Viessmann BW 110, Vitocal 350, BW 113, BW 116, BW 212 Datasheet

...
Page 1
VITOCAL 300 Typ e BW and WW
Up to 55 °C flow temperature Heat pump with electric drive for DHW and central heating
in mono or dual-mode heating systems
&
Brine/water heat pump
(typeBW)with6.4to32.6kW
&
(type WW = type BW plus conversion kit) with8.4to43.0kW
VITOCAL 350 Type BWH and WW H
Up to 65 °C flow temperature Heat pump with electric drive for DHW and central heating
in mono or dual-mode heating systems
&
Brine/water heat pump
(typeBWH)with11.0and17.1kW
&
(type WWH = type BWH plus conversion kit) with 14.1 and 20.0 kW
VIESMANN
Datasheet
Part numbers and prices: see pricelist
VITOCAL 300/350
Heat pump
Brine/Water – 6.4to32.6kW
Water/Water – 8.4to43.0kW
File in:
Vitotec folder, regi ster 11
5822 119-7 GB 4/2007
Page 2
Brine/water heat pump (type BW/BWH) with g round probe
Typ e BW/B WH – heat from the ground:
The Vitocal 300/350 extracts heat from the ground with the help of ground collectors or ground probes. The groun d provides almost completely stable temperatures all the year round, enabling the Vitocal 300/350 to operate virtually independently of the outside temperature. It can cover the entire heat demand of a building, even on colder days.
Brine/water heat pump (type BW/BWH) with ground collector
Water/water heat pump (type WW/WWH) wi th supply and return wells
Type WW/WWH – heat fr om water:
The Vitocal 300/350 draws energy from groundwater, where the temperature is stable, and therefore achieves consistently high performance factors. This means that it is suitable for year round heating operation and DHW provision.
5822 119-7 GB
2 VIESMANN VITOCAL 300/350
Product d escription
Page 3
&
Suitable for all operating modes: – Provides all DHW and central heating in mono-mode opera-
tion
– Can operate in dual-mode with a second heat source, e.g. in
modernisation projects
&
Achieves high performance factors: – up to 4.61 to DIN EN 255 with the Vitocal 300 BW
(brine: 0 °C, flow temperature: 35 °C)
– up to 5.9 to DIN EN 255 with the Vitocal 300 WW
(groundwater: 10 °C, flow temperature: 35 °C)
&
Can cover any heating requirement all the year round
&
High operational safety, reliability and quiet running through hermetically sealed Compliant scroll compressor with dual anti­vibration mounts
&
Especially s uitable for low heating system temperatures, e.g. underfloor heating
&
Vitocal 350 with 65 °C flow temperature for use in systems with radiators used in modernisation projects
&
Weather-compensated, digital heat pump control unit CD 60 with i ntegral cooling function. Menu-guided functions with plain text support and integral diagnostic system
Vitocal 300
A Evaporator
B Condenser
C Weather-compensated, digital heat pump control unit CD 60
D Hermetically sealed Compliant scroll compressor
E Additional heat exchanger
5822 119-7 GB
VITOCAL 300/350 VIESMANN 3
Benefits
Page 4
Vitocal 300 brine/water heat pump (single stage)
Vitocal 300 (single stage) Type BW 106 BW 108 BW 110 BW 113 BW 116 Output data
*
1
Rated heating output kW 6.4 8.3 10.8 14.0 16.3 Refrigerating capacity kW 5.00 6.50 8.40 10.95 12.70 Power consumption kW 1.40 1.80 2.40 3.05 3.60 Coefficient of Performance (COP) 4.57 4.61 4.50 4.59 4.53 Brine (primary) Content litre 2.3 2.8 3.7 4.7 4.7 Min. throughput
*
2
l/h 1600 2100 2700 3600 3900 Pressure dro p mbar 90 90 90 90 105 Max. inlet temperature °C 25 25 25 25 25 Min. inl et temperature °C –5 – 5 –5 –5 –5 Heating water (secondary) Content litre 1.6 2.2 2.7 3.3 3.3 Min. throughput l/h 530 700 950 1200 1400 Pressure dro p mbar 40 40 40 40 60 Max. flow temperature °C 55 55 55 55 55
Electrical values
Heat pump Rated voltage 3/N/PE 400 V/50 Hz Rated current (max.) A 4.8 6.6 7.9 10.0 13.3 Starting current A 27 14
*
3
20
*
3
23
*
3
26
*
3
Starting current (with stalled armature)
A 31.0 43.5 51.0 59.5 70.5
Fuse(slow) A 3×10 3×16 3×16 3×16 3×20 Protection IP 20 Control circuit rated voltage 230 V/50 Hz Fuse (internal) 6.3 A H (slow)
Refrigerant circuit
Refrigerant R 407 C Fill volume kg 1.9 2.2 2.6 3.1 3.4 Compressor Type Hermetically sealed scroll compressor
Dimensions
Total length mm 650 650 650 650 650 Total width mm 600 600 600 600 600 Total height mm 945 945 945 945 945
Permissible operating pressure
Brine circuit (primary) bar 4 4 4 4 4 Heating water circuit (secondary) bar 4 4 4 4 4
Connections
Primary IN and OUT R 1" 1" 1¼" 1¼" 1¼" Heating flow and return R 1" 1" 1" 1" 1" Weight kg 110 120 140 160 165
5822 119-7 GB
4 VIESMANN VITOCAL 300/350
*1
At operati ng point B0/W35 to DIN EN 255: B0 = brine inlet t emperature 0 °C/W35 = heating water outlet temperature 35 °C. For furthe r operating points, see the output diagrams.
