Please follow these safety instructions closely to prevent accidents and
material losses.
Safety instructions explained
Danger
This symbol warns against the
risk of injury.
Please note
This symbol warns against the
!
risk of material losses and environmental pollution.
Target group
These instructions are exclusively
intended for qualified contractors.
■ Work on gas installations may only
be carried out by a registered gas fitter.
■ Work on electrical equipment may
only be carried out by a qualified
electrician.
Regulations to be observed
■ National installation regulations
■ Statutory regulations for the prevention of accidents
■ Statutory regulations for environmental protection
Note
Details identified by the word "Note"
contain additional information.
■ Codes of practice of the relevant
trade associations
■ All current safety regulations as
defined by DIN, EN, DVGW, TRGI,
TRF, VDE and all locally applicable
standards
ÖNORM, EN,
a
ÖVGW G K directives,
ÖVGW-TRF and ÖVE
SEV, SUVA, SVGW, SVTI,
c
SWKI, VKF and EKAS guideline
1942: LPG, part 2
5836498
2
Page 3
Safety instructions
(cont.)
Working on the system
■ Isolate the system from the power
supply (e.g. by removing the separate fuse or by means of a mains isolator) and check that it is no longer
'live'.
■ Safeguard the system against reconnection.
■ Where gas is used as the fuel, close
the main gas shut-off valve and safeguard it against unintentional reopening.
5836498
3
Page 4
Index
Preparing for installation...................................................................................5
Declaration of conformity for extension kit..................................................... 31
4
5836498
Page 5
3.
2.
4.
1.
Preparing for installation
Removing the thermal insulation
5836498
5
Page 6
1.
2.
Ø 10
Wall mounting
Fitting a single module (without manifold)
5836498
6
Page 7
1.
2.
A
B
Wall mounting
(cont.)
A
5836498
Heating flow
Heating return
B
7
Page 8
Ø 10
300
500
2.
1.
Wall mounting
(cont.)
Fitting several modules with manifold (accessories)
Manifold for 2 Divicons
A
Manifold for 3 Divicons
B
8
5836498
Page 9
70
142
2.
1.
A
B
A
B
A
B
Wall mounting
(cont.)
Manifold (H = 70 mm) for 2 Divicons
A
5836498
Heating flow
Heating return
B
9
Page 10
2.
1.
A
B
A
B
A
B
100
167
Wall mounting
(cont.)
Manifold (H = 100 mm) for 2 Divicons
A
10
Heating flow
Heating return
B
5836498
Page 11
2.
1.
A
B
A
B
A
B
A
B
70
142
Wall mounting
(cont.)
Manifold (H = 70 mm) for 3 Divicons
A
5836498
Heating flow
Heating return
B
11
Page 12
2.
1.
A
A
B
A
B
A
B
B
100
167
Wall mounting
(cont.)
Manifold (H = 100 mm) for 3 Divicons
Heating flow
A
12
Heating return
B
5836498
Page 13
Wall mounting
(cont.)
5836498
13
Page 14
1.
3.
4.
2.
Wall mounting
(cont.)
Low loss header (if supplied)
A
14
Heating flow
Heating return
B
5836498
Page 15
1.
2.
Filling the system
1. For filling (with heating water), open
the check valve in the heating
return by positioning the slot of the
screw in the vertical position.
Note
Observe the marking on the adjusting screw.
5836498
2. For operation, position the slot of
the screw in the horizontal position.
15
Page 16
1.
3.
2.
Fitting the thermal insulation
Low loss header (if supplied)
16
5836498
Page 17
1.
2.
Fitting the thermal insulation
Manifold
(cont.)
5836498
17
Page 18
1.2.3.
A
B
3.
2.
3.
2.
1.
Fitting the thermal insulation
Divicon with mixer
Note
With several Divicons, first fit the thermal insulation on the right-hand Divicon. For the remaining Divicons, fit the
insulation from right to left.
(cont.)
Cut off if fitting a single module to
A
the wall.
18
Cut out the thermal insulation if
B
connecting with a union nut.
5836498
Page 19
2.
3.
1.
Fitting the thermal insulation
(cont.)
5836498
19
Page 20
B
1.2.3.
1.
2.
2.
A
Fitting the thermal insulation
Divicon without mixer
Note
With several Divicons, first fit the thermal insulation on the right-hand Divicon. For the remaining Divicons, fit the
insulation from right to left.
