For operation with natural gas and liquid propane gas
Floor mounted, gas-fired condensing boiler
Heating input 19 to 199 MBH
5.6 to 58 kW
VITOCROSSAL 300
Product may not be exactly as shown
Vitocrossal 300
CU3A Series 26 to 57
Floor mounted, gas-fired condensing
boiler with modulating MatriX gas burner.
For room air dependent or independent
operation.
5673 647 - 03 07/2015
H
Page 2
Product Information
Benefits
Equipped with the industry’s first intelligent combustion
management system and powerful control technology,
the new generation Vitocrossal 300 CU3A gas-fired
Floor mounted condensing boiler delivers unparalleled
performance, reliability and comfort.
The benefits at a glance:
Vitocrossal 300 CU3A 26 to 57 Technical Data
■ Best value in its class with new industry-leading
technology and the most standard features.
■ Highest Efficiency up to 98% at full modulation and up
to 95% A.F.U.E.
■ Lasting performance with industry-leading Viessmann
made SA240 316 Ti stainless steel Inox-Crossal heat
exchanger constructed to CSA B51 and ASME Section IV.
■ Low Emission Combustion with Viessmann made
stainless steel MatriX burner. Factory calibrated.
■ Fast Installation and Reduced Maintenance with Lambda
Pro, industry-first intelligent combustion management
system: Adjusts automatically to gas type and quality.
No fuel conversion kit required.
■ Powerful and User-friendly
Viessmann Vitotronic on-board multi-function outdoor
reset boiler and system control for multi-temperature
space and DHW heating.
■ Expanded Application Range with increased capacity up
to 199 MBH (58 kW). Multi-boiler installation up to
1592 MBH (464 kW) with up to 8 boilers.
■ Greater Venting Flexibility with increased vent length [up
to 198 ft. (60 m)] and multiple venting options.
- Horizontal or vertical sealed combustion coaxial
venting (field supplied).
- Horizontal or vertical single-wall venting (field
supplied).
■ Compact, Esthetic Product Design and zero clearance
to combustibles.
■ Extremely Quiet Operation; quieter than most
refrigerators.
■ True High-Altitude Operation up to 10,000 ft. (3,000 m)
with simple electronic adjustment.
■ Efficiency up to 98% through intensive condensation.
The flue gas temperature is only approximately 9-27ºF
(5-15ºC) above boiler return temperature.
2
2
5673 647 - 03
Page 3
Vitocrossal 300 CU3A 26 to 57 Technical Data
Cross-Section
Vitocrossal 300 CU3A 26 to 57
Product Information
Vitocrossal 300 CU3A boiler efficiency dependent
on system heating water return temperatures and
load conditions
Product may not be exactly as shown
Legend
A Digital Vitotronic boiler control unit
B Water-cooled stainless steel combustion chamber
C Modulating MatriX gas burner – for extremely clean
combustion
D Stainless steel Inox-Crossal heat exchanger
E Highly effective thermal insulation
F Flue gas collector with condensate drain pipe
G Combustion air intake for direct vent (two-pipe)
systems
5673 647 - 03
3
3
Page 4
Technical Data
Vitocrossal 300 CU3A 26 to 57 Technical Data
Technical Data
Boiler Model No. CU3A26354557
Natural Gas / Liquid Propane Gas
CSA input
CSA output / DOE heating capacity*1
Net AHRI RatingMBH
Heat exchanger surface areaft.
Min. gas supply pressure
Natural gas
Liquid propane gas
Max. gas supply pressure *3
Natural gas
Liquid propane gas
A.F.U.E.%95959595
Weightlbs
Boiler water contentUSG
Max. operating pressure
at 210ºF (99ºC)
Boiler water temperature
- Adjustable high limit (AHL) range
space heating (steady state)
DHW production
- Fixed high limit (FHL)
Boiler connections
Boiler heating supply and return
Pressure relief valve
Boiler drain
Gas valve connection
MBH
(kW)
MBH
(kW)
(kW)
(m2)
“w.c.
“w.c.
“w.c.
“w.c.
(kg)
(L)
psig
(bar)
ºF
(ºC)
ºF
(ºC)
ºF
(ºC)
NPTM
NPTF
NPTM
NPTF
2
19-94
(5.6-27.5)
17.7-87
(5.2-25.5)
76
(22)
16.7
(1.5)
4
10
14
14
269
(122)
13.5
(51)
30
(2)
68-194
(20-90)
194
(90)
210
(99)
1a”
¾”
1”
¾”
25-125
(7.3-36.6)
23.3-116
(6.8-34)
101
(30)
20.7
(1.9)
4
10
14
14
275
(125)
13.0
(49)
30
(2)
68-194
(20-90)
194
(90)
210
(99)
1a”
¾”
1”
¾”
43-160
(12.6-47)
40-149
(11.7-43.7)
129
(38)
34.1
(3.2)
4
10
14
14
352
(160)
18.8
(71)
30
(2)
68-194
(20-90)
194
(90)
210
(99)
1a”
¾”
1”
¾”
43-199
(12.6-58)
40-185
(11.7-54.2)
161
(47)
34.1
(3.2)
4
10
14
14
352
(160)
18.8
(71)
30
(2)
68-194
(20-90)
194
(90)
210
(99)
1a”
¾”
1”
¾”
*1 Output based on 140ºF (60ºC), 120ºF (49ºC) system supply/return temperature.
*2 Net AHRI rating based on piping and pick-up allowance of 1.15.
*3 If the gas supply pressure exceeds the maximum gas supply pressure value, a separate gas pressure regulator
must be installed upstream of the heating system.
Note: For high altitude installation at 10,000 ft. the input for model Vitocrossal 300 CU3A will have an altitude
de-ration of 18%.
