Based upon W/nominal tonnage, dry coil and lter should be installed.
①
Use 0.96 as approximate CFM correction factor for wet coil.
②
See the following table for how to set the DIP switch of the unit VAF-36A308I and VAF-42A308I:
table 7
Model/DIP SwitchCOOLHEAT
VAF-24A308I
//
VAF-36A308I
VAF-42A308I
VAF-55A308I
Note: The black part presents the switch rod.
2
Air Handler
2. Pre-Installation Instruction
2.1 Checking Product Received
After receiving the product, please check if there is any damage caused by transportation.
Shipping damage is the responsibility of the carrier. Verify the model number, specications and
accessories are correct prior to installation. The distributor or manufacturer will not accept claims
from dealers for transportation damage or installation of incorrectly shipped units.
2.2 Before Beginning Installation
Carefully read all instructions for the installation prior to installing product. Make sure each step
or procedure is understood and any special considerations are taken into account before starting
installation. Assemble all tools, hardware and supplies needed to complete the installation. Some
items may need to be purchased locally. Make sure everything needed to install the product is on
hand before starting.
2.3 Codes & Regulations
DANGER
IMMEDIATE HAZARDS WHICH WILL RESULT IN PROPERTY DAMAGE, PRODUCT
DAMAGE, SEVERE PERSONAL INJURY OR DEATH.
WARNING
HAZARDS OR UNSAFE PRATICES COULD RESULT IN PROPERTY DAMAGE, PRODUCT
DAMAGE, SEVERE PERSONAL INJURY OR DEATH.
CAUTION
HAZARDS OR UNSAFE PRACTICES WHICH MAY RESULT IN PROPERTY DAMAGE,
PRODUCT DAMAGE, SEVERE PERSONAL INJURY OR DEATH.
WARNING
BEFORE SERVING OR INSTALLING THIS EQUIPMENT.THE ELECTRICAL POWER TO
THIS UNIT MUST BE IN THE “OFF” POSITION. CAUTION, MORE THAN ONE DISCONNECT
MAY EXIST. FAILURE TO OBSERVE THIS WARNING MAY RESULT IN AN ELECTRICAL SHOCK
THAT CAN CAUSE PERSONAL INJURY OR DEATH .
WARNING
THE UNITED STATES ENVIRONMENTAL PROTECTION AGENCY (‘EPA”) HAS
ISSUED VARIOUS REGULATIONS REGARDING THE INTRODUCTION AND DISPOSAL
OF REFRIGERANTS INTRODUCED INTO THIS UNIT. FAILURE TO FOLLOW THESE
REGULATIONS MAY HARM THE ENVIROMENT AND CAN LEAD TO THE IMPOSITION OF
SUBSTANTIAL FINES. THESE REGULATIONS MAY VARY DUE TO THE PASSAGE OF LAWS.
A CERTIFIED TECHNICIAN MUST PERFORM THE INSTALLATION AND SERVICE OF THIS
PRODUCT. SHOULD QUESTIONS ARISE, CONTACT YOUR LOCAL EPA OFFICE.
3
Air Handler
WARNING
DUE TO HIGH SYSTEM PRESSURE AND ELECTRICAL SHOCK IN POTENTIAL,
INSTALLATION AND SERVICE WORK CAN BE DANGEROUS. ONLY TRAINED AND QUALIFIED
PERSONNELS ARE PERMITTED TO INSTALL OR SERVICE THIS EQUIPMENT. OBSERVE
ALL WARNINGS CONTAINED IN THIS MANUAL AND LABELS/TAGS ATTACHED TO THE
EQUIPMENT.
WARNING
THIS PRODUCT IS FACTORY SHIPPED FOR USE WITH A 208-230/1/60 ELECTRICAL
POWER SUPPLY. THIS AIR HANDLER MUST NOT BE RECONFIGURED TO OPERATE WITH
ANY OTHER POWER SUPPLY.