(cont.)
Cut off if fitting a single module to
A
the wall.
20
Cut out the thermal insulation if
B
connecting with a union nut.
5836498
Page 21
2.
3.
1.
4.
Fitting the thermal insulation
(cont.)
5836498
21
Page 22
L
?
N
?
N
jFjF
[{] [{] [{][{]
fÖ
M
1~
230 V~/50 Hz
M
1~
L
?
N
L
?
N
gS
sÖ
?)
[{{]
Extension kit with mixer PCB
Note
Bundle individual wires from the connecting cables directly below the plugs
and secure with cable ties.
Overview of electrical connections
Plug 230 V~
P1 sÖ
P3 gS
fÖ
fÖA
LV connections
PWM1 No function
TS1 ?
TS2No function
TS3 )
jF
22
Heating circuit pump
Mixer motor
Power supply
Power supply for accessories
Flow temperature sensor
Temperature sensor, low loss
header
PlusBus
Please note
Electronic assemblies can be
!
damaged by electrostatic discharge.
Prior to commencing any work,
touch earthed objects such as
heating or water pipes to discharge static loads.
Note
Apply strain relief to on-site cables.
Seal any unnecessary apertures with
cable grommets (not cut open).
5836498
Page 23
B
A
jFjF
[{][{][{]
DI1 DI2 DI3
12341
2
3
4
5
6
Extension kit with mixer PCB
Rotary switch S1
(cont.)
If several mixer extension kits are being
connected, set rotary switch S1.
Set the rotary switch on each extension
kit to a consecutive number:
■ Heating circuit with mixer M2: Rotary
switch to 1
■ Heating circuit with mixer M3: Rotary
switch to 2
■ Heating circuit with mixer M4: Rotary
switch to 3
Note
If additional EM-P1 extensions are connected, always set the subscriber numbers for the EM-P1 extensions to consecutive numbers after the mixer extension kits.
Connecting the PlusBus to the heat generator control unit
A
B
5836498
Extension
PlusBus to heat generator
Note
If making the connection to the heat
generator with an external plug for the
bus connection, connect the wires
directly.
Heat generator installation and
service instructions
23
Page 24
L
?
N
L
?
N
156
LN
Extension kit with mixer PCB
Power supply
Power supply at the heat generator
control unit
Extension
A
Power supply
fÖ
Power supply for further accesso-
fÖA
ries
Plug for power supply to accesso-
aBH
ries in the heat generator control
unit
(cont.)
Create the power supply connection.
Route the power cable to the heat generator control unit and connect to plug
.
aBH
If power is supplied to a further accessory, use plug fÖA provided
Heat generator installation and
service instructions
Danger
Incorrect core assignment can
result in serious injury and damage to the appliance.
Take care not to interchange
wires "L1" and "N".
Separate power supply
If the power supply for the extension is
not made at the heat generator control
unit.
Danger
Incorrect electrical installations
can lead to serious injury from
electrical current and result in
appliance damage.
Connect the power supply and
implement all safety measures
(e.g. RCD circuit) in accordance
with the following regulations:
■ IEC 60364-4-41
■ VDE regulations
■ Technical connection requirements (TAB) specified by the
local grid operator
24
5836498
Page 25
L1
B
FE
D
D
N
C
A
40
Extension kit with mixer PCB
Danger
The absence of system component earthing can lead to serious injury from electric current if
an electrical fault occurs.
The appliance and pipework
must be connected to the equipotential bonding of the building.
(cont.)
Isolators for non-earthed conductors
■ The mains isolator (if installed) must
simultaneously isolate all nonearthed conductors from the mains
with a minimum contact separation of
3 mm.
■ If no mains isolator is installed, all
non-earthed conductors must be isolated from the power supply by the
upstream circuit breaker with a minimum contact separation of 3 mm.
Connect the power supply in accordance with the diagram.
If the power supply to the appliance is
connected with a flexible cable, ensure
that the live conductors are pulled taut
before the earth conductor in the event
of strain relief failure. The length of the
earth conductor wire will depend on the
design.
Danger
Incorrect core assignment can
result in serious injury and damage to the appliance.
Never interchange cores "L" and
"N".
