Vision Spirit II G XL User Manual

Page 1
User Manual
Vision Spirit II G XL
6-10KVA
PF0.9
– 3/1 phase
True online double conversion UPS
Page 2
All rights reserved. The information in this document is subject to change without notice.
Thank you for purchasing this series UPS.
This series UPS is an intelligent, three phase in single phase out, high frequency online UPS designed by our R&D team who is with years of designing experiences on UPS. With excellent electrical performance, perfect intelligent monitoring and network functions, smart appearance, complying with EMC and safety standards, This UPS has become standard product which meets the worlds advanced level.
Read this manual carefully before installation. This manual offers technical support for equipment operator.
Page 3
1
Contents
1SAFETY ................................................................................................................................................ - 2 -
1.1 Safety notes.................................................................................................................................... - 2 -
1.2 Symbols used in this guide........................................................................................................ - 2 -
2MAIN FEATURES ............................................................................................................................... - 3 -
2.1 Summarization............................................................................................................................... - 3 -
2.2 Functions and features .............................................................................................................. - 3 -
3INSTALLATION ................................................................................................................................... - 4 -
3.1 Unpack checking.......................................................................................................................... - 4 -
3.2 UPS module outlook .................................................................................................................... - 4 -
3.3 LCD control panel ......................................................................................................................... - 5 -
3.4 Installation notes........................................................................................................................... - 5 -
3.5 External protective devices ........................................................................................................ - 6 -
3.6 Power cables .................................................................................................................................. - 7 -
3.7 Power cable connect.................................................................................................................... - 8 -
3.8 Battery connection ....................................................................................................................... - 8 -
3.9 UPS multi-module Installation .................................................................................................. - 10 -
3.9.1 Cabinet installation ............................................................................................................... - 10 -
3.9.2 Parallel cable installation ..................................................................................................... - 11 –
3.9.3 Requirement for the parallel system.................................................................................. - 11 –
4OPERATION ......................................................................................................................................... - 12 -
4.1 Operation modes............................................................................................................................ - 12 -
4.2 Turn on/off UPS ............................................................................................................................. - 13 -
4.2.1 Connecting with utility......................................................................................................... - 13 -
4.2.2 Black (Cold) start procedure............................................................................................... - 13 -
4.2.3 Inverter Off .............................................................................................................................. - 14 -
4.2.4 Disconnecting with utility .................................................................................................. - 14 -
4.3 LCD Display instruction .............................................................................................................. - 14 -
4.4 Working mode and transferring ................................................................................................ - 16 -
4.4.1 Transfer to bypass if overload ........................................................................................... - 16 -
4.4.2 Normal mode to battery mode ........................................................................................... - 17 -
4.4.3 Go to bypass mode due to over temperature ................................................................ - 17 -
4.4.4 Output short circuit............................................................................................................... - 17 -
4.5 UPS monitoring ............................................................................................................................ - 17 -
4.6 LCD operation menu .................................................................................................................... - 17 -
5MAINTENANCE................................................................................................................................... - 19 -
5.1 Ventilator maintenance................................................................................................................ - 19 -
5.2 Battery maintenance..................................................................................................................... - 19 -
5.3 Visual control…………….............................................................................................................. - 19 -
5.4 Control of the UPS status............................................................................................................ - 19 -
5.5 Function control………................................................................................................................. - 20 -
APPENDIX 1 SPECIFICATIONS ............................................................................................................................ - 20 -
APPENDIX 2 COMMUNICATION PORT DEFINITION ....................................................................................... - 22 -
APPENDIX 3 OPTION .............................................................................................................................................. - 22 -
APPENDIX 4 UPS MESSAGE TABLE .................................................................................................................. - 23 -
Page 4
2
1Safety
Important safety instructions – Save these instructions
There exists dangerous voltage and high temperature inside the UPS. During the installation, operation and maintenance, please abide the local safety instructions and relative laws, otherwise it will result in personnel injury or equipment damage. Safety instructions in this manual act as a supplementary for the local safety instructions. Our company will not assume the liability that caused by disobeying local safety instructions.