*2
Always safeguard the min. throughput.
*3
With starting current limiter.
Specification
Page 5
Vitocal 300 brine/water heat pump (two-stage)
Vitocal 300 (two-stage) Type BW 212 BW 216 BW 220 BW 226 BW 232 Output data
*
1
Rated heating output kW 12.8 16.6 21.6 28.0 32.6 Refrigerating capacity kW 10.0 13.0 16.8 21.9 25.4 Power consumption kW 2.8 3.6 4.8 6.1 7.2 Coefficient of Performance (COP) 4.56 4.60 4.49 4.57 4.51 Brine (primary) Content litre 4.6 5.6 7.4 9.4 9.4 Min. throughput
*
2
l/h 3200 4200 5400 7200 7800 Pressure dro p mbar 100 100 100 100 120 Max. inlet temperature °C 25 25 25 25 25 Min. inl et temperature °C –5 – 5 –5 –5 –5 Heating water (secondary) Content litre 3.2 4.4 5.4 6.6 6.6 Min. throughput
*
2
l/h 1100 1400 1900 2400 2800 Pressure dro p mbar 100 100 100 100 130 Max. flow temperature °C 55 55 55 55 55
Electrical values
Heat pump Rated voltage 3/N/PE 400 V/50 Hz Rated current (max.) A 9.6 13.2 15.8 20.0 26.6 Starting current (per compressor) A 27 14
*
3
20
*
3
23
*
3
26
*
3
Starting current (per compressor) (with stalled armature)
A 31.0 43.5 51.0 59.5 70.5
Fuse(slow) A 3×16 3×20 3×20 3×35 3×35 Protection IP 20 Control circuit rated voltage 230 V/50 Hz Fuse (internal) 6.3 A H (slow)
Refrigerant circuit
Refrigerant R 407C Fillvolume kg 2×1.9 2×2.2 2×2.6 2×3.1 2×3.4 Compressor Type 2 hermetically sealed scroll compressors
Dimensions
Total length mm 650 650 650 650 650 Total width mm 780 780 780 780 780 Total height mm 1245 1245 1245 1245 1245
Permiss. operating pressure
Brine circuit (primary) bar 4 4 4 4 4 Heating water circuit (secondary) bar 4 4 4 4 4
Connections
Primary IN and OUT R 1" 1¼" 1¼" 1½" 1½" Heating flow and return R 1" 1" 1" 1" 1" Weight kg 250 270 280 300 310
5822 119-7 GB
VITOCAL 300/350 VIESMANN 5
*1
At operati ng point B0/W35 to DIN EN 255: B0 = brine inlet t emperature 0 °C/W35 = heating water outlet temperature 35 °C. For furthe r operating points, see the output diagrams.
*2
Always safeguard the min. throughput.
*3
With starting current limiter.
Specification (cont.)
