Viessmann VITODENS 242-F, B2UB, B2SB, B2TB Technical Manual

VIESMANN
VITODENS
Gas condensing boiler
VITODENS 222-F
Type B2TB
Gas condensing storage combi boiler
1.9 to 35.0 kW For natural gas and LPG
VITODENS 222-F
Type B2SB
Gas condensing storage combi boiler
1.9 to 26.0 kW For natural gas and LPG
VITODENS 242-F
Type B2UB
Gas/solar condensing storage combi boiler with solar DHW heating
1.9 to 26.0 kW For natural gas and LPG
5822431 GB 5/2018
Technical guide
Index
1. Vitodens 222-F, type B2TB 1.1 Product description ....................................................................................................... 4
1.2 Specification ................................................................................................................. 6
2. Vitodens 222-F, type B2SB 2.1 Product description ....................................................................................................... 11
2.2 Specification ................................................................................................................. 13
3. Vitodens 242-F, type B2UB 3.1 Product description ....................................................................................................... 18
3.2 Specification ................................................................................................................. 20
4. Installation accessories 4.1 Installation accessories Vitodens 222-F and Vitodens 333-F ....................................... 26
■ Low loss headers ...................................................................................................... 31
■ Flue gas cascade (positive pressure) for multi boiler systems with Vitodens 222-F . 34
4.2 Installation accessories Vitodens 242-F ....................................................................... 35
■ Low loss headers ...................................................................................................... 40
5. Design information 5.1 Siting, installation .......................................................................................................... 43
■ Siting conditions for open flue operation (appliance type B) ..................................... 43
■ Siting conditions for room sealed operation (appliance type C) ................................ 44
■ Operation of the Vitodens in wet rooms .................................................................... 44
■ Electrical connection ................................................................................................. 45
■ Gas connection ......................................................................................................... 45
■ Minimum clearances ................................................................................................. 46
■ Installation Vitodens 222-F and 333-F ...................................................................... 47
■ Installation Vitodens 242-F ....................................................................................... 56
5.2 Decision making aids for DHW heating ........................................................................ 62
■ Information on water quality ...................................................................................... 62
5.3 Connections on the water side ..................................................................................... 63
■ Connections on the DHW side .................................................................................. 63
5.4 Condensate connection ................................................................................................ 65
■ Condensate drain pipe and neutralisation ................................................................ 65
5.5 Hydraulic connection .................................................................................................... 66
■ General ..................................................................................................................... 66
■ Expansion vessels for the heating circuit .................................................................. 67
■ Low loss header ........................................................................................................ 68
■ Expansion vessel and heat sink for the solar circuit ................................................. 69
■ Low loss header ........................................................................................................ 72
5.6 Sizing the solar thermal system .................................................................................... 72
■ Influence of orientation, inclination and shade .......................................................... 72
■ Solar coverage .......................................................................................................... 73
■ DHW demand of apartments .................................................................................... 73
■ Determining the required solar collector area ........................................................... 73
■ Sizing aid for the Vitodens 242-F .............................................................................. 74
5.7 Intended use ................................................................................................................. 77
6. Control units 6.1 Vitotronic 100, type HC1B, for constant temperature operation ................................... 78
■ Layout and functions ................................................................................................. 78
■ Specification Vitotronic 100, type HC1B ................................................................... 79
6.2 Vitotronic 200, type HO2C, for weather-compensated operation ................................. 79
■ Design and functions ................................................................................................ 79
■ Specification Vitotronic 200, type HO2C ................................................................... 81
■ Solar control module, type SM1 ................................................................................ 81
6.3 Vitotronic accessories ................................................................................................... 82
■ Allocation to control unit types .................................................................................. 82
■ Vitotrol 100, type UTA ............................................................................................... 83
■ Vitotrol 100, type UTDB ............................................................................................ 83
■ External H4 extension ............................................................................................... 84
■ Vitotrol 100, type UTDB-RF ...................................................................................... 84
■ Notes regarding room temperature hook-up (RS function) for remote control units . 85
■ Information on the Vitotrol 200-A and Vitotrol 300-A ................................................ 85
■ Vitotrol 200-A ............................................................................................................ 85
■ Vitotrol 300-A ............................................................................................................ 85
■ Information regarding Vitotrol 200-RF ....................................................................... 86
■ Vitotrol 200-RF .......................................................................................................... 86
■ Wireless base station ................................................................................................ 87
■ Wireless repeater ...................................................................................................... 87
■ Room temperature sensor ........................................................................................ 88
■ Immersion temperature sensor ................................................................................. 88
■ Immersion temperature sensor ................................................................................. 88
■ KM BUS distributor ................................................................................................... 89
Index
2
VIESMANN
VITODENS
5822431
■ Mixer extension kit with integral mixer motor ............................................................ 89
■ Mixer extension kit for separate mixer motor ............................................................ 90
■ Immersion thermostat ............................................................................................... 90
■ Contact thermostat .................................................................................................... 90
■ Internal H1 extension ................................................................................................ 91
■ Internal H2 extension ................................................................................................ 91
■ AM1 extension .......................................................................................................... 91
■ EA1 extension ........................................................................................................... 92
■ LON connecting cable for data exchange between control units .............................. 93
■ Extension of the connecting cable ............................................................................ 93
■ Terminator (2 pce) ..................................................................................................... 93
■ LON communication module ..................................................................................... 93
■ Vitoconnect 100, type OPTO1 .................................................................................. 93
7. Appendix 7.1 Regulations / Directives ................................................................................................ 94
■ Regulations and directives ........................................................................................ 94
8. Keyword index ............................................................................................................................................ 95
Index
(cont.)
VITODENS
VIESMANN
3
5822431
1.1 Product description
A
Inox-Radial heat exchanger made from stainless steel – for high operational reliability, a long service life and high heating output on a very small footprint
B
Modulating MatriX cylinder burner with intelligent Lambda Pro Control Plus combustion controller for clean combustion and quiet operation
C
Integral diaphragm expansion vessel
D
Digital boiler control unit
E
Integral variable speed high efficiency circulation pump
F
DHW loading cylinder
The Vitodens 222-F gas condensing storage combi boiler is designed specifically for heating system modernisation projects and as a replacement for older gas boilers with cylinders installed below. With an output of up to 35 kW, this heating centre is designed for high DHW convenience. The integral loading cylinder with 100 l capacity (up to 26 kW) or 130 l capacity (35 kW) offers the DHW convenience of a separate DHW cylinder approximately twice the size. As with all Viessmann storage combi boilers, the Vitodens 222-F gas condensing boiler requires very little space, as its width and depth correspond to the dimensions of standard kitchen units. The proven MatriX cylinder burner with Lambda Pro Control Plus combustion controller automatically adjusts to varying gas qualities and ensures a constantly high standard seasonal efficiency [to DIN] of 98 % (Hs) [gross cv].