Power supply for extension
A
Power supply for heat generator
B
C
D
E
F
5836498
control unit
Power supply 1/N/PE, 230 V/50 Hz
Fuse (max. 16 A)
Mains isolator, 2-pole, on site
Junction box (on site)
Please note
Incorrect phase sequence can
!
cause damage to the appliance.
Ensure phase equality with the
power supply of the heat generator control unit.
Colour coding to IEC 60757
BNBrown
BUBlue
GNYE Green/yellow
25
Page 26
74
74
40A
40
74
74
40A
40
BC
74
40
96/156
A
74
74
40A
40
D
E
74
74
40A
40
74
74
40A
40
BC
74
40
96/156
A
74
74
40A
40
D
E
Extension kit with mixer PCB
(cont.)
Connecting several accessories
Power supply and PlusBus connection
Power supply to all accessories via heat generator control unit
Some accessories with direct power supply
A
B
C
D
26
Heat generator control unit
Mixer extension kit for heating
circuit with mixer M2
Mixer extension kit for heating
circuit with mixer M3
Further accessories
E
fÖ (A)
jF
lH/aBH
ON/OFF switch
Power supply
PlusBus
Accessories power supply in
the control unit of the heat
generator
5836498
Page 27
Extension kit with mixer PCB
■ In the following circumstances, use
the output for the accessories only to
switch an on-site relay:
An actuator (e.g. circulation pump)
with a higher power demand than the
fuse rating required for the accessories is connected at the accessories
output.
■ In the following circumstances, connect one or more accessories directly
to the mains supply via an ON/OFF
switch:
The max. permissible total current of
the control unit for the heat generator
is exceeded.
Separate power supply: See the following chapter.
Note
In this event, the accessories concerned cannot be isolated with the
ON/OFF switch on the control unit.
(cont.)
5836498
27
Page 28
Extension kit with mixer PCB
Connection and wiring diagram
(cont.)
A1 Mixer extension kit, ADIO control
unit
A2 PCB
230 V~ plugs
P1 sÖ
P3 gS
fÖ
fÖA
28
Heating circuit pump
Mixer motor
Power supply 230 V/50 Hz
Power supply for accessories
F1 Fuse
S1 Rotary switch
LV plugs
PWM1 No function
TS1 ?
TS2No function
TS3 )
jF
Flow temperature sensor
Low loss header temperature
sensor (separate accessories)
PlusBus connection for connecting to the heat generator
and another accessory
5836498
Page 29
gS
BU
|
~
Extension kit with mixer PCB
(cont.)
Changing the rotational direction (if required)
1. Danger
An electric shock can be life
threatening.
Before opening the boiler,
disconnect it from the mains
voltage, e.g. at the fuse or
mains isolator.
Remove the casing cover (see
chapter "Overview of electrical connections").
2.
Switch cores BK and BK on
plug gS.
3. Refit the casing cover.
4. Check the rotational direction.
5836498
29
Page 30
10
1
10 30 50 70 90 110
Temperature in °C
0.4
0.6
0.8
2
4
6
8
20
Resistance in kΩ
Specification
Rated voltage230 V∼
Rated frequency50 Hz
Rated current2 A
Power consumption5.5 W
Protection classI
IP ratingIP 20 D to EN 60 529; ensure through
design/installation.
Permissible ambient temperature
■ During operation0 to +40 °C
■ During storage and transport–20 to +65 °C
Rated relay output breaking capacity
■ Heating circuit pump1 A 230 V~
■ Mixer motor0.1 A 230 V~
Flow temperature sensor/low loss header temperature sensor (separate
accessories)
Sensor typeNTC 10 kΩ, at 25 °C
IP ratingIP 53 to EN 60529; ensure through de-
sign/installation.
Permissible ambient temperature
■ Operation0 to +120 °C
■ Storage and transport−20 °C to +70 °C
Curve
30
5836498
Page 31
Declaration of conformity for extension kit
We, Viessmann Werke
GmbH & Co. KG, D-35107 Allendorf,
declare as sole responsible body that
the named product complies with the
European directives and supplementary
national requirements in terms of its
design and operational characteristics.
Conformity has been verified with the
CE designation. Using the serial number, the full Declaration of Conformity
can be found on the following website:
www.viessmann.co.uk/eu-conformity
5836498
31
Page 32
Viessmann Werke GmbH & Co. KG
D-35107 Allendorf
Telephone: +49 6452 70-0
Fax: +49 6452 70-2780
www.viessmann.com