Visonic PowerMaster-10 G2, PowerMaster-30 G2 Installer's Manual

www.visonic.com
PowerMaster-10 G2
INSTALLER GUIDE
Fully supervised wireless alarm control system
D-303222 PowerMaster-10/30 G2 Installer's Guide 1
PowerMaster-10/30 G2
Version 16
Installer's Guide
Table of Contents
1. INTRODUCTION ................................................... 3
1.1 System Features ............................................ 3
2. CHOOSING THE INSTALLATION LOCATION ... 7
3. POWERMASTER-10 G2 INSTALLATION ........... 8
3.1 Opening the PowerMaster-10 G2 Control
Panel and Bracket Mounting .............................. 8
3.2 Connecting to the Telephone Line ............... 9
3.3 System Planning & Programming .............. 10
3.4 GSM Module Installation ............................. 10
3.5 PGM-5 Installation ....................................... 11
3.6 Adding Wired Zones or PGM Device ......... 12
3.7 Connecting Power to the Control Panel .... 13
3.8 Supplying Power to the Unit ....................... 16
3.9 Closing the PowerMaster-10 G2 Control
Panel ................................................................... 16
4. POWERMASTER-30 G2 INSTALLATION ......... 17
4.1 PowerMaster-30 G2 Wiring Diagram .......... 17
4.2 Opening the PowerMaster-30 G2 Control
Panel and Bracket Mounting ............................ 18
4.3 Connecting to the Telephone Line (detail
"M" in Figure 4.1) ............................................... 18
4.4 Connecting Wired Zone and Siren (detail
"B" in Figure 4.1)................................................ 19
4.5 System Planning & Programming .............. 19
4.6 GSM Module Installation (detail "N" in
Figure 4.1) ........................................................... 20
4.7 DUAL RS-232 Optional Module Mounting
(detail "F" in Figure 4.1) .................................... 20
4.8 PGM-5 Installation (located instead of detail
"F" in Figure 4.1) ................................................ 21
4.9 Optional Expander Module (detail "K" in
Figure 4.1) ........................................................... 22
4.10 Connecting Power to the Control Panel .. 24
4.11 Battery Insertion ........................................ 25
4.12 Supplying Power to the Unit ..................... 25
4.13 Closing the PowerMaster-30 G2 Control
Panel ................................................................... 26
5. PROGRAMMING ................................................ 27
5.1 General Guidance ....................................... 27
5.1.1 Navigation ........................................... 27
5.1.2 Feedback Sounds ............................... 27
5.2 Entering the "Installer Mode" and Selecting
a Menu Option ................................................... 27
5.2.1 Entering the "Installer Mode" if "User
Permit" is enabled ........................................ 28
5.2.2 Selecting options ................................ 28
5.2.3 Exiting the Installer Mode ................... 28
5.3 Setting Installer Codes ............................... 29
5.3.1 Identical Installer and Master Installer
Codes ........................................................... 29
5.4 Zones / Devices ........................................... 30
5.4.1 General Guidance & Zones/Devices
Menu Options............................................... 30
5.4.2 Adding New Wireless Devices or Wired
Sensors ........................................................ 30
5.4.3 Deleting a Device ................................ 34
5.4.4 Modifying or Reviewing a Device ....... 34
5.4.5 Replacing a Device ............................. 34
5.4.6 Defining Configuration Defaults for
"Device Settings" ......................................... 35
5.4.7 Updating Devices after Exiting Installer
Mode ............................................................ 36
5.5 Control Panel ............................................... 36
5.5.1 General Guidance – "Control Panel"
Flow-Chart & Menu Options ........................ 36
5.5.2 Configuring Arming/Disarming and
Exit/Entry Procedures .................................. 37
5.5.3 Configuring Zones Functionality ......... 38
5.5.4 Configuring Alarms & Troubles ........... 39
5.5.5 Configuring Sirens Functionality ......... 40
5.5.6 Configuring Audible & Visual User
Interface ....................................................... 41
5.5.7 Configuring Jamming and Supervision
(Missing device) ........................................... 42
5.5.8 Configuring Miscellaneous Features .. 43
5.6 Communication ........................................... 43
2 D-303222 PowerMaster-10/30 G2 Installer's Guide
5.6.1 General Guidance – "Communication"
Flow-Chart & Menu Options ........................... 43
5.6.2 Configuring PSTN (landline phone)
Connection ................................................... 45
5.6.3 Configuring GSM-GPRS (IP) - SMS
Cellular Connection ...................................... 45
5.6.4 Configuring Events Reporting to
Monitoring Stations ....................................... 47
5.6.5 Configuring Events Reporting to Private
Users ............................................................ 51
5.6.6 Configuring Motion Cameras for Visual
Alarm Verification ......................................... 51
5.6.7 Configuring Upload / Download Remote
Programming Access Permission ................ 52
5.7 PGM Output .................................................. 53
5.7.1 General Guidance ............................... 53
5.7.2 Open Collector States ......................... 53
5.7.3 Configuring a PGM device .................. 53
5.7.4 Entering Daytime Limits ...................... 53
5.7.5 PGM Output Configuration .................. 54
5.8 Custom Names ............................................. 54
5.8.1 Custom Zone Names .......................... 54
5.8.2 Record Speech .................................... 55
5.8.3 Voice Box Mode1 ................................. 56
5.9 Diagnostics .................................................. 56
5.9.1 General Guidance – "Diagnostics" Flow-
Chart & Menu Options .................................. 56
5.9.2 Testing Wireless Devices .................... 56
5.9.3 Testing the GSM module ..................... 57
5.10 User Settings .............................................. 58
5.11 Factory Default ........................................... 58
5.12 Serial Number ............................................ 58
5.13 Start UL/DL ................................................. 59
