Viessmann Dekamatik-HK1 Installation Instructions Manual

Page 1
Installation Instructions
Dekamatik-HK1
Digital indoor/outdoor heating circuit control unit
for mounting on the mixing valve, Part No. 7450 107 for wall mounting, Part No. 7450 110
Please file in Service Binder
Dekamatik-HK1
5167 137 1/99
Page 2
Safety
Safety, Installation and Warranty Requirements
Please ensure that this manual is read and understood before commencing installation. Failure to comply with the issues listed below
and details printed in this manual can cause product/property damage, and/or severe personal injury. Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections).
H Licensed professional heating
contractor
The installation, adjustment, service, and maintenance of this equipment must be performed by a licensed professional heating contractor.
"
Please see sections entitled “Safety” and “Important Installation Requirements.”
H Product documentation
Read all applicable documentation before commencing installation. Store documentation near boiler in a readily accessible location for reference in the future by service personnel.
"
For a listing of applicable literature, please see section entitled “Important Installation Requirements.”
H Advice to owner
Once the installation work is complete, the heating contractor must familiarize the system operator/ultimate owner with all equipment, as well as safety precautions/ requirements, shut-down procedure, and the need for professional service annually before the heating season begins.
H Warranty
Information contained in this and related product documentation must be read and followed. Failure to do so renders warranty
null and void.
Safety Terminology
The following terms are used throughout this manual to bring attention to the presence of potential hazards or important product information.
Please heed the advice given!
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death, seriou s injury or substantial product/property damage.
WARNING
Indicates an imminently hazardous situation which, if not avoided, could result in death, seriou s injury or substantial product/property damage.
CAUTION
Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or product/property damage.
IMPORTANT
Helpful hints for installation, operation or maintenance which pertain to the product.
2
5167 137
Page 3
Page
Contents
Important Precautions
Information
Heating System Types
Installation
Electrical Connections
Safety 4...........................................................................................
Important Installation Requirements
Product Information 5................................................................
-
Application Example 1 6...........................................................
- One heating circuit with mixing valve
- Dekamatik-HK 1 for mounting on the mixing valve or
- for wall mounting
Application Example 2 7
- One underfloor heating circuit with mixing valve
- Dekamatik-HK 1 for mounting on the mixing valve or
- for wall mounting
Dekamatik-HK1 for Mounting on the Mixing Valve 8.......
Dekamatik-HK1 for Wall Mounting 9.....................................
Overview 10.....................................................................................
Sensors 12.......................................................................................
Supply temperature sensor 12.....................................................
Outdoor temperature sensor 13...................................................
...........................................................
Appendix
Accessories 14...............................................................................
Room temperature sensor 14.......................................................
Wall mounting fixture 14.................................................................
WS/RS remote control unit 15......................................................
Heating circuit pump 115 V 16.......................................................
Heating circuit pump with high current or 3-phase 17..............
Other Connection Facilities 18..................................................
External heat demand / External heat disable 18....................
Mixing valve motor 18.....................................................................
Compiled fault indication 19...........................................................
Power Supply 20............................................................................
Post-Installation Testing 21........................................................
Checklist 21......................................................................................
Service binder 21.............................................................................
Dimensions / Technical Data 22................................................
5167 137
3
Page 4
Important Precautions
Safety
Take note of all symbols and notations intended to draw attention to potential hazards or important product information. These include “DANGER,” “WARNING,” “CAUTION,” and “INFORMATION.” See page 2 for details.
Approvals
Viessmann boilers, burners and controls are approved for sale in North America by International Approval Services (IAS). All electrical wiring is to be done in accordance with the latest edition of the National Electrical Code ANSI/NFPA 70. In Canada use latest edition of CSA C22.1 Part 1 and/or local codes.
Working on the equipment
The installation, adjustment, service, and maintenance of this boiler must be done by a licensed professional heating contractor who is qualified and experienced in the installation, service, and maintenance of hot water heating equipment. There are no user-serviceable parts on this equipment.
IMPORTANT
Please carefully read this manual prior to attempting installation. Any warranty is null and void if these instructions are not followed. We offer frequent installation and service seminars to familiarize our partners with our products. Please inquire.