Recommended applications
■ Installation in detached and terraced houses
■ New build (e.g. prefabricated houses and developer projects): Installation in utility rooms and attics
■ Modernisation: Replacement of gas system boilers, floorstanding atmospheric gas boilers and oil/gas boilers with DHW cylinders installed below.
Benefits at a glance
■ Standard seasonal efficiency [to DIN]: Up to 98 % (Hs) [gross cv]
■ Durable and efficient thanks to the Inox-Radial heat exchanger
■ Modulating MatriX cylinder burner with a long service life thanks to stainless steel MatriX gauze – Tolerant to high temperature loads – Modulation range down to 01:19 (35 kW)
■ High DHW convenience through enamelled loading cylinder with 100 l capacity (35 kW: 130 l capacity)
■ Power saving, high efficiency circulation pump
■ New, innovative operating concept using colour touchscreen with plain text and graphic display, commissioning assistant and dis­plays for energy consumption, as well as alternative operation from a mobile end device
■ Web-enabled through Vitoconnect (accessories) for operation and service via Viessmann apps
■ Lambda Pro Control Plus combustion controller for all gas types – saves on costs by extending the inspection interval to 3 years [in Germany]
■ Automatic flue adaptor
■ No lateral service clearance required
■ Assembly kit (accessories) with the dimensions and design of the appliance, for the connection of one regulated and one unregula­ted heating circuit
Delivered condition
Gas condensing boiler with Inox-Radial stainless steel heat exchanger, modulating MatriX cylinder burner for natural gas and LPG to DVGW Code of Practice G260 [Germany], expansion vessel, variable speed high efficiency circulation pump and integral DHW loading cylinder. Fully plumbed and wired.
Vitodens 222-F, type B2TB
4
VIESMANN
VITODENS
1
5822431
White epoxy-coated casing. Packed separately: Vitotronic 100 for constant temperature operation or Vitotronic 200 for weather-compensated operation. Preset for operation with natural gas. Conversion within gas groups E/LL is not required. The conversion to LPG is made at the control unit (a conversion kit is not required).
Accessories required (order separately)
Installation on finished walls
■ Connection set for installation on finished walls, for upward con­nection or
■ Connection set with pre-mounting bracket for installation on fin­ished walls, for upward connection or
■ Connection set for installation on finished walls, for connection to the left or right or
■ Connection set with pre-mounting bracket for installation on fin­ished walls, for connection to the left or right or
■ Connection set with pre-mounting bracket for installation on fin­ished walls, for downward connection or
■ Assembly kit with mixer
Installation on unfinished walls
■ Connection set for unfinished walls or
■ Assembly kit with mixer
Tested quality
CE designation according to current EC Directives
ÖVGW Quality Mark for gas and water equipment
Meets the requirements for the "Blue Angel" eco-label RAL UZ 61.
Vitodens 222-F, type B2TB
(cont.)
VITODENS
VIESMANN
5
5822431
1
1.2 Specification
Gas boiler, type B and C, category II
2N3P
Rated heating output range (to EN 15502-1) Values in ( ) when operating with LPG P TF/TR = 50/30 °C kW 1.9 - 13.0 1.9 - 19.0 2.6 - 26.0 1.8 (3.5) - 35.0 TF/TR = 80/60 °C kW 1.7 - 12.1 1.7 - 17.6 2.4 - 24.1 1.6 (3.2) - 32.5
Rated heating output for DHW heating kW 1.7 - 17.2 1.7 - 17.2 2.4 - 29.3 1.6 (3.2) - 33.5 Rated heat input kW 1.8 - 17.9 1.8 - 17.9 2.5 - 30.5 1.7 (3.3) - 34.9 Product ID CE-0085CN0050 IP rating IP X4 to EN 60529 Gas supply pressure
Natural gas mbar 20 20 20 20 kPa 2 2 2 2 LPG mbar 50 50 50 50 kPa 5 5 5 5
Max. permissible gas supply pressure
*1
Natural gas mbar 25.0 25.0 25.0 25.0 kPa 2.5 2.5 2.5 2.5 LPG mbar 57.5 57.5 57.5 57.5 kPa 5.75 5.75 5.75 5.75
Sound power level
(to EN ISO 15036-1) – At partial load dB(A) 35 35 40 37 – At rated heating output (DHW heating) dB(A) 39 41 48 52 Power consumption – In the delivered condition W 28 42 65 95 – Max. W 126 126 148 163
Weight kg 129 129 132 141 Heat exchanger capacity Litre 1.8 1.8 2.4 2.8 Max. flow temperature °C 74 74 74 74 Max. flow rate
(Limit for the use of hydraulic separation)
l/h 1200 1200 1400 1600
Nominal circulating water volume
At TF/TR = 80/60 °C
l/h 507 739 1018 1361
Expansion vessel Capacity Litre 12 12 12 12 Pre-charge pressure bar 0.75 0.75 0.75 0.75 kPa 75 75 75 75
Permiss. operating pressure (on the heating water side)
bar 3 3 3 3
MPa 0.3 0.3 0.3 0.3 Connections (with connection accessories) Boiler flow and return R ¾ ¾ ¾ ¾ Cold water and DHW R ½ ½ ½ ½ DHW circulation R ½ ½ ½ ½ Dimensions Length mm 595 595 595 595 Width mm 600 600 600 600 Height mm 1426 1426 1426 1626
Gas connection (with connection accessories) R ½ ½ ½ ½ DHW loading cylinder
Capacity Litre 100 100 100 130 Permiss. operating pressure (DHW side) bar 10 10 10 10 MPa 1 1 1 1 Continuous DHW output kW 17.2 17.2 29.3 33.5 For DHW heating from 10 to 40 °C l/h 493 493 840 960 Performance factor N
L
1.8 1.8 3.0 4.8 Initial DHW output For DHW heating from 10 to 40 °C
l/10 min 182 182 230 273
Connection values
relative to max. load With gas Natural gas E
m3/h
1.89 1.89 3.23 3.69
Natural gas LL
m3/h
2.20 2.20 3.75 4.30
LPG P kg/h 1.40 1.40 2.38 2.73
*1
If the gas supply pressure is higher than the maximum permissible value, install a separate gas pressure governor upstream of the sys­tem.
Vitodens 222-F, type B2TB
(cont.)
