Viessmann Vitogas 050, ECV-65, ECV-80, ECV-100, ECV-115 Technical Data Manual

...
Page 1
Technical Data Manual
Model Nos. and pricing: see Price List
VITOGAS 050
Cast iron hot water heating boiler
65 to 200 MBH / 19 to 59 kW
Vitogas 050
ECV Series
cast iron construction atmospheric Heating input: 6 5 to 200 MBH
5167 449 v1.3 01/2008
19 to 59 kW
Page 2
Product Information
Vitogas 050
Impressive performance, yet a very compact design. Due to its compact dimensions, the Vitogas 050 is ideal for installation in small mechanical rooms and even in closets. In addition to saving space, the Vitogas 050 is economical in two ways - initial investment and operational cost.
The benefits at a glance:
H Economical, compact,withintegrated
power vent for side wall venting only.
H High operational relia bility and a long
service life due to special high-grade gray
cast iron with lamellar graphite and uniform heat transfer to avoid stress fractures.
H Large diameter, stainless steel burners
provide quiet, reliable performance;
Annual Fuel Utilization Efficiency (A.F.U.E.) of up to 83.1%.
H Optimal operation due to wide water
passageways and a wet-base, sectional design.
H Compact dimensions – therefore suitable
for installation in almost any mechanical room, or even closet installation.
H Problem-free transport into
difficult-to-access boiler rooms due to light
weight and compact design.
Heat exchanger surfaces of special high-grade gray cast iron for high operational reliability and a long service life
2
5167 449 v1.3
Page 3
Technical Data
Technical data
Boiler Model Model No. ECV-65 ECV-80 ECV-100 ECV-115 ECV-140 ECV-155 ECV-180 ECV-200 CSA input MBH
kW
CSA / DOE output MBH
kW
A.F.U.E. Heat exchanger surface area ft
*1
% 83.1 83.1 83.1 83.1 83.1 83.1 83.1 83.1
2
2
m
Cast iron sections 3 3 4 4 5 5 6 6 Burners 2 2 3 3 4 4 5 5
Manifold pressure
Natural gas Propane gas
Max. gas supply pressure
“w.c. “w.c.
*2
“w.c. 14 14 14 14 14 14 14 14
Overall dimensions
Overall depth
inches mm
Overall width
inches mm
Overall height
inches
mm Height of Vitocell-H DHW tank under boiler – 130 to 200 ltr /
34 to 53 USG capacity
inches
mm
65 19
55 16
14.32
1.33
3.5 10
19¾
502
13½
340
41½
1030
28¼
715
80 23
67 20
14.32
1.33
3.5 10
19¾
502
13½
340
41½
1030
28¼
715
100
29
84 25
21.10
1.96
3.5 10
19¾
502
17
432
41½
1030
28¼
715
115
34
97 28
21.10
1.96
3.5 10
19¾
502
17
432
41½
1030
28¼
715
140
41
118
35
27.99
2.60
3.5 10
19¾
502
21
533
41½
1030
155
45
131
38
27.99
2.60
3.5 10
19¾
502
21
533
41½
1030
180
53
151
44
34.88
3.24
3.5 10
19¾
502
25
635
41½
1030
200
59
168
49
34.88
3.24
3.5 10
19¾
502
25
635
41½
1030
– 350 ltr / 92 USG capacity
– 450 ltr / 120 USG capacity
Weight, boiler with insulation, lbs burners and packaging kg
Boiler water content USG
Max. operating pr essure psig
inches mm
inches mm
ltr
kPa
33¼
847
243 110
2.6
9.9
50
345
33¼
847
243 110
2.6
9.9
50
345
33¼
847
293 133
3.5
13.2
50
345
33¼
847
293 133
3.5
13.2
50
345
33¼
847
37¼
947
364 165
4.3
16.5
50
345
33¼
847
37¼
947
364 165
4.3
16.5
50
345
33¼
847
37¼
947
430 195
7.1
26.8
50
345
Boiler connections
Boiler supply and return Ø”
(male thread)
Gas supply connection Ø”
½ ½ ½ ½ ½ ½ ½ ½
(male thread)
Vent pipe collar
Maximum equivalent vent length
*1
With intermittent pilot electronic ignition system and integrated power vent, Vitogas ECV Series boilers exceed the Canadian and U.S. minimum A.F.U.E. requirement of 80%.
*2
If the gas supply pressure is highe r than the maximum permissible value, a separate field supplied gas regulator must be installed upstream of the boiler gas train.
*3
Venting material to be 3” / 76 mm or 4” / 10 2 mm diameter (depending on maximum equivalent vent length, see above) stainless steel
*3
inches 3 3 3 3 3 3 3 3 ft./m 20 ft. / 6 m with 3” Ø vent pipe
30 ft. / 9 m with 4” Ø vent pipe
UL approved venting system for positive pressure. Do not use any other venting materials. See Price List.
