Viessmann VITODENS 242-F, B2UA Installation And Service Instructions Manual

Page 1
Installation and service instructions
for contractors
VIESMANN
Vitodens 242-F Type B2UA, 3.2 to 26 kW
Gas condensing/solar storage combi boiler Gas council no. 41-819-18; 41-819-19 Natural gas and LPG version
For applicability, see the last page
VITODENS 242-F
5773 238 GB 4/2013
Please keep safe.
Page 2
2
Please follow these safety instructions closely to prevent accidents and mate­rial losses.
Safety instructions explained
Danger
This symbol warns against the risk of injury.
!
Please note
This symbol warns against the risk of material losses and envi­ronmental pollution.
Note
Details identified by the word "Note" con­tain additional information.
Target group
These instructions are exclusively inten­ded for qualified contractors.
■ Work on gas installations must only be carried out by a registered gas fitter.
■ Work on electrical equipment must only be carried out by a qualified elec­trician.
■ The system must be commissioned by the system installer or a qualified per­son authorised by the installer.
Regulations
Observe the following when working on this system:
■ Statutory regulations regarding the prevention of accidents
■ Statutory regulations regarding envi­ronmental protection
■ Codes of practice of the relevant trade associations
■ All current safety regulations as defined by DIN, EN, DVGW, TRGI, TRF, VDE and all locally applicable standards
■ Gas Safety (Installation & Use) Regu­lations – the appropriate Building Regulation either the Building regulations, the Building Regulation (Scotland), Build­ing Regulations (Northern Ireland), – the Water Fittings Regulation or Water Bylaws in Scotland, – the current I.E.E. Wiring Regula­tions.
If you smell gas
Danger
Escaping gas can lead to explo­sions which may result in serious injury.
■ Do not smoke. Prevent naked flames and sparks. Do not switch lights or electrical appli­ances on or off.
■ Close the gas shut-off valve.
■ Open windows and doors.
■ Evacuate any people from the danger zone.
■ Notify your gas or electricity supply utility from outside the building.
■ Shut off the electricity supply to the building from a safe place (outside the building).
Safety instructions
Safety instructions
5773 238 GB
Page 3
3
If you smell flue gas
Danger
Flue gas can lead to life-threat­ening poisoning.
■ Shut down the heating system.
■ Ventilate the installation site.
■ Close all doors in the living space.
Flue systems and combustion air
Ensure that flue systems are clear and cannot be sealed, for instance due to accumulation of condensate or other causes. Ensure a sufficient supply of combustion air. Instruct system users that subsequent modifications to the building characteris­tics are not permissible (e.g. cable/pipe­work routing, cladding or partitions).
Danger
Life-threatening poisoning caused by carbon monoxide in the flue gas occurs as a result of leaking or blocked flue systems or an insufficient supply of com­bustion air. Ensure the flue system is in proper working order. It must not be possible to close apertures for interconnected combustion air supply.
Extractors
Operating appliances that extract air to the outside (cooker hoods, extractors, air conditioning units, etc.) can create neg­ative pressure. If the boiler is operated at the same time, this can lead to reverse flow of the flue gas.
Danger
The simultaneous operation of the boiler and appliances that extract air to the outside can result in life threatening poison­ing due to reverse flow of the flue gas. Fit an interlock circuit or take suit­able steps to ensure a sufficient supply of combustion air.
Working on the system
■ Where gas is used as the fuel, close the main gas shut-off valve and safe­guard it against unintentional reopen­ing.
■ Isolate the system from the power sup­ply (e.g. by removing the separate fuse or by means of a mains isolator) and check that it is no longer 'live'.
■ Safeguard the system against recon­nection.
!
Please note
Electronic assemblies can be damaged by electrostatic dis­charge. Prior to commencing any work, touch earthed objects, such as heating or water pipes to dis­charge static loads.
Repair work
!
Please note
Repairing components that fulfil a safety function can compromise the safe operation of your sys­tem. Defective components must be replaced with genuine Viessmann spare parts.
Safety instructions
Safety instructions
(cont.)
5773 238 GB
Page 4
4
Auxiliary components, spare and wearing parts
!
Please note
Spare and wearing parts that have not been tested together with the system can compromise its function. Installing non-author­ised components and making non-approved modifications or conversions can compromise safety and may invalidate our warranty. For replacements, use only orig­inal spare parts supplied or approved by Viessmann.
Safety instructions
Safety instructions
(cont.)
5773 238 GB
Page 5
5
Installation instructions
Preparing for installation
Product information.............................................................................................. 7
Preparing the installation...................................................................................... 7
Installation sequence
Installing the boiler............................................................................................... 21
Opening the control unit casing............................................................................ 29
Electrical connections........................................................................................... 30
Closing the control unit casing............................................................................. 39
Fitting the front panels.......................................................................................... 41
Service instructions
Commissioning, inspection, maintenance
Steps - commissioning, inspection and maintenance.......................................... 42
Further details regarding the individual steps....................................................... 45
Code 1
Calling up coding level 1...................................................................................... 85
"General".............................................................................................................. 85
"Boiler" ................................................................................................................. 88
"DHW".................................................................................................................. 89
"Solar".................................................................................................................. 89
"Heating circuit ..."................................................................................................ 90
Code 2
Calling up coding level 2...................................................................................... 97
"General".............................................................................................................. 97
"Boiler".................................................................................................................. 105
"DHW".................................................................................................................. 106
"Solar".................................................................................................................. 108
"Heating circuit ..."................................................................................................ 110
Diagnosis and service scans
Service menu....................................................................................................... 119
Diagnosis.............................................................................................................. 120
Checking outputs (actuator test).......................................................................... 123
Troubleshooting
Fault display......................................................................................................... 124
Fault codes........................................................................................................... 125
Repair................................................................................................................... 137
Index
Index
5773 238 GB
Page 6
6
Function description
Control unit........................................................................................................... 151
Internal extensions (accessories)......................................................................... 153
External extensions (accessories)........................................................................ 156
Control functions.................................................................................................. 160
Allocating heating circuits to the remote control................................................... 168
Electronic combustion control unit........................................................................ 168
Designs
Internal connection diagram................................................................................. 170
External connection diagram................................................................................ 171
Connection diagram, solar control module........................................................... 173
Parts lists
Ordering individual parts...................................................................................... 174
Overview of the assemblies................................................................................. 175
Casing.................................................................................................................. 176
Hydraulics............................................................................................................. 178
Cylinder module................................................................................................... 181
Heat cell............................................................................................................... 186
Control unit........................................................................................................... 189
Miscellaneous....................................................................................................... 191
Commissioning/service reports........................................................................ 193
Specification....................................................................................................... 194
Certificates
Declaration of conformity...................................................................................... 195
Manufacturer's certificate according to the 1st BImSchV [Germany]................... 196
Keyword index.................................................................................................... 197
Index
Index
(cont.)
