OPERATIONS
Expansion Valve. The expansion valve was adjusted before shipment and it is rarely necessary to
change this setting.
If considerably less ice than shown in TABLE 11-1 is being produced per discharge, check the water
supply, circulating water pump, water distributors, liquid line valves, refrigerant level, freezer
pressure switch and all other avenues BEFORE changing the factory setting of the expansion valve.
HES Series Service Manual
FIGURE 7-11
Thermal Expansion Valve (TXV)
Vogt Part #
Machine R22 404A
HES-20 12A4200C0312 12A4200C0318
HES-30 and HES-40 12A4200C031112A4200C0306
TABLE 7-3
Thermal Expansion Valve Usage (TXV)
By Superheat. Superheat is the difference between the refrigerant vapor temperature and its
saturation temperature. (Translate the pressure reading to saturated temperature and subtract it from
the actual temperature reading.)
Checking Superheat. Follow this procedure:
1. Attach an accurate pressure gage to the freezer-charging valve (#28).
2. Using a digital thermometer, attach the thermocouple to the suction line directly below and inline with the existing TXV sensing bulb.
3. Hold the thermocouple in place with tape and insulation to assure good contact and a true reading.
4. Operate the machine and monitor the superheat during the freeze cycle after the first four
minutes and at two minute intervals for at least two cycles. Refer to the chart below for
recommended superheat ranges.
3/25/08
5. Adjust the valve only 1/4 turn at a time. Close (turn stem in) to raise superheat. Open (turn stem
out) to lower superheat. Monitor at least two cycles after each adjustment before adjust further.
Page 75
HES Series Service Manual
Machine Minimum Target Maximum
HES-20 5 6 8
HES-30 4 5 6
HES-40 4 5 6
If the valve cannot be adjusted satisfactorily, check the bulb insulation as follows:
1. Remove the insulation from the sensing bulb.
2. Loosen the bulb clamps and remove the bulb.
3. Clean and polish the sensing bulb and suction line to assure maximum contact between them.
4. Install the bulb in the same place tightening the clamps securely.
5. Replace the insulation around the bulb making sure it is well sealed. Repeat the adjustment
procedure and if you are still unable to accomplish the proper superheat setting, the valve must
be replaced.
When installing a new valve, be sure to use the proper soldering techniques to prevent overheating
the valve body, which could damage the superheat spring and result in flood back problems.
When soldering:
TABLE 7-4
Recommended Superheat Range
7-13
SERVICE OPERATIONS
1. Wrap a wet cloth around the valve body and element.
2. Direct the flame away from the valve body.
3. Apply only enough heat to flow the alloy material into all the joint areas. Do not overheat.
4. After the brazing alloy has set, quench or apply a wet brush or swab to remove the flux residue.
Use Emery cloth or a wire brush if necessary.
3/25/08
Page 76
7-14
SERVICE OPERATIONS
HES Series Service Manual
“A” (#20) Liquid Line
“D” (#18) Thaw Gas
“X” (#53) Comp Discharge
(Air-Cooled Only)
Sporlan#: OE34S290
“SS” (#49) Suction Stop
(with bypass)
Note: Suction Stop valve is a special valve
available through Vogt only
Sporlan#: OE35S190
FIGURE 7-12
Solenoid Valves
Solenoid Valves. The solenoid valves (#18, #20 and #53) are pilot-operated with “floating” type
diaphragm. For satisfactory operation, be sure that the manual opening stem, which is located on the
bottom of the Sporlan valve, is in the “automatic” or “closed” position.
The suction stop valve (#49) is a normally open solenoid valve that is energized during the harvest
cycle. The valve is equipped with a bypass line designed to create a 20 to 30-psig-pressure drop
across the valve during the harvest.
These valves will operate on voltages within 10% of rating but dirt or sludge will affect the
operation. Care should be taken to assure the enclosing tube is not bent or dented so as to cause the
plunger to stick and prevent proper operation. Valves should be dismantled (or wrapped with wet
rags if valve ends are the extended type) before applying heat for brazing.