1.1 Safety notes
1. Even no connection with utility power, 220/230/240VAC voltage may still exist at UPS
outlet
2. For the sake of human being safety, please well earth the UPS before starting it. 3. Don’t open or damage battery, for the liquid spilled from the battery is strongly
poisonous and do harmful to body
4. Please avoid short circuit between anode and cathode of battery, otherwise, it will
cause spark or fire 5. Don’t disassemble the UPS cover, or there may be an electric shock 6. Check if there exists high voltage before touching the battery 7. Working environment and storage way will affect the lifetime and reliability of the UPS.
Avoid the UPS from working under following environment for long time
Area where the humidity and temperature is out of the specified
range (temperature 0 to 40℃, relative humidity 5%-95%)
Direct sunlight or location nearby heat
Vibration Area with possibility to get the UPS crashed.
Area with erosive gas, flammable gas, excessive dust, etc.
8Keep ventilations in good conditions otherwise the components inside the UPS will
be over-heated which may affect the life of the UPS.
1.2 Symbols used in this guide
WARNING!
Risk of electric shock
CAUTION!
Read this information to avoid equipment damage
Page 5
3
2Main Features
2.1 Summarization
This series UPS is a kind of three phase in single phase out high frequency online
UPS,
it
provides two capacities: The 6kVA and 10kVA. The products are modularized and adopt the N+X redundancy. It can flexibly increase the number of the UPS modules according to the load capacity which is convenient for flexible allocation and gradually investment.
The UPS can solve most of the power supply problems, such as blackout, over-voltage, under-voltage, voltage sudden drop, oscillating of decreasing extent, high voltage pulse, voltage fluctuation, surge, inrush current, harmonic distortion (THD), noise interference, frequency fluctuation, etc..
This UPS can be applied to different applications from computer device, automatic equipment, communication system to industry equipment.
2.2 Functions and f
eatures
1Phase In/1Phase Out UPS It is 3Phase In/1Phase Out high-density UPS system, of which input current is kept in
balance. No unbalance problem might occur. And also support for three phase input.
Digital Control This series UPS is controlled by Digital Signal Processor (DSP); ehance, it increases
reliability, performance, self-protection, self-diagnostics and so on.
Battery Configurable from 16pcs to 20pcs
The battery voltage of this series UPS can be configured at 16pcs, 18pcs or 20pcs
according to your convenience.
Intelligent Charging Method The series UPS adopts advanced three-stage charging method 1
st
stage: high current constant current charging
to guarantee to charge back to 90%;
2nd-stage: Constant Voltage
In order to vitalize battery and make sure batteries are fully charged
3
rd
stage: floating mode. With this 3-stage charging method, it extends the life of the batteries and guarantees fast charging.
LCD Display
With LCD plus LED displays, the user may easily get UPS status and its operational parameters, such as input/output voltage, frequency & load%, battery % and ambient temperature, etc.
Intelligent Monitoring Function Via optional SNMP Card, you may remotely control and monitor the UPS.
Page 6
4
3Installation
3.1 Unpack checking
1. Don’t lean the UPS when moving it out from the packaging.
2. Check the appearance to see if the UPS is damaged or not during the transportation, do not switch on the UPS if any damage found. Please contact the dealer right away.
3. Check the accessories according to the packing list and contact the dealer in case of missing parts.
3.2 UPS module outlook
Front View
Rear View
Page 7
5
Side View
(1) handles (2) fixing screw hole (3) LCD Display (4) Intelligent slot (5) EPO (6)
COM(RS232
)(7)
Parallel
Port 1 8)USB port (9) Parallel Port 2 (10) Output terminal (11) Output breaker (12) Battery Slot (13) Output IEC (14) PDU (15) Input breaker (16) Input terminal
3.3 LCD control panel
开机
关机
退出
旁路
故障
主路 逆 变 输出
确认
LCD control panel introduction
1LCD screen 2)ESC 3)OFF button 4)ON button 5)forward
button
6Enter7backward button 8Output Indicator 9Inverter Indicator (10
Battery Indicator 11)Mains (AC)
Indicator(12)Bypass
Indicator 13Fault
Indicator
3.4 Installation notes
Please place the UPS in a clean, stable environment, avoid the vibration, dust,
humidity, flammable gas and liquid, corrosive objects. To avoid from high room
Page 8
6
temperature, a system of room extractor fans is recommended to be installed. Optional air filters are available if the UPS operates in a dusty environment.