4
4
5673 647 - 03
Page 5
Vitocrossal 300 CU3A 26 to 57 Technical Data
Technical Data
Technical Data
Boiler Model No. CU3A26354557
Dimensions
Overall depth
Overall width
Overall height
(with control interface open)
Overall height
Flue gas *4
Temperature (at boiler return
temperature of 86ºF (30ºC)
- at rated full load
- at rated partial load
Temperature (at boiler return
temperature of 140ºF (60ºC)
Max. condensate flow rate *5
for NG and LPG
T
S/TR =104/86ºF (40/30ºC)USG/h
Condensate connection hose
Boiler flue gas connection *6Ø
Combustion air supply connection outer
Sound Rating (A scale)
- at maximum input
- at minimum input
Standby losses *7BTU/hr
inches
(mm)
inches
(mm)
inches
(mm)
inches
(mm)
ºF (ºC)
ºF (ºC)
ºF (ºC)
(L/h)
nozzle
Ø in.
in. (mm)3 (80)3 (80)4 (110)4 (110)
Ø in. (mm)3 (80)3 (80)3 (80)3 (80)
dB
dB
W/hr
27
684
26
660
67
1707
61.5
1562
113 (45)
90 (32)
167 (75)
0.9
3.43
27
684
26
660
67
1707
61.5
1562
113 (45)
90 (32)
167 (75)
1.2
4.62
31b
801
26
660
67
1707
61.5
1562
113 (45)
90 (32)
167 (75)
1.6
5.95
31b
1707
61.5
1562
113 (45)
90 (32)
167 (75)
7.92
¾¾ ¾ ¾
48
32
1128
330
55
33
1000
292
53
33
1120
328
801
26
660
67
2.1
58
33
995
291
*4 Measured flue gas temperature with a combustion air temperature of 68°F (20°C).
*5 Based on maximum input rate.
*6 For side wall vent installations (coaxial system):
Do not exceed max. equivalent length specified in the Installation Instructions of the Vitocrossal 300 CU3A
Venting System.
Do not attempt to common-vent Vitocrossal 300 CU3A with any other appliance.
Side wall co-axial vent installation must include Viessmann protective screen!
For details refer to the Installation Instructions for the Vitocrossal 300 CU3A Venting System.
*7 Standby losses measured from the boiler temperature sensor well based on a boiler water temperature of 158°F
(70°C) and a room temperature of 68°F (20°C).
For information regarding other Viessmann System Technology componentry, please reference documentation
of respective product.
5673 647 - 03
5
5
Page 6
Dimensional Information
Models 300 CU3A 26 to 57
Vitocrossal 300 CU3A 26 to 57 Technical Data
Legend
A Overall boiler height (boiler control open)
B Overall boiler height (boiler control closed)
C Safety header connection
D Boiler supply
E Gas connection
F Boiler return
G Boiler drain
H Vent connection
I Condensate drain connection
J Combustion air connection
Model 26 to 35Model 45 and 57
a in. (mm)
b in. (mm)
c in. (mm)
d in. (mm)
Note: All height dimensions of the boiler have a tolerance of +.6 in. (+15 mm) due to the factory installed adjustable feet.
27 (684)
17 (430)
23b (595)
4
¾ (120)
a in. (mm)
b in. (mm)
c in. (mm) 28 (712)
d in. (mm)
31b (801)
21b (545)
5b (140)
6
6
5673 647 - 03
Page 7
Vitocrossal 300 CU3A 26 to 57 Technical Data
Recommended Minimum Service Clearances
Note: The Vitocrossal 300 CU3A series boiler conforms
on the special venting system label.
The back or side clearance shall be increased if
piping installation is required.
Minimum Clearances
to the zero inches vent clearance to combustibles
testing requirements dictated by the boiler
Harmonized Standard ANSI Z21.13. CSA/4.9
and therefore is listed for zero clearance to
combustibles when vented with a single-wall UL/
ULC certified special venting system. The zero
inches vent clearance to combustibles for the
Vitocrossal 300 CU3A boiler supercedes the
clearance to combustibles listing that appears
Clearances
TopFrontRearLeftRightVent pipe
00 AL CL0000
AL = Alcove
CL = Closet
The Vitocrossal CU3A series boiler is approved for
closet and alcove installation with the clearances to
combustibles listed above.
Recommended minimum service clearances
For typical Vitocrossal CU3A series boiler installations,
Viessmann recommends installing the boiler with the
clearances shown in the illustration on the left.
See the Vitocrossal 300 CU3A Venting
System Installation Instructions for details.
5673 647 - 03
7
7
Page 8
Waterside Flow
Pressure Drop (heating water side)
Pressure drop
Vitocrossal 300 CU3A 26 to 57 Technical Data
Flow rate
Legend
A Boiler models CU3A 26 to 35 kW
B Boiler models CU3A 45 to 57 kW
The Vitocrossal 300 is only suitable for fully pumped hot
water heating systems.
∆T = 20ºF (10 K)∆T = 30ºF (15 K)∆T = 40ºF (20 K)
Boiler models CU3A
269.9 (2.2)6.6 (1.5)4.9 (1.1)
3513.3 (3.0)8.9 (2.0)6.6 (1.5)
4517.0 (3.9)11.4 (2.6)8.5 (2.0)
5722.7 (5.2)15.0 (3.4)11.4 (2.6)
Note: This boiler does not require a flow switch.
Flow rate
USGPM (m
3
/h)
Flow rate
USGPM (m3/h)
Flow rate
USGPM (m3/h)
8
5673 647 - 03
Page 9
Vitocrossal 300 CU3A 26 to 57 Technical Data
On-Board Vitotronic 200, HO1B Control
Modular structure
The control unit is integrated into the boiler. The control
unit comprises a standard unit, electronics modules and
a programming unit.
