Vision™ OPLC™ Installation Guide
V130-33-TA24/V130-J-TA24
V350-35-TA24/V350-J-TA24
V430-J-TA24
12 Digital Inputs, including 2 Analog,
2 PT100/TC ,1 HSC/Shaft-encoder input
10 Transistor Outputs, 2 Analog Outputs
General Description
All of the controllers covered in this guide are micro-OPLCs, rugged programmable logic controllers that
comprise built-in operating panels and on-board I/Os.
Item
On-board I/O Model Dependent
Screen 2.4" 3.5" Color Touch 4.3" Color Touch
Keypad Yes None
Function Keys None Yes
Com Port, Built-in
RS232/485 Yes Yes Yes Yes Yes*
USB device,
mini-B
Com Ports, separate
order, user-installed
* V430J comprises both RS232/485 and USB ports; note that only one channel may be used at a time.
The user may install a CANbus port (V100-17-CAN), and one of the following:
V130-TA24
V130J-TA24
None None None None Yes*
• RS232/RS485 port (V100-17-RS4/V100-17-RS4X)
• Ethernet (V100-17-ET2)
• Profibus Slave (V100-17-PB1)
Standard Kit Contents
Item
Controller Yes
Terminal Blocks Yes
Battery (installed) Yes
Slides
(2 sets of key labels)
Mounting Brackets Yes (2 parts) Yes (4 parts)
Rubber Seal Yes
Programming cable
+ RS232 adapter
USB
programming cable
V130-TA24
V130J-TA24
None Yes None
Yes None
None Yes
V350-TA24
V350J-TA24
V350-TA24
V350J-TA24
V430J-TA24
V430J-TA24
Unitronics 1
![](/html/8d/8dff/8dffce288f1c1fb0afaf3a07f21daf6132d8c706d3c48c04c32db4457738f2ab/bg2.png)
Vision™ OPLC™ Installation Guide
Alert Symbols and General Restrictions
When any of the following symbols appear, read the associated information carefully.
Symbol Meaning Description
Danger The identified danger causes physical and property damage.
Warning The identified danger could cause physical and property damage.
Caution Caution Use caution.
Before using this product, the user must read and understand this document.
All examples and diagrams are intended to aid understanding, and do not guarantee operation.
Unitronics accepts no responsibility for actual use of this product based on these examples.
Please dispose of this product according to local and national standards and regulations.
Only qualified service personnel should open this device or carry out repairs.
Failure to comply with appropriate safety guidelines can cause severe injury or property
damage.
Do not attempt to use this device with parameters that exceed permissible levels.
To avoid damaging the system, do not connect/disconnect the device when power is on.
Environmental Considerations
Do not install in areas with: excessive or conductive dust, corrosive or flammable gas,
moisture or rain, excessive heat, regular impact shocks or excessive vibration, in
accordance with the standards given in the product’s technical specification sheet.
Do not place in water or let water leak onto the unit.
Do not allow debris to fall inside the unit during installation.
Ventilation: 10mm space required between controller’s top/bottom edges & enclosure walls.
Install at maximum distance from high-voltage cables and power equipment.
Mounting
Note that figures are for illustrative purposes only.
Dimensions: V130/V350/V130J/V350J
* Note that for models V130J/V350J, the bezel width is 6.7 mm (0.26”).
2 Unitronics
![](/html/8d/8dff/8dffce288f1c1fb0afaf3a07f21daf6132d8c706d3c48c04c32db4457738f2ab/bg3.png)
Vision™ OPLC™
Dimensions: V430J
Panel Mounting
Before you begin, note that the mounting panel cannot be more than 5 mm thick.
UL listed models:
To meet the UL508 standard, panel-mount the device on the flat surface of a Type 1 enclosure.
1. Make a panel cut-out of the appropriate size:
V130/V350/V130J/V350J: 92x92 mm (3.622”x3.622”).
V430J: 122.5x91.5 mm (4.82”x3.6”).
2. Slide the controller into the cut-out, ensuring that the rubber seal is in place.
3. Push the mounting brackets into their slots on the sides of the panel as shown in the figure below.
4. Tighten the bracket’s screws against the panel. Hold the bracket securely against the unit while
tightening the screw.
5. When properly mounted, the controller is squarely situated in the panel cut-out as shown in the
accompanying figures.
V130/V350/V130J/V350J
Unitronics 3
![](/html/8d/8dff/8dffce288f1c1fb0afaf3a07f21daf6132d8c706d3c48c04c32db4457738f2ab/bg4.png)
Vision™ OPLC™ Installation Guide
V430J
DIN-rail Mounting (V130/V350/V130J/V350J)
1. Snap the controller onto the DIN rail as
shown in the figure to the right.
2. When properly mounted, the controller is
squarely situated on the DIN-rail as
shown in the figure to the right.
4 Unitronics