Page 6
Vitocal 300 water/water heat pump (single stage)
Vitocal 300 (single stage) Type WW 106 WW 108 WW 110 WW 113 WW 116 Output data
*
1
Rated heating output kW 8.4 10.9 14.2 18.3 21.5 Refrigerating capacity kW 6.90 9.00 11.70 15.20 17.80 Power consumption kW 1.50 1.90 2.50 3.10 3.70 Coefficient of Performance (COP) 5.60 5.74 5.68 5.90 5.81 Groundwater (primary) Content litre 2.3 2.8 3.7 4.7 4.7 Min. throughput
*
2
l/h 1600 2100 2700 3600 3900 Pressure dro p mbar 90 90 90 90 105 Max. inlet temperature °C 25 25 25 25 25 Min. inl et temperature
at min. throughput °C 7.5 7.5 7.5 7.5 7.5at min. throughput +40 °C 6.5 6.5 6.5 6.5 6.5
Heating water (secondary) Content litre 1.6 2.2 2.7 3.3 3.3 Min. throughput
*
2
l/h 580 730 1000 1250 1500 Pressure dro p mbar 45 45 45 40 60 Max. flow temperature °C 55 55 55 55 55
Electrical values
Heat pump Rated voltage 3/N/PE 400 V/50 Hz Rated current (max.) A 4.8 6.6 7.9 10.0 13.3 Starting current A 27 14
*
3
20
*
3
23
*
3
26
*
3
Starting current (with stalled armature)
A 31.0 43.5 51.0 59.5 70.5
Fuse(slow) A 3×10 3×16 3×16 3×16 3×20 Protection IP 20 Control circuit rated voltage 230 V/50 Hz Fuse (internal) 6.3 A H (slow)
Refrigerant circuit
Refrigerant R 407 C Fill volume kg 1.9 2.2 2.6 3.1 3.4 Compressor Type Hermetically sealed scroll compressor
Dimensions
Total length mm 650 650 650 650 650 Total width mm 600 600 600 600 600 Total height mm 945 945 945 945 945
Permissible operating pressure
Groundwater circuit (primary) bar 4 4 4 4 4 Heating water circuit (secondary) bar 4 4 4 4 4 Intermediate circuit for indirect operation bar 4 4 4 4 4
Connections
Primary IN and OUT R 1" 1" 1¼" 1¼" 1¼" Heating flow and return R 1" 1" 1" 1" 1" Weight kg 110 120 140 160 165
5822 119-7 GB
6 VIESMANN VITOCAL 300/350
*1
At operati ng point W10/W35 to DIN EN 255: W10 = groundwater inlet temperature 10 °C/W35 = heating water outlet temperature 35 ° C. For furthe r operating points, see the output diagrams.
*2
Always safeguard the min. throughput.
*3
With starting current limiter.
Specification (cont.)
Page 7
Vitocal 300 water/water heat pump (two-stage)
Vitocal 300 (two-stage) Type WW 212 WW 216 WW 220 WW 226 WW 232
Output data
*
1
Rated heating output kW 16.8 21.8 28.4 36.6 43.0 Refrigerating capacity kW 13.80 18.00 23.40 30.40 35.60 Power consumption kW 3.00 3.80 5.00 6.20 7.40 Coefficient of Performance (COP) 5.58 5.72 5.66 5.87 5.79 Groundwater (primary) Content litre 4.6 5.6 7.4 9.4 9.4 Min. throughput
*
2
l/h 3200 4200 5400 7200 7800 Pressure dro p mbar 100 100 110 120 120 Max. inlet temperature °C 25 25 25 25 25 Min. inl et temperature
for min. throughput °C 7.5 7.5 7.5 7.5 7.5for min. throughput +40 °C 6.5 6.5 6.5 6.5 6.5
Heating water (secondary) Content litre 3.2 4.4 5.4 6.6 6.6 Min. throughput
*
2
l/h 1160 1460 2000 2500 3000 Pressure dro p mbar 105 105 105 110 110 Max. flow temperature °C 55 55 55 55 55
Electrical values
Heat pump Rated voltage 3/N/PE 400 V/50 Hz Rated current (max.) A 9.6 13.2 15.8 20.0 26.6 Starting current (per compressor) A 27 14
*
3
20
*
3
23
*
3
26
*
3
Starting current (per compressor) A 31.0 43.5 51.0 59.5 70.5 (with stalled armature) Fuse(slow) A 3×16 3×20 3×20 3×35 3×35 Protection IP 20 Control circuit rated voltage 230 V/50 Hz Fuse (internal) 6.3 A H (slow)
Refrigerant circuit
Refrigerant R 407 C Fill volume kg 2 × 1.9 2 × 2.2 2 × 2.6 2 × 3.1 2× 3.4 Compressor Type 2 hermetically sealed scroll compressors
Dimensions
Total length mm 650 650 650 650 650 Total width mm 780 780 780 780 780 Total height mm 1245 1245 1245 1245 1245
Permissible operating pressure
Groundwater circuit (primary) bar 4 4 4 4 4 Heating water circuit (secondary) bar 4 4 4 4 4 Intermediate circuit for indirect operation
bar 4 4 4 4 4
Connections
Primary IN and OUT R 1" 1¼" 1¼" 1½" 1½" Heating flow and return R 1" 1" 1" 1" 1" Weight kg 250 270 280 310 320
5822 119-7 GB
VITOCAL 300/350 VIESMANN 7
*1
At operati ng point W10/W35 to DIN EN 255: W10 = groundwater inlet temperature 10 °C/W35 = heating water outlet temperature 35 ° C. For furthe r operating points, see the output diagrams.
