Viessmann Divicon Installation Instructions Manual

Page 1

Installation instructions

for contractors

Divicon

Heating circuit distributor
Divicon
VIESMANN
5836498 GB 11/2018
Page 2

Safety instructions

Safety instructions explained
Danger
This symbol warns against the risk of injury.
Please note
This symbol warns against the
!
risk of material losses and envi­ronmental pollution.
Target group
These instructions are exclusively intended for qualified contractors.
■ Work on gas installations may only be carried out by a registered gas fit­ter.
■ Work on electrical equipment may only be carried out by a qualified electrician.
Regulations to be observed
■ National installation regulations
■ Statutory regulations for the preven­tion of accidents
■ Statutory regulations for environmen­tal protection
Note
Details identified by the word "Note" contain additional information.
■ Codes of practice of the relevant trade associations
■ All current safety regulations as defined by DIN, EN, DVGW, TRGI, TRF, VDE and all locally applicable standards
ÖNORM, EN,
a
ÖVGW G K directives, ÖVGW-TRF and ÖVE SEV, SUVA, SVGW, SVTI,
c
SWKI, VKF and EKAS guideline 1942: LPG, part 2
5836498
2
Page 3
Safety instructions
(cont.)
Working on the system
■ Isolate the system from the power supply (e.g. by removing the sepa­rate fuse or by means of a mains iso­lator) and check that it is no longer 'live'.
■ Safeguard the system against recon­nection.
■ Where gas is used as the fuel, close the main gas shut-off valve and safe­guard it against unintentional reopen­ing.
5836498
3
Page 4

Index

Preparing for installation................................................................................... 5
Installation sequence
Wall mounting....................................................................................................... 6
■ Fitting a single module (without manifold)......................................................... 6
■ Fitting several modules with manifold (accessories)......................................... 8
Filling the system.................................................................................................. 15
Fitting the thermal insulation................................................................................ 16
■ Low loss header (if supplied)............................................................................ 16
■ Manifold............................................................................................................ 17
■ Divicon with mixer............................................................................................. 18
■ Divicon without mixer........................................................................................ 20
Extension kit with mixer PCB............................................................................... 22
■ Overview of electrical connections.................................................................... 22
■ Rotary switch S1............................................................................................... 23
■ Connecting the PlusBus to the heat generator control unit.............................. 23
■ Power supply.................................................................................................... 24
■ Connecting several accessories....................................................................... 26
■ Connection and wiring diagram........................................................................ 28
■ Changing the rotational direction (if required)................................................... 29
Specification....................................................................................................... 30
Declaration of conformity for extension kit..................................................... 31
4
5836498
Page 5
3.
2.
4.
1.

Preparing for installation

Removing the thermal insulation
5836498
5
Page 6
1.
2.
Ø 10

Wall mounting

Fitting a single module (without manifold)

5836498
6
Page 7
1.
2.
A
B
Wall mounting
(cont.)
A
5836498
Heating flow
Heating return
B
7
Page 8
Ø 10
300 500
2.
1.
Wall mounting
(cont.)

Fitting several modules with manifold (accessories)

Manifold for 2 Divicons
A
Manifold for 3 Divicons
B
8
5836498
Page 9
70
142
2.
1.
A
B
A
B
A
B
Wall mounting
(cont.)
Manifold (H = 70 mm) for 2 Divicons
A
5836498
Heating flow
Heating return
B
9
Page 10
2.
1.
A
B
A
B
A
B
100
167
Wall mounting
(cont.)
Manifold (H = 100 mm) for 2 Divicons
A
10
Heating flow
Heating return
B
5836498
Page 11
2.
1.
A
B
A
B
A
B
A
B
70
142
Wall mounting
(cont.)
Manifold (H = 70 mm) for 3 Divicons
A
5836498
Heating flow
Heating return
B
11
Page 12
2.
1.
A
A
B
A
B
A
B
B
100
167
Wall mounting
(cont.)
Manifold (H = 100 mm) for 3 Divicons
Heating flow
A
12
Heating return
B
5836498
Page 13
Wall mounting
(cont.)
5836498
13
Page 14
1.
3.
4.
2.
Wall mounting
(cont.)
Low loss header (if supplied)
A
14
Heating flow
Heating return
B
5836498
Page 15
1.
2.

Filling the system

1. For filling (with heating water), open
the check valve in the heating return by positioning the slot of the screw in the vertical position.
Note
Observe the marking on the adjust­ing screw.
5836498
2. For operation, position the slot of the screw in the horizontal position.
15
Page 16
1.
3.
2.