33¼
847
37¼
947
430 195
7.1
26.8
50
345
"
For information regarding other Viessmann System Technology componentry, plea se reference documentation of the respective product.
5167 449 v1.3
3
Page 4
Technical Data
FGC
BWS
GC
BWR
13” / 330 mm
3” / 76 mm
26½” / 673 mm
Overall width
Overall depth
Overall Height
32” / 813 mm
Legend
BWR Boiler Water Return BWS Boiler Water Supply FGC Flue Gas Collar GC Gas Connection
Vitogas 050, ECV Series Vitocell-H 100 or 300 (see separate Tec hnical Data Manuals)
Note: Support Bars are installed lengthwise for ECV-65 through ECV-115 and widthwise for ECV-140 through ECV-200. Widthwise installation is pictured. The Base Pan is installed between the boiler and the Support Bars (also shown).
Dimensions
Boiler
ECV -65 -80 -100 -115 -140 -155 -180 -200
Model
With Vitocell-H DHW tank under boiler
a inches
USG
ltr
mm
34 to
53
130 to
200
28¼
715
92
350
33¼
847
34 to
53
130 to
200
28¼
715
92
350
33¼
847
34 to
53
130 to
200
28¼
715
92
350
33¼
847
34 to
53
130 to
200
28¼
715
92
35092350
33¼
847
33¼
847
120
45092350
37¼
33¼
947
847
a
120
45092350
37¼
947
33¼
847
120
45092350
37¼
33¼
947
847
120
450
37¼
947
4
5167 449 v1.3
Page 5
Standard Equipment / Boiler Control Alternatives
Minimum Clearances to Combustibles
Closet installation, ECV-65 to -155 (top view) Alcove installation, ECV-180 and -200 (top view)
Technical Data
min. 1” 25 mm
Top clearance:
min. 6” / 150 mm
min. 18” 460 mm
Front of boiler
min. 1” 25 mm
min. 6” 150 mm
Recommended Minimum Service Clearances
For all Vitogas 050, ECV models
min. 18” 460 mm
min. 6” / 150 mm
min. 1” 25 mm
Top clearance: min. 18” 460 mm
Front of boiler
min. 1” 25 mm
Installation on combustible flooring
A Base Pan (Optional Equipment) must be ordered if the Vitogas 050, ECV Series is to be installed on combustible flooring. See Price List.
Top clearance:
min. 18” 460 mm
min. 18” 460 mm
Front of boiler
Standard Equipment
Boiler shell with mounted insulation jacket and atmospheric burners for natural gas or propane gas (as per order) conforming to local regulations.
Standard equipment includes 30 psig pressure relief valve, pressure gage, installation fittings, and clean ing brush.
5167 449 v1.3
min. 18” 460 mm
Boiler Control
Standard control (included with boiler)
control with temperature gage, adjustable high limit, and fixed high limit.
Vitotronic 200-H, HK1M Series (Optional Equipment)
Digital mixing valve mounted heating circuit control with outdoor reset function to operate a heating circuit with a mixing valve.
Mounting the Vitogas 050 on a Vitocell-H
The Vitogas 050 can be mounted on a Vitocell-H as shown previously to reduce the footprint of heating equipment in the mechanical room. Two Support Bars and one Base Pan are necessary. Order a Support Bar Kit from the Price List. Do not attempt to install combinations not listed in the Price List.
5
Page 6
System Design Considerations
System Design Considerations
The Vitogas 050 is designe d for closed loop, forced circulation hot water heating systems only.
Boiler selection
The boiler model size should be based on an accurate heat loss calculation of the building. The boile r selected must be compatible with the connected radiation.
Venting
The Vitogas 050, ECV Series boiler must be vented with AL 29-4C 3” or 4” (depending on maximum equivalent vent length required) stainless steel rigid positive pressure vent pipe. Do not use any other venting materials.
The boiler must be located so that the vent length is as short and direct as possible. All products of combustion must be safely vented to the outdoors. Do not common vent with any other appliance.
The vent terminal was certified by an independent testing agency to withstand 40 mph winds. This boiler may not be suitable for areas with frequent winds above 40 mph. The vent termination should be located on a wall that is least affected by prevailing winds. High winds may affect the boiler operation and/or degrade the exterior finish of the w all. If wind is a problem, then steps should be considered to protect the vent term inal from high winds, such as a fence or shrub.
Maximum equivalent vent le ngth
The maximum equivalent vent length (for all ECVSeriessizes)is20ft./6mof3”Ø pipe or 30 ft. / 9 m of 4” Ø pipe. Do not exceed the maximum equivalent vent length.
Details of venting instructions are found in the ECV Series Installation/Service Manual. To order venting materials, see Price List.
