Viessmann Vitocrossal 300, CU3A Technical Manual

Technical Data Manual
Model Nos. and pricing: see Price List
For operation with natural gas and liquid propane gas Floor mounted, gas-fired condensing boiler Heating input 19 to 199 MBH
5.6 to 58 kW
VITOCROSSAL 300
Vitocrossal 300 CU3A Series 26 to 57
Floor mounted, gas-fired condensing boiler with modulating MatriX gas burner. For room air dependent or independent operation.
5673 647 - 03 07/2015
H
Product Information
Benefits
Equipped with the industry’s first intelligent combustion management system and powerful control technology, the new generation Vitocrossal 300 CU3A gas-fired Floor mounted condensing boiler delivers unparalleled performance, reliability and comfort.
The benefits at a glance:
Vitocrossal 300 CU3A 26 to 57 Technical Data
Best value in its class with new industry-leading technology and the most standard features.
Highest Efficiency up to 98% at full modulation and up to 95% A.F.U.E.
Lasting performance with industry-leading Viessmann made SA240 316 Ti stainless steel Inox-Crossal heat exchanger constructed to CSA B51 and ASME Section IV.
Low Emission Combustion with Viessmann made stainless steel MatriX burner. Factory calibrated.
Fast Installation and Reduced Maintenance with Lambda Pro, industry-first intelligent combustion management system: Adjusts automatically to gas type and quality. No fuel conversion kit required.
Powerful and User-friendly Viessmann Vitotronic on-board multi-function outdoor reset boiler and system control for multi-temperature space and DHW heating.
Expanded Application Range with increased capacity up to 199 MBH (58 kW). Multi-boiler installation up to 1592 MBH (464 kW) with up to 8 boilers.
Greater Venting Flexibility with increased vent length [up to 198 ft. (60 m)] and multiple venting options.
- Horizontal or vertical sealed combustion coaxial venting (field supplied).
- Horizontal, vertical or hybrid sealed combustion double-pipe venting (field supplied).
- Horizontal or vertical single-wall venting (field supplied).
Compact, Esthetic Product Design and zero clearance to combustibles.
Extremely Quiet Operation; quieter than most refrigerators.
True High-Altitude Operation up to 10,000 ft. (3,000 m) with simple electronic adjustment.
Efficiency up to 98% through intensive condensation. The flue gas temperature is only approximately 9-27ºF (5-15ºC) above boiler return temperature.
2
2
5673 647 - 03
Vitocrossal 300 CU3A 26 to 57 Technical Data
Cross-Section
Vitocrossal 300 CU3A 26 to 57
Product Information
Vitocrossal 300 CU3A boiler efficiency dependent on system heating water return temperatures and load conditions
Legend
A Digital Vitotronic boiler control unit B Water-cooled stainless steel combustion chamber C Modulating MatriX gas burner – for extremely clean
combustion
D Stainless steel Inox-Crossal heat exchanger E Highly effective thermal insulation F Flue gas collector with condensate drain pipe G Combustion air intake for direct vent (two-pipe)
systems
5673 647 - 03
3
3
Technical Data
Vitocrossal 300 CU3A 26 to 57 Technical Data
Technical Data
Boiler Model No. CU3A 26 35 45 57
Natural Gas / Liquid Propane Gas CSA input
CSA output / DOE heating capacity*1
Net AHRI Rating MBH
Heat exchanger surface area ft.
Min. gas supply pressure
Natural gas Liquid propane gas
Max. gas supply pressure *3
Natural gas Liquid propane gas
A.F.U.E. %95 95 95 95 Weight lbs
Boiler water content USG
Max. operating pressure
at 210ºF (99ºC)
Boiler water temperature
- Adjustable high limit (AHL) range space heating (steady state)
DHW production
- Fixed high limit (FHL)
Boiler connections
Boiler heating supply and return Pressure relief valve Boiler drain
Gas valve connection
MBH (kW) MBH (kW)
(kW)
(m2)
“w.c. “w.c.
“w.c. “w.c.
