Visonic PowerMaster 360 Installer's Manual

D-305735 PowerMaster 360 Installer's Guide 1
Pow erMaster 360
Version 1 8
Installer's Guide
Ta ble of Cont ent s
1. INTRODUCTION ................................................. 3
2. CHOOSING THE INSTALLATION LOCATION .. 6
3. INSTALLATION .................................................. 7
3.1 Connections and LED Indications .............. 7
3.2 Inserting the Battery .................................... 8
3.3 PowerManage 360 Connections ................. 9
3.4 GSM Connection and Configuration ......... 10
3.6 PowerMaster 360 Prerequisites ................ 10
3.7 Enrolling / Deleting a Z-Wave Device ....... 10
3.8 Panel Reset................................................. 11
3.9 Factory Default Restore ............................. 11
4. PROGRAMMING .............................................. 12
4.1 General Guidance ...................................... 12
4.1.1 Navigation .......................................... 12
4.1.2 Feedback Sounds .............................. 14
4.2 Entering the "Installer Mode" and Selecting
a Menu Option .................................................. 14
4.2.1 Entering the "Installer Mode" if "User
Permit" is enabled ....................................... 14
4.2.2 Selecting options ................................ 15
4.2.3 Exiting the Installer Mode ................... 15
4.3 Setting Installer Codes .............................. 15
4.3.1 Identical Installer and Master Installer
Codes ......................................................... 16
4.4 Zones / Devices .......................................... 16
4.4.1 General Guidance & Zones/Devices
Menu Options ............................................. 16
4.4.2 Adding New Wireless Devices ........... 17
4.4.3 Deleting a Device ............................... 21
4.4.4 Modifying or Reviewing a Device ....... 21
4.4.5 Replacing a Device ............................ 22
4.4.6 Configuring Soak Test Mode .............. 22
4.4.7 Defining Configuration Defaults for
"Device Settings" ........................................ 23
4.4.8 Updating Devices after Exiting Installer
Mode ........................................................... 23
4.5 Control Panel .............................................. 24
4.5.1 General Guidance – "Control Panel"
Flow-Chart & Menu Options ........................ 24
4.5.2 Configuring Arming/Disarming and
Exit/Entry Procedures .................................. 25
4.5.3 Configuring Zones Functionality ......... 26
4.5.4 Configuring Alarms & Troubles ........... 27
4.5.5 Configuring Sirens Functionality ......... 28
4.5.6 Configuring Audible & Visual User
Interface ...................................................... 28
4.5.7 Configuring Jamming and Supervision
(Missing device) .......................................... 29
4.5.8 Configuring Miscellaneous Features ... 30
4.6 Communication .......................................... 31
4.6.1 General Guidance – "Communication"
Flow-Chart & Menu Options .......................... 31
4.6.2 Configuring GSM-GPRS (IP) - SMS
Cellular Connection ..................................... 32
4.6.3 Configuring Events Reporting to
Monitoring Stations ...................................... 33
4.6.4 Configuring Events Reporting to Private
Users ........................................................... 36
4.6.5 Configuring Motion Cameras for Visual
Alarm Verification ........................................ 36
4.6.6 Configuring Upload / Download Remote
Programming Access Permission ................ 37
4.6.7 Broadband .......................................... 38
4.7 Custom Names ........................................... 39
4.7.1 Custom Zone Names .......................... 39
4.8 Diagnostics ................................................. 40
4.8.1 General Guidance – "Diagnostics" Flow-
Chart & Menu Options ................................. 40
4.8.2 Testing Wireless Devices ................... 40
4.8.3 Testing the GSM module .................... 42
4.8.4 Testing the SIM Number ..................... 42
4.8.5 Testing the Broadband/PowerLink
Module ........................................................ 43
4.9 User Settings .............................................. 43
4.10 Factory Default ......................................... 44
4.11 Serial Number ........................................... 44
4.12 Partitioning................................................ 44
2 D-305735 PowerMaster 360 Installer's Guide
4.12.1 General Guidance – "Partitioning"
Menu ........................................................... 44
4.12.2 Enabling / Disabling Partitions .......... 44
4.13 Operation Mode ........................................ 45
4.13.1 General Guidance – "Operation Mode"
Menu ........................................................... 45
4.13.2 Select setting ................................... 45
4.13.3 BS8243 Setup .................................. 45
4.13.4 DD243 Setup ................................... 46
4.13.5 CP01 Setup ...................................... 48
4.13.6 OTHERS Setup ................................ 49
5. PERIODIC TEST ............................................... 51
5.1 General Guidance ...................................... 51
5.2 Conducting a Periodic Test ....................... 51
6. MAINTENANCE ................................................ 54
6.1 Handling System Troubles ........................ 54
6.2 Replacing the Backup Battery................... 55
6.3 Replacing/Relocating Detectors ............... 55
6.4 Annual System Check................................ 55
7. READING THE EVENT LOG ............................ 56
APPENDIX A. PowerMaster 360 Configurator ... 57
A1. Working with the PowerMaster
Configurator ..................................................... 57
A2. Manually Installing the USB Driver .......... 63
A3. Virtual Keypad Controls ............................ 68
LED Icons ................................................... 69
Control Keys ............................................... 69
Arming Keys ............................................... 69
Other Keys .................................................. 69
APPENDIX B. VISONIConfig Mobile Installer App.
For PowerMaster 360........................................... 70
B1. Working with the PowerMaster
Configurator ..................................................... 70
B2. VISONIConfig Controls ............................. 73
LED Icons ................................................... 73
Control Keys ............................................... 74
Arming Keys ............................................... 74
Other Keys .................................................. 74
APPENDIX C. User Mobile Application with
PowerMaster 360 .................................................. 75
C1. Security Only Via PowerManage ............... 75
C2. Security and Smart Home Via 3rd Party .... 75
APPENDIX D. Specifications ............................... 76
D1. Functional ................................................... 76
D2. Wireless ...................................................... 76
D3. Electrical ..................................................... 77
D4. Communication .......................................... 77
D5. Physical Properties .................................... 77
D6. Peripherals and Accessory Devices ......... 77
APPENDIX E. Working with Partitions ................ 78
E1. User Interface and Operation .................... 78
E2. Common Areas ........................................... 78
APPENDIX F. Detector Deployment & Transmitter
Assignments......................................................... 79
F1. Detector Deployment Plan ......................... 79
F2. Keyfob Transmitter List ............................. 79
F3. Emergency Transmitter List ...................... 80
F4. Non-Alarm Transmitter List ....................... 80
APPENDIX G. Event Codes.................................. 81
G1. Contact ID Event Codes ............................ 81
G2. SIA Event Codes ........................................ 81
G3. Understanding the Scancom Reporting
Protocol Data Format ....................................... 82
G4. SIA over IP - Offset for Device User ......... 82
APPENDIX H. Sabbath Mode ............................... 83
H1. General Guidance ...................................... 83
H2. Connection ................................................. 83
H3. Arming the System by Sabbath Clock ...... 83
APPENDIX I. Glossary .......................................... 84
APPENDIX J. Compliance with Standards ........... 86
PowerMaster 360 Quick User Guide .................... 89
1. INTRODUCTION
D-305735 PowerMaster 360 Installer's Guide 3
1. INTRODUCTION
The PowerMaster 360 security and smart home platform is a comprehensive security system based on the PowerMastersecurity logic and PowerG proven RF security technology with IP communication. The PowerMaster 360 platform allows adding cellular (2G or 3G) communication. Property owners receive notifications of events by email and/or SMS. In addition, the system includes a WiFi module that supports IP cameras and a Z-Wave controller that supports Z-Wave devices.
The PowerMaster 360 security system is fully controllable from a computer, and accessible to home and property owners through their mobile devices. Installers program and configure the system remotely through the computer and mobile application’s Virtual Keypad (see APPENDIX A / B).
This manual refers to PowerMaster 360 v18 and above. The most updated manuals can be downloaded from the Visonic Web site http://www.visonic.com. The PowerMaster 360 control panel is supplied with 2 instruction manuals:
Installer's Guide (this manual) – for use of system installer during system installation and configuration User’s Guide -– also for use of system installer during system installation and configuration, but also for the master
user of the system, once installation is completed. Hand over this manual to the master user of the system.