Note: * Rebuild Kit / Coil for Sporlan OE34S290 Valve
** Rebuild Kit / Coil for Sporlan OE35S190 Valve
Sporlan Solenoid valve OE34S290 (12A4200A0902) discontinued in Aug 2006
TABLE 7-5
Solenoid Valve Part #’s
10/17/13
Page 77
HES Series Service Manual
Freezer Pressure Switches. The freezing time period for the production of crushed ice is controlled
by the freezer pressure switch (FPS1) located inside the control panel. The freezing time period for
cylinder ice is controlled likewise by the second switch (FPS2).
These switches were set at the factory to produce ice of recommended thickness. Look at the
“Certificate of Test” which was provided with the machine for a sample set of pressure readings
with corresponding time periods and water temperatures. Also see TABLE 11-2 for typical settings.
Do not make adjustments until several ice discharging cycles have been made.
Vogt Part #: 12A2117E04
Turn top screw to adjust the pressure setting
(also referred to as the Range)
The freezing time can be such that a small percentage of the ice is frozen solid. If so, some ice from
the top and bottom of the freezer should have a small hole in the center to insure that the freezing
time has not been extended to where a loss in capacity would result.
It is preferable that the freezing cycle be such that a small diameter hole remains in the center of the
ice cylinder. (1/16” diameter for 7/8” diameter ice, and 1/8” diameter for 1 1/8” diameter ice.) This
insures that the freezing cycle is not extended unnecessarily and eliminates a possible opaque core in
the center of the ice.
3/25/08
When crushed ice is produced, the freezer pressure switch should be set to produce ice having a wall
thickness of approximately 3/16”.
Note: (Dual Ice machines only) While making crushed ice, if machine harvests after running a five
minute freeze cycle, the crushed ice pressure switch (FPS1) is set too high. Lower pressure setting
by turning the range adjustment (top screw) counter clockwise.
Page 78
7-16
SERVICE OPERATIONS
High/Low Pressure Safety Switch. The high-low pressure switch (4PS) (FIGURE 7-14) is a twopole dual function switch. Located in the machine outside the control panel, it protects the machine
from possible damage due to abnormal pressure during operation.
The LOW pressure cut-in should be set at 40 psig (R-22), 50 psig (R-404A) and the cutout set at 20
psig (R-22), 30 psig (R-404A). After tripping at the cutout setting, the switch will reset
automatically when the pressure rises to the cut-in setting.
The HIGH-pressure cutout should be set at 300 psig (R-22) & 350 psig (R-404A). After tripping,
reset the switch manually.
Note: After a high-pressure trip, the discharge pressure must drop 50 psig before the switch can be
reset.
HES Series Service Manual
! CAUTION !
When this switch causes the machine to stop, the cause should be
identified and corrected before resuming normal operation.
See Fault Identity, Section 6, Table 6-2.
! CAUTION !
DIFFERENTIAL ADJUSTING SCREW
(CCW RAISES SETTING)
Vogt Part #: 12A2117D02
RANGE ADJUSTING SCREW
(CW RAISES SETTING)
HIGH PRESSURE ADJUSTMENT SCREW
(DIFFERENTIAL FACTORY SET AT 55 PSIG)
FIGURE 7-14
High /Low Pressure Safety Switch
NOTE: High-low pressure switch contains both high and low voltage circuits. Line numbers 12 and
X6 supply a low voltage signal to the PLC. Line numbers Y2 and 18-supply power to the
compressor contactor coil.
10/17/13
If it becomes necessary to install a new high/low pressure switch, the following procedure is
recommended for its adjustment:
Turn the adjusting screws clockwise to raise the pressure setting. Turn counter-clockwise to lower
the setting. Adjust the switch to the indicated pressure settings and test with an accurate gage to be
sure the switch functions properly before installation.
Page 79
HES Series Service Manual
Head Pressure. The head pressure should be maintained at 100-105 degF condensing during the
freeze cycle. The compressor discharge pressure can be checked at the test connection on the highlow pressure switch.
Air-Cooled Units. The condenser fan switch (FIGURE 7-15) (CPS) has a two-pole switch that is
used to regulate the head pressure. This is an adjustable pressure switch located on the right-hand
side of the machine directly controls the operation of the condenser fan motor(s). The switch is set
to cycle the fan motor(s) “On” at 210 psig (R-22), 250 psi (R-404A) and “Off” at 190 psig (R-22),
230 psi (R-404A).
