The PowerMaxExpress control panel is supplied with 2 instruction manuals:
Installer Guide (this manual - for your exclusive use)
User’s Guide (for your use during installation only - Must be handed over to the master user after testing the system).
Appendices A.1 and A.2 will help you prepare an installation plan. Please take time to fill out the forms - your job will
become much easier and confusion will be prevented. Filling out the forms will also help you create a list of detectors and
transmitters that must be obtained for the particular application. Compatible detectors and transmitters are listed and
described briefly in Appendix D.
Remember - it is advisable to power up the control panel temporarily after unpacking and program it on the work bench, in
accordance with the installation plan.
The programming flow charts in the programming section show all options available for each parameter. Factory defaults
are marked with a dark box to their right, and other options (that can be selected instead) are marked by clear boxes. This
method allows you to put a checkmark in the appropriate clear box whenever you deviate from the factory defaults.
Most of the programming section paragraph numbers correlate with the programming menu numbers. For example,
paragraph 4.4.19 describes the "Jam detect", that exists in menu 4 (define panel), sub-menu 19 (Jam detect).
Although setting the correct time and date is one of the user tasks, we recommend that you set the time and date in the
course of programming. Access to the “User Settings” for the installer is possible through item 10 on the installer‘s menu or
through the user menu (see User’s manual section 7).
After programming, proceed to install the system as detailed in the Installation Instructions, from paragraph 3.4 onward.
The installer should verify line seizure. Be aware of other phone line services such as DSL. If DSL service is present
on the phone line, you must install a filter. It is suggested to use the DSL alarm filter model Z-A431PJ31X
manufactured by Excelsus Technologies, or equivalent. This filter simply plugs into the RJ-31X jack and allows alarm
reporting without breaking the internet connection. If the user has a Voice over IP phone system only, the control
panel will not be able to communicate with the central station via the PSTN telephone line. In this case, the user will
either need to install an additional telephone line, or connect a GSM module.
2 D-302989
1. INTRODUCTION
Compatibility: This manual refers to PowerMaxExpress
v1.3.71 and above.
The PowerMaxExpress is a user and installer-friendly, 29zone fully-supervised wireless control system.
The system is designed to function in an appealing way to
the user and also offers features that make installers’ life
easier than ever before:
EASY TO MAINTAIN
•Alarm memory and trouble data are displayed upon
request.
2. SPECIFICATIONS
2.1 General Data
Zones Number: 28 wireless zones, 1 hardwired input.
Hardwired Zone Requirements: 2.2 kΩ E.O.L. resistance
(max. resistance of wires 220 Ω). Zone Types: Interior follower, interior, perimeter,
perimeter follower, delay 1, delay 2, 24h silent, 24h
audible, fire, non-alarm, emergency, gas, flood,
temperature and home/delay.
User Codes: 8 codes, 4 digits each (9999 different
combinations). Code 0000 is not allowed.
Control Facilities:
Alarm inhibited during a single arming period (swinger
stop) after: 1, 2, 3, alarm/tamper/fault, or not inhibited
(programmable / selectable).
Note: To comply with EN requirements, the swinger stop
should be set to 3.
Alarm Types: Silent alarm, siren alarm (future option) or
sounder (internal) alarm, in accordance with zone
attributes.
Siren Signals: Continuous
triple pulse - pause - triple pulse...
Siren (bell) Timeout: Programmable (4 min. by default).
Internal Sounder Output: At least 85 dBA at 10 ft (3 m).
Supervision: Programmable time frame for inactivity alert
Special Functions:
- Chime zones
- Diagnostic test and event log.
- Local and Remote Programming over Telephone, GSM
/GPRS connections.
- Calling for help by using an emergency transmitter.
- Tracking inactivity of elderly, physically handicapped and
infirm people.
Data Retrieval: Alarm memory, trouble, event log.
Real Time Clock (RTC): The control panel keeps and
displays time and date. This feature is also used for the log file
by providing the date and time of each event.
Compliance with U.S. Standards:
USA: (FCC) CFR 47part 15 and part 68, UL 1023, UL 985,
UL 1635, UL 1637, SIA CP-01
(intrusion / 24 hours / panic);
(fire).
•Diagnostic test provides visual and audible indication of
the signal level of each detector.
• Remote control from distant telephones.
• Event log stores and displays information.
• Upload / download from distant computer via telephone
line or cellular modem.
QUICK PROGRAMMING
• Simple programming logic, fully menu driven.
• Multiple-choice selection of options for each parameter.
• Unequivocal visual prompts.
• Installer access to the user menu.