1.1 System Features
The following table lists the PowerMaster 360 features with a description of each feature and how to use it.
Feature Description How to configure and use
Visual Alarm Verification
The PowerMaster 360 when used with Next CAM PG2 PIR-camera detector and GPRS communication is able to provide the Monitoring Station with clips captured in alarm situations. The system sends the clips to the Monitoring Station automatically for burglary alarms and, depending on setup, also for fire and personal emergency alarms.
1. Setup GPRS communication: see GSM Module Installation (section 3.4).
2. Configure camera settings: refer to the Next CAM PG2 Installation Instructions.
3. Enable fire and personal alarm verification: see section 4.6.5 Configuring
Motion Cameras for Video Alarm Verification.
On demand clips from cameras
The PowerMaster 360 can provide images from the Next CAM PG2 by demand from a remote PowerManage server. Pictures are taken based on a command from the monitoring station. To protect customers' privacy, the system can be customized to enable the "On Demand View" only during specific system modes (i.e. Disarm, Home & Away) and also to a specific time window following an alarm event.
1. Setup the On demand feature: see section 4.6.5 Configuring Motion Cameras for Video Alarm Verification.
2. To request and view images: refer to the PowerManage User's Guide, Chapter 5 Viewing and Handling Events..
Easy Enrollment PowerG devices are enrolled from the control
panel’s Virtual Keypad. "Pre-enrollment" can also be performed by entering the PowerG device ID number and then activating the device in the vicinity of the panel.
To enroll or pre-enroll devices: see section
4.4.2 Adding New Wireless Devices.
Device Configuration Device parameters and related system
behavior can be configured from the control panel or from a remote location.
Each PowerG device has its own settings which can be configured through the control panel by entering the "DEVICE SETTINGS" menu.
Note: The minimum configuration of the system includes one detector.
To configure devices from the control panel: see Chapter 4 Programming and also
the individual device's Installation Instructions.
To configure devices from a remote location: refer to the PowerManage User's
Guide Chapter 3 Working with Panels and to the Remote Programmer PC software User's Guide, Chapters 6 and 7.
1. INTRODUCTION
4 D-305735 PowerMaster 360 Installer's Guide
Diagnostics of the control panel and peripherals
You can test the function of all wireless sensors deployed throughout the protected area, to collect information about the received signal strength from each transmitter and to review accumulated data after the test.
To perform diagnostics and to obtain signal strength indication: see section 4.8
Diagnostics.
Conducting periodic tests
The system should be tested at least once a week and after an alarm. The periodic test can be conducted locally or from a remote location (with the assistance from a non­technical person in the house).
To conduct a walk test locally: see Chapter 5 Periodic Test.
To conduct a walk test from remote location: refer to the Remote Programmer
PC software User's Guide, Chapter 6 Data Details Tables.
Partitions The partitioning feature, when enabled,
divides your alarm system into distinct areas each of which operates as an individual alarm system. Partitioning can be used in installations where shared security systems are more practical, such as a home office or warehouse building.
1. Enable partitioning: see section 4.12 Partitioning.
2. Setup partition association for each device: see section 4.4.2 Adding New
Wireless Devices.
To understand more about partitioning: see APPENDIX E. Working with Partitions and APPENDIX B. in the User's Guide.
Device configuration templates
The default parameters with which a new device is enrolled into the system can be set before you enroll devices. This default template saves time on device configuration.
1. Define enrollment defaults for devices: see section 4.4.7 Defining Configuration Defaults for "Device Settings".
2. Enroll or pre-enroll devices: see section
4.4.2 Adding New Wireless Devices.
SirenNet - distributed siren using Smoke detectors
All PowerG smoke detectors are able to function as sirens, alerting on any of 4 types of alarm in the system: fire, gas, burglary and flood.
Enable and configure SirenNet for each smoke detector: refer to the SMD-426 PG2
/ SMD-427 PG2 Installation Instructions.
Reporting to Private Users and/or Monitoring Station by SMS and IP communication
The PowerMaster 360 system can be programmed to send notifications of alarm and other events to 4 SMS cellular phone numbers and to report these events to the Monitoring Station by SMS or IP communication.
To configure notifications to Private phones: refer to the PowerMaster 360
User's Guide, Chapter 4, section B.12 Programming Email, MMS and SMS Reporting.
To configure reporting to the Monitoring Station: see section 4.6.3 Configuring
Events Reporting to Monitoring Stations.
Quick installation with link quality indication
With PowerG devices, there is no need to consult the control panel when mounting a wireless device, because PowerG devices include a built-in link quality indicator. Choosing the mounting location is a quick and easy process.
To choose the ideal location to mount a wireless device, see Chapter 2 Choosing the Installation Location.
1. INTRODUCTION
D-305735 PowerMaster 360 Installer's Guide 5
Device Locator Helps you to easily identify the actual device
displayed on the LCD display.
To read more on the Device Locator: refer to the PowerMaster 360 User's Guide, Chapter 2, Operating the PowerMaster 360 System.
To use the device locator when bypassing a zone or when clearing a bypassed zone:
refer to the PowerMaster 360 User's Guide, Chapter 4, section B.1 Setting the Zone Bypass Scheme.
To use the device locator when conducting the periodic test: see
Chapter 5 Periodic Test or refer to the PowerMaster 360 G2 User's Guide, Chapter 7 Testing the System.
Guard key-safe PowerMaster is able to control a safe that
holds site keys that are accessible only to the site's guard or Monitoring Station's guard in the event of an alarm. Operates with the magnetic contact device with auxiliary input only (MC-302E PG2)
1. Configure the safe's zone type to "Guard Zone": see section 4.4.2 Adding New Wireless Devices.
2. Setup guard code: see section 4.3
Setting Installer Codes.
Arming Key External system may control arming and
disarming of the PowerMaster system.
Refer to the MC-302 PG2 / MC-302E PG2 / MC-302V PG2 Installation Instructions.
2. CHOOSING THE INSTALLATION LOCATION
6 D-305735 PowerMaster 360 Installer's Guide
2. CHOOSING THE INSTALLATION LOCATION
To ensure the best possible mounting location of the PowerMaster 360 control panel, the following points should be observed:
The selected location should be approximately in the center of the installation site between all the transmitters, preferably in a hidden location.
In close proximity to an AC source
Where there is good cellular coverage, if WCDMA-350 is used
Far from sources of wireless interference, such as:
o Computers or other electronic devices, power conductors, cordless phones, light dimmers, etc. o Large metal objects (such as metal doors or refrigerators)
Note: A distance of at least 1 meter (3 ft) is recommended.
When mounting wireless devices:
Make sure that the signal reception level for each device is either "Strong" or "Good", but not "Poor".
Wireless magnetic contacts should be installed in a vertical position and as high up the door or window as possible.
Wireless PIR detectors should be installed upright at the height specified in their Installation Instructions
Repeaters should be located high on the wall in mid-distance between the transmitters and the control panel.
WARNING! To comply with FCC and IC RF exposure compliance requirements, the control panel should be located at a distance of at least 20 cm from all persons during normal operation. The antennas used for this product must not be co-located or operated in conjunction with any other antenna or transmitter. Le dispositif doit être placé à une distance d'au moins 20 cm à partir de toutes les personnes au cours de son fonctionnement normal. Les antennes utilisées pour ce produit ne doivent pas être situés ou exploités conjointement avec une autre antenne ou transmetteur.
3. INSTALLATION
D-305735 PowerMaster 360 Installer's Guide 7
3. INSTALLATION
3.1 Connections and LED Indications
A. Power indication
B. Status indication
C. Trouble indication
D. Service server indication
E. Smart Home Service
Indication
F. WiFi indication
G. Micro USB connection
H. 5V DC Power connection
I. LAN connection
J. Functional pushbuttons
(for future use): + button - Add Visonic /
Z-Wave devices
_
button - Delete Visonic /
Z-Wave devices
K. Hole for reset button
L. Back to factory: Press for
30 sec. to restore system parameters to factory default parameters
M. Micro SD memory card
holder (for future use)
N. Enroll LED (for future use)
A
B
C
D
E
F
H
I
G
K
J
L
N
M
3. INSTALLATION
8 D-305735 PowerMaster 360 Installer's Guide
O. Battery plug socket
P. GSM Module SIM card
holder
Q. Rechargeable battery
Figure 3.1 – Connections and LED indications
3.2 Inserting the Battery
1. Press on the tab inward
and lift to remove the battery cover.