The environment temperature around the UPS should keep in a range of 0℃40℃. If the environment temperature exceeds 40℃, the rated load capacity should be reduced by 12per 5℃. The max temperature can't be higher than 50℃.
If the UPS is dismantled under low temperature, it might be in a condensing condition. The UPS can't be installed unless the internal and external of the equipment is
fully dry. Otherwise, there will be in danger of electric shock.
Batteries should be mounted in an environment where the temperature is within the required specs. Temperature is a major factor in determining battery life and capacity. In a
normal installation, the battery temperature is maintained between 15°C and 25°C. Keep batteries away from heat sources or main air ventilation area, etc.
WARNING!
Typical battery performance data are quoted for an operating temperature between 20°C and 25°C. Operating it above this range will reduce the battery life while operation below this range will reduce the battery capacity.
Should the equipment not be installed immediately it must be stored in a room so as
to protect it against excessive humidity and or heat sources.
CAUTION!
An unused battery must be recharged every 3 months. Temporarily connecting the UPS to a suitable AC supply and activating it for the time required for recharging the batteries are required.
The highest altitude that UPS may work normally with full load is 1500 meters. The
load capacity should be reduced when this UPS is installed in place whose altitude is higher than 1500 meters, shown as the following table:
Load coefficient equals max load in high altitude place divided by nominal power of
the UPS
Altitudem
1500
2000
2500
3000
3500
4000
4500
5000
Load coefficient
100%
95%
90%
85%
80%
75%
70%
65%
To get the UPS completely monitored by the software, you just simply connect RS232
cable to each end of the computer and the UPS respectively.
3.5 External Protective Devices
For safety reasons, it is necessary to install, external circuit breaker at the input A.C. supply and the battery. This chapter provides guidelines for qualified installers that must have the knowledge of local wiring practices for the equipment to be installed.
External Battery
The UPS and its associated batteries are protected against the effect of
Page 9
7
over-current through a DC compatible thermo-magnetic circuit-breaker (or a set of fuses) located close to the battery.
UPS Output
Any external distribution board used for load distribution shall be fitted with
protective devices that may avoid the risk of UPS overloaded.
Over-current
Protection device shall be installed at the distribution panel of the incoming main supply. It may identify the power cables current capacity as well as the overload capacity of the system.
CAUTION!
Select a thermo magnetic circuit-breaker with an IEC 60947-2 trip curve C
(normal) for 125% of the current as listed below.
3.6 Power
Cables
The cable design shall comply with the voltages and currents provided in this section,
Kindly follow local wiring practices and take into consideration the environmental conditions (temperature and physical support media) .
WARNING!
UPON STARTING, PLEASE ENSURE THAT YOU ARE AWARE OF THE LOCATION AND OPERATION OF THE EXTERNAL ISOLATORS WHICH ARE CONNECTED TO THE UPS INPUT/BYPASS SUPPLY OF THE MAINS DISTRIBUTION PANEL.CHECK TO SEE IF THESE SUPPLIES ARE ELECTRICALLY ISOLATED, AND POST ANY NECESSARY WARNING SIGNS TO PREVENT ANY INADVERTENT OPERATION
Cable
Dimension
UPS
module
Cable Dimension
AC Input
(mm2)
AC
Output
(mm2)
DC Input
(mm2)
Grounding
(mm2)
6KVA
6 6 6
6
10KVA
10 10 10 10
CAUTION!
Protective earth cable: Connect each cabinet to the main ground system. For Grounding connection, follow the shortest route Possible.
Page 10
8
WARNING!
FAILURE TO FOLLOW ADEQUATE EARTHING PROCEDURES MAY RESULT IN ELECTROMAGNETIC INTERFERENCE OR IN HAZARDS INVOLVING ELECTRIC SHOCK AND FIRE
3.7 Power cable connect
Once the equipment has been finally positioned and secured, connect the power cables
as described in the following procedure.
Verify the UPS is totally isolated from its external power source and also all power isolators of the UPS are open. Check to see if they are electrically isolated, and post any necessary warning signs to prevent their inadvertent operation.