Canada: RSS 210, ULC S545-02, ULC C1023,CSA
C22.2#205
On the bottom (side) panel of this equipment is a label,
that contains among other information, a product identifier
in the format US:VSOAL03BPMEXPRESS. If requested,
this number must be provided to the telephone company.
Compliance with European CE Standards:
The Powermax Express has been certified to EN 50082-1,
EN301489-3,7, EN61000-4-6, EN60950, EN300220,
EN50130-4, EN50130-5, EN50131-3, EN50131-6 tested by
the Dutch testing and certification body Telefication B.V.
The PowerMaxExpress is compatible with the RTTE
requirements - Directive 1999/5/EC of the European
Parliament and of the Council of 9 March 1999.
According to the European standard EN50131-1, the
PowerMaxExpress security grading is 2 – "low to medium
risk" and environmental classification is II – "indoor general"
and the power supply type is A.
GSM standards:
Europe: Complies with CE standards 3GPP TS 51.010-1,
EN 301 511, EN301489-7
USA: FCC 47 Part 22 (GSM850) and Part 24 (GSM 1900).
EMC standard: FCC 47 Part 15.
2.2 RF Section
Operating Frequencies (MHz): 315 (in USA & Canada),
433.92, 868.95 or other UHF channel per local
requirement in the country of use.
Receiver Type: Super-heterodyne, fixed frequency
Receiver Range: 600 ft (180 m) in open space
Antenna Type: Spatial diversity
Coding: PowerCode and/or CodeSecure™
2.3 Electrical Data
External AC/AC adapter:
• Europe: 230VAC 50Hz input, 9VAC 700mA output.
• USA: 120VAC 60Hz input, 9VAC 1000mA output.
Current Drain: Approx. 70 mA standby, 1600 mA peak at
full load.
Minimum battery voltage: 4.8V
Note: For CE compliance the battery backup period shall
exceed 12 hours.
Backup Battery Pack: 4.8V 1300 mAh, rechargeable
NiMH battery pack, p/n GP130AAM4YMX, manufactured
by GP or equivalent.
Note: For compliance with UL standards the battery
backup period shall exceed 24 hours.
Backup Battery Pack: 4.8V 2200 mAh, rechargeable
NiMH battery pack, p/n GP230AAHC4YMX, manufactured
by GP.
Battery Test: Once every 10 seconds.
D-302989 3
2.4 Communication
Built-in Modem: 300 baud, Bell 103 protocol
Data Transfer to Local Computer: Via RS232 serial port
Report Destinations: 2 central stations, 4 private telephones.
Reporting Format Options: SIA, Pulse 4/2 1900/1400 Hz,
Pulse 4/2 1800/2300 Hz, Contact ID, Scancom.
Pulse Rate: 10, 20, 33 and 40 pps - programmable
Message to Private Phones: Tone
Ring Detection: The unit does not support ring detection
without DC voltage present on the telephone lines.
3. INSTALLATION
Note: This system must be checked by a qualified
technician at least once every three (3) years.
This equipment is designed to be connected to the telephone
network using RJ11 connector which complies with Part 68
rules and requirements adopted by ACTA and properly
installed RJ31X connector. See drawing below for details.
In the case that RJ31X is not available (consult your
telephone company or a qualified installer), the telephone
line should be connected to the PowerMaxExpress unit
first and then all other home equipment should be
connected to PowerMaxExpress "Phone" outlet.
2.5 Physical Properties
Operating Temp. Range: 14°F to 120°F (-10°C to 49°C)
Storage Temp. Range: -4°F to 140°F (-20°C to 60°C)
Humidity: 85% relative humidity, @ 30°C (86°F)
Size: 193 x 178 x 50 mm (7-5/8 x 7 x 2 in.)
Weight: 658g (23 Oz) (with battery)
Color: White
The REN is used to determine the number of
Note:
devices that may be connected to a telephone line.
Excessive RENs on a telephone line may result in the
devices not ringing in response to an incoming call. In
most but not all areas, the sum of RENs should not
exceed five (5.0). To be certain of the number of devices
that may be connected to a line, as determined by the
total RENs, contact the local telephone company. The
REN of alarm system is part of the product identifier that
has the format US:VSOAL03BPMEXPRESS.
Connection to telephone company provided coin service is
prohibited. Connection to party lines service is subject to
state tariffs.
3.1 Unpacking the Equipment
Open the cardboard packing box and check whether all
items have been included. If you find out that an item is
missing, contact your vendor or dealer immediately.
3.2 Supplying Power to the Unit
Connect power to the PowerMaxExpress temporarily (see
figure 3.8). Alternatively, you may power up from the
backup battery, as shown in figure 3.3.