5.14 Partitioning ................................................. 59
5.14.1 General Guidance – "Partitioning"
Menu ............................................................. 59
5.14.2 Enabling / Disabling Partitions .......... 59
5.15 Operation Mode ......................................... 59
5.15.1 General Guidance – "Operation Mode"
Menu ............................................................. 59
5.15.2 Select between EN-50131, DD243 and
BS8243 ......................................................... 60
5.15.3 BS8243 Setup ................................... 60
5.15.4 DD243 Setup ..................................... 61
6. PERIODIC TEST ................................................. 62
6.1 General Guidance ........................................ 62
6.2 Conducting a Periodic Test ........................ 63
7. MAINTENANCE .................................................. 65
7.1 Handling System Troubles ......................... 65
7.2 Dismounting the Control Panel .................. 66
7.3 Replacing the Backup Battery ................... 66
7.4 Fuse Replacement ...................................... 66
7.5 Replacing/Relocating Detectors ................ 66
7.6 Annual System Check ................................ 67
8. READING THE EVENT LOG ............................. 67
APPENDIX A. Specifications ............................... 68
A1. Functional ................................................... 68
A2. Wireless ....................................................... 69
A3. Electrical...................................................... 69
A4. Communication .......................................... 70
A5. Physical Properties .................................... 70
A6. Peripherals and Accessory Devices ........ 71
APPENDIX B. Working with Partitions ............... 71
B1. User Interface and Operation .................... 71
B2. Common Areas ........................................... 72
APPENDIX C. Detector Deployment & Transmitter
Assignments ......................................................... 72
C1. Detector Deployment Plan ........................ 72
C2. Keyfob Transmitter List ............................. 74
C3. Emergency Transmitter List ...................... 74
C4. Non-Alarm Transmitter List ....................... 74
APPENDIX D. Event Codes .................................. 74
D1. Contact ID Event Codes............................. 74
D2. SIA Event Codes ......................................... 75
D3. Understanding the Scancom Reporting
Protocol Data Format ....................................... 76
D4. SIA over IP - Offset for Device User ......... 76
APPENDIX E. Sabbath Mode ............................... 76
E1. General Guidance ....................................... 76
E2. Connection .................................................. 76
E3. Arming the System by Sabbath Clock ..... 77
APPENDIX F. Glossary ......................................... 77
APPENDIX G. Compliance with Standards.......... 79
1. INTRODUCTION
D-303222 PowerMaster-10/30 G2 Installer's Guide 3
1. INTRODUCTION
PowerMaster-10 G2 and PowerMaster-30 G2 are PowerG-enabled professional all-in-one wireless security, fire and safety systems supporting advanced applications and Visonic's new revolutionary PowerG™ Two-Way, Time Division Multiple Access (TDMA) and Frequency Hopping Spread Spectrum (FHSS) wireless technology. This offers unmatched wireless robustness, superior range and long battery life; a perfect and user friendly solution for both monitoring service providers and professional installers.
This manual refers to PowerMaster-10/30 G2 v16 and above. The most updated manuals can be downloaded from the Visonic Web site http://www.visonic.com.
Note: For UL installations, please contact the manufacturer for the most recent version of UL approved documentation. Note: "Pmaster" is used as an abbreviation for "PowerMaster".
The PowerMaster-10/30 G2 control panel is supplied with 2 instruction manuals:
Installer's Guide (this manual) – for use of system installer during system installation and configuration User’s Guide -– also for use of system installer during system installation and configuration, but also for the master
user of the system, once installation is completed. Hand over this manual to the master user of the system.
1.1 System Features
The following table lists the PowerMaster features with a description of each feature and how to use it.
Feature
Description
How to configure and use
Visual Alarm Verification
The PowerMaster when used with Next CAM PG2 PIR-camera detector and GPRS communication is able to provide the Monitoring Station with clips captured in alarm situations. The system sends the clips to the Monitoring Station automatically for burglary alarms and, depending on setup, also for fire and personal emergency alarms.
Note: PowerMaster-10 G2 / PowerMaster-30 G2 are compatible with the following UL/ULC listed receivers: SG-System I, SG-System III, SG-System IV.
1. Setup GPRS communication: see GSM Module Installation (section 3.4 for PowerMaster-10 G2 or section 4.4 for PowerMaster-30 G2)
2. Configure camera settings: refer to the Next CAM PG2 Installation Instructions
3. Enable fire and personal alarm
verification: see section 5.6.6 Configuring
Motion Cameras for Video Alarm Verification
On demand clips from cameras
The PowerMaster can provide images from the Next CAM PG2 by demand from a remote PowerManage server. Pictures are taken based on a command from the monitoring station. To protect customers' privacy, the system can be customized to enable the "On Demand View" only during specific system modes (i.e. Disarm, Home & Away) and also to a specific time window following an alarm event.
1. Setup the On demand feature: see section 5.6.6 Configuring Motion Cameras for Video Alarm Verification
2. To request and view images: refer to the PowerManage User's Guide, Chapter 5 Viewing and Handling Events
Easy Enrollment
PowerG devices are enrolled from the control panel. "Pre-enrollment" can also be performed by entering the PowerG device ID number and then activating the device in the vicinity of the panel.
To enroll or pre-enroll devices: see section
5.4.2 Adding New Wireless Devices or Wired Sensors
1. INTRODUCTION
4 D-303222 PowerMaster-10/30 G2 Installer's Guide
Device Configuration
Device parameters and related system behavior can be configured from the control panel or from a remote location.