Choose appropriate power cable, and pay attention to the diameter of the connection terminal of the cable that should be greater than or equal to that of the connection poles;
Input connection “3phase 4wires + ground”
WARNING! If the load equipment is not ready to accept power on the arrival of
the commissioning engineer then ensure that the system output cables are safely isolated at their ends.
CAUTION! The earthing and neutral bonding arrangement must be in accordance with local and national codes of practice.
3.8 Battery connection
The UPS uses a positive and negative double battery framework, total 16 (optional 18 / 20 pieces) pieces in series. A neutral cable is retrieved from the joint between the cathode
Page 11
9
of the 8
th (9th
/10th) and the anode of the 9
th
(10th/11th) of the batteries. Then the neutral, the battery positive and the battery negative are connected with the UPS respectively. The battery sets between the Battery anode and the neutral are called positive batteries and that between neutral and cathode are called negative ones. Users can choose the capacity and the numbers of the batteries according to their demands. The connection is shown as following:
Note
The BAT+ of the UPS connect poles is connected to the anode of the positive battery, the BAT-N is connected to the cathode of the positive battery and the anode of the negative battery, the BAT- is connected to the cathode of the negative battery.
Factory default setting for battery quantity is 16pcs and for battery capacity is 7AH (charger current 1A). When connecting 18pcs or 20pcs batteries, please re-set battery quantity and its capacity after UPS starts at AC mode. Charger current could be adjusted automatically according to battery capacity selected. (Also charger current is selectable). Via the setting tool, all related parameter settings can be performed. These corresponding settings are done though LCD.
CAUTION! Ensure correct
polarity
battery string series connection. i.e. inter-tier and inter block connections are from (+) to (-)terminals. Don’t mix batteries with different capacity or different brands, or even mix up new and old batteries, either.
Page 12
10
WARNING! Ensure correct polarity of string end connections to the Battery Circuit Breaker and from the Battery Circuit Breaker to the UPS terminals i.e. (+) to (+) / (-) to (-) but disconnect one or more battery cell links in each tier. Do not reconnect these links and do not close the battery circuit breaker unless authorized by the commissioning engineer.
3.9 UPS multimodule installation
The basic installation procedure of a parallel system comprising of two or more UPS modules is the same as that of single module system. The following sections introduce the installation procedures specified to the parallel system.
3.9.1 Cabinet installation
Connect all the UPSes needed to be put into parallel system as below picture.
Make sure each UPS input breaker is in “off” position and there is no any output from each UPS connected. Battery groups can be connected separately or in parallel, which means the system itself provides both separate battery and common battery.
WARNING! Make sure the N and L lines are correct, and grounding is
well connected.
Page 13
11
3.9.2 Parallel cable installation
Shielded and double insulated control cables available must be interconnected in a ring configuration between UPS modules as shown below. The parallel control board is mounted on each UPS module. The ring configuration ensures high reliability of the control.
3.9.3 Requirement for the parallel system
A group of paralleled modules behave as one large UPS system but with the advantage of presenting higher reliability. In order to assure that all modules are equally utilized and comply with relevant wiring rules, please follow the requirements below:
1) All UPS must be of the same rating and be connected to the same bypass source.
2) The Bypass and the Main input sources must be referenced to the same neutral potential.
Page 14
12
3) The outputs of all the UPS modules must be connected to a common output bus.
4) The length and specification of power cables including the bypass input cables and the UPS output cables should be the same. This facilitates load sharing when operating in bypass mode.
4Operation
4.1 Operation modes
The UPS is a double-conversion on-line UPS that may operate in the following
alternative modes
Normal mode
The rectifier/charger derives power from the AC Mains and supplies DC power to the inverter while floating and boosting charge the battery simultaneously. Then, the inverter converts the DC power to AC and supplies to the load.
Battery mode (Stored Energy Mode)
If the AC mains input power fails, the inverter, which obtains power from the battery, supplies the critical AC load. There is no power interruption to the critical load. The UPS will automatically return to Normal Mode when AC recovers.
Bypass mode
If the inverter is out of order, or if overload occurs, the static transfer switch will be activated to transfer the load from the inverter supply to bypass supply without interruption to the critical load. In the event that the inverter output is not synchronized with the bypass AC source, the static switch will perform a transfer of the load from the inverter to the bypass with power interruption to the critical AC load. This is to avoid paralleling of unsynchronized AC sources. This interruption is programmable but typically set to be less than an electrical cycle e.g. less than 15ms (50Hz) or less than 13.33ms (60Hz).