Standard unit:
■ ON/OFF switch
■ Optolink laptop interface
■ Operating and fault indicators
■ Reset button
■ Fuses
Boiler Control
Programming unit:
■ Easy operation through:
– Plain text display with graphic ability
– Large font and black & white depiction for good
contrast
– Context-sensitive help text
– Removable programming unit; can be mounted
on the wall with separate accessory
■ With digital time switch
■ Control keys for:
– Navigation
– Confirmation
– Help and additional information
– Menu
■ Setting the:
– Room temperature
– Reduced room temperature
– DHW temperature
– Heating program
– Time programs for central heating, DHW heating
and DHW recirculation
– Economy mode
– Party mode
– Holiday program
– Heating curves
– Codes
– Actuator tests
– Test mode
■ Displaying the:
– Boiler water temperature
– DHW temperature
– Operating details
– Diagnostic details
– Fault messages
5673 647 - 03
9
Page 10
Boiler Control
Design and Function
Vitocrossal 300 CU3A 26 to 57 Technical Data
Functions
■ Weather-compensated control of the boiler water
and/or supply temperature
■ Control of one heating circuit without mixer and two
heating circuits with mixer (with accessory mixing
valve extension modules)
■ Demand-dependent heating circuit pump and burner
off control
■ Adjustment of a variable heating limit
■ Anti-seizing pump protection
■ Integral diagnostic system
■ Maintenance display
■ DHW temperature control with priority
■ Auxiliary function for DHW heating (short-term
heating to a higher temperature)
■ 0-10V External signal input
■ 0-10V Pump speed control output signal
Control Characteristics
PI characteristics with modulating output.
Time Switch
Digital time switch.
■ Individual and 7-day program
■ Automatic daylight savings time changeover
■ Automatic function for DHW heating and DHW
recirculation pump
■Time, day and standard switching times for space heating, DHW heating and the DHW recirculation
pump are factory-set
■Switching times are individually programmable, i.e. up to four switching periods per day
Shortest switching interval: 10 minutes
Power backup: 14 days.
Setting the Operating Programs
The heating system frost protection (see
frost protection function) applies to all heating programs.
You can select the following heating programs with the
program keys:
■ Heating and DHW
■ DHW only
■ Standby mode
External heating program changeover.
Frost protection
■The frost protection function will be started when the outside temperature drops below approx. 34°F (1°C).
With the frost protection function, the heating circuit
pump will be switched ON and the boiler water is
maintained at a lower temperature of approx. 68°F
(20°C).
The DHW tank will be heated to approx. 68°F (20°C).
■ The frost protection function will be stopped when the
outside temperature rises above approx. 37°F (3°C)
(default settings).
Summer Operation
Heating program “w”
The burner is only activated upon a call for domestic hot
water from the DHW storage tank (controlled by DHW
tank temperature sensor).
10
5673 647 - 03
Page 11
Vitocrossal 300 CU3A 26 to 57 Technical Data
Design and Functions (continued)
Boiler Control
Technical Data
Rated supply voltage: 120VAC
Rated frequency: 60 Hz
Rated current: Less than 12 A
Max. ambient temp.
- at operation: 32 to 104ºF (0 to 40ºC)
Installation in living spaces or
boiler rooms (standard ambient
conditions)
- when storing
or transporting: -4 to +158ºF (-20 to +70ºC)
Setting fixed high limit: 210ºF (99ºC)
(not adjustable)
Adjustment range of
DHW tank set-point
temperature: 50 to 149ºF (10 to 65ºC)
Heating curve settings
- Heating curve slope: 0.2 to 3.5
- Heating curve shift: -12 to +33ºC
-13 to 40 K
Heating Curve Adjustment (slope and shift)
The control unit regulates the boiler water temperature
(= supply temperature of heating circuit without mixing
valve) and the supply temperature of the heating circuit
with mixing valve (in conjunction with the accessory kit
for a heating circuit with mixing valve) according to the
outdoor temperature. The boiler water temperature is
automatically raised by 0 to 72 F / 0 to 40 K higher than
the currently required set supply temperature
(in the factory default setting the differential temperature
is 14.4 F / 8 K). See Service Instructions for coding
address “9F” in coding level 2.
The supply temperature that is required to achieve a
given room temperature depends on the heating system
and the thermal insulation of the building that is being
heated.
The adjustment of the two heating curves is used to
match the boiler water temperature and the supply
temperature to these conditions. The boiler water
temperature is limited upwards by the fixed high limit
and the temperature set for the electronic high limit.
The supply temperature cannot rise above the boiler
water temperature.
Boiler water or supply
temperature
Room
set-point
temperature
Outdoor temperature
Legend
A Low temperature heating system, e.g. radiant floor heating
B Medium temperature heating system,
e.g. cast iron radiation, staple-up radiant floor heating
C High temperature heating system,
e.g. fintube radiation, fan coils
5673 647 - 03
11
Page 12
Accessories
Sensors
Vitocrossal 300 CU3A 26 to 57 Technical Data
Boiler Temperature Sensor(supplied)
The boiler temperature sensor is connected at the control
unit for weather-responsive operation and is built into the
boiler.
Specification sensor type: Viessmann NTC 10K ohms
at 77ºF (25ºC)
Max. ambient temp.
- at operation: 32 to 266ºF (0 to 130ºC)
- when storing
or transporting: - 4 to+158ºF (-20 to+70ºC)
DHW Tank Temperature Sensor
- integrated DHW temperature sensor
Immersion Temperature Sensor(accessory)
To capture the low loss temperature
(if the LLH is used)
Specification
Lead length fully wired: 12 ft. (3.75 m),
Permissible ambient temp.
- during operation: 32 to 194°F (0 to 90°C)
- when storing
or transporting: - 4 to+158°F (-20 to+70°C)
(supplied)
Outdoor Temperature Sensor
Sensor location:
- North or northwest wall of building
- 6.6 to 8.2 ft. (2 to 2.5 m) above ground or in case
of a multi-storey building approximately halfway up
the second floor
Electrical connection:
- 2-wire cable, max. cable length 115 ft. (35 m)
with a wire size of min. AWG 16 copper
- Cable to the outdoor sensor must not be laid near
line voltage wiring (120/240V)
Max. ambient temp.
- at operation: 32 to 194ºF (0 to 90ºC)
- when storing
or transporting: - 4 to+158ºF (-20 to+70ºC)
(supplied)
Optional Accessories
Supply Temperature Sensor
(strap-on sensor, included with mixing valve actuator
accessory kit),
- when storing
or transporting: -4 to+158°F (-20 to+70ºC)
Installed with a strapping band.
