Viessmann Dekamatik-M1 Operating Instructions Manual

Operating Instructions
Dekamatik-M1
Digital indoor/outdoor boiler and heating system control
Dekamatik-M1
Please file in Sercice Binder
5302 682 1/98
1.0 Contents
1.1 Safety
1.0 Contents Page
1 Important Precautions 1.1 Safety 2
.......................................................................................................................................
2 Operating Instructions (overview) 2.1 Operating Controls / Display Elements 3............................................................................
2.2 Method of Operation of the Heating System 4..................................................................
2.3 Control Activation 4..................................................................................................................
2.4 Settings and Adjustments 4...................................................................................................
H Comfortrol control unit 4......................................................................................................
H Symbols in the display 4.....................................................................................................
H Setting the heating program 5...........................................................................................
H Altering room temperatures 6............................................................................................
H Altering the DHW temperature 6.......................................................................................
H Setting party mode 7............................................................................................................
H Setting energy saving mode 7...........................................................................................
H Day, date and time 7............................................................................................................
H Menu structure 8...................................................................................................................
H Time program
- Explanatory remarks 10
.....................................................................................................
- Altering the switching times 11.........................................................................................
- Calling up the switching times 11....................................................................................
- Deleting activation periods 12..........................................................................................
- Altering the date/time 12....................................................................................................
H Holiday program 13................................................................................................................
H Installer set-up 14....................................................................................................................
H Altering operating program from remote (via telephone) 14.........................................
H Maximum temperature limit 15.............................................................................................
H Differential temperature 15...................................................................................................
H Heating curves 16...................................................................................................................
H Lead boiler selection control 19...........................................................................................
H Default factory settings “ ” button 20................................................................................
H Heating system shut-down 20..............................................................................................
3 Override 3 Override Switch 21.....................................................................................................................
4 Information 4.1 Scanning Temperatures (Desired/Actual Values) and
Operating Status Information 22
.............................................................................................
H Explanation of “damped” outdoor temperature 22...........................................................
4.2 Fault Indication 23......................................................................................................................
4.3 Troubleshooting Guide 24........................................................................................................
4.4 Operating the Comfortrol Control Unit 25.............................................................................
H Operational information 25....................................................................................................
H Language selection 26...........................................................................................................
H Battery replacement 26..........................................................................................................
4.5 Settings Checklist 27..................................................................................................................
2
2.1 Operating Controls / Display Elements
1.1 Safety
This “Attention” symbol is positioned b efore all important safety tips. Please follow these instructions in detail to avoid property damage, personal injury, or loss of life.
H Installation
Please carefully read this manual prior to attempting equipment operation. Any warranty is null and void when these instructions are not followed. Viessmann boilers, burners and controls are approved for sale in North America by International Approval Services (IAS).
All electrical wiring is to be done in accordance with the latest edition of the National Electrical Code ANSI/NFPA 70. In Canada use latest edition of CSA C 22.1 Part 1 and/or local codes. We offer frequent installation and service seminars to familiarize our partners with our products. Please inquire.
H Working on the equipment
All personnel working on the equipment or the heating system must have the proper qualifications and hold all necessary licenses. Ensure main power supply to equipment, heating system, and all external controls and power supplies has been deactivated. Close main gas or oil supply valve. Take precautions in both instances to avoid accidental activation of power during service work.
2.1 Operating Controls / Display Elements with flip-down covers open
Dials shown in default factory position.
1
Comfortrol control unit
2
Lead boiler selection switch FK/WA.....
3
Boiler sequence selection switch
4
Burner status indicator ............................
5
On/off switch ..........................................
I=on O=off
6
Additional feature slots operating hour counter
7
Safety temperature high limit .............
8
Adjustable high limit .............................
9
TUV service button (for service purposes only) TUV
10
Right flip-down cover
11
Override switch .....................................
12
Middle flip-down cover
13
Boiler code plug
= Manual operation = Automatic operation
.......................
= provisional operation = automatic operation
h
............
A
Display
B
Program selection switch .......................
C
Temperature normal operation .............
D
Party button ..............................................
E
Temperature reduced operation ...........
F
Energy saving button ..............................
G
Information key (overview) ......................
H
Default factory settings ............................
K
Adjustment knob .................................
L
Selection keys , , ,.......................
M
Flip-down cover
3
2.2 Method of Operation of the Heating System
2.3 Control Activation
2.4 Settings and Adjustments
2.2 Method of Operation of the Heating System
Optimum interplay of the individual components of the heating system is required in order to generate the right amount of heat needed to cover the heating requirements at all times and in all weather conditions; the boiler and the heat distribution system (radiators, domestic hot water tank, pipes etc.) must be correctly matched to each other. To control this system, your Viessmann boiler is equipped with the Dekamatik digital indoor/outdoor boiler and heating system control.