6
VIESMANN
VITODENS
1
5822431
Gas boiler, type B and C, category II
2N3P
Rated heating output range (to EN 15502-1) Values in ( ) when operating with LPG P TF/TR = 50/30 °C kW 1.9 - 13.0 1.9 - 19.0 2.6 - 26.0 1.8 (3.5) - 35.0 TF/TR = 80/60 °C kW 1.7 - 12.1 1.7 - 17.6 2.4 - 24.1 1.6 (3.2) - 32.5
Flue gas parameters
*2
Flue gas category to G 635/G 636 G52/G
51
G52/G
51
G52/G
51
G52/G
51
Temperature (at a return temperature of 30 °C) – At rated heating output °C 45 45 45 45 – At partial load °C 35 35 35 35 Temperature (at a return temperature of 60 °C) °C 68 68 68 70 Mass flow rate – For natural gas – At rated heating output (DHW heating) kg/h 31.8 31.8 54.3 62.1 – At partial load kg/h 5.5 5.5 8.7 8.7 – For LPG – At rated heating output (DHW heating) kg/h 30.2 30.2 51.5 58.9 – At partial load kg/h 7.6 7.6 14.0 14.0 Available draught Pa 250 250 250 250 mbar 2.5 2.5 2.5 2.5 Max. amount of condensate To DWA-A 251 l/h 2.3 2.5 4.3 4.9
Condensate connection (hose nozzle) Ø mm 20-24 20-24 20-24 20-24 Flue outlet Ø mm 60 60 60 60 Ventilation air connection Ø mm 100 100 100 100 Standard seasonal efficiency [to DIN] at
TF/TR = 40/30 °C % up to 98 (Hs) [gross cv] Energy efficiency class
– Heating A A A A – DHW heating, draw-off profile XL A A A A
*2
Calculation values for sizing the flue system to EN 13384. Flue gas temperatures as actual gross values at 20 °C combustion air temperature. The flue gas temperature at a return temperature of 30 °C is significant for the sizing of the flue system. The flue gas temperature at a return temperature of 60 °C is used to determine the application range of flue pipes with maximum permissi­ble operating temperatures.
Vitodens 222-F, type B2TB
(cont.)
VITODENS
VIESMANN
7
5822431
1
80
f
50
595
50
600
100
569
46
40
50
c
d
a
b
140
50
G C F
A
B
D E
G
K
A
B
C
F
D
E
E
D
F
C
B
A
G
H
e
A
Heating flow R ¾
B
DHW R ½
C
Gas connection R ½
D
Cold water R ½
E
Heating return R ¾
F
DHW circulation R ½ (separate accessories)
G
Condensate drain facing backwards into the wall
H
Condensate drain to the side
K
Wiring area
Rated heating output kW
a
mmbmmcmmdmmemmfmm
13 to 19 745 750 1426 1466 1572 201 26 745 750 1426 1466 1572 224 35 945 950 1626 1666 1772 224
Note
The dimensioned drawing shows example fittings for installation on finished walls, for upward connection and connection to the left/right. Order the connection sets separately as accessories. For the dimensions of the individual connection sets, see the design information. If using the connection set with pre-mounting bracket for downward connections on finished walls, maintain a wall clearance of 70 mm.
Note
All height dimensions have a tolerance of +7 mm on account of the adjustable feet.
Note
Height dimensions in combination with a balanced flue bend Ø 60/100 mm. In combination with a balanced flue bend Ø 60/100 mm, the total height is reduced by 10 mm.
Vitodens 222-F, type B2TB
(cont.)
8
VIESMANN
VITODENS
1
5822431
Variable speed heating circuit pump in the Vitodens 222-F
The integral circulation pump is a highly efficient pump with substan­tially lower power consumption than conventional pumps. The pump speed and consequently the pump rate are regulated sub­ject to the outside temperature and the switching times for heating or reduced mode. The control unit transmits the current default settings to the circulation pump via an internal data bus. The min. and max. speed and the speed in reduced mode can be adjusted using codes at the control unit of the existing heating sys­tem. In the delivered condition, the minimum pump rate (coding address "E7") and the maximum pump rate (coding address "E6") are set to the following values:
Rated heating output in kW Speed settings in the delivered
condition in %
Min. pump rate Max. pump
rate
13 45 60 19 45 65 26 45 80 35 45 90
Note
In conjunction with a low loss header, heating water buffer cylinder and heating circuits with mixer, the internal circulation pump runs at a constant speed. The speed can be adjusted subject to demand by changing the code at the control unit.
Specification circulation pump Rated heating out­put
kW 13 19 26 35
Circulation pump TypeUPM3
15-75
UPM3
15-75
UPM3
15-75
UPM3
15-75
Rated voltage V~ 230 230 230 230 Power consumption – max. W 60 60 60 60 – min. W 2 2 2 2 – Delivered condi-
tion
W 12 20 38 45
Energy efficiency class A A A A Energy efficiency index (EEI)
≤ 0.20 ≤ 0.20 ≤ 0.20 ≤ 0.20
Residual head of the integral circulation pump
Residual head
0
kPa
0 200 400 600 800 1000
Flow rate in l/h
100
200
300
400
0
10
20
30
40
500
50
C
E
H
mbar
600
60
G
F
A
1200
B
100 300 500 700 900 1100 1300
D
5
50
150 15
250 25
350 35
450 45
550
55
650
65
H
Upper operational limit
Vitodens 222-F, type B2TB
(cont.)
VITODENS
VIESMANN
9
5822431
1
Curve Pump rate, circulation
pump
Coding address setting "E6"
A
40 % E6:040
B
50 % E6:050
C
60 % E6:060
D
70 % E6:070
E
80 % E6:080
F
90 % E6:090
G
100 % E6:100
Vitodens 222-F, type B2TB
(cont.)
10
VIESMANN
VITODENS
1
5822431
2.1 Product description
A
Inox-Radial heat exchanger made from stainless steel – for high operational reliability, a long service life and high heating output on a very small footprint
B
Modulating MatriX cylinder burner with intelligent Lambda Pro Control Plus combustion controller for clean combustion and quiet operation
C
Integral diaphragm expansion vessel
D
Digital boiler control unit
E
Integral variable speed high efficiency circulation pump
F
DHW cylinder with internal indirect coil
The Vitodens 222-F storage combi boiler combines the benefits of the Vitodens 200-W with the high level of DHW convenience of a separate DHW cylinder. As with all Viessmann storage combi boilers, the Vitodens 222-F gas condensing boiler requires very little space, as its width and depth correspond to the dimensions of standard kitchen units. The proven MatriX cylinder burner with Lambda Pro Control Plus combustion controller automatically adjusts to varying gas qualities and ensures a constantly high standard seasonal efficiency [to DIN] of 98 % (Hs) [gross cv]. The Vitodens 222-F, type B2SB with integral 130 l cylinder with inter­nal indirect coil is particularly suitable for hard water areas. Due to its smooth surface the internal indirect coil is resistant to lime­scale deposits.