2. Insert the battery cable plug into the battery socket.
3. To close the battery cover, align the two tabs of the battery cover with their respective slots and press down on the cover in the direction shown until a click is heard.
O
P
Q
2
1
3. INSTALLATION
D-305735 PowerMaster 360 Installer's Guide 9
Figure 3.2 – PowerMaster 360 Battery Insertion
3.3 PowerManage 360 Connections
Note: If there is a GSM module in your control panel, connect first the SIM card before performing the following procedure (see section 3.5).
1. Connect the DC power supply from the mains electrical socket to the power connection.
2. Connect the IP cable from the LAN connection to the local home-router connection.
3. To work with the Configurator, connect the micro USB cable from the micro USB connection to the PC/laptop/tablet
connection.
4. After completing the setup in the Configurator, disconnect the USB cable from the PowerMaster 360.
Note: See APPENDIX A for using the PC configurator and APPENDIX B for the VISONIConfig.
Figure 3.3 – PowerMaster 360 Panel Connections
3
2
1
3
3. INSTALLATION
10 D-305735 PowerMaster 360 Installer's Guide
3.4 GSM Connection and Configuration
The GSM modem auto detection feature enables automatic enrollment of the GSM modem into the control panel memory. GSM modem auto detection is activated after reset (power-up or after exiting the Installer Mode menu). This causes the PowerMaster 360 to automatically scan GSM COM ports for the presence of the GSM modem.
In the event that the GSM modem auto detection fails and the modem was previously enrolled in the control panel, the message "Cel Remvd Cnfrm" will be displayed on the Configurator’s Virtual Keypad. This message will disappear from the display only after the user presses the <OK> button. The modem is then considered as not enrolled and no GSM trouble message will be displayed.
Notes:
1) A message is displayed only when the alarm system is disarmed.
2) The GSM Alarm Transmission System is designed to comply with EN 50131-1 ATS4.
3.5 SIM Card Insertion
Insert the SIM card into the GSM module (indicated “O”
in section 3.1 above) as shown in the drawing.
1. Slide top cover.
2. Open cover
3. Align SIM card in cover (note cover orientation)
4. Slide SIM card into cover
5. Rotate cover to close
6. Lock cover to close
IMPORTANT! Do not insert or remove the SIM card
when the control panel is powered by AC power or battery.
To configure the GSM modem, see section 4.6.2.
3.6 PowerMaster 360 Prerequisites
Connection to PowerManage requires the following ports to be open on the router. From home to internet:
TCP ports : 8080, 5001
UDP port: 5001
FTP port: 21
Note: In a typical home router these ports should already be open.
The Windows 7 PC Operation System is supported for the Configurator.
3.7 Enrolling / Deleting a Z-Wave Device
Enrolling a Z-Wave Device
To enroll a device, proceed as follows.
1. Press and hold the (+) button (“J” in Figure 3.1) for 2 seconds. The red LED (“N” in Figure 3.1) blinks slowly.
2. Press the device Enroll button.
3. If Enroll is successful, the green LED blinks quickly and a happy beep is heard and then the LED turns off.
Notes:
1. To abort enrollment during this stage, press and hold the (+) or (-) buttons for 2 seconds. The LED will stop
blinking.
2. If enroll fails, the red LED lights constantly for 3 seconds and a sad beep is heard.
3. Long press on the (+) button, returns the panel to normal operation.
3. INSTALLATION
D-305735 PowerMaster 360 Installer's Guide 11
Deleting a Z-Wave Device
To delete an enrolled device, proceed as follows.
1. Press and hold the (-) button (“J” in Figure 3.1) for 2 seconds. The red LED (“N” in Figure 3.1) blinks quickly and a happy beep is heard and then the LED turns off.
Notes:
1. To abort the procedure during this stage, press and hold the (+) or (-) buttons for 2 seconds. The LED will stop
blinking.
2. If the procedure fails, the red LED lights constantly for 3 seconds and a sad beep is heard.
3. Long press on the (-) button, returns the panel to normal operation
3.8 Panel Reset
To reset the panel, use a blunt instrument to press the Reset button (“K” in Figure 3.1), or, alternatively, exit the Installer Mode. The Orange LED (“N” in Figure 3.1) lights constantly until Panel initialization is completed and the PowerLink is reset. Finally, the Orange LED (“N”) turns off.
3.9 Factory Default Restore
This procedure is performed to restore system parameters to factory default parameters. Back to Factory can be performed only when the panel is in the Disarmed state.
1. Press the Back to Factory button (“L” in Figure 3.1) for 30 seconds.
Note: During Back to Factory, the red LED (“N” in Figure 3.1) blinks.
2. If Back to Factory is successful: the green LED blinks 3 times and a happy beep is heard and then the panel
immediately initiates software reset.
Note: If the Back to Factory procedure fails, the red LED lights constantly for 3 seconds and a sad beep is heard.
4. PROGRAMMING
12 D-305735 PowerMaster 360 Installer's Guide
4. PROGRAMMING
4.1 General Guidance
This chapter explains the Installer programming (configuration) options of your PowerMaster 360 system and how to customize its operation to your particular needs and end user requirements. Software configuration of the alarm system is performed using the Virtual Keypad which contains the control keys,
numerical keypad and display. The control panel includes a partition feature. Partitioning allows you to have up to three independently controllable
areas with different user codes assigned to each partition. A partition can be armed or disarmed regardless of the status of the other partitions within the system.
The Soak Test feature allows selected zones to be tested for a pre-defined period of time. When in Soak Test mode, activating a zone does not cause an alarm and siren and strobe are not activated. The zone activation is recorded in the event log and is not reported to the Monitoring Station. The zone remains in Soak Test until the pre-defined period of time for the Soak Test has elapsed without any alarm activation.
The zone then automatically removes itself from
Soak Test mode and returns to normal operating mode. Software Upgrade allows you to upgrade the software of the control panel from the remote PowerManage server.
During software upgrade, the PowerMaster 360 Virtual Keypad display will read "UPGRADING…" which is displayed throughout the software upgrade procedure.
Note: Software Upgrade cannot be performed when the control panel is armed AWAY or there is an AC failure.
Tech Tip
:
For your convenience, we recommend programming the PowerMaster 360 on the work bench before actual installation. Operating power may be obtained from the backup battery or from the AC power supply.
ATTENTION! FIRST SWITCH ON THE CONTROL PANEL and then INSERT BATTERIES INTO ACCESSORIES DEVICES.
The devices "search" for the control panels to which they are enrolled for a period of only 24 hours from the time of battery insertion.
Note: If you have switched on the control panel a long time after inserting batteries into the accessories devices: Open and then close the cover to activate the tamper switch (where applicable), or remove the battery and then put back the battery.
4.1.1 Navigation
The Virtual Keypad's buttons are used for navigation and configuration when programming. The following table provides a detailed description of the function or use of each button.
Button
Definition
Navigation / Setting Function
NEXT
Use to move / scroll forward to the next menu options.
BACK
Use to move / scroll backward to the previous menu options.
OK
Use to select a menu option or to confirm a setting or action.
HOME
Use to move one level up in the menu or to return to previous setting step. AWAY
Use to jump back to the [<OK> TO EXIT] screen to quit programming.
OFF
Use to cancel, delete, clear or erase setting, data, etc. 0 – 9
Numerical keypad used to enter numerical data when needed.
Note: The above buttons are identical in function to the corresponding buttons shown throughout the document.
To review the options within the control panel menus and select an option, repeatedly press the Next
or Back
button until the desired option is displayed (also designated as
in this guide), then press the OK
button to select the desired option (also designated as in this guide). To return to the previous options repeatedly
press the Home button and to exit the programming menu press the Away button.
To simplify the procedure further, you really need two basic buttons to program the entire panel: The Next and the OK button. The button scrolls through the options, and the button selects the option
4. PROGRAMMING
D-305735 PowerMaster 360 Installer's Guide 13
you want.