Cable length 19.7 ft. (6 m), ready to plug in.
Max. ambient temp.
- at operation: 32 to 212ºF (0 to 100ºC)
- when storing
or transporting: -4 to+149ºF (-20 to+70ºC)
KM BUS Expansion Module
To connect 2 to 9 devices (mixing valve actuator,
Vitotrol, input module, etc.) to the single KM BUS
connection of the boiler.
Specification
Lead length 10 ft. (3.0 m), fully wired
Permissible ambient temp.
- during operation 32 to 104°F (0 to 40°C)
- during storage and
transport: - 4 to+149°F (-20 to+65°C)
12
5673 647 - 03
Page 13
Vitocrossal 300 CU3A 26 to 57 Technical Data
Optional Accessories (continued)
Accessories
Room Temperature Sensor,
Separate room temperature sensor as supplement to the
Vitotrol 200A and 300A; to be used if the Vitotrol 200A
or 300A cannot be installed inside the main living room
or in a suitable position where the unit can capture and
adjust the temperature.
Installation in the main living room on an internal wall
opposite radiators. Never install inside shelf units,
recesses, immediately by a door or heat source
(e.g. direct sunlight, fireplace, TV set, etc.).
Connect the room temperature sensor to the Vitotrol
200A or 300A.
Electrical connection:
- 2-wire cable with a wire size of min. AWG 18 copper
- The cable length between the control unit, remote
control unit and room temperature sensor must not
exceed 98 ft. (30 m)
Max. ambient temp.
- at operation: 32 to 104ºF (0 to 40ºC)
- when storingor transporting: -4 to+149ºF (-20 to +65ºC)
Mixing Valve Extension Module
Mixing Valve Actuator Kit
The mixing valve actuator is mounted directly on the
Viessmann ¾ to 2½” mixing valve.
The mixing valve actuator is a motor-driven control unit.
The rotational direction is reversible.
Rated voltage: 120VAC
Rated frequency: 60 Hz
Power consumption: 4W max. ambient temperature
- at operation: 32º F to 104ºF (0º C to 40ºC)
application in living areas and installation sites
(normal ambient conditions)
-storage & shipping: -4ºF to 149ºF (-20ºC to 65ºC)
LON Communication Module
Electronic PCB for data exchange with the Vitotronic
200-H, Vitocom 200 and for connecting to a higher level
building management system.
LON Connecting Cable
(for data exchange between control units)
Cable length 23 ft. (7 m), fully wired
Rated voltage: 120VAC
Rated frequency: 60 Hz
Rated current: 2 A
Power consumption: 4 W
Max. ambient temp.
- at operation: 32 to 104ºF (0 to 40ºC)
- when storing
or transporting: -4 to+149ºF (-20 to+65ºC)
Relay output for
heating circuit pump: 2 A, 120VAC
Actuator torque: 3 Nm
Time of 90º: 120 seconds
5673 647 - 03
LON Terminal End Resistor
To terminate the LON BUS at the first and the last control
unit.
13
Page 14
Accessories
Optional Accessories (continued)
Vitotrol 200A
One Vitotrol 200A can be used for every heating circuit
in a heating system. The Vitotrol 200A can regulate one
heating circuit and up to two remote controls may be
connected to the control unit.
KM BUS Participant
The Vitotrol 200A remote control regulates the required
set room temperature in standard mode, from any room
in the house.
- Party and economy mode can be enabled via keys
- Only for heating circuit with mixing valve
Fitted room temperature sensor for room temperature
hook-up
Vitocrossal 300 CU3A 26 to 57 Technical Data
Connection:
- 2-core lead 18 AWG, length max. 164 ft. (50 m)
(even if connecting
several remote control units)
- Never route this lead immediately next to 120/208/460 V
cables
- LV plug as standard delivery must be installed in the
main living room (lead room).
Specification:
Power supply via KM BUS
Power consumption: 0.2 W
Max. ambient temp.
- at operation: 32 to 104ºF (0 to 40ºC)
- when storingor transporting: -4 to+149ºF (-20 to+65ºC)
Set room temp. range 37 to 99ºF (3 to 37ºC)
The set room temperature for reduced mode is adjusted
at the control unit.
WS function:
Installation anywhere in the building.
RS function:
Note: Never activate the RS function for underfloor
heating circuits (inertia). In heating systems with
a heating circuit without mixing valve and heating
circuits with mixing valve, the RS function must
only affect the heating circuit with mixing valve.
Room temperature hook-up:
Installation in the main living room on an internal wall
opposite radiators. Never install inside shelf units,
recesses, immediately by a door or heat source (e.g.
direct sunlight, fireplace, TV set, etc.).
The integral room temperature sensor captures the actual
room temperature and effects any necessary corrections
of the supply temperature as well as a rapid heat-up
at the start of the heating operation (if appropriately
programmed).
14
5673 647 - 03
Page 15
Vitocrossal 300 CU3A 26 to 57 Technical Data
Optional Accessories (continued)
Vitotrol 300A
One Vitotrol 300A can be used for every heating circuit
in a heating system. The Vitotrol 300A can regulate up
to three heating circuits. Up to two remote controls may
be connected to the control unit.
KM BUS Participant
The Vitotrol 300A remote control regulates the required
set room temperature for one heating circuit in standard
and reduced mode, the heating program and the switching
times for central heating, DHW heating and the DHW
recirculation pump.
Displaying:
- Room temperature
- Outside temperature
- Heating program
- Operating condition
- Solar yield as graphic display
Settings:
- Set room temperatures for standard mode
(day temperature) and reduced mode (night temperature)
via the standard display
- Heating program, switching times for heating circuits,
DHW heating and DHW recirculation pump plus further
settings via plain text menu on the display
- Party and economy mode can be enabled via the menu
- Only for heating circuit with mixer:
Fitted room temperature sensor for room temperature
hook-up
Note: For room temperature hook-up, the Vitotrol 300A
must be installed in the main living room (lead room).