WARNING
Turn off electric power supply before servicing. Contact with live electric components can cause shock or loss of life.
Important Installation Requirements
Power supply
Install power supply in accordance with the regulations of the authorities having jurisdiction or, in the absence of such requirements, in accordance with National Codes. Viessmann recommends the installation of a disconnect switch to the 120 V power supply outside of the boiler room. The installer must provide maximum 15 A overcurrent protection for the 120 V power supply (fuse or circuit breaker).
Literature applicable to installation of the Dekamatik-HK 1:
- Installation Instructions
- Start-up and Service Instructions
- Operating Instructions
- Installation codes mentioned in this manual
IMPORTANT
Ensure that all contacts have sufficient insulation clearance to live parts and are certified for these applications. Proper consultation with Viessmann Manufacturing Company Inc. should occur when installing components not included in the Viessmann product line.
No static discharge to the internal componentry must ever occur when working with opened control equipment.
IMPORTANT
Leave all literature at the installation site and advise the system operator/ultimate owner where the literature can be found. Contact Viessmann for additional copies.
5167 137
4
Page 5
Product Information
Information
Digital indoor/outdoor heating circuit control unit for one heating circuit with mixing valve, either with drive module for mounting on Viessmann mixing valve or for wall mounting and connection of a separate mixing valve motor.
5167 137
5
Page 6
Heating System Types
Application Example 1
- One heating circuit with mixing valve
- Dekamatik-HK1
Instead of the Dekamatik-HK 1 for mounting on the mixing valve it is also possible to use a Dekamatik-HK 1 for wall mounting in conjunction with a separate mixing valve motor.
Dekamatik-HK 1 for mounting on the mixing valve Heating circuit Supply header Return header
*1
It is possible to connect a separate room temperature sensor (accessory) instead of the outdoor temperature sensor for the purpose of
*1
a purely room temperature dependent control.
*1
If the outdoor temperature value of the boiler or heating circuit control unit is used via the Viessmann 2-wire BUS, a room temperature
*1
sensor can be connected for room temperature dependent control (only possible with communication module, accessory).
*2
Only in conjunction with communication module (accessory).
6
Outdoor temperature sensor Supply temperature sensor Heating circuit pump Power supply Remote control
ATS = Outdoor temperature sensor VTS = Supply temperature sensor
*1
*2
Viessmann 2-wire BUS for communication with other Dekamatik control units External heat demand / external heat disable
5167 137
Page 7
Heating System Types
Application Example 2
- One underfloor heating circuit with mixing valve
- Dekamatik-HK1
Instead of the Dekamatik-HK 1 for mounting on the mixing valve it is also possible to use a Dekamatik-HK 1 for wall mounting in conjunction with a separate mixing valve motor.
Dekamatik-HK 1 for mounting on the mixing valve Underfloor heating circuit Supply header Return header
*1
It is possible to connect a separate room temperature sensor (accessory) instead of the outdoor temperature sensor for the purpose of
*1
a purely room temperature dependent control.
*1
If the outdoor temperature value of the boiler or heating circuit control unit is used via the Viessmann 2-wire BUS, a room temperature
*1
sensor can be connected for room temperature dependent control (only possible with communication module, accessory).
*2
Only in conjunction with communication module (accessory).
5167 137
Outdoor temperature sensor
*1
Supply temperature sensor Return temperature sensor (accessory) (see separate instructions regarding installation and electrical connections) Heating circuit pump Power supply Remote control
ATS = Outdoor temperature sensor VTS = Supply temperature sensor RLS = Return temperature sensor
*2
Viessmann 2-wire BUS for communication with other Dekamatik control units External heat demand / external heat disable
7
Page 8
Installation
Dekamatik-HK1 for Mounting on the Mixing Valve
1. Screw the threaded bolts (M6 or M8
female thread depending on size of mixing valve) onto the threaded bolts
of the mixing valve.
Fig. 1 Mounting the Dekamatik-HK 1 on the mixing valve
2. Place the base plate screw on with the washers and nuts provided.
3. Snap the control unit module fasten with the screws provided.
onto the base plate ;
in position and
with drive
8
5167 137
Page 9
Dekamatik-HK1 for Wall Mounting
Installation
1. Pull the wall mounting fixture off the control unit
.