*2
Always safeguard the min. throughput.
*3
With starting current limiter.
Specification (cont.)
Page 8
Vitocal 350 brine/water heat pump (single stage)
Vitocal 350 (single stage) Type BWH 110 BWH 113 Output data
At operati ng point
*
1
B0/W35 B2/W55 B2/W65 B0/W35 B2/W55 B2/W65 Rated output kW 11.0 13.2 13.2 16.2 17.7 17.7 Refrigerating capacity kW 8.45 9.00 8.10 12.45 12.00 10.60 Power consumption kW 2.55 4.20 5.10 3.75 5.70 7.10 Coefficient of Performance (COP) 4.31 3.14 2.59 4.32 3.11 2.49 Brine (primary) Content litre 3.7 4.7 Min. throughput
*
2
l/h 2700 3800 Pressure dro p mbar 90 100 Max. inlet temperature °C 20 20 Min. inl et temperature °C -5 -5 Heating water (secondary) Content litre 3.3 3.3 Min. throughput
*
2
l/h 1060 1350 Pressure dro p mbar 40 35 Max. flow temperature °C 65 65
Electrical values
Heat pump Rated voltage 3/N/PE 400 V/50 Hz Rated current (max.) A 9.1 14.0 Starting current A 23
*
3
26
*
3
Starting current A 59.5 70.5 (with stalled armature) Fuse (slow) A 3 × 20 3 × 20 Protection IP 20 Control circuit rated voltage 230 V/50 Hz Fuse (internal) 6.3 A H (slow)
Refrigerant circuit
Refrigerant R 407 C Fill volume kg 2.9 3.2 Compressor Type Hermetically sealed scroll compressor with injection
Dimensions
Total length mm 650 650 Total width mm 600 600 Total height mm 945 945
Permissible operating pressure
Brine circuit (primary) bar 4 4 Heating water circuit (secondary) bar 4 4
Connections
Primary IN and OUT R 1¼" 1¼" Heating flow and return R 1" 1" Weight kg 145 165
5822 119-7 GB
8 VIESMANN VITOCAL 300/350
*1
Operating point to DIN EN 255: B0 = brine inlet temperature 0 °C/W35 = heating water outlet temperature 35 °C. Operating point: B2 = brine inlet temperature 2 °C/W35 = heating water outlet temperature 55 °C. Operating point: B2 = brine inlet temperature 2 °C/W35 = heating water outlet temperature 65 °C. For furthe r operating points, see the output diagrams.
*2
Always safeguard the min. throughput.
*3
With starting current limiter.
Specification (cont.)
Page 9
Vitocal 350 water/water heat pump (single stage)
Vitocal 350 (single stage) Type WWH 110 WWH 113 Output data
At operati ng point
*
1
W10/W35 W8/W55 W8/W65 W10/W35 W8/W55 W8/W65 Rated heating output kW 14.1 14.6 14.6 19.7 19.4 19.4 Refrigerating capacity kW 11.40 10.30 9.45 15.90 13.65 12.15 Power consumption kW 2.70 4.30 5.15 3.80 5.75 7.25 Coefficient of Performance (COP) 5.22 3.39 2.83 5.18 3.37 2 .68 Groundwater (primary) Content litre 3.7 4.7 Min. throughput
*
2
l/h 2700 3800 Pressure dro p mbar 90 100 Max. inlet temperature °C 20 20 Min. inl et temperature
for min. throughput °C 7.5 7.5for min. throughput +40 °C 6.5 6.5
Heating water (secondary) Content litre 3.3 3.3 Min. throughput
*
2
l/h 1060 1430 Pressure dro p mbar 40 45 Max. flow temperature °C 65 65
Electrical values
Heat pump Rated voltage 3/N/PE 400 V/50 Hz Rated current (max.) A 9.1 14.0 Starting current A 23
*
3
26
*
3
Starting current A 59.5 70.5 (with stalled armature) Fuse(slow) A 3×20 3×20 Protection IP 20 Control circuit rated voltage 230 V/50 Hz Fuse (internal) 6.3 A H (slow)
Refrigerant circuit
Refrigerant R 407 C Fill volume kg 2.9 3.2 Compressor Type Hermetically sealed scroll compressor with injection
Dimensions
Total length mm 650 650 Total width mm 600 600 Total height mm 945 945
Permissible operating pressure
Groundwater circuit (primary) bar 4 4 Heating water circuit (secondary) bar 4 4 Intermediate circuit for indirect operation
bar 4 4
Connections
Primary IN and OUT R 1¼" 1¼" Heating flow and return R 1" 1" Weight kg 145 165
5822 119-7 GB
VITOCAL 300/350 VIESMANN 9
*1
Operating point to DIN EN 255: W10 = groundwater i nlet temperature 10 °C/W35 = heating water outlet temperature 35 °C. Operating point: W8 = groundwater inlet temperature 8 °C/W55 = heating water outlet temperature 55 °C. Operating point: W8 = groundwater inlet temperature 8 °C/W65 = heating water outlet temperature 65 °C. For furthe r operating points, see the output diagrams.