Recommended applications
■ Installation in detached and terraced houses
■ New build (e.g. prefabricated houses and developer projects): Installation in utility rooms and attics
■ Modernisation: Replacement of gas system boilers, floorstanding atmospheric gas boilers and oil/gas boilers with DHW cylinders installed below
For use in areas with a water hardness of > 20 °dH (3.58 mol/m3)
Benefits at a glance
■ Standard seasonal efficiency [to DIN]: Up to 98 % (Hs) [gross cv]
■ Durable and efficient thanks to the Inox-Radial heat exchanger
■ Modulating MatriX cylinder burner with a long service life thanks to stainless steel MatriX gauze – Tolerant to high temperature loads – Modulation range down to 01:10 (26 kW)
■ Enamelled DHW cylinder with internal indirect coil and 130 l capacity (NL factor up to 1.8)
■ Power saving, high efficiency circulation pump
■ New, innovative operating concept using colour touchscreen with plain text and graphic display, commissioning assistant and dis­plays for energy consumption, as well as alternative operation from a mobile end device
■ Web-enabled through Vitoconnect (accessories) for operation and service via Viessmann apps
■ Lambda Pro Control Plus combustion controller for all gas types – saves on costs by extending the inspection interval to 3 years [in Germany]
■ Automatic flue adaptor
Vitodens 222-F, type B2SB
VITODENS
VIESMANN
11
5822431
2
■ No lateral service clearance required
■ Assembly kit (accessories) with the dimensions and design of the appliance, for the connection of one regulated and one unregula­ted heating circuit
Delivered condition
Gas condensing boiler with Inox-Radial heat exchanger, modulating MatriX cylinder burner for natural gas and LPG to DVGW Code of Practice G260 [Germany], expansion vessel, variable speed high efficiency circulation pump and integral DHW cylinder. Fully plumbed and wired. White epoxy-coated casing. Packed separately: Vitotronic 100 for constant temperature operation or Vitotronic 200 for weather-compensated operation. Preset for operation with natural gas. Conversion within gas groups E/LL is not required. The conversion to LPG is made at the control unit (a conversion kit is not required).
Accessories required (order separately)
Installation on finished walls
■ Connection set for installation on finished walls, for upward con­nection or
■ Connection set with pre-mounting bracket for installation on fin­ished walls, for upward connection or
■ Connection set for installation on finished walls, for connection to the left or right or
■ Connection set with pre-mounting bracket for installation on fin­ished walls, for connection to the left or right or
■ Connection set with pre-mounting bracket for installation on fin­ished walls, for downward connection or
■ Assembly kit with mixer
Installation on unfinished walls
■ Connection set for unfinished walls or
■ Assembly kit with mixer
Tested quality
CE designation according to current EC Directives
ÖVGW Quality Mark for gas and water equipment
Meets the requirements for the "Blue Angel" eco-label RAL UZ 61.
Vitodens 222-F, type B2SB
(cont.)
12
VIESMANN
VITODENS
2
5822431
2.2 Specification
Gas boiler, type B and C, category II
2N3P
Rated heating output range (to EN 15502-1) TF/TR = 50/30 °C kW 1.9 - 13.0 1.9 - 19.0 2.6 - 26.0 TF/TR = 80/60 °C kW 1.7 - 12.1 1.7 - 17.6 2.4 - 24.1
Rated heating output for DHW heating kW 1.7 - 17.2 1.7 - 17.2 2.4 - 23.7 Rated heat input kW 1.8 - 17.9 1.8 - 17.9 2.5 - 24.7 Product ID CE-0085CN0050 IP rating IP X4 to EN 60529 Gas supply pressure
Natural gas mbar 20 20 20 kPa 2 2 2 LPG mbar 50 50 50 kPa 5 5 5
Max. permissible gas supply pressure
*3
Natural gas mbar 25.0 25.0 25.0
2.5 2.5 2.5 LPG mbar 57.5 57.5 57.5
5.75 5.75 5.75
Sound power level
(to EN ISO 15036-1) – At partial load dB(A) 33 33 42 – At rated heating output (DHW heating) dB(A) 39 41 48 Power consumption – In the delivered condition W 28 42 65 – Max. W 86 86 95
Weight kg 139 139 142 Heat exchanger capacity Litre 1.8 1.8 2.4 Max. flow temperature °C 74 74 74 Max. flow rate
(Limit for the use of hydraulic separation)
l/h 1200 1200 1400
Nominal circulating water volume
At TF/TR = 80/60 °C
l/h 537 739 1018
Expansion vessel Capacity Litre 12 12 12 Pre-charge pressure bar 0.75 0.75 0.75 kPa 75 75 75
Permiss. operating pressure (on the heating water side)
bar 3 3 3
MPa 0.3 0.3 0.3 Connections (with connection accessories) Boiler flow and return R ½ ¾ ¾ Cold water and DHW R ½ ½ ½ DHW circulation R ½ ½ ½ Dimensions Length mm 595 595 595 Width mm 600 600 600 Height mm 1626 1626 1626
Gas connection (with connection accessories) R ½ ½ ½ DHW cylinder
Capacity Litre 130 130 130 Permiss. operating pressure (DHW side) bar 10 10 10 MPa 1 1 1 Continuous DHW output kW 17.2 17.2 23.7 For DHW heating from 10 to 40 °C l/h 493 493 680 Performance factor N
L
*4
1.3 1.3 1.8 Initial DHW output For DHW heating from 10 to 40 °C
l/10 min 153 153 182
*3
If the gas supply pressure is higher than the maximum permissible value, install a separate gas pressure governor upstream of the sys­tem.
*4
At 70 ºC average boiler water temperature and cylinder storage temperature Tcyl = 60 ºC. DHW performance factor NL depends on cylinder storage temperature Tcyl. Standard values: Tcyl = 60 ºC → 1.0 × NL Tcyl = 55 ºC → 0.75 × NL Tcyl = 50 ºC → 0.55 × NL Tcyl = 45 ºC → 0.3 × NL.
Vitodens 222-F, type B2SB
(cont.)