CUT IN ADJUSTING SCREW
(CW LOWERS SETTING)
Vogt Part #: 12A2117F08
Condenser Fan Switch
FIGURE 7-15
CUT IN ADJUSTING SCREW
(CW RAISES SETTING)
SERVICE OPERATIONS
7-17
NOTE: Older HE and R12 machines used a single pole fan switch and a fan contactor to control the
fan motor (s). The HE S-series machine no longer uses a fan contactor.
Cleaning Air-Cooled Condenser. Visual inspection will indicate if dirt is accumulating and
clogging the fin face of the condenser. A vacuum cleaner, compressor air or a brush may be used to
remove an accumulation of dirt from the fin section of the condenser.
Sporlan Solenoid valve OE34S290 (12A4200A0902) discontinued in Aug 2006
TABLE 7-6
Cold Weather Kit Replacement Parts
10/17/13
Page 80
7-18
Note:
SERVICE OPERATIONS
Ice Machine Model
Recommended Condenser
HE20
DVT005
(DVT008)
HES Series Service Manual
HE30
DVT008
(DVT012)
For continuous operation at ambient above 90 °F, use larger condenser shown in parenthesis
Total Heat Rejection:
(15°F TD)
Fans:
Full Load Amps:
Weight, lbs.:
Condenser dimensions, inches:
Recommended Line Sizes,
OD:
Connections at Condenser: Liquid (ODC)
Connections at Machine: Liquid & Discharge Gas (ODC) 1-1/8” 1-1/8” 1-1/8”
BTU/hr at 60 Hz.
BTU/hr at 50 Hz.
Number
HP, Each
Total, CFM
1 ph., 208/230V, 60 Hz
3 ph., 208/230V, 60 Hz
3 ph., 460V, 60 Hz
1 ph., 200/220V, 50 Hz
3 ph., 200/220V, 50 Hz
3 ph., 400V, 50 Hz
Net
Shipping
Operating (maximum flooded)
A (Width)
B (Length)
C (Height)
D (Leg centerline)
E (Leg centerline)
F (Clearance below)
Liquid (All lengths and orientations)
Discharge Gas Vertical Up, All lengths
Horizontal Or Down, < 75 ft.
Horizontal Or Down, > 75 ft.
Discharge Gas (ODC)
35,700
32,800
1
1/3 (1/2)
5,050 (6,450)
3.4 (3.9)
N/A
1.3 (1.3)
3.4 (3.9)
N/A
1.3 (1.3)
180 (260)
320 (390)
195 (285)
43”
39.75” (49.75”)
30” (40”)
17”-3
30” (40”)
24.5”
1/2”
5/8”
5/8”
7/8”
5/8”(7/8”)
7/8” (1 1/8”)
58,800
54,100
1 (2)
1/2
6,450 (12,400)
3.9 (7.8)
N/A
1.3 (2.6)
3.9 (7.8)
N/A
1.3 (2.6)
260 (470)
390 (520)
285 (500)
43”
49.75” (69.75”)
40” (60”)
17” - 3
40” (60”)
24.5”
5/8”
7/8”
7/8”
1-1/8”
7/8”
1 1/8”
HE40
DVT012
(DVT016)
12,400 (12,900)
7.8 (7.8)
2.6 (2.6)
7.8 (7.8)
2.6 (2.6)
470 (530)
520 (680)
500 (560)
1-1/8” (1-3/8”)
117,500
108,100
2
1/2
N/A
N/A
43”
69.75”
60”
17” - 3
60”
24.5”
7/8”
1-1/8”
1-1/8”
1-3/8”
7/8”
TABLE 7-7
Air-Cooled Condenser Data
FIGURE 7-16
Condenser Dimensions
10/17/13
Page 81
HES Series Service Manual
Wiring For BOHN DVT012 /DVT016 with Cold Weather Valve and Two Fan,
Water-Cooled Units. A water-regulating valve (FIGURE 7-18) located in the condenser water inlet line
is used to control the water flow through the condenser. This valve should be adjusted to maintain a head
pressure of 190-210 psig for R22 or 230-250 psig for R404A. Increasing the water flow lowers the head
pressure and decreasing the water flow raises the head pressure.