2.3 Control Activation
On/off switch
I=ON
The Dekamatik matches the boiler water temperature to various changing conditions (e.g. the outdoor temperature or a higher boiler water temperature for heating up a domestic hot water tank, if installed). Domestic hot water priority is feasible. The Dekamatik possesses an integrated diagnostic system which can recognize and indicate any malfunctions.
The initial start-up must be conducted by the heating contractor.
H Activate main power to system.
H Activate Dekamatik-M1:
Switch On multi-boiler systems also switch on the control units of the follow-up boilers.
to “I”.
2.4 Settings and Adjustments
Comfortrol control unit
After activation, the control unit shows
- the date and time (as preset in the factory)
- the selected heating program
- the boiler water temperature
The following display appears:
Tuesday,A 04.02.96
10:20 HRS
PROGRAM
DHW: ON SPACE HEATING:ON
BOILER TEMP. : 62 ºC
................STÖRUNG.................
INFO: OPEN COVER
Example of a display (with cover closed)
The heating system is now ready for operation.
4
Symbols in the display
(
g
r
r
2.4 Settings and Adjustments
The symbols “ ” , “ ” or “ ” appear
individually or in combination
according to the current operating status of
Heating program “ ”
DHW: OFF
Space heating: OFF
No symbols are displayed
after the above data
Heating program “ ” Heating program “
DHW: ON Space heating: OFF
The symbol ” ” appears if domestic hot water is being heated (according to activa­tion period)
the system, i.e. depending on the program or activation periods.
DHW: ON Space heating: ON
Both symbols appear in combination if the heating circuit is currently switched to heating (according to activation period) and the priority control for domestic hot water heating is not activated.
DHW: ON Space heating: ON
Both symbols appear in combination if the heating circuit is switched to reduced operation (according to activation period) and the priority con­trol for domestic hot water heating is not activated.
If only the symbol ” ” appears, the DHW priority control is activated.
DHW: ON Space heating: OFF
The cu water heating is provided. Domestic hot water heating does not take place. Space heating is OFF. The current point in time is outside the selected activation period. The system goes to standby mode, i.e. with frost protection. The selector knob “ ” is turned to “0”.
ent point in time is outside the period in which domestic hot
Setting the heating program
Three heating programs can be set with the program selection switch.
Program selection switch
Frost protection of the heating system
If the outdoor temperature falls below
+34 ºF /+1ºC, the first boiler in a
multi-boiler system is operated with a
minimum boiler water temperature in order
to avoid damage to the heating system due
to freezing. The system pump is activated.
The frost protection function is cancelled
Heating program When setting required
DHW:ON Space heating:ON with frost protection
Factory setting
DHW:ON Space heating:OFF with frost protection
DHW:OFF Space heating:OFF Frost protection :ON
with outdoor temperatures over +37 ºF / +3 ºC. The system pump is switched off.
i.e. during the heating season
i.e. in summer when space heating is not re­quired
i.e. when away on holidays or during a long period of absence
5
2.4 Settings and Adjustments
Altering room temperatures
Normal operation (i.e. during daytime)
colder warmer
Reduced operation (i.e. during nighttime)
colder warmer
Altering the DHW temperature
SELECTED ROOM TEMP.A
PREVIOUS: 20 ºC CURRENT: . . ºC
INFO: OPEN COVER
SELECTED ROOM TEMP.
A
PREVIOUS: 14 ºC CURRENT: . . ºC
INFO: OPEN COVER
H Set selector knob to required
temperature.
H The previous and current room
temperatures appear immediately in the display.
H After approx. 5 seconds, the display
changes and the new temperature is stored.
Note:
The selected room temperatures apply to a correctly adjusted heating curve (see page
16). Setting “0” corresponds to approx. 41 ºF / 5 ºC (factory setting) Setting “3” corresponds to approx. 57 ºF / 14 ºC room temperature. Frost protection of the heating system is guaranteed in setting ”0”.
DHW TANK / TEMP..
A
WATER TEMP.:
50 ºC
>CHANGE TEMP. A..........
>BACK: C..................
>MAIN MENU: D............
If you wish to adjust the domestic hot water temperature, open the cover and scroll through the menu as follows:
H Select DHW.
H Select TEMPERATURE.
You are now in the TEMPERATURES menu. Follow the menu and adjust the domestic hot water temperature. Please refer also to the sections headed ”Menu Structure” on pages 8 and 9.
6
Setting party mode
2.4 Settings and Adjustments
TUESDAY,
A 04.02.96
18:30 HRS
PART Y MO D E
SELECTED: 20 ºC
CHANGE PARTY TEMP:
OPEN COVER
BOILER TEMP.: 62 ºC
Setting energy saving mode
TUESDAY,
A 04.02.96
10:35 HRS
ENERGY SAVING MODE S
BOILER TEMP.: 62 ºC
INFO: OPEN COVER
Note:
Set the party mode when you require room heating outside the preset heating program and the preset switching times. Domestic hot water heating is also available.