5773 238 GB
Page 7
7
Vitodens 242-F, type B2UA
Preset for operation with natural gas E and natural gas LL. For conversion to LPG P (without con­version kit), see page 53.
In principle the Vitodens 242-F may only be delivered to countries listed on the type plate. For deliveries to alternative countries, an approved contractor must arrange individual approval on his own initiative and in accordance with the law of the country in question.
Intended use
The appliance is only intended to be installed and operated in sealed unven­ted heating systems that comply with EN 12828, with due attention paid to the associated installation, service and operating instructions. It is only designed for the heating of water that is of potable water quality.
Intended usage presupposes that a fixed installation in conjunction with permissi­ble, system-specific components has been carried out.
Commercial or industrial usage for a pur­pose other than heating the building or DHW does not comply with regulations.
Any usage beyond this must be approved by the manufacturer for the individual case.
Incorrect usage or operation of the appli­ance (e.g. the appliance being opened by the system user) is prohibited and results in an exclusion of liability. Incor­rect usage also occurs if the components in the heating system are modified from their intended function (e.g. if the flue gas and ventilation air paths are sealed).
Preparing the installation
Handling
If possible, leave the boiler on the pallet during handling. If space constraints make it necessary, the boiler can be split for handling.
!
Please note
Prevent damage to the appliance during handling. Never set the boiler down on its front or sides, or apply any load to these surfaces.
Preparing for installation
Product information
5773 238 GB
Installation
Page 8
8
Dividing the boiler into sections
6.
7.
3.
5.
2.
1.
4. 2x
Preparing for installation
Preparing the installation
(cont.)
5773 238 GB
Page 9
9
8.
9.
4x
8x
12.
10.
11.
Preparing for installation
Preparing the installation
(cont.)
5773 238 GB
Installation
Page 10
10
13.
14.
15.
Preparing for installation
Preparing the installation
(cont.)
5773 238 GB
Page 11
11
16.
Preparing for installation
Preparing the installation
(cont.)
5773 238 GB
Installation
Page 12
12
sF
%
%
17.
19.
21.
20.
18.
Preparing for installation
Preparing the installation
(cont.)
5773 238 GB
Page 13
13
24.
22.
23.
Preparing for installation
Preparing the installation
(cont.)
5773 238 GB
Installation
Page 14
14
27.
26.
25.
Preparing for installation
Preparing the installation
(cont.)
5773 238 GB
Page 15
15
28.
2x
2x
29.
30.
Preparing for installation
Preparing the installation
(cont.)
5773 238 GB
Installation
Page 16
16
Siting
Required room height: at least 2100 mm
Preparing for boiler installation
Use a connection set, available as an accessory, to make the connection on the gas and water sides.
Fitting accessories
Fit all accessories that are installed at the back of the boiler (e.g. connection sets).
!
Please note
Avoid device damage. Connect all pipework free of load and torque stress.
Preparing the connections on site:
Connection set installation instructions.
Preparing for installation
Preparing the installation
(cont.)
5773 238 GB
Page 17
17
The following overview shows sample connection sets for installation on fin­ished walls, with connection to the top or side.
65
1930
2008
100
719
46
40
50
1367
1422
1477
1532
1587
1642
1697
1752
1807
1875
1900
1135
1100
140
60
320
370
436
449
A
H
A
H
B
D F
E G
C
G E
C
B
F D
M
K
K
L
Preparing for installation
Preparing the installation
(cont.)
5773 238 GB
Installation
Page 18
18
440
55
220
330
a
50
595
50
600
C
F
D
A B
E
G H
A
Solar return R¾
B
Heating flow R¾
C
DHW R½
D
Gas connection R½
E
DHW circulation R½ (separate accessory)
F
Cold water R½
G
Heating return R¾
H
Solar flow R¾
K
Condensate drain facing backwards into the wall
L
Condensate drain to the side
M
Wiring area
Rated heating output range 3.2 to 19 kW 6.5 to 26 kW
a (mm) 201 224
Note
All height dimensions have a tolerance of +15 mm due to the adjustable feet.
1. Prepare the heating water connec­tions. Thoroughly flush the heating sys­tem.
Note
Should an additional expansion ves­sel be required on site, connect this vessel in the heating return.
Preparing for installation
Preparing the installation
(cont.)
5773 238 GB
Page 19
19
2. Prepare the connections on the DHW
side. Install the safety assembly (accessory or on-site provision) in the cold water line in accordance with DIN 1988 and EN 806 (see page 20). Recommendation: Install the safety valve above the DHW cylinder to protect it against contamination, scaling and high tem­peratures.
3. Prepare the solar connections.
>200
O
N
N
Drain for DHW safety valve and/or siphon air vent valve
O
Condensate drain hose
4. Prepare the condensate connection to the on-site drain line or siphon:
■ Drain towards the back:
See dimensions for condensate hose O and position K in the dia­gram on page 17.
■ Drain towards the side aperture:
See position L in diagram on page 17.
5. Prepare the gas connection accord­ing to TRGI or TRF [or local regula­tions].
6. Prepare the electrical connections.
Power cable: NYM-J 3 x 1.5 mm2, max. fuse rating 16 A, 230 V/50 Hz.
■ Accessory cables: NYM with the
required number of cores for the external connections.
Allow all cables in area M in the diagram on page 18 to protrude 2000 mm from the wall.
Preparing for installation
Preparing the installation
(cont.)
5773 238 GB
Installation
Page 20
20
Safety assembly in accordance with DIN 1988 and EN 806 to the cold water connection
A
Safety assembly (accessory for the connection sets on unfinished walls)
B
Safety valve
C
Visible discharge pipe outlet point
D
Shut-off valve
E
Flow regulating valve (installation recommended)
F
Pressure gauge connection
G
Non-return valve
H
Drain
K
Cold water
L
Drinking water filter
M
Pressure reducer to DIN 1988-2, Dec. 1988 issue
N
Non-return valve/pipe separator
O
Cold water connection at connec­tion set (accessories)
Preparing for installation
Preparing the installation
(cont.)
5773 238 GB
Page 21
21
Removing the front panels
2.
4.
2x
1.
3.
5.
Installation sequence
Installing the boiler
5773 238 GB
Installation
Page 22
22
Siting and levelling the boiler
1.
2.
SW17
Installation sequence
Installing the boiler
(cont.)