4. PROGRAMMING
14 D-305735 PowerMaster 360 Installer's Guide
4.1.2 Feedback Sounds
The sounds you will hear via the Configuration device (PC or mobile) while using and configuring the control panel are:
Sound
Definition
Single beep, heard whenever a key is pressed
Double beep, indicates automatic return to the normal operating mode (by timeout).
Three beeps, indicates a trouble event
Happy Tune (- - - –––), indicates successful completion of an operation.
Sad Tune (–––––), indicates a wrong move or rejection
4.2 Entering the "Installer Mode" and Selecting a Menu Option
All Installer Mode menu options are accessed via the "Installer Mode" which is usually one of the main panel menu options.
To enter the "Installer Mode" and select an Installer Mode menu option proceed as follows:
Step 1
Step 2
Step 3
Step 4
Select "INSTALLER MODE" Option
[1]
Enter Installer Code
[2]
Select Installer Mode menu option
[3]
See
See
READY 00:00
01:INSTALL CODES
4.3
08:USER SETTINGS
4.9
Go to
the
indicated
section
of the
selected
option
02:ZONES/DEVICES
4.4
09:FACTORY DEFLT
4.10
INSTALLER MODE
ENTER CODE:
03:CONTROL PANEL
4.5
10:SERIAL NUMBER
4.11
If the "Installer
Mode" is not shown, refer to section 4.2.1
04:COMMUNICATION
4.6
12:PARTITIONING
4.12
06:CUSTOM NAMES
4.7
13:OPERATION MOD
4.13
07:DIAGNOSTICS
4.8
<OK> TO EXIT
- Entering the "Installer Mode" menu
[1]
You can access the "Installer Mode" only when the system is disarmed. The process described refers to the
case where "User permit" is not required. If "User permit" is required, select the "User Settings" option and ask the Master User to enter his code and then scroll the "User Settings" menu and select the "Installer Mode"
option (last option in the menu). Continue to Step 2.
[2]
If you have not already changed your Installer code number, use the default settings: 8888 for installer & 9999 for
master installer. If you enter an invalid installer code 5 times, the keypad will be automatically disabled for a pre-defined period of
time and the message WRONG PASSWORD will be displayed.
[3]
You have now entered the Installer Mode menu. Scroll and select the menu you wish and continue to its corresponding section in the guide (indicated on the right side of each option).
4.2.1 Entering the "Installer Mode" if "User Permit" is enabled
In certain countries the regulations may require user permission to make changes in the configuration of the panel. To comply with these regulations, the "Installer Mode"
option can be accesses only via the "User Settings" menu. The
Master user must first enter the "User Settings" menu then scroll until the "Installer Mode" option is shown and then the installer can continue as shown in the above table (see also
[1] in Step 1 above).
To configure the panel to comply with user permission requirements - see option #91 "User Permit" in section 4.5.8.
4. PROGRAMMING
D-305735 PowerMaster 360 Installer's Guide 15
4.2.2 Selecting options
– Selecting an option from a menu
Example: To Select an Option from the "COMMUNICATION" menu:
[1]
Enter the Installer Mode menu and select the "04.COMMUNICATION" option (see section 4.2).
[2]
Select the sub-menu option you need, for example: "3: C.S. REPORTING".
[3]
Select the parameter you wish to configure for example: "11:RCVR 1 ACCOUNT"
[4] To continue, go to the section of the selected sub-menu option, for example section 4.6.3 for the
"3:C.S.REPORTING" menu, and look for the sub-menu you wish to configure (e.g. "11:RCVR 1 ACCOUNT"). After
configuring the selected parameter the display returns to step 3.
To Change the Configuration of the Selected Option:
When entering the selected option, the display shows the default (or the previously selected) setting marked with .
To change the configuration, scroll the "Options" menu and select the setting you wish and press to
confirm. When done, the display reverts to Step 3.
4.2.3 Exiting the Installer Mode
To exit the Installer Mode, proceed as follows:
Step 1
Step 2
Step 3
[1] [2] [3]
Any screen
or
<OK> TO EXIT
READY 12:00
– Exiting the Installer Mode
[1]
To exit "INSTALLER MODE", move up the menu by pressing the button repeatedly until the display reads "<OK> TO EXIT" or preferably; press the button once which brings you immediately to the exit
screen "<OK> TO EXIT".
[2]
When the display reads "<OK> TO EXIT", press .
[3]
The system exits the “INSTALLER MODE" menu and returns to the normal disarm state while showing the READY display.
4.3 Setting Installer Codes
The PowerMaster 360 system provides two installer permission levels with separate installer codes, as follows:
Master Installer: The "Master Installer" is authorized to access all Installer Mode menu and sub-menu options. The
default code is: 9999 (*).
Installer: The "Installer" is authorized to access most but not all Installer Mode menu and sub-menu options. The
default code is 8888 (*).
Guard Code: Enables an authorized guard to only Arm Away / Disarm the control panel. The default code is 0000 (*).
The following actions can be performed only by using the Master Installer code:
Changing the Master Installer code.
Defining specific communication parameters – see "3:C.S REPORTING" in sections 4.6.2 and 4.6.3.
Resetting the PowerMaster 360 parameters to the default parameters – see "09:FACTORY DEFLT" in section
4.11.
Note: Not every system includes a Master Installer code feature. In such systems, the Installer can access all Installer Mode menu and sub-menu options the same as a Master Installer.
(*) You are expected to use the default codes only once for gaining initial access, and replace it with a secret
code known only to yourself.
4. PROGRAMMING
16 D-305735 PowerMaster 360 Installer's Guide
To change your Master Installer or Installer Codes proceed as follows:
Step 1
Step 2
Step 3
Step 4
Select "01:INSTALL
CODES" Option
[1]
Select Master Installer,
Installer code or Guard
code
[2]
Enter NEW Master Installer, Installer code or Guard code
[3]
INSTALLER MODE
NEW MASTER CODE
MASTER CODE 999
to step 2
to step 2
ENTER CODE:
or
or
NEW INST. CODE
INST. CODE 888
or
or
01:INSTALL CODES
NEW GUARD CODE
GUARD CODE 000
to step 2
– Setting Installer Codes
[1]
Enter the Installer Mode menu and select the "01:INSTALL CODES" option (see section 4.2).
[2]
Select the "NEW MASTER CODE", "NEW INST. CODE" or "NEW GUARD CODE". Some panels may have only the Installer Code and New Guard Code option.
[3]
Enter the new 4-digit Code at the position of the blinking cursor and then press .
Notes:
1. Code "0000" is not valid for Master Installer or installer.
2. Inserting “0000” for the Installer will delete the Installer Code.
3. Warning! Always use different codes for the Master Installer, for the Installer and for the Users. If the Master Installer Code is identical to the Installer code, the panel will not be able to recognize the Master Installer. In such a case, you must change the Installer code to a different code. This will re-validate
the Master Installer code.
4.3.1 Identical Installer and Master Installer Codes
In a 2-installer code system, the non-master installer may inadvertently change his Installer Code to that of the Master Installer Code. In this case, the panel will allow the change in order to prevent the non-master installer from realizing the discovery of the Master Installer's Code. The next time the Master Installer enters the Installer Mode the Master Installer will be considered as an Installer and not as a Master Installer. In such a case the Master Installer should use one of the following solutions:
(a) Access the panel using the Remote Programmer PC software application and change the Master Installer Code to
a different code than the one programmed by the Installer.
(b) 1. Change the Installer Code to a temporary code, 2. exit the Installer Mode, 3. enter the Installer Mode again using
the Master Installer code (the Master Installer Code will now be accepted), 4. change the Master Installer code to a different code, 5. and change the NON-Master Installer Code back again (in other words, undo the change to the temporary code) so that the NON-Master Installer can still enter the system.
4.4 Zones / Devices
4.4.1 General Guidance & Zones/Devices Menu Options
The ZONES/DEVICES menu enables you to add new devices to the system, to configure them and to delete them, if required.
To select an option follow the instructions below. Additional details and guidance are provided in section 4.2.
INSTALLER MODE
02:ZONES/DEVICES
MENU you wish
indicates scroll
and select
Option
Use
Section
ADD NEW DEVICES
Use to enroll and configure the device's operation according to your preference
and in case of sensors to also define their zone name (location), zone type and
chime operation.
