Viessmann Vitocrossal 200 CM2 Series, Vitodens 050-T, Vitocrossal 300 CT3B, CT3U Series, Vitodens 050-W Installation Instructions Manual

...
Installation instructions
for contractors
VIESMANN
Flue system
for condensing boilers
Flue system
5780 223 GB 5/2016
2
Please follow these safety instructions closely to prevent accidents and material losses.
Safety instructions explained
Danger
This symbol warns against the risk of injury.
!
Please note
This symbol warns against the risk of material losses and envi­ronmental pollution.
Note
Details identified by the word "Note" contain additional information.
Target group
These instructions are exclusively intended for authorised contractors.
■ Work on gas installations must only be carried out by a registered gas fit­ter.
■ Work on electrical equipment must only be carried out by a qualified electrician.
Regulations to be observed
■ National installation regulations
■ Statutory regulations for the preven­tion of accidents
■ Statutory regulations for environmen­tal protection
■ Codes of practice of the relevant trade associations
■ All current safety regulations as defined by DIN, EN, DVGW, TRGI, TRF, VDE and all locally applicable standards
a
ÖNORM, EN, ÖVGW-TR Gas, ÖVGW-TRF and ÖVE
c
SEV, SUVA, SVGW, SVTI, SWKI, VKF and EKAS guideline 1942: LPG, part 2
Working on the system
■ Isolate the system from the power supply (e.g. by removing the sepa­rate fuse or by means of a mains iso­lator) and check that it is no longer 'live'.
■ Safeguard the system against recon­nection.
■ Where gas is used as the fuel, close the main gas shut-off valve and safe­guard it against unintentional reopen­ing.
Safety instructions
5780 223 GB
3
Installation sequence
General installation information............................................................................ 4
■ Design............................................................................................................... 4
■ Flue gas temperature protection....................................................................... 4
■ Installation information...................................................................................... 4
■ Required tools/equipment................................................................................. 5
■ Fitting the balanced flue slide coupling............................................................. 6
■ Tightness test.................................................................................................... 7
■ Certification of the balanced flue system.......................................................... 7
■ System certification........................................................................................... 8
Installations requirements.................................................................................... 9
■ Statutory requirements...................................................................................... 9
■ Gas safety (installation and use) regulations (current issue)............................ 9
■ Boiler position................................................................................................... 10
Routing through a shaft........................................................................................ 15
■ Installation information...................................................................................... 15
■ Rigid flue........................................................................................................... 16
■ Flexible flue....................................................................................................... 26
Installation in a disused chimney.......................................................................... 36
■ Installation requirements................................................................................... 36
■ Installation......................................................................................................... 38
Vertical outlet for pitched or flat roofs................................................................... 41
■ Maximum flue length......................................................................................... 42
■ Installation......................................................................................................... 44
External wall connection....................................................................................... 47
■ Installation......................................................................................................... 49
Routing over an external wall............................................................................... 51
■ Maximum flue length......................................................................................... 52
■ Installation......................................................................................................... 52
Plume kit............................................................................................................... 54
■ Routing options................................................................................................. 54
Index
5780 223 GB
4
Design
Prior to installation, check that the max­imum possible pipe length will not be exceeded. Max. possible pipe lengths in relation to the boiler used:
Flue systems technical guide
Flue gas temperature protection
The flue pipes are approved for flue gas temperatures up to 120 °C.
With Viessmann condensing boilers, internal safeguards ensure that the maximum permissible flue gas temper­ature is not exceeded.
Installation information
■ The component overviews for the dif­ferent types of routing also apply to floorstanding condensing boilers.
■ Keep flue gas routes short and with the fewest number of bends possible.
■ Route horizontal connection pipes with a fall of ≥ 3° (approx. 50 mm/m) towards the boiler.
■ Support horizontal connection pipes at intervals of approx. 1 m.
■ To avoid damage and leaks, isolate the flue system from sources of vibra­tion (e.g. ventilation systems).
■ Check the gaskets in all female con­nections are correctly seated.
■ Prior to installation, lubricate all gas­kets with the lubricating paste provi­ded.
■ Only use the special gaskets sup­plied with the boiler.
■ Female plug-in connections in the flue gas path must always point in the direction of flow.
■ Only use the components supplied with the Viessmann flue system.
■ Push the pipes into each other with a slight twist.
■ Balanced flue pipes can be trimmed in their assembled state.
Do not carry out commissioning until the following conditions are met:
■ Free passage through the flue gas pipes.
■ Flue system with positive pressure is gas-tight.