5773 238 GB
Page 23
23
Connections on the heating water and the DHW side
A B
D E
E D
B A
A B D E
C
C
C
Shown with connection sets for finished walls (accessories)
A
Heating flow R¾
B
DHW R½
C
DHW circulation R½ (separate accessory)
D
Cold water R½
E
Heating return R¾
Installation sequence
Installing the boiler
(cont.)
5773 238 GB
Installation
Page 24
24
Connections on the solar side
B
A
A
B
A
B
Shown with connection sets for finished walls (accessories)
A
Solar return R¾ or Ø 22 mm, smooth pipe
B
Solar flow R¾ or Ø 22 mm, smooth pipe
Note
■ The following components are instal­led inside the appliance at the factory:
■ Circulation pump for the solar circuit.
■ Expansion vessel in the solar return.
■ Safety valve on the solar side.
Install the pressure gauge for the solar circuit on site.
Installation sequence
Installing the boiler
(cont.)
5773 238 GB
Page 25
25
Condensate connection
>200
O
N
1. If a DHW safety valve is connected, connect hose N to the safety valve drain.
Note
If no DHW safety valve is connected, do not change the position of hose
N
(serves as a vent).
2.
Route condensate hose O to the back (drain in wall K) or to side aper­ture L (see page 16).
Note
Pull the condensate hose far enough out of the boiler that no unnecessary bends are created inside the boiler.
3.
Route condensate hose M as a U­bend and connect with a constant fall and a pipe vent to the public sewage system or to a neutralising system. If necessary, connect to an on-site siphon. Ensure this connection is secure. GB only:
■ The condensate pipe is connected with the discharge pipe of the safety valve. The condensate hose supplied meets the temperature requirements that are part of the CE certification.
■ We recommend connecting the con­densate pipe internally to the domestic waste water system, either directly or via a tundish.
■ If the condensate pipe is routed out­side the building, use a pipe with min.
7
30 mm and protect this pipe from
frost. Avoid long external pipelines.
!
Please note
Frozen condensate pipes can result in faults and damage to the boiler. Always insulate condensate pipes against frost.
■ Observe local building regulations.
Observe the local waste water regula­tions.
Note
Fill the siphon with water before com­missioning.
Installation sequence
Installing the boiler
(cont.)
5773 238 GB
Installation
Page 26
26
Flue gas connection
Note
■ The labels "System certificate" and "Skoberne GmbH flue system" enclosed with the technical documen­tation may only be used in conjunction with the Viessmann flue system made by Skoberne.
■ During installation and positioning of the flue system, observe Part L and BS 5440 building regulations. (GB only)
Connecting the balanced flue
Flue system installation instruc­tions
Do not carry out commissioning until the following conditions are met:
■ Free passage through the flue gas pipes.
■ Flue system with positive pressure is gas-tight.
■ Apertures for ensuring sufficient com­bustion air supply are open and cannot be closed off.
■ Applicable regulations on installing and commissioning flue systems have been followed.
Danger
Leaking or blocked flue systems or an insufficient supply of com­bustion air cause life threatening poisoning due to carbon monox­ide in the flue gas. Ensure the flue system functions correctly. Apertures for combus­tion air supply must not be able to be closed off.
Installation sequence
Installing the boiler
(cont.)
5773 238 GB
Page 27
27
Gas connection
Shown with connection sets for finished walls (accessories)
A
Gas connection R½
Information on operation with LPG
We recommend the installation of an external safety solenoid valve when installing the boiler in rooms below ground level.
1. Secure gas shut-off valve to gas con­nection A.
2. Carry out a tightness test.
Note
Only use suitable and approved leak detection agents (EN 14291) and devices for the tightness test. Leak detection agents with unsuitable con­stituents (e.g. nitrites, sulphides) can cause material damage. Remove residues of the leak detec­tion agent after testing.
Installation sequence
Installing the boiler
(cont.)
5773 238 GB
Installation
Page 28
28
!
Please note
Excessive test pressure may damage the boiler and the gas valve. Max. test pressure 150 mbar (15 kPa). Where higher pres­sure is required for tightness tests, disconnect the boiler and the gas valves from the gas supply pipe (undo the fit­ting).
3. Vent the gas line.
For conversion to a different gas type see page 53
Installation sequence
Installing the boiler
(cont.)
5773 238 GB
Page 29
29
2x
4x
4.
3.
5.
2.
1.
Installation sequence
Opening the control unit casing
5773 238 GB
Installation
Page 30
30
!
Please note
Electronic assemblies can be damaged by electrostatic dis­charge.
Before beginning work, touch earthed objects, such as heating or water pipes, to discharge static loads.
L N
230V~
230V~
96
40
1LN
2 1
145
2
1
32 15 4
145
40962035100
21
A
B
A
Radio clock receiver
B
Jumper
Connections to 230 V~ plug
Power supply
lH
■ Power supply for accessories
■ External demand/blocking
Connections to LV plug
X3 Plug X3 can be removed to facili-
tate installation.
!
Outside temperature sensor
?
Flow temperature sensor for low loss header (accessories)
A
Radio clock receiver
aVG
KM BUS subscriber (accessories)
Installation sequence
Electrical connections
5773 238 GB
Page 31
31
To connect several accessories, see page 35.
■ Vitotrol 200A or 300A remote control
■ Vitocom 100, type GSM
■ Extension kit for one heating cir­cuit with mixer
■ Extension AM1
■ EA1 extension
■ Wireless base station
■ KM BUS distributor
Information on connecting accessories
When connecting accessories observe the separate installation instructions provided with them.
Outside temperature sensor
!
For fitting the wireless outside tempera­ture sensor (wireless accessory):
Wireless base station installation and service instructions
Fitting location for outside tempera­ture sensor
■ North or north-western wall, 2 to
2.5 m above ground level; in multi storey buildings, in the upper half of the second floor
■ Not above windows, doors or vents
■ Not immediately below balconies or gutters
■ Never render over
Outside temperature sensor connec­tion
2-core lead, length max. 35 m with a cross-section of 1.5 mm
2
Connecting the collector temperature sensor
Note
Solar control module C is secured to the l.h. side of the air box.
Installation sequence
Electrical connections
(cont.)
5773 238 GB
Installation
Page 32
32
B
% &aVG
C
A
D
Connect collector temperature sensor
A
to terminal box B with the prefitted lead of SM1 solar control module C. On-site extension cable D: 2-core, cross-section of 1.5 mm2.
Note
Cylinder temperature sensor % is con­nected at the factory.
External demand via switching contact
Connection options:
■ Extension EA1 (accessory, see sepa­rate installation instructions).
Plug lH.
Burner operation is load-dependent if the contact is closed. The boiler water is heated to the value set in coding address "9b" in group "General"/1. The boiler water temperature is limited by this set value and the electronic maximum limit (coding address "06" in group "Boiler"/
2).