4.4.2
DELETE DEVICES
Use to delete devices from the system and to reset their configuration.
4.4.3
MODIFY DEVICES
Use to review and/or change the device's configuration.
4.4.4
REPLACE DEVICES
Use to replace faulty devices with automatic configuration of the new device.
4.4.5
ADD TO SOAK TEST
Use to enable the Soak Test for device zones.
4.4.6
DEFINE DEFAULTS
Use to customize the defaults of the device's parameters according to your personal preferences for each new device enrolled in the system.
4.4.7
4. PROGRAMMING
D-305735 PowerMaster 360 Installer's Guide 17
4.4.2 Adding New Wireless Devices Part A - Enrollment
To enroll and configure a device, follow the instructions in the following chart
Step 1
Step 2
Step 3
Step 4
Select "ADD NEW DEVICE" Option
[1]
Enroll the device or Enter the device ID
[2]
Select a Zone number
[3]
Configure zone & device Parameters
[4]
 
ADD NEW DEVICE
ENROLL NOW or
ENTR ID:XXX-XXXX
Z01:Motion Sens
ID No. 120-1254
Continue to the 2
nd
diagram in Part B below
Press the enrollment button or enter the device
ID. Refer to the detailed
instructions below
Z10:Motion Sens
ID No. 120-1254
- Adding New Devices
[1]
Enter "INSTALLER MODE", select "02:ZONES DEVICES" (see section 4.2) and then select "ADD NEW DEVICE".
Because of encryption, PowerG devices (including Keyfobs) cannot be used on more than one system at one time. Remember to verify panel and device compatibility.
[2]
See enrollment by button or device ID below. If enrollment is successful, the display reads "DEVICE ENROLLED" (or "ID ACCEPTED") and then shows the device details - see [3]. However, if the enrollment fails, the display will advise you the reason for failure, for example: "ALREADY ENROLLED" or "NO FREE LOCATION". If the enrolled device is adapted to operate as another device that the panel recognizes, the display then reads
ADAPTED TO <OK>”.
[3]
The display shows the device details and the first available free Zone number for example: "Z01:Motion
Sensor > ID No. 120-1254" (or "K01:Keyfob / S01:Siren etc. depending on the type of the enrolled device). Detectors can be enrolled in any zone number. To change the zone number, click the button or type in
the zone number, and then press to confirm.
[4]
Continue to Part B to configure the device – see diagram below
How to check Panel  Device compatibility
Each PowerG device bears a 7-character Customer ID printed on the device sticker in the format: FFF-M:DDD, (for example, 868-0:012) where FFF is the frequency band and M:DDD is the variant code.
For PowerG system devices compatibility, make sure the frequency band (FFF) and the variant code (M) of the devices match. The DDD can be ignored if the panel displays “ANY” for DDD.
Enrollment by using Device ID
The 7-digit Device ID can be used to register a device into the panel locally or from a remote location using the Remote Programmer PC software. The enrollment by device ID is a 2 stage procedure.
In the 1
st
stage you register the devices' ID numbers into the panel and complete the device configuration. This can be
done from a remote location using the Remote Programmer PC software. Following the 1
st
stage, the PowerMaster
360 panel waits for the device to appear on the network in order to complete the enrollment. In the 2
nd
stage, the enrollment is completed when the panel is in full working mode by inserting the battery into the device, or by pressing the tamper or enrollment button on the device. This procedure is very useful for adding devices to existing systems without the need to provide technicians with the Installer Code, or to allow access to the programming menus.
Remember! The system will indicate a "NOT NETWORKD" trouble until the 2nd stage of all registered devices is completed. Note: The Soak Test on pre-enrolled zones can be activated only when the zone is fully enrolled.
Enrollment by using the Enrollment button
The panel is set to the Enrollment mode (step #2 above) and the device is enrolled using the Enroll button (refer to the device information in the device Installation Instructions, then open the device and identify the Enroll button). For keyfobs and keypads, use the AU X '' button. For gas detectors, insert the battery.
Press the enroll button for 2-5 seconds until the LED lights steadily and then release the button. The LED will extinguish or may blink for a few more seconds until the enrollment is completed. If enrollment is successfully
4. PROGRAMMING
18 D-305735 PowerMaster 360 Installer's Guide
completed, the PowerMaster 360 sounds the "Happy Tune" and the Virtual Keypad momentarily shows "DEVICE ENROLLED" and then reads the device details.
4. PROGRAMMING
D-305735 PowerMaster 360 Installer's Guide 19
Part B - Configuration
Step 1
Step 2
Step 3
Step 4
Enter Location Menu
[1]
Select Location
(see list below)
[2]
Enter Zone Type
[3]
Select Zone Type
(see list below)
[4]
Z10:LOCATION
Dining room
Custom 5
Z10:ZONE TYPE
1:Exit/Entry1
5. Interior
Step 5
Step 6
Step 7
Step 8
Enter Chime Menu
[5]
Select Chime option
[6]
Enter Partitions Menu
[7]
Select Partition options
[8]
Z10:SET CHIME
chime OFF
melody-chime
Z10:PARTITIONS
Z10:P1
P2 P3
Step 9
Step 10
Step 11
Enter Device Settings
Menu
[9]
Configure Device
Parameters
[10]
Continue or End
Z10:DEV SETTINGS
Refer to device datasheet in the device Installation Instructions for specific configuration instructions.
To continue – See  [11]
- Configuring New Devices
Location (name) setting:
[1]
To review or change the Location (name) setting, press the button, otherwise scroll to the next option.
[2]
To change the Location name, enter the menu and select the name from the "Location List" below. You can
assign additional custom names using the "06.CUSTOM NAMES" option in the Installer Mode menu. See
section 4.7.
Note: As a shortcut, press the 2 digit serial No. of the Custom Location, which takes you directly to its menu.
Zone Type setting:
[3]
To review or change the Zone Type setting, press the button, otherwise scroll to the next option.
[4]
The zone type determines how the system handles signals sent from the device. Press and select a
suitable zone type. The list of available Zone Types and the explanation for each zone type is provided below.
Note: As a shortcut, press the 2 digit serial No. of the Zone Type shown in the Location List below, which takes you directly to its menu.
Chime setting:
[5]
All zones are set to chime OFF by default. To configure the device to cause the panel to sound (when disarmed) a
Chime melody when tripped, press the button, otherwise scroll to the next option.
[6]
Select between "Chime OFF", "melody-chime" and "zone name-chime". In "melody chime" the control
panel sounds a chime melody when the sensor is tripped. In "zone name-chime" the control panel sounds the
zone name when the sensor is tripped. The chime operates during the Disarm mode only.
Partitions setting:
Note: The "PARTITIONS" menu appears only if Partitions is enabled in the control panel (see section 4.12).
[7]
When entering the menu, the display shows the default Partition selection (marked with ).
[8]
Use the keypad keys , , to assign partitions to the device.
Device Configuration:
[9]
To review or change the Device Configuration (settings), press the button, otherwise scroll to the next
option – see  [11].
[10]
To configure the device parameters, refer to its corresponding device datasheet in the device Installation Instructions. The defaults of the device parameters can be also configured as explained in section 4.4.7.
[11]
After completing the configuration of the device, the wizard brings you to the "Next Step" menu with the following 3 options:
4. PROGRAMMING
20 D-305735 PowerMaster 360 Installer's Guide
- Configuring New Devices
"NEXT Device" to enroll the next device.
"MODIFY Same Dev." reverts to Step 1 (i.e. "LOCATION") to allow you to perform additional changes to the device, if needed. "EXIT Enrollment" exits the enrollment procedure and returns to Step 1 bringing you back to the "ADD NEW
DEVICES" menu.
Location List
No.
Location Name
No.
Location Name
No.
Location Name
No.
Location Name
01
Attic
09
Dining Room
17
Hall 25
Utility Room*
02
Back door
10
Downstairs
18
Kitchen*
26
Yard
03
Basement
11
Emergency
19
Laundry Room*
27
Custom1
04
Bathroom
12
Fire
20
Living Room*
28
Custom2
05
Bedroom
13
Front Door
21
Master Bath
*
29
Custom3
06
Child room
14
Garage
22
Master Bedr
30
Custom4
07
Closet
15
Garage Door
23
Office
31
Custom5
08
Den
16
Guest Room
24
Upstairs
Can be customized by “06:CUSTOM NAMES” menu (see section 4.7)
Zone Type List
No.