Disregard any “trouble” indications pertaining to lack of
battery or lack of telephone line connection.
For Europe Safety Compliance:
a. The model shall be installed according to the local
electrical code.
b. The circuit breaker shall be readily accessible.
c. The rating of the external circuit breaker shall be 16A
or less.
d. The cables for the AC mains connection shall have an
overall diameter of 13mm and 16mm conduit.
Please refer to Figure 3.6 "Power Cable Connection".
3.3 System Planning & Programming
It pays to plan ahead - use the tables in appendices A and
B at the end of this guide to register the intended location
of each detector, the holder and assignment of each
transmitter.
Gather up all transmitters and detectors used in the
system and mark each one in accordance with your
deployment plan.
Program the system now as instructed in the
programming section.
3.4 Mounting
Required tool: Philips screwdriver #2.
PowerMaxExpress mounting process is shown in figure
3.1 - 3.8.
3.5 Wiring
Required tools: Cutter and slotted screwdriver - 3 mm
blade.
PowerMaxExpress wiring is shown in figure 3.2.
4 D-302989
Remove
front
cover
Back unit
Cables entry
possibilities
1
Release
screws
Drill 4 holes and insert wall anchors
4
Figure 3.1 – Back Unit Mounting
CABLES ROUTING GUIDE
Mark 4 drilling points on mounting surface
3
Fasten the back unit with 4 screws
Cable clips
5
(example)
Remove the left or right side
1
cables entry knockout(s) and
enter the required cable(s).
2
Remove and use as
cable clamp(s)
D-302989 5
POWER CABLE ROUTING
PERFORM STEP 1, 2 & 3 ON A DESKTOP, BEFORE THE MOUNTING!
Extract either plastic
segments (will be used later)
4
Remove power supply terminals
cover
1
Extract plastic segment
(will be used later)
5
Insert power cable and connect it to
the Power Supply Unit terminals.
Verify that the wires are properly
fastened!
2
Power
supply
module
Extract plastic segment
(left or right, according to
the power wiring direction)
6
Insert pastic cap to the power
cable entry (extracted in step 1)
3
7
Fasten power cable by clamp (extracted in step 2).
Note: The clamp direction depends on the cable thickness.
Power cable clamp options
for
thin
cable
6 D-302989
for
cable
thick
(reversed clamp)
8
Close power
supply terminals
cover
Terminals
cover
Connect telephone cable to SET connector and telephone line cable to LINE connector (through the desired wiring cable entry).
PHONE WIRING
PHONE WIRING IN NORTH AMERICA
GRAY
RED
GREEN
BROWN
RJ-31X
CORD
PGM & ZONE WIRING
PGM output
Vmax=30v
Imax=100mA
Relay
Device
External
power supply
5 - 30VDC
8-POSITION
RJ-31X PLUG
Ta mp er
2.2 k
1
Ω
RJ-31X JACK
23
RJ-31X
7
6
GRAY
RED
4
LINE
HOUSE
FROM
PHONES
STREET
5
GRN
BROWN
Alarm
Note: Do not use mains cable other than that supplied by the manufacturer (3 m long).
Figure 3.2 - Wiring
WARNING! When plugging SIREN & ZONE terminals
back into place, be sure to align them carefully with the
pins on the PCB. Misaligned or reverse insertion of
3.6 Backup Battery Insertion
Connect battery pack as shown in the next drawing.
terminals may damage internal PowerMaxExpress circuits!
D-302989 7
1
Battery
insertion
3.8 Power Cable Connection
External power connections (Option)
Connect the power cable and close the control panel as
shown below. Electrical socket-outlet shall be installed
near the equipment and shall be easily accessible.
WARNING! DO NOT USE AN OUTLET CONTROLLED
BY A WALL SWITCH.
Note: This equipment should be installed in accordance with
Chapter 2 of the National Fire Alarm Code, ANSI/NFPA 72,
(National Fire Protection Association).
2
Battery connection
Figure 3.3 - Battery Insertion
3.7 Optional GSM Module Mounting
Note: The GSM module is used with an internal antenna.
Optional external antenna can be used.
Caution: Do not install or remove the GSM module when
the system is powered by AC power or backup battery.
1. Plug in the
GSM Module
and fasten it
as follows:
Figure 3.4 - Optional GSM Module Mounting
2. Insert the SIM card into the GSM module
GSM
Front
unit
Connect the power
adapter to the
power connector.
Fig. 3.6a - Power Cable Connection
Internal Power Connection (Option)
Fig. 3.6b
Internal Power
Cable Connection
3.9 Control Panel Final Closure
Control panel final closure is shown below.