!
Please note
'Live' contacts lead to short cir­cuits or phase failure. The external connection must be potential-free and comply with the requirements of safety cate­gory II.
Installation sequence
Electrical connections
(cont.)
5773 238 GB
Page 33
33
Plug lH
Extension EA1
A
lH
N
?
1
L
A
Floating contact (when connecting, remove jumper across L and 1)
B
[{S
DE
[{D
DE
[{A
DE
A
A
Floating contact
B
Extension EA1
Codes
■ "4b:1" in group "General"/1.
■ Effect of the function on the relevant heating circuit pump: Coding address "d7" in group "Heating circuit" (only with weather-compensa­ted control units).
■ Effect of the function on the circulation pump for cylinder heating (if installed): Coding address "5F" in group "DHW"/
3.
Codes
■ Set "3A" (DE1), "3b" (DE2) or "3C" (DE3) in group "General"/1 to 2.
■ Effect of the function on the relevant heating circuit pump: Coding address "d7" in group "Heating circuit" (only with weather-compensa­ted control units).
■ Effect of the function on the circulation pump for cylinder heating (if installed): Coding address "5F" in group "DHW"/
3.
External demand via 0 – 10 V input
Connection at 0 – 10 V input to exten­sion EA1.
Ensure DC separation between the earth conductor and the negative pole of the on-site voltage source.
Installation sequence
Electrical connections
(cont.)
5773 238 GB
Installation
Page 34
34
L
?
N
L
?
N
S
P
aBJ
230 V~
Ö
[{{]
0-10V
f-]
A
U
0-10 V
+
+
-
0 – 1 V
No default set boiler water temperature
1 V
Set value 10 °C
10 V
Set value 100 °C
External blocking via switching contact
Connection options:
Plug lH.
■ Extension EA1 (accessory, see sepa­rate installation instructions).
The burner is switched off if this contact is closed. The heating circuit pump and (if installed) the circulation pump for cyl­inder heating are switched according to the set code (see following table "Codes").
!
Please note
'Live' contacts lead to short cir­cuits or phase failure. The external connection must be potential-free and comply with the requirements of safety cate­gory II.
Installation sequence
Electrical connections
(cont.)
5773 238 GB
Page 35
35
Plug lH
Extension EA1
A
lH
N
?
1
L
A
Floating contact (when connecting, remove jumper across L and 1)
B
[{SDE[{D
DE
[{A
DE
A
A
Floating contact
B
Extension EA1
Codes
■ "4b:2" in group "General"/1
■ Effect of the function on the heating cir­cuit pump: Coding address "d6" in group "Heating circuit" (only with weather-compensa­ted control units).
■ Effect of the function on the circulation pump for cylinder heating (if installed): Coding address "5E" in group "DHW"/
3.
Codes
■ Set "3A" (DE1), "3b" (DE2) or "3C" (DE3) in group "General"/1 to 3 or 4.
■ Effect of the function on the heating cir­cuit pump: Coding address "d6" in group "Heating circuit" (only with weather-compensa­ted control units).
■ Effect of the function on the circulation pump for cylinder heating (if installed): Coding address "5E" in group "DHW"/
3.
Power supply for accessories at plug lH (230 V~)
Where the boiler is installed in a wet area, the power supply connection for accessories must not be made at the control unit. If the boiler is installed out­side wet areas, then the power supply connection for accessories can be made directly at the control unit. This connec­tion is switched directly with the ON/OFF switch of the control unit.
If the total system current exceeds 6 A, connect one or more extensions via an ON/OFF switch directly to the mains sup­ply (see next chapter).
Installation sequence
Electrical connections
(cont.)
5773 238 GB
Installation
Page 36
36
Power supply to all accessories via heat source control unit
145
145
40 A
40
145
145
40 A
40
B C
145
40
96
A
145
145
40 A
40
D
E
Some accessories with direct power supply
145
145
40 A
40
145
145
40 A
40
B C
145
40
96
A
145
145
40 A
40
D
E
A
Heat source control unit
B
Extension kit for heating circuit with mixer M2
C
Extension kit for heating circuit with mixer M3
D
Extensions AM1 or EA1
E
ON/OFF switch
The output concerned should only be used to control an on-site relay if the cur­rent flowing to the connected working parts (e.g. circulation pumps) is higher than the safety level of the relevant accessory.
Accessories Internal fuse
protection
Extension kit for heat­ing circuit with mixer
2 A
Extension AM1 4 A Extension EA1 2 A
Installation sequence
Electrical connections
(cont.)
5773 238 GB
Page 37
37
Power supply
Danger
Incorrect core allocation can result in serious injury and dam­age to the appliance. Take care not to interchange wires "L1" and "N".
Remove existing wires from plug .
■ Install an isolator in the power cable which simultaneously separates all non-earthed conductors from the mains with contact separation of at least 3 mm. In addition, we recommend the instal­lation of an AC/DC-sensitive RCD (RCD class B ) for DC (fault) currents that can be created by energy efficient equipment.
■ Max. fuse rating 16 A.
Installation sequence
Electrical connections
(cont.)
5773 238 GB
Installation
Page 38
38
Routing the connecting cables
!
Please note
Connecting cables will be dam­aged if they touch hot compo­nents.
When routing and securing cables/leads on site, ensure that the maximum permissible tem­peratures for these cables/leads are not exceeded.
A
LV connections
B
230 V connections
C
Internal extension
D
Main PCB
E
Communication module (accesso­ries)
F
Cable grommet for power cable
Installation sequence
Electrical connections
(cont.)
5773 238 GB
Page 39
39
5.
4.
2.
6.
2x
3.
1.
Installation sequence
Closing the control unit casing
5773 238 GB
Installation
Page 40
40
Insert programming unit (packed sepa­rately) into the control unit support.
Note
The programming unit can also be inser­ted into a wall mounting base (accesso­ries) near the boiler.
Wall mounting base installation instructions
Installation sequence
Closing the control unit casing
(cont.)
5773 238 GB
Page 41
41
2x
1.
4.
2.
3.
5.