Zone Type
Description
1. Exit/Entry 1 This Zone starts the exit time when the user arms the system or the entry time when the system is armed. To configure the Exit/Entry 1 time, see sections 4.5.1 & 4.5.2 - Installer
Mode menu "03.CONTROL PANEL" options 01 and 03. ()
2.
Exit/Entry 2
Same as Exit / Entry 1 but with a different delay time. Used sometimes for entrances closer to
the panel. For configuring the Exit and Entry 2 delays, see sections 4.5.1 & 4.5.2 –
Installer Mode menu "03.CONTROL PANEL" options 02 and 03. ()
3.
Home Delay
Used for Door/Window Contacts and Motion sensors protecting entrance doors to interior
living areas where you wish to move feely when the system is armed HOME. Functions as a "Delayed" zone when the system is armed HOME and as a "Perimeter Follower" zone when
the system is armed AWAY.
4. Inter-Follow
Similar to "Interior" zone but temporarily ignored by the alarm system during entry/exit delay periods. Usually used for sensors protecting the route between the entrance door and the panel.
5. Interior
This zone type generates an alarm only when the system is armed AWAY but not when the system is armed HOME. Used for sensors, installed in interior areas of the premises, that
need to be protected when people are not present inside the premises.
6. Perimeter
This zone type generates an alarm when the system is armed both in AWAY and HOME modes. Used for all sensors protecting the perimeter of the premises.
7.
Perim–Follow
Similar to "Perimeter" zone, but is temporarily ignored by the alarm system during entry/exit
delay periods. Usually used for sensors protecting the route between the entrance door and
the control panel.
8. 24h silent
This zone type is active 24 hours, even when system is DISARMED. It is used to report alarm
events from sensors or manually activated buttons to the Monitoring Station or private
telephones (as programmed) without activating the sirens.
9.
24h audible
Similar to 24hr silent zone, but also provides an audible siren alarm.
Note: This zone type is used only for burglary applications.
10. Emergency
This zone type is active 24 hours, even when the system is DISARMED. It is used to report
an emergency event and to initiate an Emergency call to the Monitoring Stations or private
telephones (as programmed).
11.
Arming Key
An Arming key zone is used to control the arming and disarming of the system.
Note: Operates with the magnetic contact device, magnetic contact device with auxiliary input
and vanishing magnetic contact device.
12.
Non-Alarm
This zone does not create an alarm and is often used for non-alarm applications. For example, a detector used only for sounding a chime.
13.
Fire
A Fire zone is used for connecting the MC-302E (magnetic contact with hard-wired input) to a wired smoke detector.
17.
Guard keybox
A Guard keybox zone is usually connected to a metal safe containing the physical keys
needed to enter the building. Following an alarm, the safe becomes available to a trusted
Guard who can open the Guard keybox, obtain the keys and enter the secured premises. The
4. PROGRAMMING
D-305735 PowerMaster 360 Installer's Guide 21
No.
Zone Type
Description
Guard keybox zone acts just like a 24H audible zone. The Guard keybox zone also provides
automatic audible internal and external siren alarm that is immediately reported to the Monitoring Station (and does not depend on the Abort Time).
Notes:
1. Opening/closing the Guard keybox causes the PowerMaster 360 to signal the Monitoring
Station.
2. Operates with the magnetic contact device with auxiliary input.
18
Outdoor
A zone for outdoor areas where an activated alarm does not indicate intrusion into the house.
Note: The PIR camera / Outdoor PIR camera detector cannot be set to Outdoor Zone Type.
()
These Zone types are useful mainly when you arm and disarm the system from inside the protected premises. If
you arm and disarm the system from outside (without tripping any sensor), such as using a keyfob, it is
preferred to use the other Zone Types.
4.4.3 Deleting a Device
Step 1
Step 2
Step 3
Step 4
Step 5
Select "DELETE DEVICES" Option
[1] Select the respective
device Group
[2] Select exact device
you wish to delete
[3]
To delete the device:
press the key
[4]
02:ZONES DEVICES
CONTACT SENSORS
DELETE DEVICES
MOTION SENSORS
Z01:Motion Sens
ID No. 120-1254
<OFF> to delete
to
step 2
– Deleting a Device
[1]
Enter the Installer Mode Menu, select the "02.ZONES/DEVICES" option (see section 4.2) and then select the "DELETE DEVICES" option.
[2]
Select the respective group of the device you wish to delete. For example, "MOTION SENSORS".
[3]
Scroll the Device Group, identify (by zone and/or ID number) the exact device you wish to replace, for example: "Z01: Motion Sensor > ID No. 120-1254" and press the button.
[4] The display prompts you "<OFF> to delete". To delete the device, press the (OFF) button.
4.4.4 Modifying or Reviewing a Device
To Modify or Review the device parameters proceed as follows:
Step 1
Step 2
Step 3
Step 4
Step 5
Select "MODIFY
DEVICES" Option
[1] Select the respective
device Group
[2] Select exact device
you wish to modify
[3] Select the Parameter
you wish to modify
[4] Modify the
Parameter
02:ZONES DEVICES
CONTACT SENSORS
MODIFY SENSORS
MOTION SENSORS
Z10:Motion Camra
ID No. 140-1737
Z10:LOCATION Z10:ZONE TYPE Z10:SET CHIME Z10:PARTITIONS
Z10:DEV SETTINGS
See  [4] When done
to
step 2
– Modifying or Reviewing a Device
[1]
Enter the Installer Mode menu, select the "02:ZONES/DEVICES" option (see section 4.2) and then select the
"MODIFY DEVICES" option.
[2]
Select the respective group of the device you wish to review or modify. For example, "MOTION SENSORS".
[3] Scroll the Device Group, identify (by zone and/or ID number) of the exact device you wish to modify or review, for
example: "Z10:Motion Camra > ID No. 140-1737".
[4] From here on the process is same as the configuration process that follows the enrollment of that device. To
continue, refer to Section 4.4.2 "Adding a New Wireless Device" Part B. When done, the display will show the
next device of the same type (i.e. "Motion camera").
4. PROGRAMMING
22 D-305735 PowerMaster 360 Installer's Guide
4.4.5 Replacing a Device
Use this option to replace a faulty device that is enrolled in the system with another device of the same type number (i.e. same first 3 digit of the ID number – see section 4.4.2.A) while keeping the same configuration of the original device. There is no need to delete the faulty device or to reconfigure the new device. Once enrolled, the new device will be configured automatically to the same configuration of the faulty (replaced) device.
To Replace, a device proceed as follows:
Step 1
Step 2
Step 3
Step 4
Step 5
Select "REPLACE
DEVICES" Option
[1] Select the respective
device Group
[2] Select exact device
you wish to replace
[3] Enroll the new device [4]
02:ZONES/DEVICES
CONTACT SENSORS
 
REPLACE DEVICES
KEYFOBS
K03:Keyfob
ID No. 300-0307
ENROLL NOW or
ENTR ID:300-XXXX
See 
[4].
– Replacing a Device
[1]
Enter the Installer Mode menu, select the "02:ZONES/DEVICES" option (see section 4.2) and then select the "REPLACE DEVICES" option.
[2]
Select the respective group of the device you wish to replace. For example, "KEYFOBS".
[3]
Scroll the Device Group, identify (by zone and/or ID number) the exact device you wish to replace, for example: "K03: Keyfob > ID No. 300-0307".
If you try enrolling a new device of a different type than the replaced device, the PowerMaster 360 will reject the
new device and the Virtual Keypad display will read "WRONG DEV.TYPE".
When done, the Virtual Keypad display shows the device details of the new device.
4.4.6 Configuring Soak Test Mode
This option enables you to enter device zones into Soak Test mode. To Enable the Soak Test proceed as follows:
Step 1
Step 2
Step 3
Step 4
Step 5
Select "ADD TO SOAK TEST" Option
[1] Select the respective
device Group
[2] Select device zone
number
[3] Select to enable or
disable the Soak Test
[4] [5]
02:ZONES/DEVICES
CONTACT SENSORS
Z09:Motion Sens
ID No. 120-2468
 
ADD TO SOAK TEST
MOTION SENSORS
Disable test 
Enable test
See 
[5]
to
Step 3
– Enabling Soak Test mode
[1]
Enter the Installer Mode menu, select the "02.ZONES/DEVICES" option (see section 4.2) and then select the "ADD TO SOAK TEST" option.