*2
Always safeguard the min. throughput.
*3
With starting current limiter.
Specification (cont.)
Page 10
Dimensions
Left illustration - Vitocal 300/350, single stage; right illustration: Vitocal 300, two-stage
A Primary OUT (brine) B Primary IN (brine) C Cable entries
HR Heating return HV Heating flow
5822 119-7 GB
10 VIESMANN VITOCAL 300/350
Specification (cont.)
Page 11
Wall clearances
5822 119-7 GB
VITOCAL 300/350 VIESMANN 11
Specification (cont.)
Page 12
Vitocal 300, type BW 106 and WW 106 (single stage)
A Heating output B Refrigerating capacity C Power consumption D T
HV
=35°C
E T
HV
=45°C
F T
HV
=55°C
Note
COP details in the following tab les and diagrams calculated with reference to DIN EN 255.
Performance data type BW 106 Operating point B0/W35 B2/W45 B2/W55
Heating output kW 6.40 6.60 6.20 Refrigerating capa­city
kW 5.00 4.80 4.10
Power consumption kW 1.40 1.75 2.10 Coefficient of Performance (COP)
4.57 3.76 2.95
Performance data type WW 106 Operating point W10/W35 W8/W45 W8/W55
Heating output kW 8.40 7.60 7.30 Refrigerating capa­city
kW 6.90 5.75 5.05
Power consumption kW 1.50 1.85 2.25 Coefficient of Performance (COP)
5.60 4.11 3.24
5822 119-7 GB
12 VIESMANN VITOCAL 300/350
Output diagrams for the Vitocal 300 (single stage)
Page 13
Vitocal 300, type BW 108 and WW 108 (single stage)
A Heating output B Refrigerating capacity C Power consumption D T
HV
=35°C
E T
HV
=45°C
F T
HV
=55°C
Performance data type BW 108 Operating point B0/W35 B2/W45 B2/W55
Heating output kW 8.30 8.50 8.10 Refrigerating capa­city
kW 6.50 6.25 5.30
Power consumption kW 1.80 2.25 2.75 Coefficient of Performance (COP)
4.61 3.77 2.95
Performance data type WW 108 Operating point W10/W35 W8/W45 W8/W55
Heating output kW 10.90 9.90 9.50 Refrigerating capa­city
kW 9.00 7.55 6.65
Power consumption kW 1.90 2.35 2.85 Coefficient of Performance (COP)
5.74 4.21 3.33
5822 119-7 GB
VITOCAL 300/350 VIESMANN 13
Output diagrams for the Vitocal 300 (single stage) (cont.)
Page 14
Vitocal 300, type BW 110 and WW 110 (single stage)
A Heating output B Refrigerating capacity C Power consumption D T
HV
=35°C
E T
HV
=45°C
F T
HV
=55°C
PerformancedatatypeBW110 Operating point B0/W35 B2/W45 B2/W55
Heating output kW 10.80 11.10 10.60 Refrigerating capa­city
kW 8.40 8.10 7.00
Power consumption kW 2.40 3.00 3.60 Coefficient of Performance (COP)
4.50 3.70 2.94
PerformancedatatypeWW110 Operating point W10/W35 W8/W45 W8/W55
Heating output kW 14.20 12.90 12.40 Refrigerating capa­city
kW 11.70 9.80 8.68
Power consumption kW 2.50 3.10 3.75 Coefficient of Performance (COP)
5.68 4.16 3.31
5822 119-7 GB
14 VIESMANN VITOCAL 300/350
Output diagrams for the Vitocal 300 (single stage) (cont.)