Accessories
RS function:
Installation in the main living room on an internal wall
opposite radiators. Never install inside shelving units,
in recesses, or immediately by a door or heat source
(e.g. direct sunlight, fireplace, TV set, etc.). The fitted
room temperature sensor captures the actual room
temperature and effects any necessary correction of
the flow temperature.
WS function:
Installation anywhere in the building.
Connection:
- 2-core lead 18 AWG, length max. 164 ft. (50 m)
(even if connecting several remote control units)
- Never route this lead immediately next to 120/208/460V
cables
- LV plug as standard delivery must be installed in the main
living room (lead room).
Specification:
Power supply via KM BUS
Power consumption: 0.2 W
Max. ambient temp.
- at operation: 32 to 104ºF (0 to 40ºC)
- when storingor transporting: -4 to+149ºF (-20 to+65ºC)
Set room temp. range 37 to 99ºF (3 to 37ºC)
The set room temperature for reduced mode is adjusted
at the control unit.
5673 647 - 03
15
Page 16
Accessories
Accessories for Vitocrossal 300 CU3A
Vitocrossal 300 CU3A 26 to 57 Technical Data
Fuel Conversion Label Kit (NG>LPG)
(included in boiler technical literature set)
The Vitocrossal 300 CU3A boiler comes factory set for
operation with natural gas. All Vitocrossal 300 CU3A
models can be field converted to operate with liquid
propane gas (as well as back to natural gas as required).
The kit includes instructions and labels for field conversion.
Low-Loss Header
When used in conjunction with the Vitocrossal 300
CU3A boiler, the low-loss header acts as hydraulic break,
decoupling boiler and system circuits from each other.
Viessmann recommends the use of a low-loss header
in cases where the system head and flow rates are
unknown.
The temperature sensor connection [TS] typically located
at the top of the low-loss header ensures low return
temperatures to the Vitocrossal 300 CU3A boiler at all
times, increasing operational efficiency.
IMPORTANT
Use only a Viessmann temperature sensor (accessory).
Do not use any other manufacturer’s temperature sensor.
Low-loss header design (Typical)
Legend
AB Air Bleed
BR Boiler Return
BS Boiler Supply
BY Bypass (with laminar flow)
D Debris and/or air
DV Drain Valve
SC Sensor Cable
SR System Return
SS System Supply
TS Viessmann Temperature Sensor
SW Sensor Well
In addition, the low-loss header helps eliminate air and
debris [D] from the heating system.
See illustrations for design and principle of operation.
16
5673 647 - 03
Page 17
Vitocrossal 300 CU3A 26 to 57 Technical Data
Accessories for Vitocrossal 300 CU3A
Low-Loss Header (continued)
Principle of Operation
Accessories
IMPORTANT
When installing a low-loss header, the system mixed
supply temperature (T3) must be calculated as follows:
T1 Boiler supply temperature
T2 Boiler return temperature
T3 System supply temperature
T4 System return temperature
Vprimary Boiler circuit flow rate
Vsecondary Heating circuit flow rate
Vbypass Bypass flow rate
Qprimary Heat supplied by boiler
Qsecondary Heat consumed by system
*1 Floor-mounted version (typically used for
multiple-boiler installations).
5673 647 - 03
17
Page 18
Standard Equipment/Management System
Standard Equipment
Combustion Management System
Vitocrossal 300 CU3A 26 to 57 Technical Data
The Vitocrossal 300 CU3A gas-fired condensing combiboiler with Inox-Crossal heat exchanger, modulating
MatriX burner for liquid propane gas and natural gas
(available on all models), comes standard with:
■ boiler control unit with outdoor
temperature sensor, power/pump module:
- installation fittings with 30 psig pressure relief valve
- Temperature and pressure gauge field installation
on supply pipe.
- The boiler comes prewired and fully piped
internally for field connections.
- Side wall vent installations must include
Viessmann protective screen!
- Enclosure finish: black steel, powder-coated
Viessmann silver
- The Vitocrossal 300 CU3A comes ready for use
with natural gas and can be fuel converted to liquid
propane gas in the field.
The combustion management system utilizes the physical
correlation between the level of the ionization current
and the air factor λ. For all gas qualities, the maximum
ionization current results with air factor λ.
The ionization signal is evaluated by the combustion
management system, and the air factor is adjusted to
between λ=1.24 and 1.44. This range provides for an
optimum combustion quality. Thereafter, the electronic
To achieve an optimum combustion control, the system
regularly performs an automatic self-calibration; also after
a power failure (shutdown). For this, the combustion is
briefly regulated to max. ionization current (equals air factor
λ=1). The automatic calibration is performed shortly after
the burner starts and lasts approximately 5 seconds. During
the calibration, higher than normal CO2 emissions may
occur briefly.
gas valve regulates the required gas volume based on the
prevailing gas quality.
To check the combustion quality, the CO2 content or the
O2 content of the flue gas is measured. The actual values
enable the prevailing air factor to be determined. The
relationship between the CO2 or O2 content and air factor
λ is illustrated in the table below.
Air factor λ - CO
Air factor λ
/O2 content
2
O
2 content (%)CO
content (%) for natural gasCO2 content (%) for liquid propane gas
2
1.203.89.611.3
1.244.49.210.9
1.274.99.010.6
1.305.38.710.3
1.345.78.510.0
1.376.18.39.8
1.406.58.19.6
1.446.97.89.3
1.487.37.69.0
The Vitocrossal 300 CU3A boilers come equipped with Lambda Pro, the industry’s first intelligent combustion
management system. The boiler adjusts automatically to any gas type and quality without the need for a fuel
conversion kit.
18
5673 647 - 03
Page 19
Vitocrossal 300 CU3A 26 to 57 Technical Data
Hydraulic Connection
Installation
System design
Viessmann condensing boilers can generally be installed
in any pumped hot water heating system (closed system).
Minimum system pressure 14 psi.
The boiler water temperature is limited to 194ºF (90ºC).
To minimize distribution losses and for increased
efficiency we recommend that you size the heat
distribution system to a max. supply temperature of
158ºF (70ºC). This can be achieved through the use of
a low temperature heating system (such as a radiant
floor).