[2]
Select the respective Group of the device you wish to add the Soak Test. For example, "MOTION SENSORS".
[3]
Scroll to select the specific device zone number.
[4]
Select between “Disable test” (default) or “Enable test”.
[5]
If set to “Enable Test” you must set the duration of the Soak Test before the Soak Test will start (see section
4.5.8). You can stop the test for the relevant zone by changing the setting to "Disable test" at any time during the testing period. All Soak test zones will be reset to start a new test upon occurrence of one of the following:
1) Power up of the system; 2) Setup of Factory Default; 3) Change in system Soak Time.
4. PROGRAMMING
D-305735 PowerMaster 360 Installer's Guide 23
4.4.7 Defining Configuration Defaults for "Device Settings"
PowerMaster 360 enables you to define the Default Parameters used during enrollment and to change them whenever you wish so that new devices enrolled into the system will be configured automatically with these default parameters without the need to modify the configuration of each new enrolled device. You can use a certain set of defaults for certain group of devices and then change the defaults for another group.
IMPORTANT! Devices that were already enrolled in the PowerMaster 360 system before the defaults have been changed will not be affected by the new default settings.
To Define the Default parameters of a device Group proceed as follows:
Step 1
Step 2
Step 3
Step 4
Step 5
Select "DEFINE
DEFAULTS" Option
[1] Select the respective
device Group
[2] Select the Default
Parameter
[3] Select the new
Default Setting
[4] [5]
02:ZONES/DEVICES
CONTACT SENSORS
 
DEFINE DEFAULTS
MOTION SENSORS
Alarm LED
Event Counter Disarm Activity
Low 
High
See 
[5]
to
Step 3
– Changing Defaults
[1]
Enter the Installer Mode menu, select the "02.ZONES/DEVICES" option (see section 4.2) and then select the "DEFINE DEFAULTS" option.
[2]
Select the respective Group of the device you wish to define its defaults. For example, "MOTION SENSORS".
[3]
Scroll the parameter list of the Device Group and select the Default Parameter you wish to change, for example:
"Event Counter". The list combines the parameters of all devices in the group, for example, the parameters of all
types of Motion sensors.
[4]
In the example, the existing default setting of the "Event Counter" for enrolled motion sensors was
"Low Sensitivity" (marked with ) . To change it to "High", scroll the menu until the display shows "High" and press the button. The new default for the Event Counter parameter setting of Motion Sensors enrolled
from now on will be "High".
[5]
The new default does not affect motions sensors that were already enrolled before the change was made but only new motion sensors that will be enrolled in the PowerMaster 360 after the change is performed.
4.4.8 Updating Devices after Exiting Installer Mode
When exiting the "Installer mode", the PowerMaster 360 panel communicates with all devices in the system and updates them with the changes that have been performed in their "Device Settings" configuration. During the updating period, the display indicates "DEV UPDATING 018" where the number (for example, 018) is a countdown of the remaining number of devices yet to be updated.
4. PROGRAMMING
24 D-305735 PowerMaster 360 Installer's Guide
4.5 Control Panel
4.5.1 General Guidance – "Control Panel" Flow-Chart & Menu Options
The "CONTROL PANEL" menu enables you to configure and customize the operation of the control panel. The "CONTROL PANEL" menu provides you with configurable parameters divided into several groups, each dealing with certain aspects of the system operations as follows (see detailed list in Step 2 of the chart below):
Group
Description of Group Features and Parameters
Section
Arming/Disarming
and Exit/Entry
Procedures
Contains configurable features and parameters related to Arming and Disarming of the system and the Exit and Entry procedures.
4.5.2
Zone Behavior
Contains configurable features and parameters related to the functionality of the Zones.
4.5.3
Alarms & Troubles
Contains configurable features and parameters related to initiating, canceling and
reporting of Alarm and Trouble events.
4.5.4
Sirens
Contains configurable features and parameters common to all sirens in the system.
4.5.5
User Interface
Contains configurable features and parameters related to the functionality of the panel's
audible and visual indications.
4.5.6
Jamming &
Supervision
Contains configurable features and parameters related to detecting and reporting of RF
Jamming and device Supervision (missing device) events.
4.5.7
Miscellaneous
Contains a variety of other configurable features and parameters related to the system.
4.5.8
To enter the "03.CONTROL PANEL" menu and to select and configure an option, proceed as follows:
Step 1 Step 2 Step 3
Select "CONTROL PANEL"
option
Select the "Control Panel" Parameter you wish to configure
Configure option
See
See
See
INSTALLER MODE
4.5.2
4.5.4
4.5.6
03.CONTROL PANEL
01:ENTRY DELAY1
31:PANIC ALARM
53:MEMORY PROMPT
Go to the indicated group section of the selected option
02:ENTRY DELAY2
32:DURESS ALARM
54:LOW-BAT ACK
03:EXIT DELAY
33:INACTIVE ALRT
56:SCREEN SAVER
04:EXIT MODE
34:TAMPER ALARM
05:QUICK ARM
35:AC FAIL REPRT
06:BYPASS ARM
36:CONFIRM ALARM
07:LATCHKEY ARM
37:ABORT TIME
08:DISARM OPTION
38:CANCEL ALARM
09:ARMING KEY
39:ALARM RESET
40:ABORT FIRE T.
4.5.3
4.5.5
4.5.7
21:SWINGER STOP
61:JAM DETECT
When done
to
Step 2
22:CROSS ZONING
44:SIREN TIME
62:MISSING REPRT
45:STROBE TIME
63:NOT READY
64:MISS/JAM ALRM
65:SMOK FAST MIS
4.5.8
91:USER PERMIT
93:SOAK PERIOD
Arming &
Disarming
Alarms &
Troubles
User
Interface
Zone
Behavior
Sirens
Jamming and
Supervision
Miscellaneous
4. PROGRAMMING
D-305735 PowerMaster 360 Installer's Guide 25
4.5.2 Configuring Arming/Disarming and Exit/Entry Procedures
The following table provides you with a detailed description of each option and its configuration settings. To select an option and change its configuration – refer to section 4.5.1.
Option
Configuration Instructions
01:ENTRY DELAY1 02:ENTRY DELAY2
Two different entry delays allow the user to enter the protected site (while the system is in the armed state) via dedicated exit/entry doors and routes without causing an alarm.
Following entry, the user must disarm the control panel before the entry delay expires. Slow­rate warning beeps start sounding via the Configuration device (PC or mobile) once the door is opened, until the last 10 seconds of the delay, during which the beeping rate increases. The "ENTRY DELAY 1" and "ENTRY DELAY 2" options allow you to program the time length of
these delays.
Options: 00 seconds; 15 seconds (default for entry delay 2); 30 seconds (default for entry delay 1); 45 seconds; 60 seconds; 3 minutes and 4 minutes.
Notes:
1. In some PowerMaster 360 variants, these menus are displayed in the Operation
Mode only (see section 4.13).
2. To comply with EN requirements, the entry delay must not exceed 45 sec.
03:EXIT DELAY
This option allows programming the time length of the exit delay. An exit delay allows the user to arm the system and leave the protected site via specific routes and exit/entry doors without causing an alarm. Slow-rate warning beeps start sounding via the Configuration device (PC or mobile) once the arming command has been given, until the last 10 seconds of the delay,
during which the beeping rate increases.
Options: 30 seconds; 60 seconds (default); 90 seconds; 120 seconds, 3 minutes and
4 minutes.
04:EXIT MODE
The "Exit Delay" time can be further adjusted according to your preferred exit route. The control panel provides you with the following "Exit Mode" options:
A: "normal" - The exit delay is exactly as defined. B: “restrt+arm home” - Exit delay restarts when the door is reopened during exit delay. If no
door was opened during exit delay "AWAY", the control panel will be armed "HOME".