VITODENS
VIESMANN
13
5822431
2
Gas boiler, type B and C, category II
2N3P
Rated heating output range (to EN 15502-1) TF/TR = 50/30 °C kW 1.9 - 13.0 1.9 - 19.0 2.6 - 26.0 TF/TR = 80/60 °C kW 1.7 - 12.1 1.7 - 17.6 2.4 - 24.1
Connection values
relative to max. load With gas Natural gas E
m3/h
1.89 1.89 2.61
Natural gas LL
m3/h
2.06 2.20 3.04
LPG P kg/h 1.31 1.40 1.93
Flue gas parameters
*2
Flue gas category to G 635/G 636 G52/G
51
G52/G
51
G52/G
51
Temperature (at 30 °C return temperature) – At rated heating output °C 45 45 45 – At partial load °C 35 35 35 Temperature (at a return temperature of 60 °C) °C 68 68 70 Mass flow rate – For natural gas – At rated heating output kg/h 31.8 31.8 43.9 – At partial load kg/h 5.5 5.5 8.7 – For LPG – At rated heating output kg/h 30.2 30.2 41.7 – At partial load kg/h 7.6 7.6 14.0 Available draught Pa 250 250 250 mbar 2.5 2.5 2.5 Max. amount of condensate To DWA-A 251 l/h 2.3 2.5 3.5
Condensate connection (hose nozzle) Ø mm 20-24 20-24 20-24 Flue outlet Ø mm 60 60 60 Ventilation air connection Ø mm 100 100 100 Standard seasonal efficiency [to DIN] at
TF/TR = 40/30 °C % up to 98 (Hs) [gross cv] Energy efficiency class
– Heating A A A – DHW heating, draw-off profile XL A A A
*2
Calculation values for sizing the flue system to EN 13384. Flue gas temperatures as actual gross values at 20 °C combustion air temperature. The flue gas temperature at a return temperature of 30 °C is significant for the sizing of the flue system. The flue gas temperature at a return temperature of 60 °C is used to determine the application range of flue pipes with maximum permissi­ble operating temperatures.
Vitodens 222-F, type B2SB
(cont.)
14
VIESMANN
VITODENS
2
5822431
100
569
46
40
50
1626
1666
945
80
140
50
A
C
D
F
E
B
E
F
B
A
D
C
K
G
H
G
G C
A
B
F
D E
a
50
595
50
600
1772
A
Heating flow R ¾
B
DHW R ½
C
Gas connection R ½
D
Cold water R ½
E
Heating return R ¾
F
DHW circulation R ½ (separate accessories)
G
Condensate drain facing backwards into the wall
H
Condensate drain to the side
K
Wiring area
Rated heating output kW
a
mm
13 and 19 201 26 224
Note
The dimensioned drawing shows example fittings for installation on finished walls, for upward connection and connection to the left/right. Order the connection sets separately as accessories. For the dimensions of the individual connection sets, see the design information. If using the connection set with pre-mounting bracket for downward connections on finished walls, maintain a wall clearance of 70 mm.
Note
All height dimensions have a tolerance of +7 mm on account of the adjustable feet.
Vitodens 222-F, type B2SB
(cont.)
VITODENS
VIESMANN
15
5822431
2
Note
Height dimensions in combination with a balanced flue bend Ø 60/100 mm. In combination with a balanced flue bend Ø 60/100 mm, the total height is reduced by 10 mm.
Variable speed heating circuit pump in the Vitodens 222-F
The integral circulation pump is a highly efficient pump with substan­tially lower power consumption than conventional pumps. The pump speed and consequently the pump rate are regulated sub­ject to the outside temperature and the switching times for heating or reduced mode. The control unit transmits the current default settings to the circulation pump via an internal data bus. The min. and max. speed and the speed in reduced mode can be adjusted using codes at the control unit of the existing heating sys­tem. In the delivered condition, the minimum pump rate (coding address "E7") and the maximum pump rate (coding address "E6") are set to the following values:
Rated heating output in kW Speed settings in the delivered
condition in %
Min. pump rate Max. pump
rate
13 45 60 19 45 65 26 45 80
Note
In conjunction with a low loss header, heating water buffer cylinder and heating circuits with mixer, the internal circulation pump runs at a constant speed. The speed can be adjusted subject to demand by changing the code at the control unit.
Specification circulation pump Rated heating output kW 13 19 26 Circulation pump Type UPM3
15-75
UPM3
15-75
UPM3
15-75
Rated voltage V~ 230 230 230 Power consumption – max. W 60 60 60 – min. W 2 2 2 – Delivered condition W 12 20 38 Energy efficiency class A A A Energy efficiency index (EEI) ≤ 0.20 ≤ 0.20 ≤ 0.20
Residual head of the integral circulation pump
Residual head
0
kPa
0 200 400 600 800 1000
Flow rate in l/h
100
200
300
400
0
10
20
30
40
500
50
C
E
H
mbar
600
60
G
F
A
1200
B
100 300 500 700 900 1100 1300
D
5
50
150 15
250 25
350 35
450 45
550
55
650
65
H
Upper operational limit
Vitodens 222-F, type B2SB
(cont.)
16
VIESMANN
VITODENS
2
5822431
Curve Pump rate, circulation
pump
Coding address setting "E6"
A
40 % E6:040
B
50 % E6:050
C
60 % E6:060
D
70 % E6:070
E
80 % E6:080
F
90 % E6:090
G
100 % E6:100
Vitodens 222-F, type B2SB
(cont.)
VITODENS
VIESMANN
17
5822431
2
3.1 Product description
A
Inox-Radial heat exchanger made from stainless steel – for high operational reliability, a long service life and high heating output on a very small footprint
B
Modulating MatriX gas burner for extremely clean combustion
C
Integral diaphragm expansion vessel
D
Digital boiler control unit
E
Integral solar circuit pump
F
Dual mode DHW cylinder
The Vitodens 242-F gas condensing storage combi boiler for instal­lation against the wall is affordable, compact, efficient and solar­compatible. This storage combi boiler is factory-prepared for direct connection of a solar thermal system. The solar control module is already integrated and is regulated via the Vitotronic control unit. The 170 l dual mode DHW cylinder provides a high level of DHW convenience. For ease of handling the Vitodens 242-F can be trans­ported in two parts.
Recommended applications
■ Installation in detached and terraced houses
■ New build (e.g. prefabricated houses and developer projects): Installation in utility rooms
Benefits at a glance
■ Gas condensing storage combi boiler with integral solar cylinder
■ Standard seasonal efficiency [to DIN]: Up to 98 % (Hs) [gross cv]
■ Durable and efficient thanks to the Inox-Radial stainless steel heat exchanger
■ MatriX cylinder burner with Lambda Pro Control Plus combustion controller for permanently high efficiency and clean combustion – Modulation range down to 1:10
■ Power saving, high efficiency circulation pumps for heating circuit and solar circuit
■ Enamelled dual mode loading cylinder with 170 l capacity
■ New, innovative operating concept using colour touchscreen with plain text and graphic display, commissioning assistant and dis­plays for energy consumption, as well as alternative operation from a mobile end device
■ Web-enabled through Vitoconnect (accessories) for operation and service via Viessmann apps
■ Automatic flue adaptor
■ Can be split for easier handling
Vitodens 242-F, type B2UB
18
VIESMANN
VITODENS
3
5822431
■ Solar coverage > 50 %
■ Assembly kit (accessories) with the dimensions and design of the appliance, for the connection of one regulated and one unregula­ted heating circuit
Delivered condition
Gas condensing boiler with Inox-Radial heat exchanger, MatriX cyl­inder burner for natural gas and LPG to DVGW Code of Practice G260 [Germany], expansion vessel, variable speed heating circuit pump and solar circuit pump, heat transfer medium drip pan, solar side safety valve, Vitotronic 200 for weather-compensated operation, solar control module and integral DHW solar cylinder. Fully plumbed and wired. White epoxy-coated casing. Preset for operation with natural gas. Conversion within gas groups E/LL is not required. The conversion to LPG is made at the control unit (a conversion kit is not required).