ECO Mode
When the UPS is at AC Mode and the requirement to the load is not critical, the UPS can be set at ECO mode in order to increase the efficiency of the power supplied. At ECO mode, the UPS works at Line-interactive mode, so the UPS will transfer to bypass supply. When the AC is out of set window, the UPS will transfer from bypass to Inverter and supplies power from the battery, then the LCD shows all related information on the screen.
Parallel redundancy mode (system expansion)
To achieve a higher capacity and / or increase reliability, the outputs of up to four UPS modules can be programmed to operate in parallel and the built-in parallel controller in each UPS ensures automatic load
sharing.
Page 15
13
4.2 Turn on/off UPS
4.2.1 Connecting with Utility
CAUTION!
MAKE SURE GROUNDING IS PROPERLY DONE!
Set the Battery Breaker to the “ON” position according to the user’s manual.
Switch on the
UPS
CAUTION!
Check to see if the load is safely connected with the output of the UPS. If the load is not ready to receive power from the UPS, make sure that it is safely isolated from the UPS output terminals
The internal fan of the UPS starts spinning, the UPS is performing self-diagnostics until buzzer beeps twice to show the UPS is normal. Then, the UPS goes to bypass supply, Utility LED and Bypass LED turn Green, the inverter is starting up now. When the inverter is checked “normal”, the UPS goes to working mode and the load is supplied by the inverter now.
No matter the UPS is operated normally or not, the LCD display will indicate current status. The top lines display the UPS operational status and the bottom lines indicate alarm conditions when they occur.
4.2.2 Black (Cold) start procedure
开机
关机
退出 旁
故障
主路 逆 变 输出
确认
CAUTION! Follow these procedures when the input AC Utility Failure, but battery is normal
Turn on the battery switch.
The battery will feed the Auxiliary power board.
Trigger the cold start buttons at the position 4 in above drawing.
When battery normal, rectifier starts operation, 30s later, inverter starts
and operates, INV and output light up.
Page 16
14
CAUTION! Wait for approximately 30 seconds before you press the black start
key.
4.2.3 Inverter Off
When the Utility is normal, press “Off” button for approx. 1 sec until beep sounds, the inverter LED will extinguish, the bypass LED on, then the UPS turns to bypass supply.
When the UPS is on battery mode or without AC, press “Off” button for approx. 1 sec until beep sounds, the output of the UPS is off, fan stop spinning. After 60 seconds, all the LED on the LCD display extinguish.
4.2.4 Disconnecting with utility
CAUTION!
This procedure should be followed to completely shut down the UPS and the LOAD. After all power switches, isolators and circuit breakers are opened, there will be no output.
After the inverter is off, turn the Utility and battery breakers to “OFF”, then the LCD display will extinguish completely and fan stops spinning in 60
seconds. If there are external battery packs connected, please also turn the battery breaker to “OFF”.
WARNING! Wait for about 5 minutes for the internal D.C. bus bar capacitors to be completely discharged.
4.3 LCD display instruction
1) The main interface below comes out when the power is connected or the system is cold start. See Fig 1.
10.0KVA
Fig.1Main interface
Page 17
15
2) Press ESC/ or button, it will change to the basic status interface (see Fig 2 below).
MODE:ONLINE Volt:
AN BN CN
Vin: 220 220
220
Vout:220V
50HZ
Fig.2Basic status interface
3) Press the ENT button, it will change to main menu (see Fig 3).
FIGUER STATUS SETTING
Fig.3Main menu
4) An arrow icon will come out on the LCD when pressing the ENT, then the data info, status info, setting info can be selected by pressing the right or left arrow button, and checking the details by pressing.
5) Select and confirm the data info to be viewed in detail. It contains the details of the AC input/output, inverter, battery, BUS, parallel, temperature (see Fig 4 to 12
below).