FIGURE 7-17
50/50 Condenser Split
7-19
SERVICE OPERATIONS
FIGURE 7-18
Water Regulating Valve
Machine Size Vogt Part #
HES-20 & HES-30
3/4” 12A4200E0605
HES-40 1” 12A4200E0802
* HES-20 & HES30
1/2” 12A4200E0402
* HES-40 1” 12A4200E0801
TABLE 7-8
Water Regulating Valves
Note: * High water pressure regulating valves (above 90 psig)
10/17/13
Page 82
7-20
SERVICE OPERATIONS
Water Cooled Condenser Service. High head pressure due to fouled condenser.
Eliminate other possible causes:
• Non-condensables
• Faulty gauge
• Refrigerant restriction
• Water regulating valve
• High inlet water temperature
• Insufficient water supply
Example
Liquid return (RCVR) Psig = 200 = 102°F (SAT)
Water outlet temperature = 95°F
Difference = 7°F
If difference is more than 10°F, cleaning is indicated. For cleaning procedure see, “Water Cooled
Condenser Cleaning”, Section 5.
HES Series Service Manual
Compressor Crankcase Heater. When electrical power is supplied to terminals L1, L2 & L3 of
the control panel, the crankcase heater is energized when the compressor is not operating. The
purpose of the crankcase heater is to keep the compressor warm to prevent the migration of
refrigerant to the compressor while the compressor is not running.
In case of a power interruption, or crankcase heater failure, be sure the compressor crankcase
is warm prior to restarting the machine manually
! CAUTION !
Compressor Motor Rotation. Scroll compressors must be phased properly at startup. Connect
pressure gages to the high and low side of the compressor at the High / Low Pressure safety switch.
Start machine by putting "Selector Switch" in the "Ice" position and pressing "Start / Harvest"
button. The compressor discharge pressure should start to rise as the suction pressure drops. Within
30 seconds, the discharge pressure should be approximately 180 - 200 psig. If the discharge
pressure does not rise, and the suction pressure does not drop, the compressor is running backwards.
Shut machine off power to the machine at the main disconnect and reverse wires labeled L1 and L3
in the compressor's electrical junction box.
The compressor suction rota-lock valve has two 1/4" access ports. One is a neutral port, open to the
compressor at all times. The other is a standard test port equiped with a shrader valve. The neutral
port, which is perpindicular to and lines up with the threaded connection to the compressor, is
connected to the low pressure safety switch.
During normal operation the valve should be backseated.
Diagram
Designation
A Compressor
B Neutral Port
C Suction Line
D Test Port
Description Vogt Part #
Rota-lock Valve
(1 1/4" X 12 thrd X 1 1/8" swt)
Brass adapter
(1 1/4" X 12 thrd X 7/8" swt)
Teflon Seal12A2600T01
Compressor (A) to Neutral Port (B) Open Open Open
Compressor (A) to Suction line (C) Open Open Closed
Compressor (A) to Test Port (D) Closed Open Open
HES Series Service Manual
Ports
12A4200R0801
12A2396C0402
FIGURE 7-20
Compressor Suction Rota-lock Valve
Stem Location
Back-seated Partially In Front-seated
3/25/08
TABLE 7-11
Compressor Suction Rota-lock Valve
Page 85
HES Series Service Manual
Compressor Discharge Rota-lock Valve
The compressor discharge rota-lock valve has two 1/4" neutral ports. One neutral port is connected to
the high pressure safety switch, and one is connected to the head pressure control device. (water
regulating valve or condenser pressure fan switch - CPS)
During normal operation the valve should be backseated.