Each PowerG device has its own settings which can be configured through the control panel by entering the "DEVICE SETTINGS" menu.
Note: The minimum configuration of the system includes one detector.
To configure devices from the control panel: see Chapter 5 Programming and also
the individual device's Installation Instructions.
To configure devices from a remote location: refer to the PowerManage User's
Guide Chapter 3 Working with Panels and to the Remote Programmer PC software User's Guide, Chapters 6 and 7.
Diagnostics of the control panel and peripherals
You can test the function of all wireless sensors deployed throughout the protected area, to collect information about the received signal strength from each transmitter and to review accumulated data after the test.
To perform diagnostics and to obtain
signal strength indication: see section 5.9
Diagnostics
Conducting periodic tests
The system should be tested at least once a week and after an alarm. The periodic test can be conducted locally or from a remote location (with the assistance from a non­technical person in the house).
To conduct a walk test locally: see Chapter 6 Periodic Test
To conduct a walk test from remote
location: refer to the Remote Programmer
PC software User's Guide, Chapter 6 Data Details Tables.
Partitions
The partitioning feature, when enabled, divides your alarm system into distinct areas each of which operates as an individual alarm system. Partitioning can be used in installations where shared security systems are more practical, such as a home office or warehouse building.
1. Enable partitioning: see section 5.14 Partitioning
2. Setup partition association for each
device: see section 5.4.2 Adding New
Wireless Devices or Wired Sensors To understand more about partitioning:
see APPENDIX B. Working with Partitions and APPENDIX A. in the User's Guide.
Two-way voice communication1
The PowerMaster system enables voice communication with Monitoring Stations
To enable and configure two way voice:
see section 5.6.4 Configuring Events Reporting to Monitoring Stations
Device configuration templates
The default parameters with which a new device is enrolled into the system can be set before you enroll devices. This default template saves time on device configuration.
1. Define enrollment defaults for devices: see section 5.4.6 Defining Configuration Defaults for "Device Settings"
2. Enroll or pre-enroll devices: see section
5.4.2 Adding New Wireless Devices or Wired Sensors
SirenNet - distributed siren using Smoke detectors
All PowerG smoke detectors are able to function as sirens, alerting on any of 4 types of alarm in the system: fire, gas, burglary and flood.
Enable and configure SirenNet for each
smoke detector: refer to the SMD-426 PG2
/ SMD-427 PG2 Installation Instructions
Integrated Siren built into the panel
The control panel has a high-powered built-in siren that sounds in case of alarm, enabled by default.
To define whether or not the control
panel's siren will sound upon alarms: see
section 5.5.5 Configuring Sirens Functionality
Wired Siren outputs
The control panel can operate a wired siren and strobe devices
Install and connect wired siren: see section 4.7 Optional Expander Module Mounting
1
Refers to PowerMaster-30 G2 with voice option only
1. INTRODUCTION
D-303222 PowerMaster-10/30 G2 Installer's Guide 5
Wired zones and programmable outputs (PGM)
The control panel can support wired detectors and control automation devices with programmable wired outputs.
1. Connect a wired zone or PGM device:
see section 3.6 Adding a Wired Zone or PGM.
2. Program the wired zone: see section
5.4.2 Adding New Wireless Devices or Wired Sensors
3. Program PGM outputs behavior: see section 5.7 PGM Output.
Reporting to Private Users and/or Monitoring Station by telephone, SMS and IP communication
The PowerMaster system can be programmed to send notifications of alarm and other events to 4 private telephone subscribers by voice and also to 4 SMS cellular phone numbers and to report these events to the Monitoring Station by SMS, PSTN or IP communication (IP communication not enabled in UL Listed product).
To configure notifications to Private
phones: refer to the PowerMaster-10/30 G2
User's Guide, Chapter 6, section C.11 Programming Private Phone and SMS Reporting
To configure reporting to the Montioring
Station: see section 5.6.4 Configuring
Events Reporting to Monitoring Stations
Quick installation with link quality indication
With PowerG devices, there is no need to consult the control panel when mounting a wireless device, because PowerG devices include a built-in link quality indicator. Choosing the mounting location is a quick and easy process.
To choose the ideal location to mount a wireless device, see Chapter 2 Choosing the Installation Location.
Device Locator
Helps you to easily identify the actual device displayed on the LCD display.
To read more on the Device Locator: refer to the PowerMaster-10/30 G2 User's Guide, Chapter 2, Operating the PowerMaster System
To use the device locator when bypassing a zone or when clearing a bypassed zone:
refer to the PowerMaster-10/30 G2 User's Guide, Chapter 6, section C.1 Setting the Zone Bypass Scheme
To use the device locator when conducting the periodic test: see Chapter
6 Periodic Test or refer to the PowerMaster­10/30 G2 User's Guide, Chapter 9 Testing the System
Guard key-safe
PowerMaster is able to control a safe that holds site keys that are accessible only to the site's guard or Monitoring Station's guard in the event of an alarm.
1. Connect the safe to the panel: see section 3.6 Adding Wired Zones or PGM Device, Figure 3.6b (PowerMaster-10 G2) / section 4.7 Optional Expander Module Mounting, Figure 4.8b (PowerMaster-30 G2)
2. Configure the safe's zone type to "Guard Zone": see section 5.4.2 Adding New Wireless Devices or Wired Sensors
3. Setup guard code: see section 5.3
Setting Installer Codes
Arming Key
External system may control arming and disarming of the PowerMaster system
1. Connect the external system output to the panel: see section 3.6 Adding Wired
Zones or PGM Device, Figure 3.6b (PowerMaster-10 G2) / section 4.7 Optional Expander Module Mounting, Figure 4.8b (PowerMaster-30 G2)
Note: Monitoring Station means not evaluated by UL.