Fig. 2 Mounting the Dekamatik-HK 1 on the wall
2. Fasten the wall mounting fixture the wall with three screws.
3. Carry out the electrical connections (i.e. mixing valve motor and compiled fault indication) (see page 18 and 19).
4. Pull off the cover
5. Push the control unit
guideways fixture provided.
6. Re-fit the cover .
; fasten with the screws
.
in the
onto the wall mounting
to
5167 137
9
Page 10
Electrical Connections
Overview
Open up the terminal compartment by unscrewing the screws below the programming unit .
Mother board for heating circuit pump Connect via connector for power supply. Cord and plug factory supplied; AC 120 V~ 60 Hz; 15 A receptacle required (field supplied). Fuse F1 On/off switch Strain relief clamp
Fig. 3 Electrical connections
10
in the cover
AC 120 V~
Low voltage connections
X14 for outdoor temperature
sensor or room temperature sensor (accessory)/ supply temperature sensor
X3 not used
or
X3 for return temperature
sensor (accessory) in conjunction with underfloor heating circuit
X1 for WS/RS remote control
unit (accessory) or
X16 for wall mounting fixture
(assembly) for using Comfortrol program­ming unit as a remote control
X1 1 for external heat demand
(open mixing valve) / external heat disable (close mixing valve) or for external changeover of the heating program
X16 not used
5167 137
Page 11
Overview (continued)
Electrical Connections
Wall mounting fixture Terminal strips for connection of mixing valve motor or compiled fault indication
Fig. 4 Electrical connections in the wall mounting fixture; Dekamatik-HK1 for wall mounting
5167 137
11
Page 12
Electrical Connections
Sensors
Supply temperature sensor (strap-on sensor)
Fig. 5 Supply temperature sensor
IMPORTANT
Mount the supply temperature sensor downstream from the heating circuit pump on the heating supply pipe at a distance of approx. 3 to 5 ft / 1 to 1.5 m from the mixing valve.
Where plastic pipes are used, mount the sensor on an intermediate metal pipe section. It is not necessary to use heat conductive paste.
Fig. 6 Installing the supply temperature sensor downstream from the bypass valve
Fig. 7 Opening the case
If a pressure-activated bypass valve installed, mount the sensor supply pipe immediately after the bypass valve.
1. Thoroughly clean the heating supply
pipe until metallically bright.
2. Open the case screwdriver.
3. Place the perforated mounting strap (supplied inside the sensor case) on the tensioning screw the supply pipe the tensioning screw; tighten the tensioning screw.
4. Close the sensor case.
of the sensor with a
and place back on
on the
, run it around
is
IMPORTANT
The sensor must not be insulated.
Fig. 8 Opening the supply temperature sensor and fastening with perforated mounting strap
12
5. If the outdoor temperature sensor or a room temperature sensor is to be connected, go to page 13. Otherwise, insert connector in socket “X14” in the terminal compartment (see page 10); install strain relief clamp.
5167 137
Page 13
Sensors (continued)
Outdoor temperature sensor
If the outdoor temperature sensor of the boiler or heating circuit control unit is used via the Viessmann 2-wire BUS, it is not necessary to connect the outdoor temperature sensor provided. A room temperature sensor can be connected instead of the outdoor temperature sensor (see page 14).
Electrical Connections
Fig. 9 Mounting the outdoor temperature sensor
1. Remove the cap
2. Mount the bottom part of the case
(cable entry must point downwards).
.
IMPORTANT
The outdoor temperature sensor should be mounted 6½ to 8¼ ft / 2 to 2.5 m above ground level on the north or north-west facing wall of the bu ilding. In the case of multi-storey buildings, it should be mounted in the upper half of the second storey. If different parts of the building are controlled via separate heating circuits, the outdoor temperature sensor should be mounted on the corresponding side of the building. For example, if the heating circuit controls the south- facing part of the building, the outdoor temperature sensor must be mounted on the south-facing wall. Ensure that the outdoor temperature sensor is not located over windows, doors and air vents, nor immediately beneath a balcony or guttering. The outdoor temperature sensor must not be plastered over. If mounting on an unplastered wall, make allowances for thickness of plaster or remove sensor before plastering wall.