Installation sequence
Fitting the front panels
5773 238 GB
Installation
Page 42
42
For further information regarding the individual steps, see the page indicated
Commissioning steps
Inspection steps
Maintenance steps Page
1. Removing the front panels............................................ 45
2. Checking the power supply
3. Filling the heating system.............................................. 45
4. Filling the cylinder on the DHW side............................ 47
5. Switching on the power supply and ON/OFF switch
6. Changing the language.................................................. 47
7. Setting the time and date............................................... 47
8. Note on automatic testing of the flue gas temperature
sensor.............................................................................. 48
9. Venting the boiler........................................................... 48
10. Venting the heating system........................................... 49
11. Filling the siphon with water......................................... 50
12. Filling the solar circuit................................................... 51
13. Checking all connections on the heating water side and DHW side for leaks
14. Designating the heating circuits................................... 52
15. Checking the gas type.................................................... 52
16. Gas type conversion (only for operation with LPG).... 53
17. Checking the static and supply pressure..................... 53
18. Function sequence and possible faults....................... 55
19. Setting the max. heating output.................................... 57
20. Tightness test, balanced flue system (annular gap
check).............................................................................. 58
21. Burner removal............................................................... 59
22. Checking the burner gasket and burner gauze
assembly......................................................................... 60
Commissioning, inspection, maintenance
Steps - commissioning, inspection and maintenance
5773 238 GB
Page 43
43
Commissioning steps
Inspection steps
Maintenance steps Page
23. Checking and adjusting the ignition and ionisation
electrodes........................................................................ 61
24. Cleaning the heating surfaces....................................... 61
25. Checking the condensate drain and cleaning the
siphon.............................................................................. 62
26. Installing the burner....................................................... 63
27. Checking the neutralising system (if installed)
28. Checking the anode connection................................... 64
29. Testing the anode earth current with an anode tester 65
30. Draining the boiler on the DHW side............................ 66
31. Cleaning the primary store............................................ 67
32. Checking and replacing the magnesium anode (if
required).......................................................................... 68
33. Re-assembling and filling the primary store................ 68
34. Checking the diaphragm expansion vessel and
system pressure............................................................. 69
35. Checking the pre-charge pressure and the DHW
expansion vessel (if installed)....................................... 70
36. Checking the function of safety valves
37. Checking firm seating of electrical connections
38. Checking all gas equipment for tightness at operating
pressure........................................................................... 70
39. Checking the combustion quality................................. 71
40. Checking the flue system for unrestricted flow and tightness
41. Checking the external LPG safety valve (if installed)
42. Matching the control unit to the heating system......... 72
43. Adjusting the heating curves........................................ 78
44. Connecting the control unit to the LON....................... 81
Commissioning, inspection, maintenance
Steps - commissioning, inspection and maintenance
5773 238 GB
Service
Page 44
44
Commissioning steps
Inspection steps
Maintenance steps Page
45. Scanning and resetting the "Service" display............. 83
46. Fitting the cover panel and front panels...................... 83
47. Instructing the system user........................................... 84
Commissioning, inspection, maintenance
Steps - commissioning, inspection and…
(cont.)
5773 238 GB
Page 45
45
Removing the front panels
See page 21.
Filling the heating system
Fill water
!
Please note
Unsuitable fill water increases the level of deposits and corro­sion and may lead to boiler dam­age.
■ Flush the heating system thor­oughly before filling.
■ Only use fill water of potable quality.
■ An antifreeze additive suitable for heating systems can be added to the fill water. The anti­freeze manufacturer must ver­ify its suitability.
■ Fill and top-up water with a water hardness in excess of the following values must be softened, e.g. with a small soft­ening system for heating water.
Total permissible hardness of the fill and top-up water Total heating output
Specific system volume (Conversion rate 1 mol/m3 = 100 ppm)
kW < 20 l/kW ≥ 20 l/kW to
< 50 l/kW
≥ 50 l/kW
≤ 50
≤ 3.0 mol/m
3
≤ 2.0 mol/m
3
< 0.02 mol/m
3
> 50 to ≤ 200
≤ 2.0 mol/m
3
≤ 1.5 mol/m
3
< 0.02 mol/m
3
> 200 to ≤ 600
≤ 1.5 mol/m
3
≤ 0.02 mol/m
3
< 0.02 mol/m
3
> 600
< 0.02 mol/m
3
< 0.02 mol/m
3
< 0.02 mol/m
3
Conversion rate 1 mol/m3 = 100ppm
Commissioning, inspection, maintenance
Further details regarding the individual steps
5773 238 GB
Service
Page 46
46
A
B
Shown with connection set for finished walls (accessories)
1. Check the pre-charge pressure of the diaphragm expansion vessel. See page 69.
2. Close the gas shut-off valve.
3.
Open shut-off valves B on the heat­ing water side.
4. Fill the heating system via boiler drain & fill valve A in the heating return (depending on the connection set either on the side or above the boiler).
■ Minimum system pressure
> 1.0 bar (0.1 MPa).
■ Permissible operating pressure
3.0 bar (0.3 MPa).
Note
If the control unit has not been switched on prior to filling the system, then the servomotor of the diverter valve will still be in its central position, and the system will be completely fil­led.
5. If the control unit had already been switched on before filling began: Switch control unit ON and activate fill program (see next chapter).
Note
If the control unit has not been switched on prior to filling the system, then the servomotor of the diverter valve will still be in its central position, and the system will be completely fil­led.
6.
Close boiler drain & fill valve A.
Activating the filling function
Service menu
1. Press OK and å simultaneously for
approx. 4 s.
2. "Service functions"
3. "Filling"
Filling function is enabled.
4. Ending filling function:
Press OK or ä.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Page 47
47
Filling the cylinder on the DHW side
1.
Lever on valve B must be in the "left" position.
2. Open on-site DHW supply and a DHW draw-off point.
3. Once air stops coming out of the DHW draw-off point, the DHW cylin­der is completely filled.
Changing the language
At the commissioning stage, the display is in German (factory setting).
Extended menu:
1. å
2. "Einstellungen"
3. "Sprache"
4. Select the required language with / .
Sprache
Dansk
Cesky
Bulgarski
Deutsch
Wählen mit
ê
ê
ç
DE
BG CZ DK
ê
ê
(
Setting the time and date
The time and date need to be reset dur­ing commissioning or after a prolonged time out of use.
Extended menu:
1. å
2. "Settings"
3. "Time / Date"
4. Set current time and date.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Service
Page 48
48
Note on automatic testing of the flue gas temperature sensor
As soon as the time and date have been set, the control unit automatically checks the function of the flue gas temperature sensor. The display shows: "Flue gas temp sensor test" and "Active".
Note
If the flue gas temperature sensor is incorrectly positioned, commissioning will be cancelled and fault message A3 will be shown (see page 145).
Venting the boiler
A
C
B
1. Close the shut-off valves on the heat­ing water side.
2.
Remove cover panel A.
3. Push the drain hose onto air vent valve B and connect to a drain.
4.
Open air vent valve B and fill valve C
in the heating return and vent using mains pressure (flush) until no more air noise can be heard.
5.
First close air vent valve B.
6. When the required operating pres­sure has built up, close fill valve C. Open the shut-off valves on the heat­ing water side.