FIGURE Mains: A:220.0
B:220.1
FIGURE Output
220.0V
0.0A
FIGURE Output 0KW
0KVA
C:220.0
50.0Hz
50.0Hz
Load: 0%
Fig.4Main input info Fig.5Output info Fig.6Output info
FIGURE Invert
220.0V
50.0HZ
FIGURE P Battery
0V
0.0A
FIGURE N Battery
0V
0.0A
0min
0%
0min
0%
Fig.7Inverter info Fig.8Battery info Fig.9 battery info
FIGURE BUS
-370V +370V CAP 0Hour
FIGURE Parallel ID: 1 P Amount0
FIGURE Temperature PFC:27 INV:27 ENV:27
Fig.10bus info Fig.11Parallel info Fig.12Temperature info
Page 18
16
6) Select and confirm the status info can view the details, including status information, alarm information, code, power rating and version (see Fig 13 to 14).
STATUS Code11 Fault 0. 0.0.0 Model06.0KVA
STATUS Version V03B05D002
Fig.13main menu Fig.14main menu
7) Select and confirm setting menu, setting information will be displayed on the screen, which includes user set, system set, parallel set, battery sett, revise set (see Fig 15 to 19).
SETTING Mode NOR Batt num16 Batt cap7AH
SETTING V-Level 220V F-Level50Hz
Fig.15setting menu Fig.16setting menu
SETTING V-upper 15% V-lower -45%
SETTING Buzzer Enable
Fig.17setting menu Fig.18setting menu
SETTING Parallel set ID 1
P-amount 2 P-Redund 0
Fig.29Parallel setting
4.4 Working mode and
transferring
Usually, the UPS should be set to work in AC mode, so it will transfer to battery mode
automatically without interruption when AC fails. When the UPS is overloaded, it will
transfer
to
bypass mode without interruption. When the inverter is defective or over temperature
occurred inside the UPS, the UPS will transfer to bypass mode if the bypass is normal.
4.4.1 Transfer to bypass if overload
When the load of UPS is beyond normal range and lasts for the time set, it will
Page 19
17
transfer to bypass mode and beeps twice every second, then the load is powered by AC directly. Please decrease the load immediately until the alarm is eliminated. The UPS will start the inverter after 5 min. In order to protect the load and the UPS, it is required to set the limitation times of transferring to bypass mode due to overload in 1 hour. If it exceeds the limitation times set, the UPS will keep in bypass mode.
4.4.2 Normal mode to battery mode
The UPS will go to battery mode if the AC is failed. The UPS will shut down automatically if batteries are drained. When AC recovers, the UPS will start the inverter automatically.
4.4.3 Go to bypass mode due to over temperature
The temperature inside UPS may be high if ambient temperature is high or the ventilation is poor, then the UPS will go to Bypass mode, fault indicator will be on (red), the LCD will display that the inner temperature is high, long beeps will come. If so, please cut off the input power of the UPS, move objects that affecting the ventilation far from the UPS if any or increase the distance between the UPS and the wall. Wait until the UPS temperature becomes normal then restart it.
4.4.4 Output short circuit
When the UPS output is in short circuit, the UPS will cut off the output, fault indictor will be on (red), the LCD will display output is in short circuit, long beeps come. If so, please disconnect the load in short circuit, cut off the UPS input power and wait for 10mins, the UPS will shut down automatically or press the off button to shut down in after10s. Before restarting the UPS, please make sure that the short circuit problem has been solved.
4.5 UPS monitoring
Please refer to the instruction of the UPS monitoring software provided.
4.6 LCD operation menu
1 Main menu switching
Pressing the left/right arrow and ENT button can switch among alarm info, running parameter and function settings. Press ENT to enter alarm info, running parameters or function settings. To enter function settings, double pressing on ENT is required.
2 Submenu switching
1) Press the arrow button can view the details after entering the running function interface, and press ESC to return to main menu.
2) Press the arrow button can view the details after entering the function settings interface, press the ESC to return to main menu.
3) Parameter which has been selected and changed will be highlighted. Press arrow
Page 20
18
button to change the value and press ENT to confirm it. Once confirmed, it will not be highlighted.
4) Press the arrow button can view the detailed alarm info after entering the alarm info interface, press the ESC to return to main menu.
3 Priority of info displayed on LCD
1) If there is alarm but no valid operation on buttons, the alarm info with top priority will be shown on LCD automatically.
