Viessmann EA1 Installation Instructions And Operators Manual

Page 1
Installation Instructions
for use by heating contractor
EA1 Extension Module for programmable inputs and outputs
EA1 Extension Module
Certified as a component part for Viessmann boilers
5774 470 - 02 03/2015
IMPORTANT
Read and save these instructions for future reference.
Please file in Service Binder
Page 2
Safety
Safety, Installation and Warranty Requirements
Safety, Installation and Warranty Requirements
Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the instructions listed below and details printed in this manual can cause product/property damage, severe personal injury, and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections).
EA1 Extension Module Installation
Product documentation Read all applicable documentation before commencing installation. Store documentation near boiler in a readily accessible location for reference in the future by service personnel.
For a listing of applicable literature, please see section entitled “Important Regulatory and Safety Requirements”.
Licensed professional heating contractor The installation, adjustment, service and maintenance of this equipment must be performed by a licensed professional heating contractor.
Please see section entitled Safety and “Important Regulatory and Installation Requirements”.
Advice to owner Once the installation work is complete, the heating contractor must familiarize the system operator/ ultimate owner with all equipment, as well as safety precautions/requirements, shutdown procedure, and the need for professional service annually before the heating season begins.
Warranty Information contained in this and related product documentation must be read and followed. Failure to do so renders the warranty null and void.
2
2
5774 470 - 02
Page 3
EA1 Extension Module Installation
Table of Contents
Page
Page
Safety
Important Precautions
General Information
Installation
Connections
Additional Information
Safety, Installation and Warranty Requirements..............2
Product documentation...........................................2
Licensed professional heating contractor...................2
Advice to owner....................................................2
Warranty...............................................................2
Important Regulatory and Installation Requirements........4
Approvals.............................................................4
Codes..................................................................4
Working on the equipment......................................4
Power supply........................................................4
About these Installation Instructions..............................5
Mounting the Extension Kit............................................6
Extension kit for installation on a wall......................6
Overview of Electrical Connections...............................7
Connecting Digital Inputs.............................................8
Connecting the Analog Input 0-10V............................10
Connecting the KM Bus to the Boiler Control Unit.........10
Connecting the Circulation Pump or a
Fault Message Facility...............................................11
Power Supply..........................................................12
Connection and Wiring Diagram.................................14
Specifications..........................................................15
5774 470 - 02
3
3
Page 4
Important Precautions
Important Regulatory and Installation Requirements
EA1 Extension Module Installation
Approvals
Viessmann boilers, burners and controls are approved for sale in North America by CSA International.
Codes
The installation of this unit shall be in accordance with local codes. In the absence of local codes, use:
- CSA C22.1 Part 1 and/or local codes in Canada
- National Electrical Code ANSI/NFPA 70 in the U.S. Always use latest editions of codes.
The heating contractor must comply with the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1 where required by the authority having jurisdiction.
Working on the equipment
The installation, adjustment, service, and maintenance of this product must be done by a licensed professional heating contractor who is qualified and experienced in the installation, service, and maintenance of hot water boilers. There are no user serviceable parts on the boiler, burner, or control.
Power supply
Install power supply in accordance with the regulations of the authorities having jurisdiction or, in absence of such requirements, in accordance with National Codes. Viessmann recommends the installation of a disconnect switch to the 120V power supply outside of the boiler room.
Ensure main power supply to equipment, the heating system, and all external controls have been deactivated. Close main oil or gas supply valve. Take precautions in both instances to avoid accidental activation of power during service work.
Please carefully read this manual prior to attempting installation. Any warranty is null and void if these instructions are not followed.
For information regarding other Viessmann System Technology componentry, please reference documentation of the respective product.
We offer frequent installation and service seminars to familiarize our partners with our products. Please inquire.
The completeness and functionality of field supplied electrical controls and components must be verified by the heating contractor. These include low water cut-offs, flow switches (if used), staging controls, pumps, motorized valves, air vents, thermostats, etc.
WARNING
Turn off electric power supply before servicing. Contact with live electric components can cause shock or loss of life.
4
5774 470 - 02
Page 5
EA1 Extension Module Installation
About these Installation Instructions
Take note of all symbols and notations intended to draw attention to potential hazards or important product information.