Note:
In the energy saving mode, the room temperature is lowered by approx. 4_F/ 2_C.
H Press “ ” button.
To change the party temperature
H Follow the instructions in the display.
To cancel the party mode:
H Press the “
mode is cancelled automatically the next time the preset heating program switches from reduced operation to normal operation.
H Press “ ” button.
To cancel the energy saving mode:
H Press the “
the energy saving mode is cancelled automatically the next time the preset heating program switches from normal operation to reduced operation.
” button. Otherwise, the party
” button. Otherwise,
Day, date and time
This data is preset in the factory and is
updated through the built-in long-life battery.
If it is necessary to make any adjustment for
daylight-savings time, please refer to
”Altering the date/time” on page 12.
7
2.4 Settings and Adjustments
Menu Structure
The following descriptions provide you with an overview of the menu structure within the menu-driven Comfortrol control unit. In this way, finding information in the menu is simplified. Please proceed as follows:
“Heating circuit” menu structure (Overview 1)
1st level
>BOILER CIRCUIT A: A.
>DHW: C..............
>SYSTEM: D..........
2nd level 3rd level
TIMER
HEATING CURVE
MAIN MENU
H Pinpoint the information you wish to query
on the 2nd, 3rd, or 4th level (see overview).
H Trace the necessary path through the
menu back to the first level.
SWITCHING TIMES
HOLIDAY PROGRAM
HEATING CURVE
DIFFEREN­TIAL-TEMP.
TIME SCHEDULE
DIFFERENT DAYS
CHANGE
DELETE
SLOPE
BC. DIFF.TEMP.
H Follow the appropriate sequence on the
control unit as described in the diagram below.
Note:
The levels appear consecutively in the display.
4th level
continue with
SHIFT
MAX. LIMIT
”DHW” menu structure (Overview 2)
1st level
>BC CIRCUIT A: A.....
>:BC CIRCUIT B B.....
>DHW: C..............
>SYSTEM: D..........
DHW TANK
RECIRCU­LATION PUMP
MAIN MENU
8
2nd level
3rd level
TIME SCHEDULE
TEMPERA­TURE
OPERATING STATUS
TIME SCHEDULE
OPERATING STATUS
4th level
TIME SCHEDULE
DIFFERENT DAYS
CHANGE TEMP.
DHW TANK CONDITION
TIME SCHEDULE
DIFFERENT DAYS
DHW CIRC. PUMP STATUS
”System” menu structure (Overview 3)
2.4 Settings and Adjustments
1st level
>BC CIRCUIT A: A.....
>DHW: C.............
>SYSTEM: D..........
2nd level 3rd level
FACTORY
CLOCK
SETTING
LANGUAGE/ LANGUE
OPERATING STATUS
OUTDOOR TEMP.
COMMON FLOW TEMP.:
INSTALLER SETUP
CODE PLEASE: ABORT
MAIN MENU
CHANGE DATE
CHANGE TIME
ENGLISH FRANÇAIS
BOILER TEMP.:
TEMP. BOILER 1 TEMP. BOILER 2 TEMP. BOILER 3
*1
BURNER
STAGE1/2: ON/OFF.....
OPERATION 1/2: h......
4th level
Continue with
*2
or
*3
FLUE GAS TEMP. MAX./CURRENT:
RETURN TEMP.
*1Only to be carried out by the
1
*
heating contractor.
2
Can be selected by the heating
*
1
contractor via the coding address.
*
3
Display for 3 boilers.
*
OP. STATUS PUMPS
SCAN 1, 2, 3: CODING PLUG:
ASSIGNED TO COMFORTROL
9
2.4 Settings and Adjustments
Time program - Explanatory remarks
General information A time program consists of switch-on and switch-off times which are set on the Comfortrol control unit. Depending on the heating program you have s elected, these control the switching (on and off) of:
- normal operation (room heating ON
- reduced operation (room heating ON
- standby mode (room heating OFF)
- domestic hot water heating (if installed)
)
)
Example:
Heating program “ (Domestic hot water ON/room heating ON)
Please note:
knob not turned to “0”.
Activation time: i.e. 6:00 HRS Changeover from reduced operation to normal operation
Activation time i.e. 22:00 HRS
You can set up to four activation periods per day for room heating and domestic hot water heating
Example of activation periods for room heating: 05:00 - 08:00 HRS
11:00 - 13:00 HRS 16:00 - 18:00 HRS 21:00 - 24:00 HRS
Illustration of the default factory timer program
Only the first activation period is preset in the factory. Switch-on time: 6:00 HRS Switch-off time: 22:00 HRS
The use of the selectable activation periods ensures economic fuel consumption.
“on” and “off” reaction times
10
Loading...
+ 22 hidden pages