Page 15
Vitocal 300, type BW 113 and WW 113 (single stage)
A Heating output B Refrigerating capacity C Power consumption D T
HV
=35°C
E T
HV
=45°C
F T
HV
=55°C
PerformancedatatypeBW113 Operating point B0/W35 B2/W45 B2/W55
Heating output kW 14.00 14.40 13.90 Refrigerating capa­city
kW 10.95 10.65 9.35
Power consumption kW 3.05 3.75 4.55 Coefficient of Performance (COP)
4.59 3.84 3.05
PerformancedatatypeWW113 Operating point W10/W35 W8/W45 W8/W55
Heating output kW 18.30 16.70 16.10 Refrigerating capa­city
kW 15.20 12.85 11.40
Power consumption kW 3.10 3.85 4.70 Coefficient of Performance (COP)
5.90 4.34 3.43
5822 119-7 GB
VITOCAL 300/350 VIESMANN 15
Output diagrams for the Vitocal 300 (single stage) (cont.)
Page 16
Vitocal 300, type BW 116 and WW 116 (single stage)
A Heating output B Refrigerating capacity C Power consumption D T
HV
=35°C
E T
HV
=45°C
F T
HV
=55°C
PerformancedatatypeBW116 Operating point B0/W35 B2/W45 B2/W55
Heating output kW 16.30 16.70 16.10 Refrigerating capa­city
kW 12.70 12.20 10.70
Power consumption kW 3.60 4.50 5.40 Coefficient of Performance (COP)
4.53 3.71 2.98
PerformancedatatypeWW116 Operating point W10/W35 W8/W45 W8/W55
Heating output kW 21.50 19.60 18.90 Refrigerating capa­city
kW 17.80 15.00 13.30
Power consumption kW 3.70 4.60 5.60 Coefficient of Performance (COP)
5.81 4.26 3.37
5822 119-7 GB
16 VIESMANN VITOCAL 300/350
Output diagrams for the Vitocal 300 (single stage) (cont.)
Page 17
Vitocal 300, type BW 212 and WW 212 (two-stage)
A Heating output B Refrigerating capacity C Power consumption D T
HV
=35°C
E T
HV
=45°C
F T
HV
=55°C
Note
COP details in the following tab les and diagrams calculated with reference to DIN EN 255.
Performance data type BW 212 Operating point B0/W35 B2/W45 B2/W55
Heating output kW 12.80 13.20 12.40 Refrigerating capa­city
kW 10.00 9.60 8.20
Power consumption kW 2.80 3.50 4.20 Coefficient of Performance (COP)
4.56 3.75 2.94
Performance data type WW 212 Operating point W10/W35 W8/W45 W8/W55
Heating output kW 16.80 15.20 14.20 Refrigerating capa­city
kW 13.80 11.50 10.10
Power consumption kW 3.00 3.70 4.50 Coefficient of Performance (COP)
5.58 4.09 3.22
5822 119-7 GB
VITOCAL 300/350 VIESMANN 17
Output diagrams for the Vitocal 300 (two-stage)
Page 18
Vitocal 300, type BW 216 and WW 216 (two-stage)
A Heating output B Refrigerating capacity C Power consumption D T
HV
=35°C
E T
HV
=45°C
F T
HV
=55°C
Performance data type BW 216 Operating point B0/W35 B2/W45 B2/W55
Heating output kW 16.60 17.00 16.20 Refrigerating capa­city
kW 13.00 12.50 10.60
Power consumption kW 3.60 4.50 5.50 Coefficient of Performance (COP)
4.60 3.76 2.94
Performance data type WW 216 Operating point W10/W35 W8/W45 W8/W55
Heating output kW 21.80 18.80 19.00 Refrigerating capa­city
kW 18.00 15.10 13.30
Power consumption kW 3.80 4.70 5.70 Coefficient of Performance (COP)
5.72 4.19 3.31
5822 119-7 GB
18 VIESMANN VITOCAL 300/350
Output diagrams for the Vitocal 300 (two-stage) (cont.)