Diagram
Designation
A Compressor
B Neutral Port
C Suction Line
Description Vogt Part #
Rota-lock Valve
(1" X 14 thrd X 5/8" swt)
Brass adapter
(1" X 14 thrd X 1/2" swt)
Teflon Seal12A2600T02
Compressor (A) to Neutral Port (B) Open Open Open
Compressor (A) to Suction line (C) Open Open Closed
7-23
SERVICE OPERATIONS
Ports
12A4200R0402
12A2396C0201
FIGURE 7-21
Compressor Discharge Rota-lock Valve
Stem Location
Back-seated Partially In Front-seated
3/25/08
TABLE 7-12
Compressor Discharge Rota-lock Valve
Page 86
7-24
SERVICE OPERATIONS
HES Series Service Manual
Cutter / Pump and Fan Motor
Circuit Breakers (15 amps)
Vogt Part #:
Short Circuit Protection (Control Circuit / Pump & Cutter motors)
Note: Machines manufactured after May 1999 will use Allen-Bradley controls.
Control Circuit Protection. Two control circuit breakers (CB3 and CB4) located in the control
panel (FIGURE 4-1) provide short circuit protection for the compressor crankcase heater, all
solenoid valves, contactors and motor starter coils. These circuit breakers are current limiting
thermal magnetic breakers rated at 3 amps. Part #: 12A7515E20 (Cutler-Hammer) or 12A7515E21
(Allen-Bradley).
If either circuit breaker “trips” for any reason, voltage will be removed from the control circuit,
shutting off all of the motors and de-energizing all valves. The machine is wired so the PLC will
continue to “run” if this occurs. This will cause the machine to run an extended freeze cycle and
shut off on a Long Cycle Fault – Fault # 6.
Note: If a circuit breaker “trips”, the crankcase heater will be not be energized.
! CAUTION !
In case of a power interruption or outage, be sure the compressor crankcase
is warm and there is no liquid refrigerant in the crankcase prior to restarting
the machine manually
! CAUTION !
Motor Short Circuit Protection.
Cutter / Water pump motor: A two pole, 15 amp magnetic circuit breaker (CB1) is used for short circuit
protection in the cutter or pump motor circuit. If breaker trips, power is removed from control circuit,
shutting machine down. (Part #: 12A7515E19)
Condenser fan motor (Air Cooled Only): A two pole, 15 amp magnetic circuit breaker (CB2) is used for
short circuit protection in the cutter or pump motor circuit. If breaker trips, power is removed from
control circuit, shutting machine down. (Part #: 12A7515E19)
Compressor motor: The compressor motor circuit is protected from a short circuit by the main fuse that
supplies power to the machine. (See TABLE 4-1 for recommended fuse sizes).
3/25/08
Page 87
HES Series Service Manual
Cutler
-
Hammer
Motor Over Current Protection.
Cutter / Water pump motor: The cutter and water pump motors are protected by a three phase motor
starter with adjustable bimetallic heater packs, wired for use on single phase. Can be configured to reset
automatically (“A”) or manually (“M”). PLC controlled machines will have the overload reset in the
“automatic” position. When a overload condition occurs, an auxiliary contact signals the PLC of a
problem and shuts the machine off (PLC input light # 5 will be “off” when overload is tripped). Will
automatically reset after an overloads cool.
Machine will have either Cutler-Hammer or Allen-Bradley controls. (Machines manufactured after May
1999 will use Allen-Bradley controls)
Cutler-Hammer - Use motor starter 12A7530E11 with heater packs (see table below for ratings).
Allen-Bradley - Use contactor 12A7516E23 w/solid state overload relay 12A7538E01
Current
Range
Setting
A 3.38 4.96
B 4.10 6.03
C 4.82 7.09
D 5.54 8.16
1/2 HP Cutter Motor
Overload (Amps)
Part #: 12A 7508H2108
1/2 HP Pump Motor
Overload (Amps)
Part #: 12A 7508H2109
7-25
SERVICE OPERATIONS
(rated 3.2-16A)
TABLE 7-13
Cutler-Hammer Heater Pack Current Settings
The cutter motor overload should be set at the motor FLA rating. The pump motor overloads should
be set a motors Service Factor FLA rating.
Note: Water pump motor has internal thermal overload protection
Allen Bradley Overload Relay
Vogt Part #: 12A7538E01
"Current Range"
and "Auto /
Manual Reset"
adjustment
behindaccess
plate
Current
Range
Automatic
or Manual
Reset
Reset
Original AB Overload Relay
Allen-Bradley
Automatic or
Manual Reset
*Push to reset
After July 2007
Current
Range
Dip switch on the side of OL Relay
FIGURE 7-23
Motor Overloads (Pump & Cutter motors)
Condenser fan motor (Air Cooled Only): The fan motor(s) on the air-cooled condenser have internal
thermal overload protection and will shut off if an overload condition occurs. If this occurs, the machine
will eventually shut off on a High / Low-pressure fault.
