Vitocal 200-G Type BWP 106 BWP 108 BWP 110
Heat pump performance data
*
1
Heating output kW 6.1 7.7 9.7
Refrigerating capacity kW 4.7 5.9 7.5
Power consumption kW 1.4 1.8 2.2
Coefficient of Performance ∊ (COP)
during heating operation
4.3 4.3 4.3
Instantaneous heating water heater (accessories) performance data
Heat output kW stepped 3/6/9
Instantaneous heating water heater output kW 15.1 16.7 18.7
Brine (primary)
Capacity litres 1.6 2.1 2.6
Min. throughput
*
2
l/h 1200 1400 1800
Max. external pressure drop mbar 400 480 380
Max. inlet temperature °C 25 25 25
Min. inl et temperature °C –5 –5 –5
Heating water (secondary)
Content, heat pump litres 1.6 1.8 2.0
Content, total litres 7.0 7.2 7.4
Min. throughput
*
2
l/h 800 800 800
Max. external pressure drop mbar 450 450 450
Max. flow temperature °C 60 60 60
Electrical values
Rated voltage (heat pump, complete) 3/N/PE 400 V/50 Hz
Rated voltage (control circuit) 230 V/50 Hz
Rated current (compressor) A 5.5 6.0 8.0
Starting current (compressor) A 25.0 14.0
*
3
20.0
*
3
Starting current (compressor
with stalled armature)
A 32.0 35.0 48.0
Power consumption
– Solar circuit pump for stage 1/2/3 W 62/92/132 195/175/120 195/175/120
– Heating circuit pump for stage 1/2/3 W 62/92/132
Fuse(slow) A 3×16 3×16
*
4
3×16
*
4
Protection IP 20
Fuse (internal) 6.3 A H (slow)
Refrigerating circuit
Refrigerant R 410 A
Fill volume kg 1.050 1.200 1.350
Compressor Type Hermetically sealed scroll compressor
Dimensions
– Total length mm 720 720 720
– Total width mm 600 600 600
– Total height mm 1145 1145 1145
Weights
– Total weight kg 120 130 135
– Standard equipment weight kg 70 70 70
– Heat pump weight kg 50 60 65
Permissible operating pressure
Brine circuit (primary) bar 4.0 4.0 4.0
Heating water circuit (secondary) bar 3.0 3.0 3.0
Connections
Primary flow and return (brine) optionally Rp ¾" or multi-connect system DN 20
Heating flow and return Multi-connect system DN 20
DHW R Multi-connect system DN 20
5822 347-2 GB
4 VIESMANN VITOCAL 200-G
*1
At operati ng point B0/W35 to EN 255: B0 = Brine i nlet temperature 0 °C/W 35 = Heating water outlet temperature 35 °C.
For furthe r operating points, see the outpu t diagrams.
*2
Always safeguard the min. throughput.
*3
With electronic starting current limiter (full wave soft starter; the Z characteristic is required for protection).
*4
Z characteristic required.
Specification