■ Apertures for ensuring sufficient com­bustion air supply are open and can­not be closed off.
■ Applicable regulations on installing and commissioning flue systems have been followed.
General installation information
5780 223 GB
5
Danger
Leaking or blocked flue systems or an insufficient supply of com­bustion air cause life threatening poisoning due to carbon monox­ide in the flue gas.
Ensure the flue system functions correctly. Apertures for combus­tion air supply must not be able to be closed off.
Required tools/equipment
■ Rope for lowering the flue system into a shaft (length: chimney height plus 3 m)
■ Saw and file for trimming and cham­fering the pipe sections
■ Power drill for securing the shaft cover and the support rail
General installation information
(cont.)
5780 223 GB
6
Fitting the balanced flue slide coupling
Note
The slide coupling enables a gap of approx. 45 mm to be covered. Prior to installation, compensate for surplus or insufficient length on the incoming pipe.
1.
120
4.
3.
5.
6.
2.
1. Push the pipe section into the female connection of the incoming balanced flue component.
2. Shorten the ongoing balanced flue pipe to create a gap of 120 mm between the pipe section and the balanced flue pipe.
3. Push the slide coupling onto the ongoing flue pipe.
4. Open the collar and push it over the ongoing balanced flue pipe.
5. Pull the slide coupling out and push it onto the incoming flue pipe.
6. Align the collar and close the toggle fasteners.
General installation information
(cont.)
5780 223 GB
7
Tightness test
After installation, flue systems routed through a shaft must be tested for tight­ness by the flue gas inspector [check local regulations].
■ Pressurised flues which are routed inside buildings and which are not surrounded by combustion air (open flue) must be pressure-tested. For the pressure test, a leak detector is used to pump air into the flue, which has been sealed at the top and bottom, until a pressure of 200 Pa has built. This pressure is maintained while the volume of air leaking out is established. A leakage rate of up to
0.006 l/(s x m2), relative to the inter­nal surface area, is permitted for classifying a flue as sufficiently gas­tight.
■ In pressurised flues that are surroun­ded by combustion air (room sealed), the tightness can be checked by test­ing the O2 content in the combustion
air (annular gap test). The flue is considered sufficiently gas-tight if the O2 content in the com-
bustion air does not deviate from the reference value by more than the fol­lowing values. The reference value is established following the self-adjust­ment of the test meter: – For flues with general Building
Regulations approval 0.4 % by vol.
– For other flues 0.2 % by vol.
Note
Observe country-specific regulations.
Certification of the balanced flue system
The balanced flue system is CE desig­nated and approved in accordance with EN 14471 (see flue systems technical guide).
General installation information
(cont.)
5780 223 GB
8
System certification
System certification to EC Gas Applian­ces Directive EU/2009/142/EC in con­junction with PPs flues offered by Skoberne.
Vitocaldens 222-F CE-0085CO0306 Vitocrossal 200, type CM2 CE-0085BQ0021 Vitocrossal 300, type CU3 CE-0085BN0570 Vitocrossal 300, type CM3 CE-0085BN0569 Vitocrossal 300, type CT3B, CT3U CE-0085AQ0257 Vitodens 050-T CE-0085CQ0290 Vitodens 050-W CE-0085CP0029 Vitodens 100-E CE-0085BT0029 Vitodens 100-W, 111-W CE-0085BT0029, CE-0063CQ3356 Vitodens 111-F CE-0085CN0050 Vitodens 200-W CE-0085BR0432, CE-0085CN0050 Vitodens 222-F CE-0085BU0051, CE-0085CN0050 Vitodens 222-W CE-0085BR0432, CE-0085CN0050 Vitodens 242-F CE-0085BU0051, CE-0085CN0050 Vitodens 300-W CE-0085BR0433, CE-0085CM0463 Vitodens 333-F CE-0085BU0052, CE-0085CM0463 Vitodens 343-F CE-0085BU0052, CE-0085CM0463 Vitoladens 300-C CE-0035BS104, CE-0035CO106 Vitoladens 300-T CE-0035BO107 Vitoladens 300-W CE-0035BM112, CE-0035CO107 Vitoladens 333-F CE-0035BM112, CE-0035CO107 Vitorondens 200-T CE-0035CL102 Vitorondens 222-F CE-0035CL102 Vitosolar 200-F CE-0085CM0184 Vitosolar 300-F CE-0035CO107 Vitosorp 200-F CE-0085CO0146 Vitotwin 300-W CE-0085CM0150 Vitovalor 300-P CE-0085CP0028
Note
Affix the "System certification" and "Flue system ..." labels clearly visible near the flue system or on the boiler.