Outdoor temperature sensor Supply temperature sensor
Fig. 10
5167 137
Connecting the outdoor temperature sensor to the Dekamatik-HK 1
3. Connect the cable to the terminals (the wires are interchangeable). Cable: AWG 16/2, copper; max. 115 ft / 35 m.
4. Place cap
5. Connect the 2-wire cable from the
outdoor temperature sensor to connector (the wires are interchangeable).
6. Break open the cable bushing; install strain relief clamp.
7. Insert connector the terminal compartment (see page 10); install strain relief clamp.
over base and snap on.
at terminals “1” and “2”
in socket “X14” in
13
Page 14
Electrical Connections
Accessories
Room temperature sensor
1. Mount the room temperature sensor in
accordance with the separate installation instructions.
2. Connect the 2-wire cable from the room temperature sensor to connector (the wires are interchangeable).
3. Break open the cable bushing; install strain relief clamp.
4. Insert connector in socket “X 14” in the terminal compartment (see page 10); install strain relief clamp.
at terminals “1” and “2”
Room temperature sensor Supply temperature sensor
Fig. 11 Connecting the room temperature sensor to the Dekamatik-HK 1
Wall mounting fixture (for using the programming unit as a remote control)
The programming unit of the control unit can be used as a remote control in the wall mounting fixture (accessory).
1. Remove the cover
2. Take the programming unit
the control unit.
3. Fit the blank cover of the wall mounting fixture in the control unit.
.
out of
Fig. 12 Taking the programming unit out of the control unit
14
5167 137
Page 15
Accessories (continued)
Electrical Connections
4. Mount the wall mounting fixture in accordance with the separate installation instructions.
5. Connect the 2-wire cable from the wall mounting fixture to connector terminals “1” and “2” (the wires are interchangeable).
6. Break open the cable bushing; install strain relief clamp.
at
Wall mounting fixture
Fig. 13 Connecting the wall mounting fixture to the Dekamatik-HK1
WS remote control unit RS remote control unit
7. Insert connector
the terminal compartment (see page 10); install strain relief clamp.
8. Insert the programming unit in the wall mounting fixture.
1. Mount the remote control unit in accordance with the separate installation instructions.
2. Connect the 3-wire cable from the remote control unit to connector
in socket “X 16” in
.
Remote control unit
Fig. 14
5167 137
Connecting the remote control unit to the Dekamatik-HK 1
3. Break open the cable bushing; install strain relief clamp.
4. Insert connector the terminal compartment (see page 10); install strain relief clamp.
in socket “X 1” in
15
Page 16
Electrical Connections
Accessories (continued)
Heating circuit pump 115 V
WARNING
In the case of underfloor heating systems, a high limit aquastat (immersion or strap-on type) must be installed in the heating supply downstream from the mixing valve and the heating circuit pump. In this case connect the heating circuit pump to the high limit aquastat (see separate Installation Instructions).
1. Install the heating circuit pump in
accordance with the manufacturer’s specifications and instructions. Rated current : AC 4 (2) A
Fig. 15 Connecting the 115 V pump
2. Disconnect the connector from the heating circuit pump (if connected); connect the 3-wire cable from the heating circuit pump to connector
3. Insert connector the heating circuit pump.
in the socket for
.
16
5167 137
Page 17
Accessories (continued)
Heating circuit pump with high current or 3-phase
Electrical Connections
1. Install the heating circuit pump in accordance with the manufacturer’s specifications and instructions.
2. Select contactor and connection wire according to the rating of the pump to be connected.
3. Connect the heating circuit pump to the contactor.
IMPORTANT
3-Phase pumps require use of contactors with overload protection.
Contactor High current or 3-phase pump
Fig. 16 Connecting the high current or 3-phase pump
4. Connect contactor to connector
5. Insert connector
heating circuit pump in the terminal compartment (see page 10); install strain relief clamp.
in socket for
.
5167 137
17
Page 18
Electrical Connections
Other Connection Facilities
External heat demand / External heat disable
When the “external heat demand” contact is activated, the mixing valve is opened. When the “external heat disable” contact is activated, the mixing valve is closed.