WARNING
THE UNIT MUST HAVE AN UNINTERRUPTED, UNBROKEN ELECTRIC GROUNDING TO
MINIMIZE THE POSSIBILITY OF PERSONAL INJURY IF AN ELECTRIC FAULT OCCURS. THE
ELECTRIC GROUNDING CIRCUIT MAY CONSIST OF AN APPROPRIATE SIZED POWER CORD
WHICH CONNECTED WITH THE GROUNDING PIECE LOCATED IN THE UNIT CONTROL BOX
AND ALSO CONNECTING TO THE BUILDING ELECTRIC SERVICE PANEL. OTHER METHODS
OF GROUNDING ARE PERMITTED IF PERFORMED IN ACCORDANCE WITH THE “NATIONAL
ELECTRIC CODE” (NEC)/ “AMERICAN NATIONAL STANDARDS INSTITUTE” (ANSI)/ “NATIONAL
FIRE PROTECTION ASSOCIATION” (NFPA) 70 AND LOCAL/STATE CODES. IN CANADA,
ELECTRIC GROUDING CONFORMS TO THE CANADIAN ELECTRIC CODE CSA C22.1.
FAILURE TO OBSERVE THIS WARNING CAN RESULT IN ELECTRICAL SHOCK THAT CAN
CAUSE PERSONAL INJURY.
This product is designed and manufactured to comply with national codes. It is installer’s
responsibilities to install the product in accordance with such codes and/or any prevailing local
codes/regulations. The manufacturer assumes no responsibilities for equipment installed in violation
of any codes or regulations.
2.4 Replacement Parts
When reporting shortages or damages, or ordering repair parts, give the complete product
model and serial numbers as stamped on the product. Replacement parts for this product are
available through your contractor or local distributor.
3. Important Safety Instructions
3.1 Recognize Safety Symbols, Words, and Labels
The following symbols and labels are used throughout this manual to indicate immediate or
potential hazards. It is the owner’s responsibility to read and comply with all safety information and
instructions accompanying these symbols. Failure to heed safety information increases the risk of
serious personal injury or death, property damage and/or product damage.
4
Air Handler
CARBON MONOXIDE POISONING HAZARD
Special warning for installation of furnaces or air handling units in enclosed areas, such
as garages, utility rooms or parking areas.
Carbon monoxide producing devices (such as an automobile, space heater, gas water heater,
etc.) should not be operated in enclosed areas such as unventilated garages, utility rooms or
parking areas because of the danger of carbon monoxide (CO) poisoning resulting from the
exhaust emissions.If a furnace or air handler is installed in an enclosed area such as a garge, utility
room or parking area and a carbon monoxide producing device is operated therein, there must be
adequate ventilation directly to outside.
This ventilation is necessary to avoid the danger of CO poisoning which can occur if a carbon
monoxide producing device continues to operate in the enclosed area. Carbon monoxide emission
can be (re)circulated throughout the building if the furnace or air handler is operating in any mode.
CO can cause serious illness including permanent brain damage or death.
3.2 Unit Inspection
Upon delivery, inspect the unit for damage. Any damage must be reported immediately to the
carrier. Do not install such an equipment damaged by freight which determines the integrity and
safety of the unit.
Please check the equipment model number to ensure the unit is appropriately sized for the
condensing unit.
If an incorrect unit is supplied, it must not be installed and it is to be returned to the supplier.
The manufacturer assumes no responsibility for the installation of incorrectly delivered units.
evaporator coil contains high-pressure inert gas for holding charge.
The
4. Location
WARNING
THIS AIR HANDLER IS DESIGNED FOR INDOOR INSTALLATION ONLY. DO NOT INSTALL
IT OUTDOORS.
When installing the air handler, minimize the length of refrigerant piping as short as possible.