Page 19
Vitocal 300, type BW 220 and WW 220 (two-stage)
A Heating output B Refrigerating capacity C Power consumption D T
HV
=35°C
E T
HV
=45°C
F T
HV
=55°C
Performance data type BW 220 Operating point B0/W35 B2/W45 B2/W55
Heating output kW 21.60 22.20 21.20 Refrigerating capa­city
kW 16.80 16.20 14.00
Power consumption kW 4.80 6.00 7.20 Coefficient of Performance (COP)
4.49 3.69 2.93
Performance data type WW 220 Operating point W10/W35 W8/W45 W8/W55
Heating output kW 28.40 25.80 24.80 Refrigerating capa­city
kW 23.40 19.60 17.30
Power consumption kW 5.00 6.20 7.50 Coefficient of Performance (COP)
5.66 4.14 3.29
5822 119-7 GB
VITOCAL 300/350 VIESMANN 19
Output diagrams for the Vitocal 300 (two-stage) (cont.)
Page 20
Vitocal 300, type BW 226 and WW 226 (two-stage)
A Heating output B Refrigerating capacity C Power consumption D T
HV
=35°C
E T
HV
=45°C
F T
HV
=55°C
Performance data type BW 226 Operating point B0/W35 B2/W45 B2/W55
Heating output kW 28.00 28.80 27.80 Refrigerating capa­city
kW 21.90 21.30 18.70
Power consumption kW 6.10 7.50 9.10 Coefficient of Performance (COP)
4.57 3.82 3.00
Performance data type WW 226 Operating point W10/W35 W8/W45 W8/W55
Heating output kW 36.60 33.40 32.20 Refrigerating capa­city
kW 30.40 25.70 22.80
Power consumption kW 6.20 7.70 9.40 Coefficient of Performance (COP)
5.87 4.31 3.40
5822 119-7 GB
20 VIESMANN VITOCAL 300/350
Output diagrams for the Vitocal 300 (two-stage) (cont.)
Page 21
Vitocal 300, type BW 232 and WW 232 (two-stage)
A Heating output B Refrigerating capacity C Power consumption D T
HV
=35°C
E T
HV
=45°C
F T
HV
=55°C
Performance data type BW 232 Operating point B0/W35 B2/W45 B2/W55
Heating output kW 32.60 33.40 32.20 Refrigerating capa­city
kW 25.40 24.40 21.40
Power consumption kW 7.20 9.00 10.80 Coefficient of Performance (COP)
4.51 3.69 2.96
Performance data type WW 232 Operating point W10/W35 W8/W45 W8/W55
Heating output kW 43.00 39.20 37.80 Refrigerating capa­city
kW 35.60 30.00 26.60
Power consumption kW 7.40 9.20 11.20 Coefficient of Performance (COP)
5.79 4.24 3.35
5822 119-7 GB
VITOCAL 300/350 VIESMANN 21
Output diagrams for the Vitocal 300 (two-stage) (cont.)
Page 22
Vitocal 350, type BWH 110 and WWH 110
A Heating output B Refrigerating capacity C Power consumption D T
HV
=35°C
E T
HV
=45°C
F T
HV
=55°C
G T
HV
=65°C
Note
COP details in the following tab les and diagrams calculated with reference to DIN EN 255.
PerformancedatatypeBWH110 Operating point B0/W35 B2/W55 B2/W65
Heating output kW 11.00 13.20 13.20 Refrigerating capa­city
kW 8.45 9.00 8.10
Power consumption kW 2.55 4.20 5.10 Coefficient of Performance (COP)
4.31 3.14 2.59
PerformancedatatypeWWH110 Operating point W10/W35 W8/W55 W8/W65
Heating output kW 14.10 14.60 14.90 Refrigerating capa­city
kW 11.40 10.30 9.45
Power consumption kW 2.70 4.30 5.15 Coefficient of Performance (COP)
5.22 3.39 2.83
5822 119-7 GB
22 VIESMANN VITOCAL 300/350
Output diagrams for the Vitocal 350
Page 23
Vitocal 350, type BWH 113 and WWH 113
A Heating output B Refrigerating capacity C Power consumption D T
HV
=35°C
E T
HV
=45°C
F T
HV
=55°C
G T
HV
=65°C
PerformancedatatypeBWH113 Operating point B0/W35 B2/W55 B2/W65
Heating output kW 16.20 17.70 17.70 Refrigerating capa­city
kW 12.45 12.00 10.60
Power consumption kW 3.75 5.70 7.10 Coefficient of Performance (COP)
4.32 3.11 2.49
PerformancedatatypeWWH113 Operating point W10/W35 W8/W55 W8/W65
Heating output kW 19.70 19.40 19.40 Refrigerating capa­city
kW 15.90 13.65 12.15
Power consumption kW 3.80 5.75 7.25 Coefficient of Performance (COP)
5.18 3.37 2.68
5822 119-7 GB
VITOCAL 300/350 VIESMANN 23
Output diagrams for the Vitocal 350 (cont.)
