Technical Data Manual
Model Nos. and pricing: see Price List
VITOGAS 050
Cast iron hot water heating boiler
65 to 200 MBH / 19 to 59 kW
Vitogas 050
ECV Series
Gas-/Propane-Fired Boiler
cast iron construction
atmospheric
Heating input: 6 5 to 200 MBH
5167 449 v1.3 01/2008
19 to 59 kW

Product Information
Vitogas 050
Impressive performance, yet a very compact
design. Due to its compact dimensions, the
Vitogas 050 is ideal for installation in small
mechanical rooms and even in closets. In
addition to saving space, the Vitogas 050 is
economical in two ways - initial investment
and operational cost.
The benefits at a glance:
H Economical, compact,withintegrated
power vent for side wall venting only.
H High operational relia bility and a long
service life due to special high-grade gray
cast iron with lamellar graphite and
uniform heat transfer to avoid stress
fractures.
H Large diameter, stainless steel burners
provide quiet, reliable performance;
Annual Fuel Utilization Efficiency
(A.F.U.E.) of up to 83.1%.
H Optimal operation due to wide water
passageways and a wet-base, sectional
design.
H Compact dimensions – therefore suitable
for installation in almost any mechanical
room, or even closet installation.
H Problem-free transport into
difficult-to-access boiler rooms due to light
weight and compact design.
Heat exchanger surfaces of special
high-grade gray cast iron for high
operational reliability and a long
service life
2
5167 449 v1.3

Technical Data
Technical data
Boiler Model Model No. ECV-65 ECV-80 ECV-100 ECV-115 ECV-140 ECV-155 ECV-180 ECV-200
CSA input MBH
kW
CSA / DOE output MBH
kW
A.F.U.E.
Heat exchanger surface area ft
*1
% 83.1 83.1 83.1 83.1 83.1 83.1 83.1 83.1
2
2
m
Cast iron sections 3 3 4 4 5 5 6 6
Burners 2 2 3 3 4 4 5 5
Manifold pressure
Natural gas
Propane gas
Max. gas supply pressure
“w.c.
“w.c.
*2
“w.c. 14 14 14 14 14 14 14 14
Overall dimensions
Overall depth
inches
mm
Overall width
inches
mm
Overall height
inches
mm
Height of Vitocell-H
DHW tank under boiler
– 130 to 200 ltr /
34 to 53 USG capacity
inches
mm
65
19
55
16
14.32
1.33
3.5
10
19¾
502
13½
340
41½
1030
28¼
715
80
23
67
20
14.32
1.33
3.5
10
19¾
502
13½
340
41½
1030
28¼
715
100
29
84
25
21.10
1.96
3.5
10
19¾
502
17
432
41½
1030
28¼
715
115
34
97
28
21.10
1.96
3.5
10
19¾
502
17
432
41½
1030
28¼
715
140
41
118
35
27.99
2.60
3.5
10
19¾
502
21
533
41½
1030
155
45
131
38
27.99
2.60
3.5
10
19¾
502
21
533
41½
1030
–
–
180
53
151
44
34.88
3.24
3.5
10
19¾
502
25
635
41½
1030
200
59
168
49
34.88
3.24
3.5
10
19¾
502
25
635
41½
1030
–
–
– 350 ltr / 92 USG capacity
– 450 ltr / 120 USG capacity
Weight, boiler with insulation, lbs
burners and packaging kg
Boiler water content USG
Max. operating pr essure psig
inches
mm
inches
mm
ltr
kPa
33¼
847
243
110
2.6
9.9
50
345
33¼
847
–
–
243
110
2.6
9.9
50
345
33¼
847
293
133
3.5
13.2
50
345
33¼
847
–
–
293
133
3.5
13.2
50
345
33¼
847
37¼
947
364
165
4.3
16.5
50
345
33¼
847
37¼
947
364
165
4.3
16.5
50
345
33¼
847
37¼
947
430
195
7.1
26.8
50
345
Boiler connections
Boiler supply and return Ø”
1¼ 1¼ 1¼ 1¼ 1¼ 1¼ 1¼ 1¼
(male thread)
Gas supply connection Ø”
½ ½ ½ ½ ½ ½ ½ ½
(male thread)
Vent pipe collar
Maximum equivalent vent
length
*1
With intermittent pilot electronic ignition system and integrated power vent,
Vitogas ECV Series boilers exceed the Canadian and U.S. minimum A.F.U.E. requirement of 80%.
*2
If the gas supply pressure is highe r than the maximum permissible value, a separate field supplied gas regulator must be installed
upstream of the boiler gas train.
*3
Venting material to be 3” / 76 mm or 4” / 10 2 mm diameter (depending on maximum equivalent vent length, see above) stainless steel
*3
inches 3 3 3 3 3 3 3 3
ft./m 20 ft. / 6 m with 3” Ø vent pipe
30 ft. / 9 m with 4” Ø vent pipe
UL approved venting system for positive pressure. Do not use any other venting materials. See Price List.
33¼
847
37¼
947
430
195
7.1
26.8
50
345
"
For information regarding other Viessmann System Technology componentry, plea se reference documentation of the respective product.
5167 449 v1.3
3