C: "restart>reentry" - The exit delay restarts when the door is reopened during exit delay. The
restart occurs once only. Restarting the exit delay is helpful if the user re-enters immediately after going out to retrieve an item that he left behind.
D: "end by exit" - The exit delay expires (ends) automatically when the exit door is closed
even if the defined exit delay time was not completed.
Options: normal (default); restrt+arm home; restart>reentry and end by exit.
Note: In some PowerMaster 360 variants, this menu is displayed in the Operation Mode only
(see section 4.13).
05:QUICK ARM
Define whether or not the user will be allowed to perform quick arming or not. Once quick
arming is permitted, the control panel does not request a user code before it arms the system.
Options: OFF (default) and ON (default in USA).
06:BYPASS ARM
Define whether or not the user will be allowed to manually bypass individual zones, or allow
the system to perform automatic bypassing of open zones during the exit delay (i.e. "force arm"). If a zone is open and "forced arming" is not permitted, the system cannot be armed and “NOT READY” is displayed. If "no bypass" is selected, neither manual bypassing
nor force arming is allowed which means that all zones must be secured before arming.
Options: no bypass (default); force arm and manual bypass (default in USA).
Notes:
1. To comply with EN requirements, "manual bypass" must be selected.
2. The option "force arm" is not applicable in the UK.
3. A zone in Soak Test mode that is configured as bypass will trigger a test fail event if the system detects a potential alarm event.
4. There is no limit of reported events when a bypass zone is in Soak Test mode.
07:LATCHKEY ARM
When "ON", a “latchkey” message will be reported by SMS message to users (see Note) upon
disarming by a “latchkey user” (users 5-8 or keyfob transmitters 5-8). This mode is useful when
parents at work want to be informed of a child’s return from school.
Options: OFF (default) and ON.
Note: To enable the reporting, you must configure the system to report "alrt" events to Private
users (Latchkey belongs to the "alerts" group of events). Refer to section 4.6.4 "REPORTED
EVENTS" option in both "
VOICE REPORT
" & "
SMS REPORT
" menus.
4. PROGRAMMING
26 D-305735 PowerMaster 360 Installer's Guide
Option
Configuration Instructions
08:DISARM OPTION
Certain regulations require that when the system is armed in AWAY mode, it may not be
disarmed from the outside of the house (such as by keyfobs) before entering the protected premises and activating an "Entry Delay" zone. To answer this requirement, the PowerMaster 360 provides you with the following configurable options to disarm the system:
A: At "any time" (default), the system can be disarmed at all times from all devices. B: During entry delay, the system can be disarmed only using keyfob or prox operated devices
("on entry wrless").
C: During entry delay by code, the system can be disarmed only using the Configuration device
(PC or mobile) ("entry + away kp.").
D: During entry delay, the system can be disarmed using keyfobs or by code using the
Configuration device (PC or mobile) ("on entry all.").
Note:
In some PowerMaster 360 variants, this menu is displayed in the Operation Mode only
(see section 4.13).
09:ARMING KEY
Determine that, when activated, the Arming Key will arm AWAY or HOME.
Options: arm AW AY (default) and arm HOME.
4.5.3 Configuring Zones Functionality
The following table provides you with a detailed description of each option and its configuration settings. To select an
option and change its configuration – refer to section 4.5.1.
Option Configuration Instructions
21:SWINGER STOP
Define the number of times a zone is allowed to initiate an alarm within a single arming/disarming period (including tamper & power failure events of detectors, etc.). If the number of alarms from a specific zone exceeds the programmed number, the control panel automatically bypasses the zone to prevent recurrent siren noise and excessive reporting to the Monitoring Station. The zone will be reactivated upon disarming, or 8 hours after having been bypassed (if the system remains armed).
Options:
after 1 alarm
(default);
after 2 alarms
(default in USA);
after 3 alarms
and
no stop
.
Note:
When a detector is in Soak Test1 mode and also set to bypass, Swinger Stop will not
prevent the sending of events. This may result in excessive reporting of Soak Fail events.
22:CROSS ZONING
Define whether cross zoning will be active "ON" or inactive "OFF" (default). Cross zoning is a method used to counteract false alarms - an alarm will be initiated only when two adjacent zones (zone couples) are violated within a 30-second time window. This feature is active only when the system is armed AWAY and only with respect to the following zone couples: 10+11, 12+13, 14+15.
Notes:
1. If one of the two crossed zones is bypassed (see Section 4.5.2), the remaining
zone will function independently.
2. It is recommended that crossed zones will be only zones used for detection of burglary i.e. "Zone Types": Entry/ Exit, Interior, Perimeter and Perimeter follower.
3.
If a cross zone is in Soak Test mode, then each zone of this zone couple functions
independently.
Important! Do not define "cross zoning" to any other zone types such as Fire,
Emergency, 24h audible, 24h silent etc.
4. PROGRAMMING
D-305735 PowerMaster 360 Installer's Guide 27
4.5.4 Configuring Alarms & Troubles
The following table provides you with a detailed description of each option and its configuration settings. To select an option and change its configuration – refer to section 4.5.1.
Option Configuration Instructions
31:PANIC ALARM
Define whether or not the user will be allowed to initiate a Panic Alarm from keypads (by simultaneous pressing the two "Panic Buttons") or keyfobs (by simultaneous pressing the "Away" + "Home" buttons) and whether the alarm will be "silent" (i.e. only reporting of the event) or also audible (i.e. the sirens will also sound).
Options: audible (default); silent and disabled.
32:DURESS ALARM
(not applicable in UK)
A duress (ambush) alarm message can be sent to the Monitoring Station if the user is forced to disarm the system under violence or menace. To initiate a duress message, the user must disarm the system using a duress code (2580 by default).
To change the code, enter the new 4-digit of the new Duress code at the position of the blinking cursor or enter 0000 to disable the duress function and then press .
Notes: The system does not allow programming a duress code identical to an existing user code.
33:INACTIVE ALRT
Previously known as "NOT ACTIVE"
If no sensor detects movement in interior zones at least once within the defined time window, an “inactive alert" event is initiated.
Define the
time window
for monitoring the
lack of motion
.
Options:
disabled
(default);
after: 3/6/12/24/48/72 hours
34:TAMPER ALARM
Define whether the Tamper switch protection of all zones and other peripheral devices (except the control panel) are "active" (default) or "not active".
Warning!: If you select "
not active
", be aware that no alarm or report will be initiated in case
of tampering with any of the system peripheral devices.
35:AC FAIL REPRT
To avoid nuisance reporting in case of short interruptions in the house of AC power, the system reports an AC Fail message only if the AC power does not resume within a pre­determined time delay.
Options:
after 5 minute
(default)
, after 30 minute, after 60 minute or after 3 hours.
Note:To comply with EN requirements, the time delay must not exceed 60 min.
36:CONFIRM ALARM
Previously known as "CONFIRM TIME"
If two successive alarm events occur within a specific time window, the system can be
configured to report the second alarm event as a "confirmed alarm" (see section 4.6.3 option
61). You can activate this feature and set the respective time window.
Options: disable (default in USA); in 30/45/60 (default)/90 minutes
Note: In some PowerMaster 360 variants, this menu is displayed in the Operation Mode only (see section 4.13).
37:ABORT TIME
The PowerMaster 360 can be configured to provide a delay before reporting an alarm to the Monitoring Station (not applicable to alarms from 24H SILENT and EMERGENCY zones). During this delay period, the siren sounds but the alarm is not reported. If the user disarms the system within the delay time, the alarm is aborted. You can activate the feature and select the "Abort Time" interval.
Options: in 00 (default in USA)/15/30 (default)/45/60 seconds; in 2/3/4 minutes
Note: In some PowerMaster 360 variants, this menu is displayed in the Operation Mode only
(see section 4.13).
38:CANCEL ALARM
Previously known as "ALARM CANCEL"
The PowerMaster 360 can be configured to provide a ”Cancel Alarm” time window that starts
upon reporting an alarm to the Monitoring Station. If the user disarms the system within that "cancel alarm" time, a “cancel alarm” message is sent to the Monitoring Station indicating that the alarm was canceled by the user.
Options: not active (default in USA); in 1/5 (default)/15/60 minute(s) and in 4 hours.
Loading...
+ 63 hidden pages