General Information
WARNING
Warnings draw your attention to the presence of potential hazards or important product information.
CAUTION
Cautions draw your attention to the presence of potential hazards or important product information.
IMPORTANT

Indicates an imminently hazardous situation which,
if not avoided, could result in death, serious injury or substantial product/property damage.
Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or product / property damage.
Helpful hints for installation, operation or maintenance which pertain to the product.
This symbol indicates to note additional information
This symbol indicates that other instructions must be
referenced.
5774 470 - 02
5
Page 6
Installation
Mounting the Extension Kit
Installation Instructions Extension EA1
Extension kit for installation on a wall
1. Loosen the retaining screws from the extension kit
encloser (do not remove) .
2. Remove cover and set aside.
3. Mount the extension module enclosure to the wall
using the supplied hardware.
4. Install the cover.
Components:
H EA1 extension module H KM BUS plug aVG H Power cord pre-wired to plug H Digital inputs DE1, DE2 and DE3 plugs H 0-10VDC input plug H Programmable output plug aBJ H Accessory power plug A
6
5774 470 - 02
Page 7
EA1 Extension Module Installation
Overview of Electrical Connections
Connections
A
Legend
DE1 Digital input 1 DE2 Digital input 2 DE3 Digital input 3 0 - 10 V 0 - 10 V input
Power supplyA Power supply for additional accessories aBJ Programmable output aVG KM BUS to the control unit
A Extension EA1 F1 Fuse
CAUTION
The electronic modules are static sensitive. To avoid damage caused by static discharge, follow Electro-Static Discharge safety procedures.
Note: Apply strain relief to all on-site cables.
Close any unnecessary knock-outs with cable entries (not cut open).
5774 470 - 02
7
Page 8
Connections
Connecting Digital Inputs
EA1 Extension Module Installation
The following functions can be connected alternatively:
H External heating program changeover for each heating
circuit H External blocking H External blocking with central fault message H External demand with set flow temperature H Central fault message H Brief operation of the DHW circulation pump
The hooked-up contacts must correspond to protection class II.
Function assignment of inputs DE1 to DE3
Select the input functions by means of the codes on the boiler control unit. Complete description of the coding addresses:
Service instructions for boiler or control unit
Control unit
Coding address
Input DE1 3A 5d Input DE2 3b 5E Input DE3 3C 5F
Vitotronic, type H... Vitotronic, type G...
Subject to function and digital input selected for the respective function, the following codes need to be changed at the boiler control unit:
Function Setting
Code 3A, 3b, 3C (Vitotronic, type H ... )
Code 5d, 5E, 5F (Vitotronic, type G ...)
No function 0 Heating program
changeover External demand with set
flow temperature External blocking 3 External blocking with fault
message input Fault message input 5 Brief operation, DHW
circulation pump
1
2
4
6
8
5774 470 - 02
Page 9
EA1 Extension Module Installation
Connecting Digital Inputs (continued)
Connections
Assigning the heating program changeover function to the heating circuits
Assign the heating program changeover function for the respective heating circuit via code d8 at the boiler control unit:
H Changeover via input DE1: Code d8:1 H Changeover via input DE2: Code d8:2 H Changeover via input DE3: Code d8:3 H Select the effect of the heating program changeover
via code d5 H Set the duration of the changeover via code F2
Effect of the external blocking function on the pumps
H Select the effect on the internal boiler circulation pump
(Vitotronic, type H ...) with code 3E H Select the effect on the respective heating circuit pump
with code d6 H Select the effect on the circulation pump for DHW tank
heating (Vitotronic, type H ...) with code 5E
Effect of the external demand function on the pumps
H Select the effect on the internal boiler circulation pump
(Vitotronic, type H ...) with code 3F H Select the effect on the respective heating circuit pump
with code d7 H Select the effect on the circulation pump for DHW tank
heating (Vitotronic, type H ...) with code 5F
Set flow temperature for external demand
H The set flow temperature can be selected with code 9b
Runtime of the DHW recirculation pump
Set the runtime:
H Vitotronic, type H ...: Code 3d H Vitotronic, type G ...: Code 12
Refer to the boiler Service Instructions
5774 470 - 02
9
Page 10
Connections