1. INTRODUCTION
6 D-303222 PowerMaster-10/30 G2 Installer's Guide
System Architecture:
Security Detectors and Transmitters
Main Control Panels
Keyfobs, Keypad and
Keyprox
Next CAM
PG2 Motion
Detector
with Camera
Next PG2
Motion
Detector
MC-302 PG2
Magnetic
Contact
TOWER-30AM
PG2
Mirror Detector
PowerMaster-10 G2
PowerMaster-30 G2
KF-234 PG2
KF-235 PG2
Two-way
Keyfobs
KP-140 PG2
Two-way
Keypad
Safety Detectors
KP-160 PG2 Keyprox
SMD-426 PG2
Smoke Detector
SMD-427 PG2 Smoke & Heat
Detector
TMD-560 PG2
Temperature
Detector
GSD-441 PG2
Gas (Methane)
Detector
GSD-442 PG2
Carbon Monoxide (CO)
Detector
FLD-550 PG2
Flood
Detector
Sirens
SR-730 PG2
Outdoor
Siren
SR-720 PG2
Indoor Siren
2. CHOOSING THE INSTALLATION LOCATION
D-303222 PowerMaster-10/30 G2 Installer's Guide 7
2. CHOOSING THE INSTALLATION LOCATION
To ensure the best possible mounting location of the PowerMaster control panel, the following points should be observed: The selected location should be approximately in the center of the installation site between all the transmitters,
preferably in a hidden location.
In close proximity to an AC source In close proximity to a telephone line connection (if PSTN is used) Where there is good cellular coverage, if GSM-350 PG2 is used Far from sources of wireless interference, such as:
o Computers or other electronic devices, power conductors, cordless phones, light dimmers, etc. o Large metal objects (such as metal doors or refrigerators)
Note: A distance of at least 1 meter (3 ft) is recommended.
If using the panel's built-in siren and/or voice, select location where audio can be heard throughout the premises.
When mounting wireless devices:
Make sure that the signal reception level for each device is either "Strong" or "Good", but not "Poor".
Note: For UL/cUL installations, the test result must be "Strong" for all wireless devices.
Wireless magnetic contacts should be installed in a vertical position and as high up the door or window as possible. Wireless PIR detectors should be installed upright at the height specified in their Installation Instructions Repeaters should be located high on the wall in mid-distance between the transmitters and the control panel.
WARNING! To comply with FCC and IC RF exposure compliance requirements, the control panel should be located at a distance of at least 20 cm from all persons during normal operation. The antennas used for this product must not be co-located or operated in conjunction with any other antenna or transmitter.
Customer Premises Equipment and Wiring
A
B
C
D
E
F
G
H
I
E
E
H
J
A. Network Service Provider's Facilities
F. Alarm Dialing Equipment
B. Telephone Line
G. Answering System
C. Network Demarcation Point
H. Unused RJ-11 Jack
D. RJ-31X Jack
I. Fax Machine
E. Telephone
J. Computer
Note: The REN is used to determine the number of devices that may be connected to a telephone line. Excessive RENs on a telephone line may result in the devices not ringing in response to an incoming call. In most but not all areas, the sum of RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to a line, as determined by the total RENs, contact the local telephone company.
Connection to telephone company provided coin service is prohibited. Connection to party lines service is subject to state tariffs.
The installer should verify line seizure. Be aware of other phone line services such as DSL. If DSL service is present on the phone line, you must install a filter. It is suggested to use the DSL alarm filter model Z-A431PJ31X manufactured by Excelsus Technologies, or equivalent. This filter simply plugs into the RJ-31X jack and allows alarm reporting without breaking the internet connection.
3. POWERMASTER-10 G2 INSTALLATION
8 D-303222 PowerMaster-10/30 G2 Installer's Guide
3. POWERMASTER-10 G2 INSTALLATION
Required tool: Philips screwdriver #2. PowerMaster-10 mounting process is shown in Figures 3.1 - 3.9.
3.1 Opening the PowerMaster-10 G2 Control Panel and Bracket Mounting
Figure 3.1 – Back Unit Mounting
To Mount the Unit:
1. Release the screws
A. Mounting surface
2. Remove the front cover
B. Back unit
3. Mark 4 drilling points on the mounting surface
4. Drill 4 holes and insert wall anchors
5. Fasten the back unit with 4 screws
WARNING! When plugging SIREN & ZONE terminals back into place, be sure to align them carefully with the pins on the PCB. Misaligned or reverse insertion of terminals may cause internal damage to the PowerMaster-10 G2!
3. POWERMASTER-10 G2 INSTALLATION
D-303222 PowerMaster-10/30 G2 Installer's Guide 9
3.2 Connecting to the Telephone Line
PHONE WIRING
Connect the telephone cable to the SET connector and connect the telephone line cable to the LINE connector (through the desired wiring cable entry).
Notes:
1. The telephone cable should be no longer than 3 meters.
2. For UL installations, the telephone cable must be no less than 26 AWG.
A. SET B. LINE C. Tel line wall jack
PHONE WIRING IN NORTH AMERICA
A. SET
G. Green
B. LINE
H. Brown
C. RJ-31X cord
I. RJ-31X jack
D. 8-position RJ-31X plug
J. Line from street
E. Gray
K. House phones
F. Red
Figure 3.2 –Phone Wiring
This equipment is designed to be connected to the telephone network using an RJ11 connector which complies with Part 68 rules and requirements adopted by ACTA and a properly installed RJ31X connector. See drawing above for details.