2
For apartments with less than 860 ft
space or for low energy houses with low heat demand
we recommend, due to the immediate capturing of the
room-influencing factors, the utilization of the Vitocrossal
300 CU3A in conjunction with the Vitotrol 200A / 300A
and room dependant control.
The use of a low loss header is not necessarily required
for single boiler CU3A installations. Use of a low loss
header when used with the CU3A offers additional
benefits as they can be an effective method of air
separation, debris removal, temperature sensing and in
installations where the flow rates are unknown.
(80 m2) living
Installation Examples
Please note that in the following piping layout examples
all pumps external to the boiler are field supplied.
IMPORTANT
The examples on the following pages depict possible
piping layouts of the Vitocrossal 300 CU3A boiler
equipped with Viessmann System Technology.
Please note that the following examples are simplified
conceptual drawings only!
Piping and necessary componentry must be field verified.
A low water cut-off (LWCO) must be installed where
required by local codes.
Proper installation and functionality in the field is the
responsibility of the heating contractor.
5673 647 - 03
19
Page 20
Installation Examples
System Layout 1
Vitocrossal 300 CU3A with a direct-connected heating circuit
Vitocrossal 300 CU3A 26 to 57 Technical Data
Legend
A Vitocrossal 300 CU3A boiler with Vitotronic 200, KW6B outdoor reset control
B Outdoor temperature sensor !
C Vitotrol remote (optional)
D Heating circuit
E Heating circuit pump
F DHW pump sA
G DHW storage tank
H DHW tank temperature sensor %
I Expansion tank
J DHW recirculation pump
K Temperature and pressure relief valve
L Pressure relief valve
* Function based on coding of address 33
20
28/20 *
Installation of ...
■ radiator heating circuit (high-temp. circuit)
■ DHW production
20
5673 647 - 03
Page 21
Vitocrossal 300 CU3A 26 to 57 Technical Data
System Layout 2
Vitocrossal 300 CU3A with...
- DHW storage tank
- one heating circuit with mixing valve and system separation
Installation Examples
Legend
A Vitocrossal 300 CU3A boiler with Vitotronic 200, KW6B outdoor reset
control
B Outdoor temperature !
C Vitotrol remote (optional)
D Underfloor heating circuit
E Mixing valve temperature sensor ?
F Pressure relief valve
G Plate heat exchanger for system
separation
H Accessory kit for heating circuit with
mixing valve
I DHW circulating pump sA
J DHW storage tank
K DHW tank temperature sensor %
L Expansion tank
M DHW recirculation pump 28/20 *
N Temperature and pressure relief valve
O Heating circuit pump 20
P Heating circuit pump
* Function based on coding of address 33
Installation of ...
■underfloor heating circuit with 3-way mixing valve
and system separation (low-temp. circuit)
■ DHW production
IMPORTANT
System separation is required of underfloor heating
systems employing non-oxygen diffusion barrier tubing.
All components on the secondary side of the heat
exchanger must be made of corrosion-resistant materials.
IMPORTANT
Sizing of field-supplied pump P is critical for proper boiler
operation in this system layout. See page 8 for the supply
head pressure drop of the boiler. An undersized pump
may cause short-cycling and/or improper operation of the
boiler.
5673 647 - 03
21
Page 22
Installation Examples
System Layout 3
Vitocrossal 300 CU3A with...
- DHW storage tank
- one direct-connected heating circuit
- two heating circuit with a mixing valve
Vitocrossal 300 CU3A 26 to 57 Technical Data
Legend
A Vitocrossal 300 CU3A boiler with Vitotronic 200, KW6B outdoor reset
control
B Outdoor temperature sensor !
C Vitotrol remote (optional)
D Under floor heating circuit
E Radiator heating circuit
F Heating circuit pump
G Mixing valve temperature sensor ?
H Accessory kit for heating circuit with mixing valve
I Domestic hot water storage tank
J DHW tank temperature sensor %
K Expansion tank
L Temperature and pressure relief valve
M Pressure relief valve
N DHW recirculation pump
O Boiler pump 20
P DHW circulating pump sA
* Function based on coding of address 33
22
28/20 *
Installation of different heating circuits...
■ radiator heating circuit (high-temp. circuit)
■ under floor heating circuit with 3-way mixing valve
(low-temp. circuit)
■ DHW production
The 3-way mixing valve, built-in to achieve the low-
temperature level of the under floor heating circuit, is
controlled by an accessory kit for a heating circuit with
mixing valve.
IMPORTANT
System separation is required of underfloor heating
systems employing non-oxygen diffusion barrier tubing.
All components on the secondary side of the heat
exchanger must be made of corrosion-resistant materials.
IMPORTANT
Sizing of field-supplied pump P is critical for proper boiler
operation in this system layout. See page 8 for the supply
head pressure drop of the boiler. An undersized pump
may cause short-cycling and/or improper operation of the
boiler.
5673 647 - 03
Page 23
Vitocrossal 300 CU3A 26 to 57 Technical Data
System Layout 4
Vitocrossal 300 CU3A with...
- direct-connected heating circuit
- one heating circuit with system separation
Installation Examples
Legend
A Vitocrossal 300 CU3A boiler with Vitotronic 200,
KW6B outdoor reset control
B Outdoor temperature sensor !
C Vitotrol remote (optional)
D Under floor heating circuit
E Radiator heating circuit
F Plate heat exchanger for system separation
G Heating circuit pump
H Mixing valve temperature sensor ?
I Accessory kit for heating circuit with mixing valve
J DHW storage tank
K DHW tank temperature sensor %
L Expansion tanks
M Temperature and pressure relief valve
N Pressure relief valve
O DHW recirculation pump 28/20*
P Boiler pump 20
Q DHW circulating pump sA
* Function based on coding of address 33
Installation of different heating circuits...
■ radiator heating circuit (high-temp. circuit)
■ under floor heating circuit with 3-way mixing valve
(low-temp. circuit)
■ DHW production
The 3-way mixing valve, built-in to achieve the low-
temperature level of the under floor heating circuit, is
controlled by an accessory kit for a heating circuit with
mixing valve I. The boiler pump
radiator heating circuit and the plate heat exchanger
for system separation.