2) When there isn’t any alarm and the LCD is displaying the submenu of running parameters, such as output current, these parameters will be always displayed on the LCD if no further operation on buttons. If the LCD is not displaying the submenu of running parameters, it will return to main menu in 30s as long as there isn’t any operation on buttons.
Page 21
19
5Maintenance
Please follow the installations notes under section 3.4. to install the UPS.
5.1 Ventilator maintenance
The continuous operating time of fan is 20000 to 40000 hours. This time will be shorten if the temperatures increases. Please check the fan periodically and ensure that it blows wind out.
5.2 Battery maintenance
Inside the series standard models are maintenance free, sealed lead acid batteries. The service lifetime of the battery depends on environmental temperature and the discharging / charging cycles. It will be shorten when temperature is rising or if the battery is deeply discharged. Therefore, a regular maintenance is recommended to keep the batteries in good condition.
1) Most appropriate operating temperature is 15-25°C.
2) Avoid small discharge current. Don’t let operate the UPS continuously during 24 hours in battery mode.
3) Charge the battery every 3 months for at least 12 hours if the battery has not been used. If the ambient temperature is high, you have to charge it every 2 months.
4) Check and clean the battery connections regularly on the models with long back-up.
If autonomy time becomes much shorter than before or if a battery default is displayed on LCD, then contact your distributor to clear up if the batteries need to be replaced or not.
CAUTION! a) Do not short-circuit the battery, otherwise this may cause fire.
b) Do not open or damage the battery: released electrolytes are harmful to eyes and skin.
5.3 Visual control
Keep the ventilation of UPS in good condition.
5.4 Control of UPS status
1) Verify if any fault did happen, a fault indicator lights or any alarm is indicated.
2) Search and find the cause when the UPS is operating in bypass mode.
3) When the UPS is operating in battery mode, then make sure that it is normal; otherwise search and find the cause.
Page 22
20
5.5 Function control
Check the functions every 6 months.
1) Press the OFF-key to determine if buzzer, indicators and LCD-display are operating normally or not. Refer for that to section «4.1 Operation modes».
2) Press the ON-key, check indicators, LCD-display and inverter of the UPS. Assure yourself, that they are all operating normally.
3) To ensure that the battery is in good condition, perform a battery test when the UPS is operating in normal condition.
Appendix 1 Specifications
Capacity
6KVA/5.4W 10KVA/9KW
T
ype
6KVA10KVA
I
nput
Input mode
Three phase +N+ Ground
Power factor
0.99
rating voltage
380/400/415VAC or 220/230/240VAC
rating frequency
50Hz/60Hzauto sensing
Voltage range
208~478VAC
Frequency range
45~55Hz/54~66Hz
Bypass voltage range
220Vac max:10%,15%,20% or 25%,default :25% 230Vac max10%15% or 20%default +20% 240Vac max+10% or 15%default +15%
min20%, 30% or 45%, default 45%
Bypass frequency range
±1%±2%±4%±5%±10%
THDI
3%100% linear load, input THDV 1%)
5% 100% non-linear loadinput THDV 1%
B attery
Battery number
16/18/20pcscan be set
Battery type
VRLA
Charge model
Boost charge or float charge auto switch
Charge time
Boost charge up to 20Hr(Max)
Charge current (A)
1A(S)/10A(H)
O utpu
Output type
Single phase + Ground
Output precision
1.0%
Voltage distortion(THD)
2% at 100% linear load
5% at 100% non-linear load
Rating voltage
220/230V /240V
Frequency precision
±0.1%
Page 23
21
Rating Frequency
50Hz/60Hz
Frequency track speed
1Hz/s
Overload
105%~110%1Hr
110%~125% 10min
125%~150% 1min
150% 200ms
Peak value factor
3:1
Efficiency at normal
90%
Dynamic respond
5.0%
20ms
DC hef
t
500mV
Switch
Between Normal mode
and battery mode
0ms
Between inverter and
bypass
0ms
unlock:<15ms (50Hz), 13.33ms (60Hz)
Norse
<55dB (1m
Display
LCD+LED
Safety
Meeting IEC62040-1 GB4943
Max input voltage
320Vac1Hr
EMI
Conduction IEC 62040-2
Radiation IEC 62040-2
Harmonics IEC 62040-2
EMS
IEC 62040-2
MTBF
250,000Hr 11 400,000Hr
MTTR
30min
Isolation resistance
> 2M500Vdc
Isolation intension
2820Vdc<3.5mA1min
Surge
Meeting IEC60664-1 1.2/50uS+8/20uS 6kV/3kA
Protection
IP20
Parallel circumfluence
118%N13%
Parallel equal current
118%N110%
Page 24
22
Appendix 2 Communication port definition
USB communication port:
1
2
4
3
Definition of male port
Pin 1 VCC, Pin 2 D­pin 3 D+, Pin 4 GND
Application: use UPSilon2000 Power Management software
Available functions of the USB
Monitor UPS power status
Monitor UPS alarm info
Monitor UPS running parameters
Timing off/on setting
Appendix 3 Option
1. Dry contact card
2. SNMP card
3. Parallel card
Page 25
23
Appendix 4 UPS message table
This section lists the event and alarm messages that the UPS might display. The messages are listed in alphabetical order. This section is listed with each alarm message to help you troubleshoot problems.