In the case that RJ31X is not available (consult your telephone company or a qualified installer), the telephone line should be connected to the PowerMaster-10 G2 unit first and then all other home equipment should be connected to the PowerMaster-10 G2 "Phone" outlet.
3. POWERMASTER-10 G2 INSTALLATION
10 D-303222 PowerMaster-10/30 G2 Installer's Guide
3.3 System Planning & Programming
Program the system now as instructed in the programming section.
The tables in APPENDIX C will help you plan and record location of each detector, the holder and assignment of each transmitter.
3.4 GSM Module Installation
The internal GSM 350 module enables the PowerMaster-10 G2 system to operate over a GSM/GPRS cellular network (for further details, see the GSM 350 PG2 Installation Instructions).
The GSM modem auto detection feature enables automatic enrollment of the GSM modem into the PowerMaster-10 G2 control panel memory. GSM modem auto detection is activated in one of two ways: after tamper restore and after reset (power-up or after exiting the installer menu). This causes the PowerMaster-10 G2 to automatically scan GSM COM ports for the presence of the GSM modem.
In the event that the GSM modem auto detection fails and the modem was previously enrolled in the PowerMaster-10 G2 control panel, the message "Cel Remvd Cnfrm" will be displayed. This message will disappear from the display only
after the user presses the button. The modem is then considered as not enrolled and no GSM trouble message will be displayed.
Notes:
1) A message is displayed only when the PowerMaster-10 G2 alarm system is disarmed.
2) The GSM Alarm Transmission System compliance with EN 50131-1 ATS4 was proven by testing the signaling
security requirements D2, M2, T3, S1, I2” detailed in EN 50136-1-1:1998/A2: 2008, EN 50136-2-1:1998/A1: 2001, EN50136-2-2: 1998.
Plug in the GSM module and fasten it as shown in the above drawing.
A. GSM B. Front unit Caution! Disconnect both batteries and AC power before
installing or removing the GSM module or SIM card.
Insert the SIM card into the GSM module as shown in the above drawing.
1. Slide top cover.
2. Open cover
3. Align SIM card in cover (note cover orientation)
4. Slide SIM card into cover
5. Rotate cover to close
6. Lock cover to close IMPORTANT! Do not insert or remove SIM card when the
control panel is powered by AC power or battery.
Figure 3.4 – Optional GSM Module Mounting and SIM Card Insertion
3. POWERMASTER-10 G2 INSTALLATION
D-303222 PowerMaster-10/30 G2 Installer's Guide 11
3.5 PGM-5 Installation
PGM-5 is an output interface module designed to provide alarm, trouble events and status signals to external devices such as long range wireless monitoring transmitters, CCTV systems, home-automation systems and LED annunciation panels (for further details see the PGM-5 Installation Instructions).
The PGM-5 provides 5 solid state relay contact outputs and is designed to be used as a plug-in internal add-on module with the PowerMaster-10 G2 control panel.
Notes:
1. The PGM-5 will be active only if the PGM-5 option was enabled in the factory default of the control panel.
2. PGM-5 plug-in module not enabled in UL Listed product.
Caution! When mounting the PGM-5 module it is strongly recommended to route the cable as shown in Figure 3.5 to prevent interference which may occur if routed too close to the control panel antennas.
A. Front unit B. Back unit C. PGM-5 Module D. 2 Screws for fastening the PGM-5 Module E. Flat cable F. Wiring
Figure 3.5 – PGM-5 Module Mounting
3. POWERMASTER-10 G2 INSTALLATION
12 D-303222 PowerMaster-10/30 G2 Installer's Guide
3.6 Adding Wired Zones or PGM Device
Required tools: Cutter and slotted screwdriver - 3 mm blade.
PowerMaster-10 G2 wiring is shown in Figures 3.6a – 3.7b.
CABLES ROUTING GUIDE
A. Cables entry options B. Back unit C. Cable clips
To Route the Cable:
1. Remove the left or
right side cables entry knockout(s) and enter the required cable(s)
2. Remove and use as cable clamp(s)
To Route the Cable (continued):
3. Position the clamp (1 of 2) as shown and then rotate into place.
4. Using a slotted screwdriver press downward gently on the point illustrated in the drawing. Make sure the clamp is
locked (a click is heard).
Figure 3.6a – Cable Wiring
3. POWERMASTER-10 G2 INSTALLATION
D-303222 PowerMaster-10/30 G2 Installer's Guide 13
PGM AND ZONE WIRING
A. PGM output
Vmax=30v Imax=100mA
B. Relay C. Device D. External power supply 5 -
30VDC
E. Wired detector's Tamper
F. Wired detector's alarm or
Arming Key (see section
5.4.2, “Zone Type List”
table).
For UL installations, D and E must be UL listed.
Note:
The wired detector should be installed at least 2 meters away from the control panel. Regarding the wired zone, the control panel classifies the events according to the resistance it measures as shown in the table below.
E.O.L or Arming Key Resistance
Range
Zone
Arming Key
0 kΩ 1.76 kΩ
Tamper
Tamper
1.76 kΩ 2.64 kΩ
Normal
Arm
2.64 kΩ 3.52 kΩ
Tamper
Tamper
3.52 kΩ 5.26 kΩ
Alarm
Disarm
5.26 kΩ
Tamper
Tamper
Notes:
1. The E.O.L resistors are 2.2 k resistors of 1/4 W, 5% supplied with the panel and are UL listed under the name EOLR-3, kit number 57000850.