Fitting the thermal insulation

Low loss header (if supplied)

16
5836498
Page 17
1.
2.
Fitting the thermal insulation

Manifold

(cont.)
5836498
17
Page 18
1.2.3.
A
B
3.
2.
3.
2.
1.
Fitting the thermal insulation

Divicon with mixer

Note
With several Divicons, first fit the ther­mal insulation on the right-hand Divi­con. For the remaining Divicons, fit the insulation from right to left.
(cont.)
Cut off if fitting a single module to
A
the wall.
18
Cut out the thermal insulation if
B
connecting with a union nut.
5836498
Page 19
2.
3.
1.
Fitting the thermal insulation
(cont.)
5836498
19
Page 20
B
1.2.3.
1.
2.
2.
A
Fitting the thermal insulation

Divicon without mixer

Note
With several Divicons, first fit the ther­mal insulation on the right-hand Divi­con. For the remaining Divicons, fit the insulation from right to left.
(cont.)
Cut off if fitting a single module to
A
the wall.
20
Cut out the thermal insulation if
B
connecting with a union nut.
5836498
Page 21
2.
3.
1.
4.
Fitting the thermal insulation
(cont.)
5836498
21
Page 22
L
?
N
?
N
jF jF
[{] [{] [{] [{]
M 1~
230 V~/50 Hz
M 1~
L
?
N
L
?
N
gS
? )
[{{]

Extension kit with mixer PCB

Note
Bundle individual wires from the con­necting cables directly below the plugs and secure with cable ties.

Overview of electrical connections

Plug 230 V~ P1 P3 gS
fÖ fÖA
LV connections PWM1 No function TS1 ? TS2 No function TS3 )
jF
22
Heating circuit pump Mixer motor Power supply Power supply for accessories
Flow temperature sensor
Temperature sensor, low loss header PlusBus
Please note
Electronic assemblies can be
!
damaged by electrostatic dis­charge. Prior to commencing any work, touch earthed objects such as heating or water pipes to dis­charge static loads.
Note
Apply strain relief to on-site cables. Seal any unnecessary apertures with cable grommets (not cut open).
5836498
Page 23
B
A
jF jF
[{][{][{]
DI1 DI2 DI3
12341
2
3
4
5
6
Extension kit with mixer PCB

Rotary switch S1

(cont.)
If several mixer extension kits are being connected, set rotary switch S1.
Set the rotary switch on each extension kit to a consecutive number:
■ Heating circuit with mixer M2: Rotary
switch to 1
■ Heating circuit with mixer M3: Rotary
switch to 2
■ Heating circuit with mixer M4: Rotary
switch to 3
Note
If additional EM-P1 extensions are con­nected, always set the subscriber num­bers for the EM-P1 extensions to con­secutive numbers after the mixer exten­sion kits.

Connecting the PlusBus to the heat generator control unit

A B
5836498
Extension PlusBus to heat generator
Note
If making the connection to the heat generator with an external plug for the bus connection, connect the wires directly.
Heat generator installation and service instructions
23
Page 24
L
?
N
L
?
N
156
LN
Extension kit with mixer PCB

Power supply

Power supply at the heat generator control unit
Extension
A
Power supply
Power supply for further accesso-
A
ries Plug for power supply to accesso-
aBH
ries in the heat generator control unit
(cont.)
Create the power supply connection. Route the power cable to the heat gen­erator control unit and connect to plug
.
aBH
If power is supplied to a further acces­sory, use plug fÖA provided
Heat generator installation and service instructions
Danger
Incorrect core assignment can result in serious injury and dam­age to the appliance. Take care not to interchange wires "L1" and "N".
Separate power supply
If the power supply for the extension is not made at the heat generator control unit.
Danger
Incorrect electrical installations can lead to serious injury from electrical current and result in appliance damage.
Connect the power supply and implement all safety measures (e.g. RCD circuit) in accordance with the following regulations:
■ IEC 60364-4-41
■ VDE regulations
■ Technical connection require­ments (TAB) specified by the local grid operator
24
5836498
Page 25
L1
B
FE
D
D
N
C
A
40
Extension kit with mixer PCB
Danger
The absence of system compo­nent earthing can lead to seri­ous injury from electric current if an electrical fault occurs. The appliance and pipework must be connected to the equi­potential bonding of the building.
(cont.)
Isolators for non-earthed conductors
■ The mains isolator (if installed) must simultaneously isolate all non­earthed conductors from the mains with a minimum contact separation of 3 mm.
■ If no mains isolator is installed, all non-earthed conductors must be iso­lated from the power supply by the upstream circuit breaker with a mini­mum contact separation of 3 mm.
Connect the power supply in accord­ance with the diagram. If the power supply to the appliance is connected with a flexible cable, ensure that the live conductors are pulled taut before the earth conductor in the event of strain relief failure. The length of the earth conductor wire will depend on the design.
Danger
Incorrect core assignment can result in serious injury and dam­age to the appliance. Never interchange cores "L" and "N".
Power supply for extension
A
Power supply for heat generator
B
C D E F
5836498
control unit Power supply 1/N/PE, 230 V/50 Hz Fuse (max. 16 A) Mains isolator, 2-pole, on site Junction box (on site)
Please note
Incorrect phase sequence can
!
cause damage to the appliance. Ensure phase equality with the power supply of the heat gener­ator control unit.
Colour coding to IEC 60757 BN Brown BU Blue GNYE Green/yellow
25
Page 26
74
74
40A
40
74
74
40A
40
B C
74
40
96/156
A
74
74
40A
40
D
E
74
74
40A
40
74
74
40A
40
B C
74
40
96/156
A
74
74
40A
40
D
E
Extension kit with mixer PCB
(cont.)