10/16/13
Compressor motor: The compressor motor has internal thermal overload protection and will shut off if
an overload condition occurs. If this occurs, the rest of the machine will continue to run but eventually
shut off on a Long cycle fault - Fault # 6.
Page 88
7-26
SERVICE OPERATIONS
Ice Bin Control. The electronic bin thermostat has a LCD readout that displays the temperature in the
bin at the sensor. The control has been preset and locked out at the factory to shut the machine down at 38°F and to re-start at 40°F. The control retains the program even if power is cut to the
machine.
NOTE: If the bin control is calling for ice, the LCD will display the current temperature and a "S1".
HES Series Service Manual
To change sensor setting,
Lockout, located on the
inside of the unit, must be
set on "unlock"
Replacement Sensor
Vogt Part #: 12A2117G0901
Electronic Bin Thermostat
Vogt Part #: 12A2117G09
FIGURE 7–24
Electronic Bin Thermostat
Programming the Electronic Bin Thermostat. Under special conditions, the settings may need to
be changed. The lockout switch is located on the inside of the control. Removal of the four screws
on the face of the control will reveal the lock-switch.
3/25/08
Follow the instructions below to reset the switch.
1) Press the “SET” button to enter the sensors setup mode
2) Select between “C”- Celsius and “F” - Fahrenheit
Use the up ↑ or down ↓ key to select “F”
3) Press the “SET” button to set the Set point (S1 will be blinking)
Use the up ↑ or down ↓ key to set the temperature at 38°F
4) Press the “SET” button to set the Differential (DIF 1 will be blinking)
Use the up ↑ or down ↓ key to set the differential at 2°F
5) Select between “C1”- Cooling mode and “H1” - Heating mode
Use the up ↑ or down ↓ key to select “C1”
NOTE: The sensor will automatically exit the programming mode if no keys are depressed for a
period of thirty seconds. Any settings that have been input to the control will be accepted at that
point.
Page 89
HES Series Service Manual
7-27
SERVICE OPERATIONS
FIGURE 7–25
Bin Thermostat Mounting Location
Electronic Bin Temperature Control Error Messages
E1 – Appears when either the up
⇧ or down ⇩ key is pressed when not in the programming mode.
To correct: If the E1 message appears even when no keys are being pressed, replace the
control.
E2 – Appears if the control settings are not properly stored in memory.
To correct: Check all settings and correct if necessary.
EP – Appears when the probe is open, shorted or sensing a temperature that is out of range.
To correct: Check to see if the sensed temperature is out of range. If the sensor is subject to
a known ambient temperature between -30°F and 220°F, and displays the EP code, replace the
damaged probe.
EE – Appears if the EEPROM data has been corrupted.
To correct: This condition cannot be field repaired. Replace the control.
Note: Sensor cable can be extended up to 400 feet. For more information, consult Tube-Ice
®
Technical Service Department.
3/25/08
Page 90
7-28
PLC: FXo
PLC: FX
s
MELSEC FX
OS
-
14MR
-
PLC: FXos
SCREW
CRU
AUTO
SERVICE OPERATIONS
HES Series Service Manual
THAW TIMER
ADJUSTMENT
SCREW
MITSUBISH
I
ES
THAW TIMER
ADJUSTMENT
Vogt Part #: 12A7536M01
Note: Must be programmed at Vogt –
specify machine model when ordering
THAW TIMER ADJUSTMENT SCREW
(LOCATED UNDER PLASTIC COVER)
RANGE: 1 ½ - 5 MINUTES
(TURN CW TO INCREASE TIME)
(TURN CCW TO DECREASE TIME)
FIGURE 7-26
Thawing Timer. (Part of PLC)
Thawing Timer. The thawing timer governs the ice thawing period. It is built into the PLC located
inside the control panel. It is started by action of one of the freezer pressure switches (FPS1 or
FPS2) or the manual harvest button. This timer is set prior to shipment for approximately a 90
second period.