2. If the Arming Key is enabled, the wired zone must be located in the protected area.
Figure 3.6b – PGM & Zone Wiring
3.7 Connecting Power to the Control Panel
CONNECTING AC POWER TO CONTROL PANEL USING AC/AC TRANSFORMER
Connect the power cable and close the control panel as shown below.
Notes:
1) Do not use mains cable (3 m long) or power supply other than that supplied by the manufacturer DONGGUAN ORIENTAL HERO ELE. CO. LTD., model no. OH-41111AT-2.
2) For UL installations (UL), the plug-in transformer must have restraining means. For Canada (CUL), it cannot have restraining means.
Note: This equipment should be installed in accordance with Chapter 2 of the National Fire Alarm Code, ANSI/NFPA 72 and CAN/ULC-S540.
3. POWERMASTER-10 G2 INSTALLATION
14 D-303222 PowerMaster-10/30 G2 Installer's Guide
Notes for UL installations:
1. A device that is connected to PGM terminal should not be programmed to be activated during standby.
2. The system shall be installed in accordance with CSA C22.1 Canadian Electrical Code, Part 1.
3. A minimum spacing of 1/4 inch shall be maintained between the telephone wiring and the low voltage wiring (zones, bell circuit, etc.). Do not route the LINE and SET wires in the same wiring channel with other wires.
4. Do not connect to a receptacle controlled by a switch.
5. Hard wired zones are for BURG use only.
6 Tamper (E) and external power supply (D) must be UL Listed.
Connect the power adapter to the power connector.
Figure 3.7a - Power Cable
Connection
3. POWERMASTER-10 G2 INSTALLATION
D-303222 PowerMaster-10/30 G2 Installer's Guide 15
CONNECTING AC POWER USING INTERNAL AC/DC POWER SUPPLY UNIT
PERFORM STEPS 1 and 2 ON A WORKBENCH BEFORE THE MOUNTING
1. Extract either plastic segment (will be used later)
7. Fasten power cable by clamp (extracted in step 2)
2. Extract plastic segment (will be used later)
8. Close power supply terminals cover
3. Knock out the plastic segment (left or right, according
to the power wiring direction)
9. Connect the DC output cable plug into the DC input
socket located on the front panel.
4. Remove power supply terminals cover (E)
A. Internal AC/DC power supply unit B. Power cable clamp options C. For thin cable D. For thick cable (reversed clamp)
E. Terminals cover F. DC input socket on front panel G. DC output cable
5. Insert the power cable through the desired wiring
channel, route it to the power supply unit and connect its 2 wires to the power supply terminal block with a screwdriver. Fasten the screws tightly. Verify that the wires are properly fastened!
6. Insert plastic cap to the power cable entry (extracted in step 1)
Figure 3.7b – Power Cable Wiring
3. POWERMASTER-10 G2 INSTALLATION
16 D-303222 PowerMaster-10/30 G2 Installer's Guide
3.8 Supplying Power to the Unit
Connect power to the PowerMaster-10 G2 temporarily (see Figure 3.7a). Alternatively, you may power up from the backup battery, as shown in Figure 3.8. Disregard any “trouble” indications pertaining to lack of battery or lack of telephone line connection.
For Europe Safety Compliance:
a. The model shall be installed according to the local electrical code. b. The circuit breaker shall be readily accessible. c. The rating of the external circuit breaker shall be 16A or less. d. The cables for the AC mains connection shall have an overall diameter of 13mm and 16mm conduit. Please refer to Figure 3.7a "Power Cable Connection".
Figure 3.8 – Connecting Power to the Control Panel
Inserting Backup Battery:
Connect battery pack as shown in Figure 3.8.
1. Insert battery
2. Connect the battery
3.9 Closing the PowerMaster-10 G2 Control Panel
Control panel final closure is shown below.
Figure 3.9 - Final Closure
To Close the Control Panel:
1. Close the front cover
2. Fasten the screws
4. POWERMASTER-30 G2 INSTALLATION
D-303222 PowerMaster-10/30 G2 Installer's Guide 17
4. POWERMASTER-30 G2 INSTALLATION
Required tool: Philips screwdriver #2. PowerMaster-30 G2 mounting process is shown in Figures 4.1 - 4.13.
4.1 PowerMaster-30 G2 Wiring Diagram
A. Expander Module Flat
Cable
B. Wired Zone / Special
Siren Terminal Block
C. Battery Connector
D. Front Unit
E. Dual RS-232 Module Flat
Cable
F. Dual RS-232 Module
G. Dual RS-232 Module
Connectors
H. Expander Module Wiring
Terminal Blocks
I. Back Unit
J. Power Supply
K. Expander Module
L. Power Connector
M. Phone Wiring
Connectors
N. GSM-350 PG2
* or PGM-5 Module ** or External Power Connector *** or Terminal Block in North American Panels
Figure 4.1 – PowerMaster-30 G2 Wiring Diagram
4. POWERMASTER-30 G2 INSTALLATION
18 D-303222 PowerMaster-10/30 G2 Installer's Guide
4.2 Opening the PowerMaster-30 G2 Control Panel and Bracket Mounting
To Mount the Unit:
1. Release the screws
2. Remove the front cover
3. Mark 4 drilling points on the mounting surface, then
drill 4 holes and insert wall anchors and then fasten the back unit with 4 screws
A. Mounting surface B. Back unit C. Screws
Figure 4.2 – Back Unit Mounting
4.3 Connecting to the Telephone Line (detail "M" in Figure 4.1)
PHONE WIRING
A. LINE B. SET C. Tel line wall jack
Connect the telephone cable to the SET connector and connect the telephone line cable to the LINE connector (through the desired wiring cable entry).