The labels are supplied with the techni­cal documentation.
General installation information
(cont.)
5780 223 GB
9
Statutory requirements
The appliance is suitable only for instal­lation in GB and IE and should be installed in accordance with the rules in force. In GB a Gas Safe Registered Installer must carry out the installation. It must be carried out in accordance with the relevant requirements of the:
Gas safety (installation and use) regulations (current issue)
It is in your own interest and safety to ensure that the law is complied with. In addition to the above regulations, this appliance must be installed in accordance with the current IEE Wiring Regulations for electrical installation (BS 7671), local Building Regulations, the Building Standards (Scotland) (Consolidation) Regulations, bye laws of the local water undertaking and Health and Safety Document NO. 635, The Electricity at Work regulations 1989, In Ireland (IE), the installation must be carried out by a Competent Person and installed in accordance with the current edition if I.S.813 "Domestic Gas Installations", The current Building Regulations and references should be made to the current ETCI rules for elec­trical installation. It should also be in accordance with the relevant recommendations in the cur­rent editions of the following British Standards and Codes of Practice: BS 5449, BS 5546, BS 5440:1, BS 5440:2, BS 6798, BS 7593, BS 6891, IGE/UP/7 and IS 813 for IE.
All Registered installers are required to notify building control when they have installed or exchanged a gas appliance in a residential dwelling, this can be done via Gas Safe. Gas Safe will then issue either a Build­ing Compliance Certificate (for England and Wales) or a Declaration of Safety (Scotland, Northern Island, Isle of Man or appliances out of the scope of Build­ing Regulations) to the homeowner, which will confirm that the work has been carried out by a competent Gas Safe Registered Installer. This docu­ment will be used to form part of the Home Information Pack (HIP).
!
Please note
Manufacturers instructions must not be taken in any way as overriding statu­tory obligations.
Installations requirements
5780 223 GB
10
Boiler position
The following limitations must be observed when siting the boiler:
■ The boiler is not suitable for external installation. The position selected for the installation should be within the building, unless otherwise protected by a suitable enclosure and must allow adequate space for installation, servicing and operation of the appli­ance and for air circulation around it.
■ The position must allow for a suitable flue system and terminal position. The boiler must be installed on a flat vertical wall capable of supporting the weight of the appliance and any ancillary equipment when full.
■ Due consideration should be given to the routing of the condensate drain from the chosen position.
■ If the boiler is to be fitted in a timber framed building it should be fitted in accordance with ige/up/7. If in doubt advice must be sought from the Insti­tute of Gas Engineers.
■ If the appliance is to be installed in a room containing a bath or shower, any electrical switch or control utilis­ing mains electricity must be so situ­ated that it cannot be touched by a person using the bath or shower. Attention is drawn to the require­ments of BS 7671 (the current I.E.E Wiring Regulations) and in Scotland the electrical provisions of the Build­ing Regulations applicable in Scot­land.
■ A compartment used to enclose the appliance must be designed and con­structed specifically for this purpose. An existing cupboard or compartment may be used provided it is modified accordingly. BS 7698:2000 gives details of the essential features of cupboard / compartment design, including airing cupboards. The Vitodens range does not require compartment ventilation.
■ Where installation will be in an unusual location, special procedures may be necessary. BS 6798 gives detailed guidance on this aspect.
Installations requirements
(cont.)
5780 223 GB
11
Flue terminal position
Horizontal flue system
a
g
f
h,i
d,n
j
b,c
k
m
e
g
a
f
f
k
b,c
k
l
l
g
c
k
Position Minimum spacing
mm
a Directly below an opening window, air vent or
any other ventilation opening
300
b Below a gutter drain or soil pipe 75 c Below eaves 200 d Below a balcony 200 e From vertical drain or soil pipes 150 f From internal and external corners 300 g Above adjacent ground or balcony level/roof 300 h From a surface facing the terminal 600 i Facing terminals 1200 j From opening door/window 1200 k Vertically from a terminal on same wall 1500 l Horizontally from a terminal on same wall 300 m Adjacent to opening 300 n Below carport/roof not recommended
Installations requirements
(cont.)
5780 223 GB
12
Vertical flue systems
q
o
o
r
p
s
t
u
t
Position Minimum spacing
mm
o From adjacent wall 300 p From adjacent opening window 1000 q From another terminal 600 r Minimum height 300 s Minimum distance measured perpendicular to
roof covering
400
t Beside or above an opening rooflight 600 u Below an opening rooflight 2000
Installations requirements
(cont.)