7. Remove drain hose from air vent valve B and retain.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Page 49
49
Venting the heating system
A
1. Close the gas shut-off valve and switch the control unit ON.
2. Check whether the air vent screw in quick-action air vent valve A of the heating circuit pump is open.
3. Activate venting program (see next chapter).
Note
For function and sequence of the venting program, see page 162.
4. Check the system pressure.
5. Open the gas shut-off valve.
Activating the venting function
Service menu
1. Press OK and å simultaneously for
approx. 4 s.
2. "Service functions"
3. "Venting" Venting function is enabled.
4. Ending venting function: Press OK or ä.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Service
Page 50
50
Filling the siphon with water
A
B
C
1. Pivot control unit forward.
2.
Remove retaining clip A.
3.
Pull filler pipe B upwards.
4.
Remove trap C downwards.
5. Fill siphon with water and refit.
6. Check that the condensate pipe is
connected correctly to the siphon and heat exchanger.
Note
Route the drain hose without any bends and with a constant fall.
7. Refit cover panel.
8. Secure control unit back into the
operating position.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Page 51
51
Filling the solar circuit
Solar thermal system installation and service instructions
A
Solar circuit fill valve
!
Please note
Overheated collector areas and overheated heat transfer medium can cause burns/scalding and equipment damage. When working on the collector and the solar circuit, protect the collector area against solar irra­diation.
1. Thoroughly flush the on-site pipe­work.
2. Fill solar circuit with "Tyfocor LS" via fill valve A.
■ Minimum system pressure: 1.7 bar
(0.17 MPa)
■ Permissible operating pressure:
6 bar (0.6 MPa)
!
Please note
To prevent appliance dam­age, only use "Tyfocor LS". Never fill with water.
3.
Close ball valve in fill valve A.
4. Open the air vent valve at the solar collector.
5. Start the solar circuit pump via the actuator test (see page 123).
6. Let the solar circuit pump run until the solar circuit is fully vented. If the sys­tem pressure is below 1.7 bar (0.17 MPa), add more "Tyfocor LS".
7. Close the air vent valve at the solar collector.
8. Check system pressure. If the system pressure is below 1.7 bar (0.17 MPa), add more "Tyfocor LS".
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Service
Page 52
52
Designating the heating circuits
In the delivered condition, the heating circuits are designated "Heating circuit
1", "Heating circuit 2" and "Heating circuit 3" (if installed).
If the system user prefers, the heating circuits can be designated differently to suit the specific system.
Enter names for heating cir­cuits:
Operating instructions
Checking the gas type
The boiler is equipped with an electronic combustion controller that adjusts the burner for optimum combustion in accordance with the prevailing gas qual­ity.
■ For operation with natural gas no adjustment is therefore required across the entire Wobbe index range. The boiler can be operated in the Wobbe index range 9.5 to
15.2 kWh/m3 (34.2 to 54.7 MJ/m3).
■ For operation with LPG the burner must be converted (see "Gas type conversion" on page 53).
1. Determine the gas type and Wobbe index by asking your local gas supply utility or LPG supplier.
2. For operation with LPG, convert the burner (see page 53).
3. Record the gas type in the report on page 193.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Page 53
53
Gas type conversion (only for operation with LPG)
1
2
A
1.
Set adjusting screw A on the gas train to "2".
2.
Turn on ON/OFF switch .
3. Select the gas type in coding address "82":
■ Call up code 2
"General"
■ Select coding address "11" and
value "9". Confirm with OK. The display shows "11:0".
■ Select coding address "82" and
value "1" (LPG operation). Confirm with OK.
■ Select coding address "11" and
value ≠ "9". Confirm with OK. The display shows "11:0".
■ End service functions.
4. Open the gas shut-off valve.
5. Affix label "G31" (supplied with the
technical documentation) adjacent to the type plate on the cover panel.
Checking the static and supply pressure
Danger
CO build-up as a result of incor­rect burner adjustment can have serious health implications. Carry out a CO test before and after work on gas appliances.
Operation with LPG
Flush the LPG tank twice during com­missioning or replacement. Vent the tank and gas connection line thoroughly after flushing.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Service
Page 54
54
A
1. Close the gas shut-off valve.
2. Loosen the screw inside test connec-
tor "PE" A at the gas train but do not remove it; then connect the pressure gauge.
3. Open the gas shut-off valve.
4. Check the static pressure and record
the actual value in the report on page 193. Set value: max. 57.5 mbar (5.75 kPa).
5. Start the boiler.
Note
During commissioning, the boiler can enter a fault state (fault EE is dis­played) because of air in the gas line. After approx. 5 s, press reset button R (see operating instructions) to reset the burner.
6. Check the supply (flow) pressure.
Set value:
■ Natural gas: 20 mbar (2.0 kPa)
■ LPG: 50 mbar (5.0 kPa)
Note
Use a suitable measuring device with a resolution of at least 0.1 mbar (0.01 kPa) to check the supply pres­sure.
7. Record the actual value in the report on page 193. Take action as shown in the following table.
8. Shut down the boiler, close the gas shut-off valve, remove the pressure gauge and tighten the screw in test connector A.
9. Open the gas shut-off valve and start the appliance.
Danger
Gas escaping from the test nipple leads to a risk of explo­sion. Check gas tightness at test connector A.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Page 55
55
Supply pressure (flow pressure) Action For natural gas For LPG
Below 17.4 mbar (1.74 kPa)
Below 42.5 mbar (4.25 kPa)
Do not start the boiler. Notify your gas supply utility or LPG supplier.
17.4 to 25 mbar (1.74 to 2.5 kPa)
42.5 to 57.5 mbar (4.25 to 5.75 kPa)
Start the boiler.
Above 25 mbar (2.5 kPa)
Above 57.5 mbar (5.75 kPa)
Install a separate gas pressure governor upstream of the system and regulate the pre-charge pressure to 20 mbar (2.0 kPa) for natural gas or 50 mbar (5.0 kPa) for LPG. Notify your gas supply utility or LPG supplier.
Function sequence and possible faults
Display Action
Control unit is­sues a heat de­mand
No
Increase set value and ensure heat is drawn off
Yes
Fan starts
No
After approx. 51 s, fault F9
Check the fan, fan connecting cables, power at the fan and fan control
Yes
Ignition
No
Fault EE
Check ignition module (control voltage 230 V across plugs "X2.1" and "X2.2"). Check the gas sup­ply.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Service
Page 56
56
Yes
Gas train opens
No
Fault EE
Check the gas train (control voltage 230 V) and gas supply pressure
Yes
Ionisation current builds Symbol
A
No
Fault EE
Check the ionisa­tion electrode ad­justment and the gas line for air­locks.