Notes:
1. The telephone cable should be no longer than 3 meters.
2. For UL installations, the telephone cable must be no less than 26 AWG.
Figure 4.3a – Phone Wiring
4. POWERMASTER-30 G2 INSTALLATION
D-303222 PowerMaster-10/30 G2 Installer's Guide 19
PHONE WIRING IN NORTH AMERICA
A. LINE B. SET C. RJ-31X cord
D. 8-position RJ-31X plug E. Brown F. Red
G. Green H. Gray I. RJ-31X jack
J. Line from street K. House phones
Figure 4.3b – Phone Wiring in North America
Phone wiring in the UK: Line terminals must be connected to pins 2 and 5 of the wall jack. For all installations: If DSL service is present on the phone line, you must route the phone line through a DSL filter
(refer to MESSAGE TO THE INSTALLER on page 2 for further details).
4.4 Connecting Wired Zone and Siren (detail "B" in Figure 4.1)
If an expander module is not used, one wired zone and one low voltage siren can be connected directly to the front panel PCB (not allowed in UL installations).
WIRED ZONE1 &SIREN WIRING
A. GND B. Wired Zone C. Siren* D. Site external siren MG electronics
MG441PDS or equivalent 6­12VDC, 150 mA Max*
E. Magnetic contact or any other
contact (not a detector)
F. Alarm N.C.
*Not to be used in UL Listed Product
Figure 4.4 – Wired Zone and Siren Wiring
4.5 System Planning & Programming
Program the system now as instructed in the programming section.
The tables in APPENDIX C will help you plan and record the location of each detector, the holder and assignment of each transmitter.
1
Wired zones can be enrolled in any zone in the PowerMaster-30 G2 control panel from 01 to 64
4. POWERMASTER-30 G2 INSTALLATION
20 D-303222 PowerMaster-10/30 G2 Installer's Guide
4.6 GSM Module Installation (detail "N" in Figure 4.1)
Plug in the GSM module and fasten it as shown in the above drawing.
A. GSM B. Front unit Caution! Do not install or remove the GSM module when the
system is powered by AC power or backup battery.
Insert the SIM card into the GSM module as shown in the above drawing.
1. Slide top cover.
2. Open cover
3. Align SIM card in cover (note cover orientation)
4. Slide SIM card into cover
5. Rotate cover to close
6. Lock cover to close
IMPORTANT! Do not insert or remove SIM card when
the control panel is powered by AC power or battery.
Note: The GSM Alarm Transmission System
compliance with EN 50131-1 ATS4 was proven by testing the signaling security requirements D2, M2, T3, S1, I2” detailed in EN 50136-1-1:1998/A2: 2008, EN 50136-2-1:1998/A1: 2001, EN50136-2-2: 1998.
Figure 4.6
– Optional GSM Module Mounting and SIM Card Insertion
4.7 DUAL RS-232 Optional Module Mounting (detail "F" in Figure 4.1)
The Dual RS-232 is a module that enables connection of any two simultaneous devices, such as Local PC programming or GSM Module.
The GSM unit enables the PowerMaster-30 G2 system to operate over a cellular network (for details regarding the GSM modem features and connections, refer to the GSM Modem installation instructions).
Note: The Dual RS-232 Module is not to be connected in UL Listed product.
4. POWERMASTER-30 G2 INSTALLATION
D-303222 PowerMaster-10/30 G2 Installer's Guide 21
1. To install the DUAL RS-232 module into
the control panel, press it into the marked location (see Figure 4.7) until a click is heard.
2. Connect the flat cable (included in the
module's package) between the front panel and the DUAL RS-232 receptacle. Caution! The receptacle with strain relief clip is for the front unit – do not connect it to the back unit!
3. Connect a local PC to the DUAL RS-
232 module connector (B) or (C), as shown in Figure 4.7.
A. DUAL RS-232 Module B. Connector for PC C. Connector for PC D. Visonic PC cable E. Flat cable with one strain relief clip
E1. This side for front unit E2. This side for back unit
F. Flat cable connector
Figure 4.7 –Dual RS-232 Module Mounting
4.8 PGM-5 Installation (located instead of detail "F" in Figure 4.1)
PGM-5 is an output interface module designed to provide alarm, trouble events and status signals to external devices such as long range wireless monitoring transmitters, CCTV systems, home-automation systems and LED annunciation panels (for further details see the PGM-5 Installation Instructions).
The PGM-5 provides 5 solid state relay contact outputs and is designed to be used as a plug-in internal add-on module with the PowerMaster-30 G2 control panel.
Mount the PGM-5 module as shown in Figure 4.8.
1. Press downward on the PGM-5 module (D), located in the back panel, between its 2 clips.
2. Connect the PGM-5 module flat cable (F) to the front panel PGM-5 receptacle and to the flat cable receptacle of
the PGM-5 (G).
Caution! The connector with strain relief clip (F1) is for the front unit – do not connect it to the back unit!
Notes:
i) The PGM-5 will be active only if the PGM-5 option was enabled in the factory default of the control panel. ii) For wiring instructions, refer to the PGM-5 Installation Instructions included in the module's package. iii) PGM-5 plug-in module not evaluated by UL.
Caution! When mounting the PGM-5 module it is strongly recommended to route the wiring cable (E) as shown in Figure 4.8) to prevent interference which may occur if routed too close to the control panel antennas.