Connecting several accessories

Power supply and PlusBus connection
Power supply to all accessories via heat generator control unit
Some accessories with direct power supply
A B
C
D
26
Heat generator control unit Mixer extension kit for heating circuit with mixer M2 Mixer extension kit for heating circuit with mixer M3 Further accessories
E
(A) jF lH/aBH
ON/OFF switch Power supply PlusBus Accessories power supply in the control unit of the heat generator
5836498
Page 27
Extension kit with mixer PCB
■ In the following circumstances, use the output for the accessories only to switch an on-site relay: An actuator (e.g. circulation pump) with a higher power demand than the fuse rating required for the accesso­ries is connected at the accessories output.
■ In the following circumstances, con­nect one or more accessories directly to the mains supply via an ON/OFF switch: The max. permissible total current of the control unit for the heat generator is exceeded. Separate power supply: See the fol­lowing chapter.
Note
In this event, the accessories con­cerned cannot be isolated with the ON/OFF switch on the control unit.
(cont.)
5836498
27
Page 28
Extension kit with mixer PCB

Connection and wiring diagram

(cont.)
A1 Mixer extension kit, ADIO control
unit
A2 PCB
230 V~ plugs P1 P3 gS
fÖ fÖA
28
Heating circuit pump Mixer motor Power supply 230 V/50 Hz Power supply for accessories
F1 Fuse S1 Rotary switch
LV plugs PWM1 No function TS1 ? TS2 No function TS3 )
jF
Flow temperature sensor
Low loss header temperature sensor (separate accessories) PlusBus connection for con­necting to the heat generator and another accessory
5836498
Page 29
gS
BU
|
~
Extension kit with mixer PCB
(cont.)

Changing the rotational direction (if required)

1. Danger
An electric shock can be life threatening. Before opening the boiler, disconnect it from the mains voltage, e.g. at the fuse or mains isolator.
Remove the casing cover (see chapter "Overview of electrical con­nections").
2.
Switch cores BK and BK on plug gS.
3. Refit the casing cover.
4. Check the rotational direction.
5836498
29
Page 30
10
1
10 30 50 70 90 110
Temperature in °C
0.4
0.6
0.8
2
4
6
8
20
Resistance in kΩ

Specification

Rated voltage 230 V Rated frequency 50 Hz Rated current 2 A Power consumption 5.5 W Protection class I IP rating IP 20 D to EN 60 529; ensure through
design/installation.
Permissible ambient temperature
■ During operation 0 to +40 °C
■ During storage and transport –20 to +65 °C Rated relay output breaking capacity
■ Heating circuit pump 1 A 230 V~
■ Mixer motor 0.1 A 230 V~
Flow temperature sensor/low loss header temperature sensor (separate accessories)
Sensor type NTC 10 kΩ, at 25 °C IP rating IP 53 to EN 60529; ensure through de-
sign/installation.
Permissible ambient temperature
■ Operation 0 to +120 °C
■ Storage and transport −20 °C to +70 °C
Curve
30
5836498
Page 31

Declaration of conformity for extension kit

We, Viessmann Werke GmbH & Co. KG, D-35107 Allendorf, declare as sole responsible body that the named product complies with the European directives and supplementary national requirements in terms of its design and operational characteristics.
Conformity has been verified with the CE designation. Using the serial num­ber, the full Declaration of Conformity can be found on the following website:
www.viessmann.co.uk/eu-conformity
5836498
31
Page 32
Viessmann Werke GmbH & Co. KG D-35107 Allendorf Telephone: +49 6452 70-0 Fax: +49 6452 70-2780 www.viessmann.com
32
Viessmann Limited Hortonwood 30, Telford Shropshire, TF1 7YP, GB Telephone: +44 1952 675000 Fax: +44 1952 675040 E-mail: info-uk@viessmann.com
5836498 Subject to technical modifications.
Loading...