4.1 Operational Status and Mode(s)
Note“X” shows that it will determined by other conditions.
4.2 Alarm Information
Item UPS Alarm Warning
Buzz
LED
1
Rectifier Fault
Beep continuously
Fault LED lit
2
Inverter fault(Including Inverter bridge is shorted)
Beep continuously
Fault LED lit
3
Inverter Thyristor short
Beep continuously
Fault LED lit
4
Inverter Thyristor broken
Beep continuously
Fault LED lit
5
Bypass Thyristor short
Beep continuously
Fault LED lit
6
Bypass Thyristor broken
Beep continuously
Fault LED lit
7
Fuse broken
Beep continuously
Fault LED lit
8
Parallel relay fault
Beep continuously
Fault LED lit
9
Fan fault
Beep continuously
Fault LED lit
10
Reserve
Beep continuously
Fault LED lit
11
Auxiliary power fault
Beep continuously
Fault LED lit
12
Initialization fault
Beep continuously
Fault LED lit
13
P-Battery Charger fault
Beep continuously
Fault LED lit
14
N-Battery Charger fault
Beep continuously
Fault LED lit
15
DC Bus over voltage
Beep continuously
Fault LED lit
16
DC Bus below voltage
Beep continuously
Fault LED lit
17
DC bus unbalance
Beep continuously
Fault LED lit
18
Soft start failed
Beep continuously
Fault LED lit
Page 26
24
Item UPS Alarm Warning
Buzz
LED
19
Rectifier Over Temperature
Twice per second
Fault LED lit
20
Inverter Over temperature
Twice per second
Fault LED lit
21
Reserve
Twice per second
Fault LED lit
22
Battery reverse
Twice per second
Fault LED lit
23
Cable connection error
Twice per second
Fault LED lit
24
CAN comm. Fault
Twice per second
Fault LED lit
25
Parallel load sharing fault
Twice per second
Fault LED lit
26
Battery over voltage
Once per second
Fault LED blinking
27
Mains Site Wiring Fault
Once per second
Fault LED blinking
28
Bypass Site Wiring Fault
Once per second
Fault LED blinking
29
Output Short-circuit
Once per second
Fault LED blinking
30
Rectifier over current
Once per second
Fault LED blinking
31
Bypass over current
Once per second
BPS LED blinking
32
Overload
Once per second
INV or BPS blinking
33
No battery
Once per second
BATTERY bli nking
34
Battery under voltage
Once per second
BATTERY bli nking
35
Battery low pre-warning
Once per second
BATTERY bli nking
36
Internal Communication Error
Once per second
Bypass LED lit
37
DC component over limit.
Once per 2 seconds
INV blinking
38
Parallel Overload
Once per 2 seconds
INV blinking
39
Mains volt. Abnormal
Once per 2 seconds
BATTERY LED lit
40
Mains freq. abnormal
Once per 2 seconds
BATTERY LED lit
41
Bypass Not Available
BPS blinking
42
Bypass unable to trace
BPS blinking
43
Inverter on invalid
▪ ▪ ▪ ▪ ▪
Loading...