20 supplies the
IMPORTANT
The pressure drop (secondary circuit) of the plate heat
exchanger F must be less/equal to the pressure drop of
the 3-way mixing valve. This must be taken into account
when sizing the plate heat exchanger.
5673 647 - 03
23
Page 24
Installation Examples
System Layout 5
Vitocrossal 300 CU3A with...
- DHW storage tank
- low-loss header
- multiple heating circuits with mixing valves
- one heating circuit without mixing valve
Vitocrossal 300 CU3A 26 to 57 Technical Data
When designing a system as illustrated above, please contact your local Viessmann Sales Representative for assistance.
Legend
A Vitocrossal 300 CU3A boiler with Vitotronic
200, KW6B outdoor reset control
B Outdoor temperature !
C Boiler pump 20
D Vitotronic 200-H, HK1B *1
E Mixing valve temperature sensor ?
F Heating circuit pumps
G Accessory kit for heating circuit with mixing valve
H Heating circuits with mixing valves
I Viessmann temperature sensor for low-loss header ?
J Low-loss header (if required)
K DHW circulating pump sA
L DHW tank temperature sensor %
M DHW storage tank
N Expansion tank
O DHW recirculation pump sK
P Heating circuit pump 28/20*
Q Vitotrol remote (optional)
R Radiator heating circuit
S Temperature and pressure relief valve
T Pressure relief valve
* Function based on coding of address 33
*1 Contact your local Sales Representative for details.
Vitotronic 200-H, HK1B mixing valve control with
LON communication module can be used instead
of the accessory kit and Vitocontrol.
IMPORTANT
Please note location of expansion tank N.
IMPORTANT
System separation is required of underfloor heating
systems employing non-oxygen diffusion barrier tubing.
All components on the secondary side of the heat
exchanger must be made of corrosion-resistant materials.
24
5673 647 - 03
Page 25
Vitocrossal 300 CU3A 26 to 57 Technical Data
System Layout 6
Multiple (up to eight) Vitocrossal 300 CU3A with...
- multiple heating circuits with mixing valves
- low-loss header
Installation Examples
Legend
A Vitocrossal 300 CU3A boiler
B Vitotronic 300K, MW2C
C Low-loss header/common supply temperature sensor
D Low-loss header
E DHW storage tank
F High temperature heating circuit
G Low temperature heating circuit
When designing a multiple Vitocrossal 300 CU3A system
as shown above, please reference applicable multiple
Vitocrossal 300 CU3A technical documentation, and
contact your local Viessmann Sales Representative for
further assistance.
This installation example depicts a possible piping layout
for multiple Vitocrossal 300 CU3A boilers equipped with
Viessmann System Technology. Please note that this
example is based on a simplified conceptual drawing only!
Piping and necessary componentry must be field verified.
A low water cut-off (LWCO) must be installed where
required by local codes.
Proper installation and functionality in the field is the
responsibility of the heating contractor.
WARNING
If a DHW storage tank other than a Viessmann
Vitocell 100 or 300 tank is used, the installer must
verify proper operation of the Viessmann DHW tank
temperature sensor with the original manufacturer
of the tank. Viessmann strongly recommends the
installation of a temperature tempering valve in the
DHW supply line.
5673 647 - 03
25
Page 26
Installation Examples
Electrical Connections
Vitocrossal 300 CU3A 26 to 57 Technical Data
26
WARNING
DISCONNECT POWER BEFORE
SERVICING BOILER.
If any of the original wires as
supplied with the appliance must
be replaced, it must be replaced
with the exact equivalent.
CAUTION
Label all wires prior to disconnection
when servicing controls. Wiring errors
can cause improper and dangerous
operation. Verify proper operation
after servicing.
* Only one function/connection may
be assigned to each connection.
5673 647 - 03
Page 27
Vitocrossal 300 CU3A 26 to 57 Technical Data
Electrical Connections (continued)
Legend
1 Outdoor Temperature Sensor
2 Supply Temperature Sensor/Low Loss Header
3/1 Boiler Temperature Sensor #1
3/2 Boiler Temperature Sensor #2
5 DHW Temperature Sensor
11 Ionization Electrode
15 Flue Gas temperature Sensor
20 Boiler Pump
21 DHW Pump
28/20 Programmable Pump Output*
35 Gas Valve
40 Power Supply
40A Accessory Power Output
54 Ignition Transformer
96 Powered Accessory Connection
100 Fan Motor
100A Fan Motor Control
111 Not Used
145 KM BUS
147 Pump Modulation Output 0-10VDC
Multi Powered Accessory Connection
156A Switched Output F2
156B Switched Output F1
DE1 Digital Input 1 (Dry Contact)
A Boiler Control
B External Accessory Connection Board
C Power/Pump Connection Interface
D Integrate EA1 Module
E KM-BUS for External Devices
F Electrical Junction Box
G Field Wiring Connections
A1 Main Board
A2 Internal Power Supply Unit
A3 Optolink
A4 Burner Control Unit
A5 Programming Unit
A6 Coding Card
A7 Connection Adaptor
A8 LON Communication Module
S1 ON/OFF Switch
S2 Reset Button
X.. Electrical Interface
5673 647 - 03
27
Page 28
System Design
System Design Considerations
Vitocrossal 300 CU3A 26 to 57 Technical Data
IN THE COMMONWEALTH OF MASSACHUSETTS...
- this product shall be installed by a licensed plumber or
gas fitter.
- the flexible connector (if used) cannot exceed 36”.
- any level type shutoff used must be of tee handle
type.
Boiler location
As a direct vent appliance, the Vitocrossal 300 CU3A can
be installed for room air independent operation (sealed
combustion) regardless of size and ventilation method
of the room in which it is located.
The Vitocrossal 300 CU3A can be installed, for example,
in the main living area of a house, in non-ventilated utility
rooms, cupboards, closets and alcoves with no clearance
required from combustible materials, as well as in attics
with a direct outlet for the flue gas/fresh air system.