Yes
Burner in opera­tion
No
Stops below the set boiler water temperature and restarts immedi­ately
Check the flue sys­tem for tightness (flue gas recircula­tion); check the gas flow pressure
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Page 57
57
Yes
Automatic calibra­tion of the com­bustion controller
No
Fault E3
Ensure adequate heat transfer. Press reset button R.
Fault Eb Check gap be-
tween ionisation electrode and burner gauze as­sembly. Check allocation of gas type (coding address 82, gas train setting). Check flue system; remedy flue gas re­circulation if re­quired. Press reset button R.
For further details regarding faults, see page 124.
Setting the max. heating output
The maximum output for heating oper­ation can be limited. The limit is set via
the modulation range. The max. adjust­able output is limited upwards by the boiler coding card.
Service menu
1. Press OK and å simultaneously for
approx. 4 s.
2. "Service functions"
3. "Max. output"
4. "Change?" Select "Yes". A value is shown on the display (e.g. "85"). In the delivered condition, this value represents 100 % of rated heat­ing output.
5. Set the required value.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Service
Page 58
58
Tightness test, balanced flue system (annular gap check)
A
Combustion air aperture (ventilation air)
For balanced flue systems tested together with the wall mounted gas fired boiler, the requirement for a tightness test during commissioning by the flue gas inspector is not applicable.
We recommend that your heating engi­neer carries out a simple leak/tightness test during the commissioning of your system. For this, it would be sufficient to check the CO2 or O2 concentration in the
combustion air at the annular gap of the balanced flue pipe. The flue pipe is deemed to be gas-tight if the CO2 concentration in the combus-
tion air is no higher than 0.2 % or the O2 concentration is at least 20.6 %.
If actual CO2 values are higher or O2 val­ues are lower, then pressure test the flue
pipe with a static pressure of 200 Pa.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Page 59
59
Burner removal
G
B
D
C
E
4x
FF
A
1. Switch OFF the power supply and the ON/OFF switch at the control unit.
2. Close the gas shut-off valve and safe­guard against reopening.
3.
Remove cables from fan motor A, gas train B, ignition and ionisation electrode C, ignition unit D and earth tab E.
4.
Undo gas supply pipe fitting F.
5.
Undo four screws G and remove the burner.
!
Please note
Prevent damage to the burner. Never rest the burner on the burner gauze assembly.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Service
Page 60
60
Checking the burner gasket and burner gauze assembly
Check burner gasket A and burner gauze assembly E for possible damage and replace if required.
A
C
2x
2x
B
D
E
F
1.
Remove electrodes B.
2.
Undo two retaining clips C on ther­mal insulation ring D and then remove thermal insulation ring D.
3. Undo two Torx screws and remove burner gauze assembly E with gas­ket F.
4. Insert new burner gauze assembly
E
with new gasket F and secure.
Torque: 5.0 Nm.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Page 61
61
5.
Fit thermal insulation ring D.
6.
Fit electrodes B. Torque: 4.5 Nm.
Checking and adjusting the ignition and ionisation electrodes
6
+2
0
4
+0,5
0
10
±1
A
A B
A
Ignition electrodes
B
Ionisation electrode
1. Check the electrodes for wear and contamination.
2. Clean the electrodes with a small brush (not with a wire brush) or sand­paper.
3. Check the electrode gaps. If the gaps are not as specified or the electrodes are damaged, replace the electrodes together with new gaskets and adjust them as required. Tighten the elec­trode fixing screws with 4.5 Nm.
Cleaning the heating surfaces
!
Please note
There should be no scratches or other damage on the heat exchanger surface that comes into contact with hot gases. This could lead to corrosion damage.
Never use brushes to clean the heating surfaces.
Brushing can cause existing deposits to get stuck in the coil gaps.
Note
Discolouration of the heat exchanger surface is a normal sign of usage. It has no impact on the function and service life of the heat exchanger. The use of chemical cleaning agents is not necessary.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Service
Page 62
62
A
1. Use a vacuum cleaner to remove deposits from heating surfaces A of the heat exchanger.
2. If required, rinse heating surfaces
A
with water.
3. Check condensate drain and clean siphon. See the following chapter.
Checking the condensate drain and cleaning the siphon
A
B
C
Flue gas cascade:
Clean the siphon in the flue gas header as well.
1. Check at the siphon that the conden­sate can drain freely.
2.
Remove retaining clip A.
3.
Pull filler pipe B upwards.
4.
Remove trap C downwards.
5. Remove the condensate hose from trap C.
6. Clean the siphon.
7. Fill siphon with water and reassemble
with retaining clip A.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Page 63
63
8. Check that the condensate pipe is
connected correctly to the siphon and heat exchanger.
Note
Route the drain hose without any bends and with a constant fall.
Installing the burner
G
B
D
C
E
4x
FF
A
1. Install the burner and tighten screws
G
diagonally with 8.5 Nm.
2.
Fit gas supply pipe F with a new gasket.
3. Check the gas connections for tight­ness.
Danger
Escaping gas leads to a risk of
explosion. Check all fittings for gas tight­ness.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Service
Page 64
64
4.
Connect cables from fan motor A, gas train B, ionisation electrode
C
, ignition unit D and earth tab
E
.
Checking the anode connection
Check that the earth cable is connected to the magnesium anode.
1.
2.
A
Magnesium anode
B
Earth cable
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Page 65
65
Testing the anode earth current with an anode tester
Note
We recommend that the magnesium anode function is checked annually. This function test can be carried out without interrupting operation, by measuring the earth current with an anode tester.
1.
Remove cover A.
2.
Remove earth cable B from tab C
.
3. Connect tester (up to 5 mA ) in series between tab C and earth cable B.
■ If the current measures > 0.3 mA
the anode is OK.
■ If the current measures < 0.3 mA or
if there is no current at all, inspect the anode visually (see page 68).
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Service
Page 66
66
Draining the boiler on the DHW side
1. Connect hose to drain valve and
route into a suitable container or drain outlet.
Note
Ensure adequate ventilation in the DHW pipework.
2. Turn drain valve from lever position
A
to lever position B or C as
required.
Lever position B: To drain the heating system but not the cylinder via the cold water connection.
Lever position C: To drain the heating system and the cylinder via the hot water connection. Cold water connection remains filled.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Page 67
67
Cleaning the primary store
Note
According to EN 806, a visual inspection and (if necessary) cleaning must be car­ried out no later than two years after commissioning and thereafter as required.
2.
1. Drain the primary store.
2.
Remove flange cover A.
3. Disconnect the primary store from the pipework to prevent contamination from entering the pipe system.
4. Remove loose deposits with a high pressure cleaner.
!