1
Set the thawing period for at least 20 seconds longer than the time required to harvest the entire
discharge of ice. If it should be necessary to change the setting of the timer, turn the adjustment
screw clockwise to increase the time or counter-clockwise to decrease the time. Check thaw time
after each adjustment FIGURE 7-26.
CYL
Vogt Part #:
Cutler-Hammer:
12A7500E44 (switch assy)
Allen-Bradley:
12A7500E61 (switch)
12A7500E73 (contact blk)
Single Ice Dual Ice
FIGURE 7-27
Selector Switch
Note: Machines manufactured after May 1999 will use Allen-Bradley controls.
Selector Switch.
Single Ice Type - A Three position rotary-type switch marked “CLEAN–OFF-ICE” used for
selecting the different machine modes. The switch is located on the control panel door.
10/16/13
Dual Ice Type – Two three position rotary-type switches, one marked “CLEAN-OFF-ICE” used for
selecting the different machine modes and one marked “CRU-AUTO-CYL” for selecting the type of
ice. These switches are located on the control panel door.
Page 91
HES Series Service Manual
Pumping Down Freezer. If it should become necessary to pump the refrigerant out of the freezer,
sufficient vapor should be retained to hold one pound of pressure in the freezer so that air will not
enter if the system is opened.
A total pump down is the first phase of the clean mode. After the pump down is accomplished, put
the selector switch in the “Off” position to stop the water pump.
Note: After completing the total pump down cycle, the liquid line will remain full of liquid
refrigerant from the receiver “king” valve (58) to the liquid feed “A” solenoid valve (20).
If it becomes necessary to open freezer to the atmosphere, you will need to remove the remaining
refrigerant by using an approved refrigerant recovery unit. Isolate that part of the system by closing
the necessary hand stop valves at the receiver, condenser, compressor, etc. before using the recovery
unit and opening the system.
Pumping Down Entire System. If it should become necessary to pump down the entire system,
including the liquid line, the following should be performed. Manually open the liquid feed “A”
solenoid valve (20) by running the stem in. Close liquid outlet “king” valve (58) on the receiver
(15R). Put machine into total pump down as described above.
Removal Of Refrigerant From The Machine. To transfer the refrigerant charge from the machine
into a separate container, proceed as instructed above under pumping down freezer. This will isolate
most of the refrigerant in the receiver and the recovery unit can be connected to the access port (44)
of the liquid outlet “king” valve (58) at the bottom of the receiver. Open the valve access port by
turning the valve stem in (front seat) and operate the recovery unit until the system is considered
empty.
Approved recovery equipment, hoses, gages, and refrigerant containers must be
free of any contaminants or foreign materials--and must be weighed
! WARNING !
used to comply with all local and federal EPA regulations.
! WARNING !
! WARNING !
Follow these instructions carefully.
Severe personal injury can result from improper
discharge of refrigerant.
! WARNING !
! WARNING !
It is not recommended that refrigerant be transferred from a
refrigeration system into a cylinder. If such a transfer is made, the
refrigerant cylinder must be an approved CLEAN cylinder--
continuously to assure contents do not exceed net weight specified
by cylinder manufacturer or any applicable code requirements.
! WARNING !
7-29
SERVICE OPERATIONS
10/18/13
Page 92
7-30
SERVICE OPERATIONS
Refrigerant Leaks. In addition to testing the machine for leaks as instructed under “Refrigerant
Charge”, it is advisable to again make a leak test after the unit has been in operation approximately
one week. Any noticeable change in operating conditions, other than shown on the “Certificate of
Test” may indicate a loss of refrigerant due to a leak. Always remove the refrigerant pressure from
the vessel or tubing before repairs are attempted.
Non-condensable Gases. Satisfactory operation of the machine is not possible if non-condensable
gases (usually air) are present in the system. Excessive condensing pressure is an indication of such
gases. Excessive condensing pressure in water-cooled condensers may also be due to the
accumulation of scale in the cooling coil or due to insufficient cooling water or excessive water
temperature. See “Water Cooled Condensers”, Section 7.