.
SIM card insertion
1
Close
front
cover
1
Slide top
cover
4
Slide SIM
card into
cover
2
Open
cover
5
Rotate cover
to close
6
Lock cover
to close
Figure 3.5 - SIM Card insertion
Align SIM
card in cover
(note cover
orientation)
IMPORTANT
Do not insert or remove
SIM card when the
control panel is powered
by AC power or battery.
3
Fasten
screws
.
Figure 3.7 - Final Closure
8 D-302989
4. PROGRAMMING
4.1 INTRODUCTION
4.1.1 General Guidance
We recommend to program the PowerMaxExpress on the
work bench before actual installation. Operating power
may be obtained from the backup battery or from the AC
power supply.
The installer’s menu is accessible only to those who know
the installer’s 4-digit code, which is 9999 by factory default.
Note: Access to the installer menu, in PowerMaxExpress
that has "User Permission" enabled (for example in UK) is
accessible only at the end of the user menu. This option
can be changed if necessary (see par. 4.4.36).
For PowerMaxExpress that has 2 installer codes (not
applicable in UK), the default INSTALLER code is 8888
and the default MASTER INSTALLER code is 9999.
The following actions can be done only by using the
master installer code:
• Changing master installer code.
• Resetting the PowerMaxExpress parameters to the
default parameters,
• Defining specific communication parameters, as
detailed in a note in figure 4.5C.
Obviously, you are expected to use this code only once for
gaining initial access, and replace it with a secret code
known only to yourself.
You will mainly use 5 control pushbuttons during the entire
programming process:
- to move one step forward in a menu.
- to move one step backward in a menu.
OKI
to enter the relevant menu or confirm data.
-
- to move one level up in a menu.
- to return to the "OK TO EXIT" state.
The sounds you will hear while programming are:
- Single beep, heard whenever a key is pressed.
- Double beep, indicates automatic return to the
normal operating mode (by timeout).
-Happy Melody (- - - –––), indicates successful
☺
completion of an operation.
-Sad Melody (–––––), indicates a wrong move
or rejection.
4.1.2 Entering an Invalid Installer Code
If you enter an invalid installer code 5 times, the keypad
will be automatically disabled for 90 seconds and the
message WRONG PASSWORD will be displayed.
4.1.3 Installer’s Menu
The installer's menu is shown in figure 4.1a. The text in
rectangles represents the current PowerMaxExpress
display.
4.1.4 Setting a New Installer Code
To set an installer code, perform the actions that are
presented in figure 4.1b. When you are instructed to enter
code, enter a 4-digit code.
4.1.5 Setting a New Installer Code in
PowerMaxExpress that has 2
Installer Codes
For PowerMaxExpress with 2 installer codes, INSTALLER
code (default 8888) and MASTER INSTALLER code
(default 9999), set new codes as shown in figure 4.1c.
For details regarding the different authorization levels
when logging in with installer code and master installer
code, refer to the note inside figure 4.5C (DEFINE
COMM).
By using the master installer code, the menu enables
changing both master installer code and installer code.
By using the installer code, the menu enables changing
the installer code only.
(First display)
READY 00:00
WALK TEST
[code]
(*)
(See fig. 4.1b & 4.1c)
(See figure 4.2)
(See figure 4.3)
(See figure 4.4)
(See figure 4.5)
(See figure 4.9)
(See figure 4.10)
(See chapter 7
in User Guide)
(See par. 4.12)
(Control Panel
serial number
display)
(See section 4.14)
USER SETTING
INSTALLER MODE
ENTER CODE
[installer code]
1. NEW INSTL CODE
2. ENROLLING
3. DEFINE ZONES
4. DEFINE PANEL
5. DEFINE COMM.
9. DEFINE CUSTOM
10. DIAGNOSTICS
11. USER SETTINGS
12. FACTORY DEFLT
13. SERIAL NUMBER
14. START UL/DL
<OK> TO EXIT
(*) Applicable only when "USER PERMIT" function is enabled
(see par. 4.4.36 - USER PERMIT)
Figure 4.1a - Installer’s Menu
(See fig . 4.1a )
1. NEW INSTL CODE
NEW INST. CODE
INST. CODE xxxx
Figure 4.1b - Setting a New Installer Code (see note)
D-302989 9
By using
INSTALLER CODE
(see fig. 4.1a)
1. NEW INSTL CODE
NEW INST. CODE
INST. CODE xxxx
[code]
MASTER INSTALLER CODE
(see fig. 4.1a)
1. NEW INSTL CODE
NEW MASTER CODE
MASTER CODE xxxx
[code]
By using
NEW INST. CODE
INST. CODE xxxx
[code]
Note:Installer Code should never be programmed as
“0000”. Doing so will lock the user out of the installer menu!