Do not install the air handler at a place either above or below the condensing unit, which violates
5
Air Handler
the installation instructions of the condensing unit. The clearance between a combustible surface
and the unit is “0”; however, service clearance takes precedence. Allow a minimum of 24” in front of
the unit for service clea
attic), a drain pan for emergency is required. Check local and state codes for requirements. When
installing this unit in an area that may become wet, elevate the unit with a rm and non-porous
material. To avoid of personal injury during installation (i.e. in a garage), it is advised to install a
protective barrier to prevent such damage.
rance. When installing in an area directly over a nished ceiling (such as an
5. Ductwork
This air handler is designed for a complete supply and return ductwork system.
WARNING
DO NOT OPERATE THE UNIT WITHOUT ALL DUCTWORK COMPLETED.
To ensure correct system performance, the ductwork is to be sized to accommodate 375-
425 CFM per ton of cooling with the static pressure or less than 5" WC. Inadequate ductwork that
restricts airow may result in improper performance and compressor or heater failure. Ductwork
is designed with less restrictions of airow and maintains suitable airow speed. And keep the
ductwork sealed with good hermeticity.
Return Ductwork. Do not place the duct inlet at a place where is filled with toxic gas or
harmful fume/odor. For upow conguration, duct terminal connects to the bottom of the air handler.
Return Air Filters. Each installation must include a return air filter. This filtering may be
performed at the air handler or externally such as a return air lter grille.
6. Electric Heat
The air handlers listed in this manual do not have factory installed electric heat. Electric heat is
available as an accessory. The only heater kits that can be used are VAFd series. Please refer to
installation instructions provided with heater kit for the correct installation procedure.
WARNING
REFER TO THE “INSTALLING ELECTRIC HEAT” SECTION OF THIS MANUAL AND THE
INSTRUCTIONS PROVIDED WITH THE HEATER KIT FOR THE CORRECT INSTALLATION
PROCEDURE.
WARNING
THE ELECTRICAL CHARACTERISTICS OF THE AIR HANDLER, THE ELECTRIC HEATER
KIT, AND THE SUPPLY POWER MUST AGREE. THIS AIR HANDLER DOES NOT HAVE
FACTORY INSTALLED ELECTRIC HEAT. ELECTRIC HEAT IS AVAILABLE AS AN ACCESSORY.
IF INSTALLING THIS OPTITION, THE ONLY HEATER KITS THAT CAN BE USED ARE THE
VAFd SERIES AS INDICATED BELOW.
6
Air Handler
The heating mode temperature rise is dependent upon the system airow, the supply voltage,
and the heater kit size (KW) selected. Use Tables 8-10 to determine the temperature rise(ºF).
table 8
CFM
600284156
800213142
100017253450
12001421284256
14001218243648
16001015213142
1800914192837
58101520
230/1/60 Supply Voltage-Temperature Rise Table ºF
CFM
600273952
800203040
100016243248
12001320274053
14001117233446
16001015203040
1800913182736
58101520
220/1/60 Supply Voltage-Temperature Rise Table ºF
CFM
600253750
800192838
100015223046
12001319253856
14001116223348
1600914192842
1800812172537
58101520
208/1/60 Supply Voltage-Temperature Rise Table ºF
Note: For installations not indicated above the following formula is to be used:
TR=(kW*3412)*(Voltage Correction)*1.08/CFM
Where:TR=Temperature Rise
KW=Heater Kit Actual kW
3412=Btu per kW
Voltage Correction= 0.96(230 Supply Volts)
0.92(220 Supply Volts)
0.87(208 Supply Volts)
1.08=Constant CFM=Measured Airow
HEATER KIT NOMINAL KW
table 9
HEATER KIT NOMINAL KW
table 10
HEATER KIT NOMINAL KW
7
Air Handler
Note: The Temperature Rise Tables can also be used to determine the air handler airflow
delivery. When using these tables for this purpose, set the room thermostat to maximum heat and
allow the system to reach steady state conditions. Set two thermometers, one in the return air inlet