(kg)
(L)
psig
(bar)
ºF
(ºC)
ºF
(ºC)
ºF
(ºC)
NPTM
NPTF
NPTM
NPTF
2
19-94
(5.6-27.5)
17.7-87
(5.2-25.5)
76
(22)
16.7 (1.5)
4
10
14 14
269
(122)
13.5 (51)
30 (2)
68-194 (20-90)
194 (90) 210 (99)
1a
¾
1
¾
25-125
(7.3-36.6)
23.3-116 (6.8-34)
101 (30)
20.7 (1.9)
4
10
14 14
275
(125)
13.0 (49)
30 (2)
68-194 (20-90)
194 (90) 210 (99)
1a
¾
1
¾
43-160
(12.6-47)
40-149
(11.7-43.7)
129 (38)
34.1 (3.2)
4
10
14 14
352
(160)
18.8 (71)
30 (2)
68-194 (20-90)
194 (90) 210 (99)
1a
¾
1
¾
43-199
(12.6-58)
40-185
(11.7-54.2)
161 (47)
34.1 (3.2)
4
10
14 14
352
(160)
18.8 (71)
30 (2)
68-194 (20-90)
194 (90) 210 (99)
1a
¾
1
¾
*1 Output based on 140ºF (60ºC), 120ºF (49ºC) system supply/return temperature.
*2 Net AHRI rating based on piping and pick-up allowance of 1.15.
*3 If the gas supply pressure exceeds the maximum gas supply pressure value, a separate gas pressure regulator
must be installed upstream of the heating system.
Note: For high altitude installation at 10,000 ft. the input for model Vitocrossal 300 CU3A will have an altitude de-ration of 18%.
4
4
5673 647 - 03
Vitocrossal 300 CU3A 26 to 57 Technical Data
Technical Data
Technical Data
Boiler Model No. CU3A 26 35 45 57
Dimensions
Overall depth
Overall width
Overall height (with control interface open) Overall height
Flue gas *4
Temperature (at boiler return temperature of 86ºF (30ºC)
- at rated full load
- at rated partial load
Temperature (at boiler return temperature of 140ºF (60ºC)
Max. condensate flow rate *5
for NG and LPG T
S/TR =104/86ºF (40/30ºC) USG/h
Condensate connection hose
Boiler flue gas connection *6 Ø
Combustion air supply connection outer
Sound Rating (A scale)
- at maximum input
- at minimum input Standby losses *7 BTU/hr
inches
(mm)
inches
(mm)
inches
(mm)
inches
(mm)
ºF (ºC) ºF (ºC)
ºF (ºC)
(L/h)
nozzle
Ø in.
in. (mm) 3 (80) 3 (80) 4 (110) 4 (110)
Ø in. (mm) 3 (80) 3 (80) 3 (80) 3 (80)
dB dB
W/hr
27
684
26
660
67
1707
61.5
1562
113 (45)
90 (32)
167 (75)
0.9
3.43
27
684
26
660
67
1707
61.5
1562
113 (45)
90 (32)
167 (75)
1.2
4.62
31b
801
26
660
67
1707
61.5
1562
113 (45)
90 (32)
167 (75)
1.6
5.95
31b
1707
61.5
1562
113 (45)
90 (32)
167 (75)
7.92
¾¾ ¾ ¾
48 32
1128
330
55 33
1000
292
53 33
1120
328
801
26
660
67
2.1
58 33
995 291
*4 Measured flue gas temperature with a combustion air temperature of 68°F (20°C).
*5 Based on maximum input rate.
*6 For side wall vent installations (coaxial system):
Do not exceed max. equivalent length specified in the Installation Instructions of the Vitocrossal 300 CU3A Venting System. Do not attempt to common-vent Vitocrossal 300 CU3A with any other appliance. Side wall co-axial vent installation must include Viessmann protective screen! For details refer to the Installation Instructions for the Vitocrossal 300 CU3A Venting System.
*7 Standby losses measured from the boiler temperature sensor well based on a boiler water temperature of 158°F (70°C) and a room temperature of 68°F (20°C).
For information regarding other Viessmann System Technology componentry, please reference documentation of respective product.
5673 647 - 03
5
5
Dimensional Information
Models 300 CU3A 26 to 57
Vitocrossal 300 CU3A 26 to 57 Technical Data
Legend
A Overall boiler height (boiler control open) B Overall boiler height (boiler control closed) C Safety header connection D Boiler supply E Gas connection F Boiler return G Boiler drain H Vent connection I Condensate drain connection J Combustion air connection
Model 26 to 35 Model 45 and 57
a in. (mm)
b in. (mm)
c in. (mm)
d in. (mm)
Note: All height dimensions of the boiler have a tolerance of +.6 in. (+15 mm) due to the factory installed adjustable feet.
27 (684)
17 (430)
23b (595)
4
¾ (120)
a in. (mm)
b in. (mm)
c in. (mm) 28 (712)
d in. (mm)
31b (801)
21b (545)
5b (140)
6
6
5673 647 - 03
Vitocrossal 300 CU3A 26 to 57 Technical Data
Recommended Minimum Service Clearances
Note: The Vitocrossal 300 CU3A series boiler conforms
on the special venting system label.
The back or side clearance shall be increased if
piping installation is required.