Connecting the Analog Input 0-10V
The 0 - 10V hook-up provides an additional set boiler water temperature:
0 - 1V seen as “no default set boiler water temperature” 1V 10V set value 212°F (100°C)
On the Vitotronic, type G ... the range of the set value default can be changed with code 1E:
1V 10V set value 248°F (120°C)
set value 50°F (10°C)
set value 86°F (30°C)
Connecting the KM BUS to the Boiler Control Unit
EA1 Extension Module Installation
Legend
A Extension EA1 B Connection area of boiler control unit
Boiler control unit installation and service instructions
10
5774 470 - 02
Page 11
EA1 Extension Module Installation
Connecting the KM BUS to the Extension Modules
Legend
A Boiler control unit B Extension kit for heating circuit with mixing valve M2 C Extension kit for heating circuit with mixing valve M3 D Extension AM1, EA1 and/or solar control module,
type SM1
5774 470 - 02
11
Page 12
Connections
EA1 Extension Module Installation
Connecting a Circulation Pump or a Fault Message Facility
The following components can be connected to plug aBJ:
H Pump speed reduction function
or
H DHW re-circulation pump
or
H Fault message facility
Rated voltage (max): 120V Rated current (max): 2 A~
Function assignment
Select the function of output aBJ:
H Vitotronic, type H ...: Code 36 H Vitotronic, type G ...: Code 5C
Legend
A Circulation pump or fault message facility
If a digital input is used as fault message input, the connected fault message facility is switched on when a fault occurs.
Refer to the boiler Service Instructions
If the relay of output aBJ is switched, contact P-Ö is open. If a fault occurs at extension EA1 or communication is interrupted, contact P-Ö is closed.
Note: If a fault message facility is connected, this will
be activated briefly when the system starts.
12
5774 470 - 02
Page 13
EA1 Extension Module Installation
Power Supply (continued)
Connections
Direct power supply
WARNING
Incorrectly executed electrical installations can result in injuries from electrical current and in equipment damage.
Connect the power supply (see page 2) and implement all grounding measures (e.g. RCD circuit) in accordance with the following regulations:
H In Canada all electrical wiring is to be done in
accordance with the latest edition of CSA C22.1 Part 1
and/or local codes. In the U.S. use the National Electrical Code ANSI/NFPA 70. The heating contractor must also comply with both the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1, and the Installation Code for Hydronic Heating Systems, CSA B214-01, where required by the authority having jurisdiction.
H Connection requirements specified by your local power
supply utility H Protect the power cable with max. 15A
Legend
A Extension EA1
WARNING
The absence of component grounding in the system can lead to serious injury from electrical current if an electrical fault occurs. Connect the appliance and pipework to the equipotential bonding of the building in question.
Isolators for non-grounded conductors
H The mains isolator (if installed) must simultaneously
isolate all non-grounded conductors from the mains
with a minimum contact separation of 3 mm. H If no mains isolator is installed, all nongrounded
conductors must be isolated from the mains by the
upstream circuit breaker with a minimum contact
separation of 3 mm.
WARNING
Incorrect core allocation can result in serious injury and damage to the appliance. Never interchange cores “L” and “N”.
CAUTION
An incorrect phase sequence can cause damage to the appliance. Check for phase equality with the power supply connection of the control unit.
5774 470 - 02
13
Page 14
Connections
Connection and Wiring Diagram
EA1 Extension Module Installation
Legend
DE1 Digital input 1 DE2 Digital input 2 DE3 Digital input 3 0 - 10 V 0 - 10 V input A Extension EA1
Power supplyA Power supply for additional accessories aBJ Fault message facility/Feed pump/DHW circulation
pump (floating) aVG KM BUS to the control unit
14
5774 470 - 02
Page 15
EA1 Extension Module Installation
Specifications
Additional Information
Rated voltage 120 V~ Rated frequency 60 Hz Rated current 2A Power consumption 1.5W Protection class I
Permissible ambient temperature
H During operation 32 to 104°F (0 to 40°C) H During storage
and transport -4 to +149°F (–20 to +65°C)
Rated breaking capacity, floating output aBJ 2A 120V~
5774 470 - 02
15
Page 16
Installation Instructions Extension EA1
(recycled and recyclable) paper.
Scan for
digital copy
of this
document
Technical information subject to change without notice. Printed on environmentally friendly