Warranty excerpts
Our warranty does not cover damages resulting from the following: – installation or service by unqualified and
not licensed personnel
– corrosion caused by flue gas condensation
due to low boiler water and/or return water temperatures
– operation with contaminated fill and
supplementary feed water For detailed w arranty information, please read warranty sheet supplied with product.
6
Combustion air supply
The boiler must not be located in areas or rooms where chemicals containing chlorine, bromine, fluorine, or other corrosive chemicals are stored. Examples include refrigerants, bleach, paint, paint thinner, hair spray, cleaning solvents, water s oftener salt, etc. The combustion air must not be contaminated with the above mentioned, or other aggressive or corrosive chemicals.
Boiler should never be installed in areas where excessive dust, high humidity, or risk of frost exist. Ensure adequate ventilation and supply of fr esh combustion air.
Consult Viessmann with uncertainties in regard to a suitable boiler installation location.
This boiler/burner unit needs c lean fresh air for safe operation and must be installed so that there are provisions for adequate combustion and ventilation air. For natural gas or propane, use the “Natural Gas Installation Code CAN/CSA-B149.1 or B149.2” (Canada), or “National Fuel Gas Code ANSI Z223.1” (USA), and/or provisions of local codes.
The sizing methods outlined in the above codes must be used when installing a round duct to supply combustion a ir from the outside. Observe local jurisdictional requirements.
System layout
The boiler water temperature limit is factory set to 167°F / 75°C. The boiler water temperature limit can be increased by altering the adjustable high limit to increase the supply water temperature. To minimize piping losses of the system however, we recommend that the radiation and domestic hot water production in the system be designed for a 158°F / 70°C boiler supply water temperature (new systems).
Water quality
Treatment for boiler feed water should be considered in areas of known problems, such as where a high mineral content and hardness exist. In areas where freezing might occur, an antifreeze may be added to the system water to protect the system. Please adhere to the specifications given by the antifreeze manufacturer. Do not use automotive silicate based antifreeze. Please observe that an antifreeze/water mixture may require a backflow preventer within the automatic water feed and influence components such as diaphragm expansion tanks, radiation, etc. A 40% antifreeze content w ill provide freeze-up protection to
-10°F / -23°C. Do not use antifreeze other than specifically made for hot water heating systems. System also may contain components which might be negatively affected by antifreeze. Check total system frequently w hen filled with antifreez e. Advise system operator/ultimate owner that system is filled with a glycol mix.
The heating contractor must provide an MSDS (Material Safety Data Sheet) for the antifreeze used to the system operator/ultimate owner.
Oxygen diffusion barrier underfloor tubing
The boiler warranty does not cover leaks resulting from corrosion caused by the use of underfloor pla stic tubing without an oxygen diffusion barrier. Such systems must have the non-oxygen diffusion barrier tubing separated from the boiler with a heat exchanger. Viessmann recommends the use of underfloor pla stic tubing with an oxygen diffusion barrier.
Low water cut-off
A low water cut-off may be required by local codes. If boiler is installed above the radiation level, a low water cut-off device of approved type must be installed in all instances. An approved type low water cut-off device must be provided by the heating contractor. Do not install an isolation valve between the boiler and the low water cut-off.
5167 449 v1.3
Page 7
Installation Examples
Installation Examples
Important!
These examples depict possible piping layouts for Viessmann product equippe d with V iessmann System Technology. For boiler and tank combinations, please install only the feasible combinations listed in the Price List.
These are simplified conceptual drawings only! Piping and necessary componentry must be field verified.
Proper installation and functionality in the field is the responsibility of the heating contractor.
Without a mixing valve
Heating circuit Spring-loaded flow check valve Circulation pump Pressure relief valve Precharged expansion tank Domestic hot water storage tank (indirect-fired) DHW Pump Module
The installation of the check valve to restrict gravity cir culation in the heating supply pipe prevents uncontrolled heat flow to the heating system by gravity dur ing priority switching of domestic hot water heating or during sum mer operation.
5167 449 v1.3
7
Page 8
Installation Examples
With a 4-way mixing valve to regulate heating circuit, with domestic hot water control, and with boiler activation capability
Heating circuit Spring-loaded flow check valve Circulation pump Pressure relief valve Precharged expansion tank Domestic hot water storage tank (indirect-fired) Vitotronic 200-H, HK1M Series mixing valve control
Printed on environmentally friendly
(recycled and recyclable) paper.
Viessmann Manufacturing Company (U.S.) Inc. 45 Access Road Warwick, Rhode Island 02886 USA Tel. (401) 732-0667 Fax (401) 732-0590 www.viessmann-us.com info@viessmann-us.com
8
Viessmann Manufacturing Company Inc. 750 McMurray Road Waterloo, Ontario N2V 2G5 Canada Tel. (519) 885-6300 Fax (519) 885-0887 www.viessmann.ca info@viessmann.ca
Technical information subject to change without notice.