Accessories required (order separately)
Installation on finished walls
■ Connection set for installation on finished walls, for upward con­nection or
■ Connection set with pre-mounting bracket for installation on fin­ished walls, for upward connection or
■ Connection set for installation on finished walls, for connection to the left or right or
■ Connection set with pre-mounting bracket for installation on fin­ished walls, for connection to the left or right or
■ Assembly kit with mixer
Installation on unfinished walls
■ Connection set for unfinished walls or
■ Assembly kit with mixer
Tested quality
CE designation according to current EC Directives
ÖVGW Quality Mark for gas and water equipment
Meets the requirements for the "Blue Angel" eco-label RAL UZ 61.
Vitodens 242-F, type B2UB
(cont.)
VITODENS
VIESMANN
19
5822431
3
3.2 Specification
Gas boiler, type B and C, category II
2N3P
Rated heating output range (to EN 15502-1) TF/TR = 50/30 °C kW 1.9 - 13.0 1.9 - 19.0 2.6 - 26.0 TF/TR = 80/60 °C kW 1.7 - 12.1 1.7 - 17.6 2.4 - 24.1
Rated heating output for DHW heating kW 1.7 - 17.2 1.7 - 17.2 2.4 - 29.3 Rated heat input kW 1.8 - 17.9 1.8 - 17.9 2.5 - 30.5 Product ID CE-0085CN0050 IP rating IP X4 to EN 60529 Gas supply pressure
Natural gas mbar 20 20 20 kPa 2 2 2 LPG mbar 50 50 50 kPa 5 5 5
Max. permissible gas supply pressure
*5
Natural gas mbar 25.0 25.0 25.0 kPa 2.5 2.5 2.5 LPG mbar 57.5 57.5 57.5 kPa 5.75 5.75 5.75
Sound power level
(to EN ISO 15036-1) – At partial load dB(A) 33 33 35 – At rated heating output (DHW heating) dB(A) 39 41 48 Power consumption – In the delivered condition W 28 42 65 – Max. W 181 181 203 Weight – Total (with casing) kg 161 161 165 – Heat cell module kg 42 42 46 – Cylinder module kg 95 95 95
Heat exchanger capacity Litre 1.8 1.8 2.4 Solar circuit capacity Litre 9.9 9.9 9.9 Max. flow temperature °C 74 74 74 Max. flow rate
(Limit for the use of hydraulic separation)
l/h 1200 1200 1400
Nominal circulating water volume
At TF/TR = 80/60 °C
l/h 507 739 1018
Expansion vessel Capacity Litre 12 12 12 Pre-charge pressure bar 0.75 0.75 0.75 kPa 75 75 75 Permiss. operating pressure – Heating circuit bar 3 3 3 MPa 0.3 0.3 0.3 – Solar circuit bar 6 6 6 MPa 0.6 0.6 0.6 Connections (with connection accessories) Boiler flow and return R ¾ ¾ ¾ Solar flow and return R/Ø mm ¾/22 ¾/22 ¾/22 Cold water and DHW R ½ ½ ½ DHW circulation R ½ ½ ½ Dimensions Length mm 595 595 595 Width mm 600 600 600 Height mm 1876 1876 1876 Height when tilted mm 2000 2000 2000 Gas connection (with connection accessories) R ½ ½ ½
*5
If the gas supply pressure is higher than the maximum permissible value, install a separate gas pressure governor upstream of the sys­tem.
Vitodens 242-F, type B2UB
(cont.)
20
VIESMANN
VITODENS
3
5822431
Gas boiler, type B and C, category II
2N3P
Rated heating output range (to EN 15502-1) TF/TR = 50/30 °C kW 1.9 - 13.0 1.9 - 19.0 2.6 - 26.0 TF/TR = 80/60 °C kW 1.7 - 12.1 1.7 - 17.6 2.4 - 24.1
DHW cylinder
Capacity Litre 170 170 170 Permiss. operating pressure (DHW side) bar 10 10 10 MPa 1 1 1 Continuous DHW output kW 17.2 17.2 29.3 For DHW heating from 10 to 40 °C l/h 493 493 840 Performance factor N
L
*6
1.4 1.4 2.0 Initial DHW output For DHW heating from 10 to 40 °C
l/10 min 164 164 190
Connection values
relative to max. load With gas Natural gas E
m3/h
1.89 1.89 3.23
Natural gas LL
m3/h
2.20 2.20 3.75
LPG P kg/h 1.40 1.40 2.39
Flue gas parameters
*2
Flue gas category to G 635/G 636 G52/G
51
G52/G
51
G52/G
51
Temperature (at a return temperature of 30 °C) – At rated heating output °C 45 45 45 – At partial load °C 35 35 35 Temperature (at a return temperature of 60 °C) °C 68 68 70 Mass flow rate – For natural gas – At rated heating output kg/h 31.8 31.8 43.9 – At partial load kg/h 5.5 5.5 8.7 – For LPG – At rated heating output kg/h 30.2 30.2 41.7 – At partial load kg/h 7.6 7.6 14.0 Available draught Pa 250 250 250 mbar 2.5 2.5 2.5 Max. amount of condensate To DWA-A 251 l/h 2.3 2.5 4.3
Condensate connection (hose nozzle) Ø mm 20-24 20-24 20-24 Flue outlet Ø mm 60 60 60 Ventilation air connection Ø mm 100 100 100 Standard seasonal efficiency [to DIN] at
TF/TR = 40/30 °C % up to 98 (Hs) [gross cv] Energy efficiency class
– Heating A A A – DHW heating, draw-off profile XL A A A
*6
At 70 ºC average boiler water temperature and cylinder storage temperature Tcyl = 60 ºC. DHW performance factor NL depends on cylinder storage temperature Tcyl. Standard values: Tcyl = 60 ºC → 1.0 × NL Tcyl = 55 ºC → 0.75 × NL Tcyl = 50 ºC → 0.55 × NL Tcyl = 45 ºC → 0.3 × NL.