1. In the plug-in connector provided, connect a potential­free contact for
- external heat demand
or external changeover of the heating program (see Service Instructions for the coding required) at terminals “3” and “2”
- external heat disable at terminals
“1” and “2.”
2. Break open the cable bushing; install strain relief clamp.
3. Insert connector the terminal compartment (see page 10); install strain relief clamp.
External heat demand or external changeover of the heating program External heat disable
Fig. 17 Connecting external heat demand / external heat disable
Mixing valve motor only with Dekamatik-HK 1 for wall mounting
H Connect the 4-wire cable from the
mixing valve motor to terminals “X3,” “X4.1,” “X4.2” and “X4.3” in the wall mounting fixture of the Dekamatik-HK 1 as shown in Fig. 18.
Mixing valve open Mixing valve closed
in socket “X 11” in
Wall mounting fixture
Fig. 18 Connecting the mixing valve motor
18
IMPORTANT
The Dekamatik-HK 1 incorporates a 120 V mixing valve output.
5167 137
Page 19
Electrical Connections
Other Connection Facilities (continued)
Compiled fault indication only with Dekamatik-HK 1 for wall mounting
Data transfer and sensor faults are reported. In conjunction with a Dekamatik boiler control unit, a compiled fault message is also relayed to these via the Viessmann 2-wire BUS (accessory).
1. Select the signal device (provided by the customer). Rated voltage: AC 120 V~ Rated current: AC 4 (2) A
2. Carry out the connection to terminals “X3,” “X4.4” and “X4.5” in the wall mounting fixture of the Dekamatik-HK 1 as shown in Fig. 19.
Wall mounting fixture
Fig. 19 Connecting the compiled fault indication
5167 137
19
Page 20
Electrical Connections
Power Supply
Safety requirements
Install power supply in accordance with the regulations of the authorities having jurisdiction or, in the absence of such requirements, in accordance with National Codes.
The Dekamatik-HK 1 is standard equipped with a 120 V power cord. A receptacle with a max. 15 A circuit breaker or fuse is required (field supplied).
20
5167 137
Page 21
Post-Installation Testing
Checklist
Appendix
Check the following conditions and correct deficiencies.
j Ensure all electrical connections have
been correctly made.
j Ensure positive connection of all
plug-in connectors.
j Ensure mixing valve motor is properly
connected.
j Ensure correct rotational direction of
mixing valve motor and, if necessary, change in accordance with the Service Instructions.
j Ensure heating circuit pump is properly
connected.
Service binder
Please keep all relevant Operating Instructions and Service Documents in the Operating and Service Document Binder. We advise you to keep the binder in a clearly visible and accessible position.
5167 137
21
Page 22
Appendix
Dimensions / Technical Data
Mounting on the mixing valve
Wall mounting
Rated voltage: AC 120 V~ Rated frequency:60 Hz Rated current: AC 4 A Power consumption: 7 VA Protection class: I Test class: II Degree of protection: IP 22 D to EN 60529 Ambient temperature
- during operation: 32 to 104 °F
0to +40°C
- during storage and transport: -4 to +104 °F
-20 to +65°C Dead zone of PI controller for mixing valve with slope
”=1.4: 1.2 K
“ Relay outputs for
- heating circuit
pump
- compiled fault
indication: AC 4(2) A 120 V~
- mixing valve: AC 0,2(0,1) A 120 V~
- total: max. AC 4 A 120 V~
: AC 4(2) A 120 V~
Fig. 20 Dimensions
22
5167 137
Page 23
Notes
Appendix
5167 137
23
Page 24
Printed on environmentally friendly
(recycled and recyclable) paper.
Viessmann Manufacturing Company (U.S.) Inc. 45 Access Road Warwick, Rhode Island 02886 USA Tel. (401) 732-0667 Fax (401) 732-0590 www.viessmann-us.com mail@viessmann-us.com
24
Viessmann Manufacturing Company Inc. 750 McMurray Road Waterloo, Ontario N2V 2G5 Canada Tel. (519) 885-6300 Fax (519) 885-0887 www.viessmann.ca mail@viessmann.ca
Technical information subject to change without notice.
5167 137
Loading...