Minimum Clearances
to the zero inches vent clearance to combustibles testing requirements dictated by the boiler Harmonized Standard ANSI Z21.13. CSA/4.9 and therefore is listed for zero clearance to combustibles when vented with a single-wall UL/ ULC certified special venting system. The zero inches vent clearance to combustibles for the Vitocrossal 300 CU3A boiler supercedes the clearance to combustibles listing that appears
Clearances
Top Front Rear Left Right Vent pipe
0 0 AL CL 0 0 0 0
AL = Alcove CL = Closet
The Vitocrossal CU3A series boiler is approved for closet and alcove installation with the clearances to combustibles listed above.
Recommended minimum service clearances
For typical Vitocrossal CU3A series boiler installations, Viessmann recommends installing the boiler with the clearances shown in the illustration on the left.
See the Vitocrossal 300 CU3A Venting System Installation Instructions for details.
5673 647 - 03
7
7
Waterside Flow
Pressure Drop (heating water side)
Pressure drop
Vitocrossal 300 CU3A 26 to 57 Technical Data
Flow rate
Legend
A Boiler models CU3A 26 to 35 kW B Boiler models CU3A 45 to 57 kW
The Vitocrossal 300 is only suitable for fully pumped hot water heating systems.
T = 20ºF (10 K) T = 30ºF (15 K) T = 40ºF (20 K)
Boiler models CU3A
26 9.9 (2.2) 6.6 (1.5) 4.9 (1.1)
35 13.3 (3.0) 8.9 (2.0) 6.6 (1.5)
45 17.0 (3.9) 11.4 (2.6) 8.5 (2.0)
57 22.7 (5.2) 15.0 (3.4) 11.4 (2.6)
Note: This boiler does not require a flow switch.
Flow rate
USGPM (m
3
/h)
Flow rate
USGPM (m3/h)
Flow rate
USGPM (m3/h)
8
5673 647 - 03
Vitocrossal 300 CU3A 26 to 57 Technical Data
On-Board Vitotronic 200, HO1B Control
Modular structure
The control unit is integrated into the boiler. The control unit comprises a standard unit, electronics modules and a programming unit.
Standard unit:
ON/OFF switch
Optolink laptop interface
Operating and fault indicators
Reset button
Fuses
Boiler Control
Programming unit:
Easy operation through: – Plain text display with graphic ability – Large font and black & white depiction for good contrast – Context-sensitive help text – Removable programming unit; can be mounted on the wall with separate accessory
With digital time switch
Control keys for:
Navigation – Confirmation – Help and additional information – Menu
Setting the: – Room temperature – Reduced room temperature – DHW temperature – Heating program – Time programs for central heating, DHW heating and DHW recirculation – Economy mode – Party mode – Holiday program – Heating curves – Codes – Actuator tests – Test mode
Displaying the: – Boiler water temperature – DHW temperature – Operating details – Diagnostic details – Fault messages
5673 647 - 03
9
Boiler Control
Design and Function
Vitocrossal 300 CU3A 26 to 57 Technical Data
Functions
Weather-compensated control of the boiler water and/or supply temperature
Control of one heating circuit without mixer and two heating circuits with mixer (with accessory mixing valve extension modules)
Demand-dependent heating circuit pump and burner off control
Adjustment of a variable heating limit
Anti-seizing pump protection
Integral diagnostic system
Maintenance display
DHW temperature control with priority
Auxiliary function for DHW heating (short-term
heating to a higher temperature)
0-10V External signal input
0-10V Pump speed control output signal
Control Characteristics
PI characteristics with modulating output.
Time Switch
Digital time switch.
Individual and 7-day program
Automatic daylight savings time changeover
Automatic function for DHW heating and DHW
recirculation pump
Time, day and standard switching times for space heating, DHW heating and the DHW recirculation pump are factory-set
Switching times are individually programmable, i.e. up to four switching periods per day
Shortest switching interval: 10 minutes
Power backup: 14 days.
Setting the Operating Programs
The heating system frost protection (see frost protection function) applies to all heating programs. You can select the following heating programs with the program keys:
Heating and DHW
DHW only
Standby mode
External heating program changeover.
Frost protection
The frost protection function will be started when the outside temperature drops below approx. 34°F (1°C). With the frost protection function, the heating circuit pump will be switched ON and the boiler water is maintained at a lower temperature of approx. 68°F (20°C). The DHW tank will be heated to approx. 68°F (20°C).
The frost protection function will be stopped when the outside temperature rises above approx. 37°F (3°C) (default settings).
Summer Operation
Heating program “w” The burner is only activated upon a call for domestic hot
water from the DHW storage tank (controlled by DHW tank temperature sensor).
10
5673 647 - 03