*2
Calculation values for sizing the flue system to EN 13384. Flue gas temperatures as actual gross values at 20 °C combustion air temperature. The flue gas temperature at a return temperature of 30 °C is significant for the sizing of the flue system. The flue gas temperature at a return temperature of 60 °C is used to determine the application range of flue pipes with maximum permissi­ble operating temperatures.
Vitodens 242-F, type B2UB
(cont.)
VITODENS
VIESMANN
21
5822431
3
a
50
595
50
600
65
1916
100
719
46
40
50
1876
1085
1100
140
60
K
C
F
D
A B
E
G H
A
H
B
D
F
E
G
C
G
E
C
B
F
D
M K
L
K
H
A
2021
A
Solar return R ¾/Ø 22 mm
B
Heating flow R ¾
C
DHW R ½
D
Gas connection R ½
E
DHW circulation R ½ (separate accessories)
F
Cold water R ½
G
Heating return R ¾
H
Solar flow R ¾/Ø 22 mm
K
Condensate drain facing backwards into the wall
L
Condensate drain to the side
M
Wiring area
Rated heating output kW
a
mm
13 and 19 201 26 224
Vitodens 242-F, type B2UB
(cont.)
22
VIESMANN
VITODENS
3
5822431
Note
The dimensioned drawing shows example fittings for installation on finished walls, for upward connection and connection to the left/right. Order the connection sets separately as accessories. For the dimensions of the individual connection sets, see the design information.
Note
All height dimensions have a tolerance of +7 mm on account of the adjustable feet.
Note
Height dimensions in combination with a balanced flue bend Ø 60/100 mm. In combination with a balanced flue bend Ø 60/100 mm, the total height is reduced by 10 mm.
Variable speed heating circuit pump in the Vitodens 242-F
The integral circulation pump is a highly efficient pump with substan­tially lower power consumption than conventional pumps. The pump speed and consequently the pump rate are regulated sub­ject to the outside temperature and the switching times for heating or reduced mode. The control unit transmits the current default settings to the circulation pump via an internal data bus. The min. and max. speed and the speed in reduced mode can be adjusted using codes at the control unit of the existing heating sys­tem. In the delivered condition, the minimum pump rate (coding address "E7") and the maximum pump rate (coding address "E6") are set to the following values:
Rated heating output in kW Speed settings in the delivered
condition in %
Min. pump rate Max. pump
rate
13 45 60 19 45 65 26 45 80
Note
In conjunction with a low loss header, heating water buffer cylinder and heating circuits with mixer, the internal circulation pump runs at a constant speed. The speed can be adjusted subject to demand by changing the code at the control unit.
Specification circulation pump Rated heating output kW 13 19 26 Circulation pump Type UPM3
15-75
UPM3
15-75
UPM3
15-75
Rated voltage V~ 230 230 230 Power consumption – max. W 60 60 60 – min. W 2 2 2 – Delivered condition W 12 20 38 Energy efficiency class A A A Energy efficiency index (EEI) ≤ 0.20 ≤ 0.20 ≤ 0.20
Vitodens 242-F, type B2UB
(cont.)
VITODENS
VIESMANN
23
5822431
3
Residual head of the integral circulation pump
Residual head
0
kPa
0 200 400 600 800 1000
Flow rate in l/h
100
200
300
400
0
10
20
30
40
500
50
C
E
H
mbar
600
60
G
F
A
1200
B
100 300 500 700 900 1100 1300
D
5
50
150 15
250 25
350 35
450 45
550
55
650
65
H
Upper operational limit
Curve Pump rate, circulation
pump
Coding address setting "E6"
A
40 % E6:040
B
50 % E6:050
C
60 % E6:060
D
70 % E6:070
E
80 % E6:080
F
90 % E6:090
G
100 % E6:100
Variable speed solar circuit pump in the Vitodens 242-F
The integral solar circuit pump is a highly efficient circulation pump with substantially lower power consumption than conventional pumps. The min. and max. speed and thus the pump rate are set via codes on the control unit. The control unit transmits the current default set­tings to the circulation pump via an internal data bus. In the delivered condition, the minimum pump rate (coding address "05" in the solar group) is set to 30 %. The maximum pump rate (coding address "06" in the solar group) is set to 100 %.
Type VI Solar PM2
15-85 Rated voltage V~ 230 Power consumption max. W 55 min. W 3 Energy efficiency class A
Vitodens 242-F, type B2UB
(cont.)
24
VIESMANN
VITODENS
3
5822431
Residual head of the integral solar circuit pump
100
0
0 500
Flow rate in l/h
200
600
800
300
400
500
700
1000 1500
10
0
20
60
80
30
40
50
70
kPa
Max.
Min.
Residual head
mbar
Handling the Vitodens 242-F in tight spaces
If required the heat cell and cylinder can be separated for easier handling at the installation location. For the weight of the individual parts, see the specification.
600
810
1310
Vitodens 242-F, type B2UB
(cont.)
VITODENS
VIESMANN
25
5822431
3
4.1 Installation accessories Vitodens 222-F and Vitodens 333-F
Connection set for installation on finished walls, for upward connection
Part no. 7348566
Components:
■ Connection pipes
■ Shut-off valves for heating water flow and return, with boiler drain & fill valve
■ 2 connectors for DHW
■ Gas shut-off valve with thermally activated safety shut-off valve
Connections (male thread) Gas R ½ Heating water R ¾ DHW R ½
Connection set with pre-mounting bracket for installation on finished walls, for upward connection
Part no. 7355317
Components:
■ Connection panel
■ Connection pipes
■ Shut-off valves for heating water flow and return, with boiler drain & fill valve
■ 2 connectors for DHW
■ Gas shut-off valve with thermally activated safety shut-off valve
Connections (male thread) Gas R ½ Heating water R ¾ DHW R ½
Connection set for installation on finished walls, for connection to the left or right
Part no. 7350854
Components:
■ Connection pipes
■ Shut-off valves for heating water flow and return, with boiler drain & fill valve
■ 2 connectors for DHW
■ Gas shut-off valve with thermally activated safety shut-off valve
Connections (male thread) Gas R ½ Heating water R ¾ DHW R ½
Connection set with pre-mounting bracket for installation on finished walls, for connection to the left or right
Part no. 7354403
Components:
■ Connection panel
■ Connection pipes
■ Shut-off valves for heating water flow and return, with boiler drain & fill valve
■ 2 connectors for DHW
■ Gas shut-off valve with thermally activated safety shut-off valve
Connections (male thread) Gas R ½ Heating water R ¾ DHW R ½
Connection set with pre-mounting bracket for installation on finished walls, for downward connection
Part no. ZK01792
Components:
■ Connection panel
■ Connection pipes
■ Shut-off valves for heating water flow and return, with boiler drain & fill valve and air vent valve
■ 2 connectors for DHW
■ Angle gas valve with thermally activated safety shut-off valve
Connections (male thread) Gas R ½ Heating water R ¾ DHW R ½
Installation accessories
26
VIESMANN
VITODENS
4
5822431
Note
This type of installation requires a wall clearance of 70 mm behind the heat generator.