Compressor Motor Burnout. There are several causes of compressor motor burnout. Some of
these are described below.
1.
Low Line Voltage. A compressor motor is designed to operate within the range of plus or minus
10% of its nameplate voltage. Low voltage or excessively high voltage requires the motor
windings to carry more current at the same compressor load. When this current gets too high or
is applied for an extended period, the motor windings overheat, resulting in a failure or burnout.
2.
Loss of Refrigerant. The hermetic compressor motor is maintained at proper operating
temperature by passing cool suction gas over the motor windings. A loss of refrigerant can
cause the winding to overheat resulting in a failure or burnout.
3.
High Head Pressure. The system is designed to operate at 200 psig. Excessive head pressure
adds refrigerating load on the compressor, which can cause the windings to overheat and result
in a failure or burnout.
4.
Moisture. Moisture in contact with refrigerant oil and the presence of heat will form
hydrochloric or hydrofluoric acid. The acid will destroy the insulation on the motor winding
causing a short circuit, which can increase motor temperature in excess of 3000°F. This extreme
temperature will also create a sludge or black residue in the system.
5.
Mechanical Failure. Mechanical failure has been determined as a major cause of motor burnout.
Bearing wear or wipeout may allow rotor to drag--overheating the windings and burnout.
Whenever there is a compressor failure due to a motor burnout, it is important that the system be
thoroughly cleaned before replacing the damaged compressor or otherwise the new compressor may
also be damaged. A suction line filter should be installed and filter cores replaced until system is
cleaned. Also replace the liquid line filter drier.
HES Series Service Manual
3/25/08
Page 93
HES Series Service Manual
Converting from Cylinder Ice to Crushed Ice (Single Ice Type Machines).
• Remove jumper from #5 and #6 on terminal block and put on #5 and #4. This will reverse the
rotation of the cutter motor.
FIGURE 7-28
• Adjust Freezer Pressure switch (FPS2) – See table below for recommended pressure settings
NOTE: Freezer pressure should be checked at freezer charging valve (# 28).
• The pressure switch should be adjusted until the desired ice thickness is obtained--See table below
MachineCylinder Ice (lbs.) Crushed Ice (lbs.)
HES-20S 41 – 43 30 – 32
HES-20M 40 – 42 29 – 31
HES-30S 41 – 43 30 – 32
HES-30M 40 – 42 29 – 31
HES-40S 41 – 43 30 – 32
HES-40M 40 – 42 29 – 31
TABLE 7-15
Recommended Ice Weights per cycle
Single To Dual Ice Conversion. Converting from single type to dual type ice consist of adding
components, rewiring, and machine adjustments. Consult factory for single to dual ice conversion
kit information.
3/25/08
Page 94
7-32
SERVICE OPERATIONS
Defrost Pressure Switch –DPS (R404A Machines only). The DPS is used to regulate the pressure
in the freezer during the harvest cycle. This pressure switch is wired in series with the D-valve
(thaw gas valve), which opens and closes during the harvest cycle to maintain 90 to 95 psig in the
evaporator.
HES Series Service Manual
CUT IN (CLOSE) ADJUSTING SCREW
SET AT 90 PSIG
(CW LOWERS SETTING)
Vogt Part #: 12A2117B03
Defrost Pressure Switch (DPS)
FIGURE 7-30
CUT OUT (OPEN) ADJUSTING SCREW
SET AT 95 PSIG
(CW RAISES SETTING)
3/25/08
FIGURE 7-31
Defrost Pressure Switch (DPS) wiring
Page 95
HES Series Service Manual
Oil Separator. A coalescent type oil separator is used to return oil to the compressor when the
system is subjected to extreme or unusual operating conditions.
7-33
SERVICE OPERATIONS
Oil Charging
Fitting “T”
(w/shrader fitting)
Oil Sightglass
X-Valve
(Used on Air Cooled machines only)
Vogt Part #: See Table 7-5
Discharge Line Check Valve
Vogt Part #: 12A4200B0502
Ice capacities are based on 60 hz. operating current and an ambient temperature not exceeding 90°F (32°C).
Reduce capacity 17% for 50 hz. operation. Reduce capacity by 3% for every 5°F over 90°F ambient.