Page 24
Complete compact design heat pump. With fitted, weather-compensated digital heat pump control unit, electronic starting current limiter (not for types BW/WW 104, 106 and 212) and adjustable anti-vibration feet; colour: Vitosilver. Additionally fo r type WW:
The water/water heat pump conversion kit comprises a flow limiter and frost stat.
Weather-compensated heat pump control unit CD 60
Digital control unit for heat pump systems with integral cooling and solar control functions, one heating circuit without mixer and up to two heating circuits with mixer (with cooling and solar control function, only one heating circuit with mixer), cylinder temperature control unit for two DHW cylinders, control of an additional heat source and control of up to 3 heat consumers.
Menu-guided operation with function-dependent plain text dis­plays, with diagnostic system and fault display in plain text. With outside and return temperature sensors.
Accessories
(subject to order, packed separately)
&
Divicon heating circuit distributor
&
Heating circuit pump
&
Safety equipment block with safety assembly
&
Three-way diverter valve R 1"
&
Instantaneous heating water heater
&
Heating water buffer cylinder
&
Cylinder temperature sensor
&
Remote control
&
Contact s ensor
&
Mixer motor
&
Central heating mixer
&
Collector temperature sensor
&
Solar collectors
&
Natural cooling contact humidistat
&
Fan convectors Vitoclima 200-C
&
Power-OFF conversi on kit
&
DHW cylinder
&
Electric i mmersion heater
Additional accessories for type BW/BWH
&
Brine accessories kit (assembled connection set) comprising: Pressure switch, air distributor, safety valve (3 bar), pressure gauge, fi ll and drain valves (2 pce.), fittings, shut-off valves, wall mounting bracket, connection for an expansion vessel, brine cir­cuit pump (supplied separately) and expansion vessel (supplied separately)
&
Brine distri butor ground collectors (10 × PE 20 × 2.0)
&
Brine distributor ground probes (4 × PE 25 × 2.3 or 4×PE32×2.9)
&
Brine circuit pressure switch
&
"Tyfocor" heat transfer medium
&
Three-way diverter valve R 1¼"
&
Plate-type heat exchanger
Additional accessories for type WW/WWH
Accessories for the groundwater circuit must be provided on site.
Design information
Positioning
Install the heat pump in a dry room free from the risk of frost. Carry out the airtight thermal insulation of the brine side of the heat pump installation in accordance with standard practice to prevent condensation and corrosion.
Pipework
Never use zinc-plated/galvanised pipes for the brine circuits.
Heat transfer medium
Order the required amount of Tyfocor for the entire system. Never di lute the premixed heat transfer medium with water (min. frost protection down to –15 °C).
5822 119-7 GB
24 VIESMANN VITOCAL 300/350
Delivered condition
Page 25
Drying buildings
The heat pump is not designed for the higher heat demand required when a building is b eing dried out. Should there be a higher heat demand to dry out a building, cover that demand with on-site equipment.
DHW cylinder
When selecting the DHW cylinder, ensure that its indirect coil sur­face area is large enough for the purpose. For connectable output, see the heat pumps technical guide or the manufacturer´s details.
Note
For heat pumps up to a rated heat output of 16 kW, we recom­mend the installation of the Vitocell 100-V, type CVW DHW cylin­der with 390 l capacity (for further details, see the separate datasheet). For heat pumps with a r ated heat output in excess of 16 kW, we recommend the installation of a cyl inder primary system w ith a Vitocell 100-V, type CVA (from 300 l capacity) in conjunction with a Vitotrans 100 plate-type heat exchanger (for further details, see the technical guide).
Tested quality
CE designation according to current EC Directives.
International quali ty seal for heat pumps.
Töss tested.
5822 119-7 GB
VITOCAL 300/350 VIESMANN 25
Design information (cont.)
Page 26
Viessmann Werke GmbH&Co KG D-35107 Allendorf Telephone: +49 6452 70-0 Fax: +49 6452 70-2780 www.viessmann.com
Subject to technical modifications.
Viessmann Limited Hortonwood 30, Telford Shropshire, TF1 7YP, GB Telephone: +44 1952 675000 Fax: +44 1952 675040 E-mail: info-uk@viessmann.com
5822 119-7 GB Printed on environmentally friendly,
chlorine-free bleached paper
26 VIESMANN VITOCAL 300/350