Connection set for unfinished walls Part no. 7351625
Comprising:
■ Mounting plate
■ Connection pipes
■ Shut-off valves for heating water flow and return, with boiler drain & fill valve
■ 2 connectors for DHW
■ Angle gas valve with thermally activated safety shut-off valve
Connections (male thread) Gas R ½ Heating water R ¾ DHW R ½
Assembly kit with mixer
For installation on finished walls
Part no. Z009888
176
520
Assembly kit accessories
Line regulating valve with flow indicator Part no. 7452078
For hydronic balancing of the heating circuits
Contact temperature limiter Part no. 7425493
Maximum temperature limiter for underfloor heating circuits Contact temperature limiter with 1.5 m long connecting lead
Specification assembly kit with mixer
Assembly for heat distribution via one heating circuit with mixer and one heating circuit without mixer, designed to match the appliance. For installation on the boiler.
Comprising:
■ Plate heat exchanger for system separation of the heating circuit with mixer
■ Variable speed high efficiency circulation pump for the heating cir­cuit with mixer
■ 3-way mixer with mixer motor
■ Mixer PCB, capable of communicating with Vitotronic 200 via KM­BUS
■ Adjustable bypass
■ Connection set for installation on finished or unfinished walls, with: – Connection pipes – Shut-off valves for heating water flow and return, with boiler
drain & fill valve – 2 connectors for DHW – Gas shut-off valve with thermally activated safety shut-off valve
■ Flow temperature sensor
■ Cover, designed to match appliance
■ Balanced flue extension, boiler flue connection
The heating circuit without mixer is supplied by the integral circula­tion pump of the Vitodens. For an installation scheme for operation with the assembly kit, see www.viessmann-schemen.com. The assembly kit can only be used in conjunction with the Vitotronic
200.
Max. transferable heating output of the heat­ing circuit with mixer (ΔT 10 K)
kW 14
Max. flow rate of the heating circuit with mixer (ΔT 10 K)
l/h 1200
Permiss. operating pressure bar 3 Max. power consumption W 48 Connections (male thread) – Gas R ½ – Heating water R ¾ – DHW R ½ Weight (incl. packaging) kg 20
Installation accessories
(cont.)
VITODENS
VIESMANN
27
5822431
4
Residual head of the integral circulation pump for the heating circuit with mixer
0
100
200
300
400
500
0
10
20
30
40
50
kPa
600 60
300 400 500 600 700 800 900 1000 1100 1200
Flow rate in l/h
1300 14002001000
Min.
Max.
Residual head
mbar
Calculating the transferable heating output (examples)
The maximum heating output that can be transferred via the plate heat exchanger of the assembly kit is 14 kW. For balanced flow rates between the regulated heating circuit (assembly kit) and the unregu­lated heating circuit (radiator heating circuit), the pressure drop in the assembly kit must be increased. For this, the line regulating valve with flow indicator available as an accessory can be fitted to the primary side of the plate heat exchanger, i.e. between the flow and return. The nominal circulation water volume of the boiler (see specification), minus the flow rate through the plate heat exchanger of the assembly kit, results in the flow rate of the unregulated heating circuit.
Example:
Vitodens 222-F, 26 kW
■ Nominal amount of circulation water at ΔT 20 K: 1018 l/h
■ Heating output for regulated heating circuit (assumed): 13 kW
■ Resulting flow rate, primary side, plate heat exchanger at ΔT 20 K: 560 l/h 9.3 l/min (to be set via the line regulating valve)
■ Flow rate of the unregulated heating circuit: 1018 l/h – 560 l/h = 458 l/h
Connection set for DHW circulation pump
Part no. 7514306
For installation in the appliance
Components:
■ High efficiency circulation pump
■ Flow regulating valve
■ Pipe assembly with thermal insulation
Connection R ½ (male thread)
Note
Vitodens with loading cylinder or solar cylinder also requires an AM1 or EA1 extension for connection to the Vitotronic.
Safety assembly to DIN 1988
DN 15
Components:
■ Shut-off valve
■ Non-return valve and test connector
■ Pressure gauge
■ Diaphragm safety valve
For on-site installation on finished walls
■ 10 bar (1.0 MPa)
Part no. 7219722
a 6 bar (0.6 MPa)
Part no. 7265023
For installation on unfinished walls in conjunction with the con­nection set
■ 10 bar (1.0 MPa)
Part no. 7351842
a 6 bar (0.6 MPa)
Part no. 7351840
Valve/fittings cover
Part no. 7352257
For connection set for installation on unfinished walls Not for use in conjunction with filling facility
Installation accessories
(cont.)
28
VIESMANN
VITODENS
4
5822431
Filling device with pipe separator
For fitting to the connection sets
■ For installation on finished walls (not for downward connection on finished walls)
Part no. 7356492
■ For downward connection on unfinished and finished walls
Part no. 7356902
Connection set for external heating water expansion vessel Part no. 7301709
Expansion vessel connection: R ½ Only for use with Vitodens 333-F
Connection bend for condensate drain
Part no. 7461025
Connection line from the appliance: DN 20 Drain connection: DN 40
Neutralising system with wall mounting bracket
Part no. ZK03652
With neutralising granulate
200
300
361
61
61
131
Neutralising granulate
Part no. ZK03654
2.5 kg To match the neutralising system, part no. ZK03652
Condensate lifting system
Part no. ZK02486
Automatic condensate lifting system for condensate with a pH value ≥ 2.5 from gas condensing boilers
Components:
■ Condensate container 2.0 l
■ Centrifugal pump
■ Non-return valve
■ Connecting cable (1.5 m long) for fault messages
■ Power cable (1.5 m long) with plug
4 connection apertures 7 30 mm for condensate drain with con­nector 7 max. 40 mm)
Drain hose 7 10 mm (5 m long)
85
171
1500
279
84
108
204 262
A
130
B
A
Condensate drain
B
4 x condensate inlet with drain plug
Specification
Rated voltage 230 V~ Rated frequency 50 Hz Power consumption 70 W IP rating IP 20
Installation accessories
(cont.)
VITODENS
VIESMANN
29
5822431
4