Figure 4.1c - Setting a New Installer Code
in System with Inst. & Master Inst. Codes (see note)
4.2 ENROLLING WIRELESS DEVICES AND KEYFOB TRANSMITTERS
• ENROLL WL SIREN (wireless siren)
Before beginning, gather all the devices that you intend to
enroll and make sure they all have batteries installed.
Your control panel must recognize the unique identification
code (ID) of each such device in order to supervise them,
receive their signals and respond accordingly.
Attention! CodeSecure transmitters are mainly used for
arming/disarming and can not be enrolled to zones. In
order to enroll to zones, use only non-CodeSecure
wireless devices.
4.2.2 Enrolling Type
Here you determine whether to enroll a wireless device by
normal transmission or by device Tamper function
(opening its cover). Options: normal, or by tamper.
4.2.3 Enroll/Delete Sensors
Wired detector can be enrolled in zone 29 and wireless
detectors can be enrolled in zones 01-28.
STOP
•Make sure that magnetic contact transmitter is
To enroll / delete wired / wireless sensors, refer to Fig. 4.2.
• Before enrolling, the lens at the front of PIR
and dual-technology sensors should be
masked to prevent inadvertent transmission.
together with its magnet, to prevent it from sending
alarm transmission.
4.2.4 Enroll/Delete Keyfob Transmitters
Keyfob transmitters are multi-button wireless CodeSecure™
transmitters. Eight system users use them for better,
quicker and safer control over various system functions.
To enroll / delete 1-way or 2-way keyfob transmitters, refer
to figure 4.2.
4.2.5 Enroll/Delete Wireless Commander
The Wireless Commander (MCM-140+) is a remote control
unit that enables the user to remotely control the system.
To enroll / delete up to 8 wireless commanders, refer to
figure 4.2 (Enroll WL 1-way KP).
4.2.6 Enroll/Delete 2-Way Keypad
The 2-way keypad, type MKP-150/MKP-151, enables the
user to remotely control the system and also to receive
data from the system (alarm and trouble data). To enroll up
to two 2-way keypads, refer to figure 4.2.
4.2.7 Enroll/Delete Wireless Siren
The wireless siren is a remote siren that is activated upon
predefined events by the PowerMaxExpress system. To
enroll / delete up to 2 wireless sirens, refer to figure 4.2.
10 D-302989
ENROLLING TYPE
normal enroll
by tamper
(First display)
READY 00:00
WALK TEST
USER SETTING
INSTALLER MODE
ENTER CODE
[installer code]
1. NEW INSTL CODE
2. ENROLLING
3. DEFINE ZONES
ENROLL SENSORS
SET SENSITIV.
higher sensitivity
lower sensitivity
Select by
or
ZONE No: - -
[wired Zone No.
29/30] (e.g. 29)
ZONE No: 29
<OK> TO ENROLL
ZONE No: 29
for next
enrolling action
Enrolling wired sensor
ENROL WL 1WAY KP
1way kp No :
1way kp No : 51way kp No : 5
[WL Zone No.
01-28] (e.g. 05)
ZONE No: 05
TRANSMIT NOW
[Initiate transmission)
(**)
ZONE No: 05
for next
enrolling action
Enrolling a WL Sensor
[WL 1-way keypad
No. 1 to 8] (e.g. 5)
(***)
(****)
[wired/WL Zone No.
01-30] (e.g. 05)
ZONE No: 05
<OFF> TO DELETE
ZONE No: 05
Deleting wired/
WL sensor
(**)
(**)
2way kp No : 22way kp No : 2
(*)
ENROLL KEYFOB
Keyfob No: -
[Keyfob No.]
Keyfob No: 5
TRANSMIT NOW
(press
any
key)
(**)
KEYFOB No: 05
for next
enrolling action
Enrolling a Keyfob
ENROL WL 2WAY KP
2way kp No:
[MKP-150/151
No. 1 or 2] (e.g. 2)
(e.g. 5)
Keyfob No: 5
<OFF> TO DELETE
KEYFOB No: 05
Deleting a Keyfob
(**)
(**)
<OK> TO EXIT
TRANSMIT NOW
press
*
key until
red LED
lights
1way kp No: 5
for next
enrolling action
Enrolling a wireless
Commander MCM-140+
ENROL WL SIREN
SIREN No :
siren No : 2siren No : 2
TRANSMIT NOW
Momentarily press the
wireless siren self-test
button until a squawk is
heard (1 sec. approx.)