4. POWERMASTER-30 G2 INSTALLATION
22 D-303222 PowerMaster-10/30 G2 Installer's Guide
A. PowerMaster-30 G2 connector B. Front unit C. PGM-5 Module D. Back unit E. Wiring Cable F. Flat cable
F1. This side for front unit F2. This side for back unit
G. PGM-5 flat cable receptacle
Figure 4.8 – PGM-5 Module Mounting
4.9 Optional Expander Module (detail "K" in Figure 4.1)
The Expander module is an optional module. If this optional module is used, the wired zone or special siren on the front panel should not be used.
Note: The optional Expander Module not to be connected in UL Listed product.
Mount the Expander module as shown in Figure 4.9a.
1. Press downward on the Expander module
(located in the back panel) between its 2 clips.
2. Connect the Expander module flat cable
to the front panel Expander receptacle.
Caution! The receptacle with strain relief clip is for the front unit – do not connect it to the back unit!
A. 2 clips B. Flat cable with one strain relief clip B1. This side for front unit B2. This side for back unit
Figure 4.9a –Expander Module
4. POWERMASTER-30 G2 INSTALLATION
D-303222 PowerMaster-10/30 G2 Installer's Guide 23
OPTIONAL EXPANDER MODULE, ZONES, SIRENS, AUDIO BOX AND WIRED DETECTORS WIRING
A. Back Unit B. Expander C. Internal siren or strobe 6-12 VDC,
150 mA Max.
D. External siren MG441PDS or similar siren 12 VDC
(nominal) 350 mA Max.
E. Voice box F. Connect wired detectors as illustrated.
Note:
The wired detector should be installed at least 2 meters away from the control panel. Regarding the two wired zones, the control panel classifies the events according to the resistance it measures as shown in the table below.
E.O.L or Arming Key Resistance
Range
Zone
Arming Key
0 kΩ 1.76 kΩ
Tamper
Tamper
1.76 kΩ 2.64 kΩ
Normal
Arm
2.64 kΩ 3.52 kΩ
Tamper
Tamper
3.52 kΩ 5.26 kΩ
Alarm
Disarm
5.26 kΩ
Tamper
Tamper
Notes:
1. The E.O.L resistors are 2.2 k resistors of 1/4 W, 5% supplied with the panel and are UL listed under the name EOLR-3, kit number 57000850.
2. If the Arming enabled is set, the wired zone must be located in the protected area.
G. Detector without tamper switch or Arming Key (see
section 5.4.2, “Zone Type List” table).
H. Detector with tamper switch or arming key's tamper I. PGM device J. Wired zone A or B K. Ground (GND)
Figure 4.9b – Zone and Siren Wiring
Notes for EXPANDER module wiring:
* Wired zone terminals can be connected to a normally closed contact of a detector, switch (for example a Tamper
switch of any device), or a pushbutton, via a 2.2 K resistor. The 12V terminal can be used to supply 12V (up to 36mA) to a detector (if necessary).
** The EXT terminal can be used to trigger an external siren.
The INT terminal can be programmed for an "internal siren" or "strobe" (see par. 5.7).
4. POWERMASTER-30 G2 INSTALLATION
24 D-303222 PowerMaster-10/30 G2 Installer's Guide
The 12V and "GND" terminals can be connected to a siren (for constant DC power supply).
*** The.12V supply to the PGM device is fused. Current is limited to 100 mA. WARNING! When plugging terminals back into place, be sure to align them carefully with the pins on the PCB.
Misaligned or reverse insertion of terminals may damage internal PowerMaster-30 G2 circuits!
IMPORTANT! The terminals for internal and external sirens are DC outputs intended for 12V sirens. Connecting a loudspeaker to any of these outputs will cause a short circuit and will damage the unit.
4.10 Connecting Power to the Control Panel
Note: Do not use mains cable (3 m long) or power supply other than that supplied by the manufacturer LEADER ELECTRONICS, model no. MU24-11125-A10F. For UL installations (UL), the plug-in transformer must have restraining means. For Canada (CUL), it cannot have restraining means. Note: This equipment should be installed in accordance with Chapter 2 of the National Fire Alarm Code, ANSI/NFPA 72 and CAN/ULC-S540.
Notes for UL installations:
1. A device that is connected to PGM terminal should not be programmed to be activated during standby.
2. The system shall be installed in accordance with CSAC22.1 Canadian Electrical Code, Part 1.
3. A minimum spacing of 1/4 inch shall be maintained between the telephone wiring and the low voltage wiring (zones, bell circuit, etc.) Do not route the LINE and SET wires in the same wiring channel with other wires.
4. Do not connect to a receptacle controlled by a switch.
5. Hard wired zones are for BURG use only.
Connect the power cable and close the control panel as shown in Figures 4.10a – 4.10b.
POWER CONNECTION FOR INTERNAL POWER SUPPLY
Perform steps 1 & 2 on a workbench before mounting.
1. Thick cable entry: Pull out a desired wiring plastic cap (1 of 4).
2. Extract cable clamp (I) for use in the next step
3. Insert the power cable through the desired wiring
channel (A). Route it to the power supply unit (E) and remove the safety cover (D). Connect the 2 wires of the power cable to the power supply terminal block (F) with a screwdriver. Fasten the screws tightly. Fasten the power cable by its clamp (B or C) and close the safety cover (D).
4. Connect the power supply output cable (G) to the power connector (H) in the front panel.
A. Optional wiring channels B. For thin cable C. For thick cable (reversed clamp) D. Safety cover E. Power supply unit F. Power supply terminal block G. Power supply output cable H. Power connector
(*) Do not route wiring in this area, to enable proper
closure of the control panel.
I. Cable clamp.
Figure 4.10a – Power Connection For Internal Power Supply
Loading...
+ 57 hidden pages