Technical Data Manual
Model Nos. and pricing : See Price List
VITOCROSSAL 200
Gas-fired Condensing Boiler
663 to 1112 MBH (194 to 326 kW)
Product may not be exactly as illustrated.
Vitocrossal 200
CM2 Series
High efficiency, gas-fired condensing boiler
with pre-mix modulating cylinder burner
for natural gas or liquid propane gas with Inox-Crossal heat
exchanger made of high-grade SA 240-316 Ti stainless steel.
For operation without low limit on boiler return water
temperature.
For closed loop hot water heating systems with maximum
supply water temperatures of 210° F (99° C) for a
maximum operating pressure of 75 psig.
Heating input: 663 to 1112 MBH
(194 to 326 kW)
5608 012 v1.1 08/2012
Please file in Service Binder

Product Information
Vitocrossal 200
Benefits at a glance:
Inox-Crossal heat exchanger surface made of high grade SA 240-316 Ti stainless steel for high
operational reliability and long service life.
- Easy dispersal of condensate through vertical gas
flues; therefore no concentration of condensate.
- Increased self-cleaning effect through smooth
stainless steel surfaces.
Highly efficient heat transfer and high condensation
rate through
- heat exchanger surfaces which intensely turbulate
the flue gas flow
- boiler water and hot gases flowing in counterflow.
Efficiency up to 98% through intensive condensation.
The flue gas temperature is only approximately 9 - 27° F
(5 - 15° C) above boiler return temperature (see chart
below).
Clean combustion - through perfect match of burner
and boiler, low combustion chamber loading and
straight-through combustion chamber.
Easy handling in boiler rooms through particularly low
build height and weight.
Vitocrossal 200 CM2 Technical Data
Easy installation and elimination of wiring mistakes
with Viessmann prewired plug-in system.
Heating boiler, heating system control, domestic
hot water storage tank and all other Viessmann
system technology components are coordinated to
one another.
All components are design-matched for quick
installation.
Pre-mix cylinder burner for environmentally-friendly
operation with a modulation range from 20 to 100%.
All hydronic connections can be fitted from above.
Economical and safe heating system operation
through Vitotronic digital control system with
communication capability. Tailored to every need,
covering all known control strategies and
applications.
Standard LON BUS for complete integration into
building management systems.
Particularly quiet operation.
High altitude operation up to 10,000 ft. (3000 m)
with a simple electronic adjustment.
Design
Supply / Return
104° F - 88° F
(40° C - 30° C)
Curve 0.5
Design
Supply / Return
167° F - 140° F
(75° C - 60° C)
Curve 1.4
Boiler Efficiency in %
Design
Supply / Return
194° F / 158° F
(90° C - 70° C)
Curve 1.8
System Partial Load in %
Vitocrossal 200 boiler efficiency dependent on system
heating water return temperatures and load conditions
Boiler Water/ Supply Temperature
Room
Set-Point
Temperature
Outdoor Temperature
2
5608 012 v1.1

Vitocrossal 200 CM2 Technical Data
Cutaway Section
Product Information
Legend
A Inox-Crossal heat exchanger surface made from
high-grade SA 240-316 Ti stainless steel
B Highly effective thermal insulation
C Water cooled stainless steel combustion chamber
D Wide water passageways with low pressure drop -
good natural circulation
E Fully modulating pre-mix cylinder burner
F Vitotronic control unit
5608 012 v1.1
3

Specifications
Vitocrossal 200 CM2 Technical Data
Technical Data
Boiler Model CM2 186 246 311
Input MBH 663 878 1112
(kW) (194) (257) (326)
Minimum Input MBH 133 175 222
(kW) (39) (51) (65)
Output*
1 MBH
(kW)
Net AHRI rating MBH
(kW)
Combustion efficiency*
Thermal efficiency*
1 % 95 95 95
1 % 97 97 97
Overall length(e) in. 73 73 73
(mm) (1852) (1852) (1852)
643
(188)
559
(164)
851
(249)
740
(217)
1078
(316)
937
(275)
Overall width (c) in.
36b 36b 36b
(including insulation) (mm) (930) (930) (930)
Overall height (a) in. 66 66 66
(including control unit) (mm) (1676) (1676) (1676)
Concrete boiler base
Length in. 40 40 40
(mm) (1005) (1005) (1005)
Width in. 31 31 31
(mm) (800) (800) (800)
Thickness in. 4 4 4
(mm) (100) (100) (100)
Weight
Boiler body lb 503 536 564
(Kg) (228) (243) (256)
Complete with the burner, control lb 726 759 792
and thermal insulation (Kg) (329) (344) (359)
*
1 Tested to AHRI, BTS-2000 Testing Standard Method to Determine Efficiency of Commercial Heating Boilers.
Note: For high altitude installations (5,000 to 10,000 ft.), the input will have an altitude de-ration of 15% for 5,000 ft.
and 18% for 10,000 ft.
4
5608 012 v1.1

Vitocrossal 200 CM2 Technical Data
Specifications
Technical Data (continued)
Boiler Model CM2 186 246 311
Boiler Water Content USG 81 77 74
(L) (306) (292) (279)
Heat exchanger surface ft.
water cooled (m
Maximum Operating Temperature °F 190 190 190
Maximum Operating Pressure psig 75 75 75
Boiler Connections
Boiler supply and return (BS), (BR) in.
(ANSI flanges)
Safety Supply in.
Boiler Drain in. 1 1 1
Condensate Drain in.
Vent pipe
Internal Diameter in. 8 8 8
Flue Gas Values
temperature (at a return
temperature of 86° F (30° C)
at rated input °F 136 132 130
at partial load °F 95 95 95
Temperature (at a return
temperature of 140° F (60° C)
at rated input °F 167 167 167
Mass flow rate (of flue gas)
at rated input lbs/h 593 785 994
2
2)
(°C) (88) (88) (88)
(kpa) (517) (517) (517)
(mm) (65) (65) (65)
(mm) (32) (32) (32)
(mm) (201) (201) (201)
(°C) (58) (55) (54)
(°C) (35) (35) (35)
(°C) (75) (75) (75)
(kg/h) (269) (356) (451)
73.2 90.4 114.1
(6.8) (8.4) (10.6)
2b 2b 2b
1a 1a 1a
c c c
at partial load lbs/h 198 262 331
Pressure
at boiler flue outlet pa 70 70 70
at rated input “w.c. 0.28 0.28 0.28
5608 012 v1.1
(kg/h) (90) (119) (150)
5