Follow all local and national codes.
Flue gas system
Viessmann PP(s) (Polypropylene) concentric flue gas/
fresh air systems for room air independent operation
(sealed combustion) and side wall venting are tested to
ANSI Z21.13 - CSA 4.9 (latest edition) and are certified
together with the Vitocrossal 300 CU3A boiler as a
constructional unit.
The Vitocrossal 300 CU3A boiler may also be vented,
using an AL29-4C® special stainless steel, single-wall, room
air dependent or independent venting system (UL listed for
category IV), polypropolene PP(s) or CPVC single wall room
air dependent or independent venting system (listed
to ULCS636 or UL1738) for CAT IV appliances.
For a more detailed description of the direct vent and
single-wall vent system, please refer to the Vitocrossal 300
CU3A Venting System Installation Instructions.
Flue gas temperature protection
Flue pipes used for the Vitocrossal 300 CU3A are suitable
for max. flue gas temperatures of up to 230°F (110°C).
No flue gas temperature protection is required as the
maximum permissible flue gas temperature is not
exceeded in any operating condition or in the event of
malfunctioning.
Total permissible hardness of the fill and top-up water
Total heating outputSpecific heating volume
MBH<5 USG per 3412 BTU
170
>170 to 682
>682 to 170
>20502 ppm0.11 gpg2 ppm0.11 gpg2 ppm 0.11 gpg
ppm - parts per million
gpg - grains per gallon
300 ppm17.5 gpg200 ppm11.7 gpg2 ppm0.11 gpg
200 ppm11.7 gpg150 ppm8.8 gpg2 ppm0.11 gpg
150 ppm8.8 gpg2 ppm0.11 gpg2 ppm0.11 gpg
Low water cut-off
A low water cut-off may be required by local codes.
If the boiler is installed above the radiation level, a low
water cut-off device of approved type must be installed
in all instances. An approved type low water cut-off
device must be provided by the heating contractor.
Do not install an isolation valve between the boiler and
the low water cut-off.
Water connections
Vitocrossal 300 CU3A boilers can be used in any fully
pumped hot water heating system.
Minimum system pressure is 14 psig.
Chemical corrosion protection products
Corrosion does not typically occur in sealed heating
systems which have been correctly installed and are
correctly operated.
Many manufacturers of plastic pipes recommend the
use of chemical additives. In this case, only those
commercially available corrosion protection products
approved for boilers with domestic hot water heating
via single-wall heat exchangers (instantaneous plate
heat exchangers or DHW tanks) must be used.
Water quality
Treatment for boiler feed water should be considered in
areas of known problems, such as where a high mineral
content and hardness exist. In areas where freezing might
occur, an antifreeze may be added to the system water
to protect the system. Please adhere to the specifications
given by the antifreeze manufacturer. Do not use
automotive silicate based antifreeze.
Please observe that an antifreeze/water mixture may
require a backflow preventer within the automatic water
feed and influence components such as diaphragm
expansion tanks, radiation, etc. Maximum antifreeze
content is 50% for the Vitocrossal 300 CU3A boiler.
Do not use antifreeze other than specifically made for
hot water heating systems. System also may contain
components which might be negatively affected by
antifreeze.
Check total system frequently when filled with antifreeze.
Advise system operator/ultimate owner that system is
filled with a glycol mix. The heating contractor must
provide a MSDS (Material Safety Data Sheet) for the
antifreeze used to the system operator/ultimate owner.
5 USG per 3412 BTU to
<13 USG per 3412 BTU
13 USG per 3412 BTU
28
5673 647 - 03
Page 29
Vitocrossal 300 CU3A 26 to 57 Technical Data
System Design Considerations (continued)
System Design
System layout
■ The max. boiler water temperature for space heating
and DHW production is 194°F (90°C). To minimize
distribution losses, Viessmann recommends that the
heating and domestic hot water systems be based
on a maximum boiler supply temperature of 194°F
(90°C).
■ Due to the low return temperatures required for gas
condensing, no mixing valves should be used in the
heating circuit whenever possible. If mixing valves
are required, e.g. for multi-circuit systems or
underfloor heating systems, only 3-way mixing valves
must be used.
Do not use 4-way mixing valves with condensing
boilers.
Underfloor heating systems
For underfloor heating systems Viessmann recommends
the use of plastic tubing with an oxygen diffusion barrier
in order to prevent the diffusion of oxygen through
tubing. If plastic tubing without an oxygen diffusion
barrier is used in underfloor heating systems, Viessmann
recommends that such systems be separated from the
boiler with a heat exchanger.
Underfloor heating systems and heating circuits
containing a very large volume of water must be
connected to the boiler via a 3-way mixing valve; please
refer to the applicable installation example in this manual.
Oxygen diffusion barrier underfloor tubing
The boiler warranty does not cover leaks resulting from
corrosion caused by the use of underfloor plastic tubing
without an oxygen diffusion barrier. Such systems must
have the non-oxygen diffusion barrier tubing separated
from the boiler with a heat exchanger. Viessmann
recommends the use of underfloor plastic tubing with
an oxygen diffusion barrier.
Warranty
Our warranty does not cover damages resulting from
the following:
- installation or service by unqualified and unlicensed
personnel.
- attempting to perform any repair work on the boiler
other than that mentioned in the boiler literature.
- tampering with or attempting, without Viessmann
permission, to readjust the factory settings of the;
-combination gas valve
-combustion air opening of the burner blower
- leaks resulting from corrosion caused by the use of
underfloor plastic tubing without an oxygen diffusion
barrier. For detailed warranty information, please read
warranty sheet supplied with product.
5673 647 - 03
29
Page 30
Vitocrossal 300 CU3A 26 to 57 Technical Data
30
5673 647 - 03
Page 31
Vitocrossal 300 CU3A 26 to 57 Technical Data
5673 647 - 03
31
Page 32
Vitocrossal 300 CU3A 26 to 57 Technical Data
(recycled and recyclable) paper.
Technical information subject to change without notice.Printed on environmentally friendly
5673 647 - 03