5780 223 GB
13
Minimum distance from terminal
2.5 m
A
A
Boundary
Not under a car port
Installations requirements
(cont.)
5780 223 GB
14
2.1 m
B
Avoid access routes and patios
B
Walkway or patio
2.5 m
C
Minimum distance to car parking space
C
Car space
Installations requirements
(cont.)
5780 223 GB
15
Installation information
Prior to installation, the local flue gas inspector should check that the shaft to be used is suitable and permissible [where applicable]. Shafts that were previously connected to oil or solid fuel boilers must be thor­oughly cleaned by a chimney sweep. Loose deposits comprising sulphur and soot must not remain on the inside of the chimney. Running a balanced flue pipe through the shaft is then not required. If thorough cleaning is impos­sible, if chloride deposits are present or if the shaft is silted up, a separate bal­anced flue pipe must be used inside the shaft. Alternatively, separate (on site) routing for the ventilation air and the flue gas may be used.
In the installation room, at least one inspection port must be provided in the flue system for inspection, cleaning and for testing the pressure (if required). If the flue is not accessible from the roof, a second inspection port must be provi­ded behind the chimney cleaning hatch in the attic. Provide an inspection port at the base of the shaft for inspecting the secon­dary ventilation. Safeguard condensate drainage from the flue to the boiler with a fall of at least 3° (approx. 50 mm/m). The flue system must protrude above the roof line. Observe 400 mm protru­sion from the roof parallel to the roof slope according to FeuVo [or local reg­ulations].
Routing through a shaft
5780 223 GB
16
Rigid flue
Room sealed operation
B5
2
A
3
2
3
2
4
3
2
2
6798 71
A
C
B
C
A
Supply air
B
Flue gas
C
Inspection port
1
Boiler flue connection
2
Standard shaft pack
Comprising:
■ Support bend
■ Support rail
■ Shaft cover
■ Spacers (5 pce)
3
Flue pipe
2 m long 1 m long
0.5 m long
Flue bend (for use in corbelled
chimneys)
30° or 15°
4
Inspection piece, straight
5
Balanced flue inspection piece,
straight
6
Balanced flue wall bezel
7
Balanced flue pipe
1 m long
0.5 m long
8
Balanced flue bend
87° or 2 x 45° or Balanced flue inspection tee or Balanced flue inspection bend
9
Balanced flue slide coupling
Fixing clamp Balanced flue adaptor
7
60/100 mm to 7 80/125 mm
Maximum flue length
Vitodens 100-W, type WB1B: 10 m
Routing through a shaft
(cont.)
5780 223 GB
17
Vitodens 100-W, type B1HA and B1KA, Vitodens 111-W Rated heating output kW 26.0 26.0 30.0 35.0
System size 60/100 m 15 15 15 15 System size 80/125 m 25 20 20 20
Vitodens 200-W, 222-F and 242-F Rated heating output
kW 13 19 26 35 45 60 80 100
System size 60/100
m 20 20 20 15
System size 80/125
m 25 25 25 25 20 15
System size 100/150
m 25 20 20 20
Note
For alternative system sizes, a bal­anced flue adaptor is required.
The following components are taken into consideration for the maximum flue lengths:
■ Balanced flue connection pipe 0.5 m long
■ 1 balanced flue bend 87° and 1 sup­port bend 87° or
■ 2 balanced flue bends 45° and 1 sup­port bend 87°
Subtract other bends, tees and straight lengths from the maximum length using the following values:
■ Balanced flue connection pipe 0.5 m long: 1 m
■ Balanced flue connection pipe 1 m long: 2 m
■ Balanced flue bends 45°: 0.5 m
■ Balanced flue bends 87°: 1 m
■ Balanced flue inspection tee: 1.5 m
Routing through a shaft
(cont.)
5780 223 GB
18
Open flue operation
3
2
3
4
3
2
2
2
2
1 65 4
A
B
A
D
E
C
3
A
Secondary ventilation
B
Flue gas
C
Inspection port
D
Supply air vent
E
Supply air
1
Boiler flue connection
2
Standard shaft pack
Comprising:
■ Support bend
■ Support rail
■ Shaft cover
■ Spacers (5 pce)
3
Flue pipe
2 m long 1 m long
0.5 m long Flue bend (for use in corbelled
chimneys)
30° or 15°
4
Inspection piece, straight
5
Flue bend
87° or 2 x 45° or Inspection tee 87°
6
Ventilation bezel Adaptor 7 60 mm to 7 80 mm
Routing through a shaft
(cont.)
5780 223 GB
Loading...
+ 42 hidden pages