Please note
When cleaning the inside, only use plastic cleaning uten-
sils.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Service
Page 68
68
5. Use a chemical cleaning agent to
remove hard deposits that cannot be removed by a high pressure cleaner.
!
Please note
Never use hydrochloric acid based cleaning agents.
6. Thoroughly flush the primary store after cleaning.
Checking and replacing the magnesium anode (if required)
Check the magnesium anode. If the anode has degraded to between 10 and 15 mm Ø, we recommend replacing the magnesium anode.
Re-assembling and filling the primary store
2.
1. Reconnect the primary store to the pipework.
2.
Insert new gasket A underneath flange cover B.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Page 69
69
3.
Fit flange cover B and tighten eight screws D with a maximum torque of 25 Nm.
4.
Push earth cable C onto the tab.
5.
Fit cover E.
6. Fill the primary store with potable water.
Checking the diaphragm expansion vessel and system pressure
A
Note
(GB only) The diaphragm expansion vessel can lose some charge pressure over a time in use. When the boiler heats up, the pressure gauge will indicate a higher pressure of 2 or 3 bar (0.2 or
0.3 MPa). The safety valve too can respond and discharge excess pres­sure.
Check whether the installed diaphragm expansion vessel is adequate for the system water volume. (GB only)
Note
Carry out this test on a cold system.
1. Drain the system until the pressure gauge shows "0".
2. If the diaphragm expansion vessel pre-charge pressure is lower than the static system pressure: Top up with nitrogen at connection A until the pre-charge pressure is 0.1 to 0.2 bar (10 to 20 kPa) higher than the static system pressure.
3. Top up with water until the charge pressure of the cooled system is 0.1 to 0.2 bar (10 to 20 kPa) higher than the pre-charge pressure of the dia­phragm expansion vessel. Permiss. operating pressure: 3 bar (300 kPa).
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Service
Page 70
70
Checking the pre-charge pressure and the DHW expansion ves­sel (if installed)
A
1. Check the static pressure of the DHW line downstream of the pressure reducer and adjust if required. Set value: max. 3.0 bar (0.3 MPa).
2. Close the on-site shut-off valve in the cold water line.
3.
Turn operating lever of valve A to the "front" position.
4. Check the pre-charge pressure of the DHW expansion vessel and adjust if required. Set value: Static pressure minus 0.2 bar (0.02 MPa).
5.
Turn operating lever of valve A back to the "left" position and open the on­site shut-off valve in the cold water line.
Checking all gas equipment for tightness at operating pressure
Danger
Escaping gas leads to a risk of explosion. Check all gas equipment for tight­ness.
Note
Only use suitable and approved leak detection agents (EN 14291) and devi­ces for the tightness test. Leak detection agents with unsuitable constituents (e.g. nitrites, sulphides) can cause mate­rial damage. Remove residues of the leak detection agent after testing.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Page 71
71
Checking the combustion quality
The electronic combustion controller automatically ensures optimum combus­tion quality. During commissioning/ maintenance, only the combustion val­ues need to be checked. For this, meas­ure the CO content and the CO2 or O
2
content. For a description of the elec­tronic combustion controller functions, see page 168.
Note
Operate the appliance with uncontami­nated combustion air to prevent operat­ing faults and damage.
CO content
■ The CO content must be < 1000 ppm for all gas types.
CO2 or O2 content
■ The CO2 content must be within the following limits for upper and lower
heating output respectively: – 7.5 to 9.5 % for natural gas E and LL – 8.8 to 11.1 % for LPG P
■ For all gas types, the O2 content must be between 4.0 and 7.6 %.
If the actual CO2 or O2 values lie outside their respective ranges, proceed as fol-
lows:
■ Check the balanced flue system for tightness, see page 58.
■ Check the ionisation electrode and connecting cable, see page 61.
Note
During commissioning, the combustion controller carries out an automatic cali­bration. Only test the emissions approx. 30 s after the burner has started.
1. Connect a flue gas analyser at flue gas port A on the boiler flue con­nection.
2. Open the gas shut-off valve, start the boiler and create a heat demand.
3. Set the lower heating output (see page 72).
4. Check the CO2 content. Should the actual value deviate from the afore-
mentioned ranges by more than 1 %, implement steps on page 71.
5. Enter the actual values into the report.
6. Set the upper heating output (see page 72).
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Service
Page 72
72
7. Check the CO2 content. Should the
actual value deviate from the afore­mentioned ranges by more than 1 %, implement steps on page 71.
8. After testing, press OK.
9. Enter the actual values into the
report.
Select higher/lower heating output
Service menu
1. Press OK and å simultaneously for
approx. 4 s.
2. "Actuator test"
3. Select the lower heating output: Select "Base load OFF". Then "Base load ON" appears and the burner operates at its lower heating output.
4. Select the upper heating output: Select "Full load OFF". Then "Full load ON" appears and the burner operates at its upper heating output.
5. Ending output selection: Press ä.
Matching the control unit to the heating system
The control unit must be adjusted subject to the system equipment level.
■ To do this, select the relevant system scheme (see the following diagrams).
■ Set the codes in conjunction with the accessories fitted.
Accessories installation and service instructions
Note
Various system components are auto­matically recognised by the control unit and the codes are automatically adjus­ted. For individual coding steps, see page 85.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Page 73
73
System version 1
One heating circuit without mixer A1
3
1
2
wP
wQ
1
Vitodens 242-F
2
Outside temperature sensor
3
Heating circuit without mixer A1
wP
Solar collectors
wQ
Collector temperature sensor
Function/system components Code
Adjust Group
Operation with LPG 82:1 "General" System with DHW circulation pump: DHW circulation pump connected at internal exten­sion H1 or H2
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Service
Page 74
74
System version 2
One heating circuit with mixer M2 and a low loss header
1
M
3
4 5
6
7
2
9
8
wP
wQ
1
Vitodens 242-F
2
Outside temperature sensor
3
Heating circuit with mixer M2
4
Temperature limiter to restrict the maximum temperature of underfloor heating systems
5
Flow temperature sensor M2
6
Heating circuit pump M2
7
Extension kit for one heating circuit with mixer M2
8
Low loss header
9
Flow temperature sensor, low loss header
wP
Solar collectors
wQ
Collector temperature sensor
Function/system components Code
Adjust Group
Operation with LPG 82:1 "General" System with only one heating circuit with mixer, with extension kit for mixer with DHW heating
00:4 "General"
System with DHW circulation pump: DHW circulation pump connected at internal exten­sion H1 or H2
System with low loss header 04:0 "Boiler"
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Page 75
75
System version 3
One heating circuit without mixer A1 and one heating circuit with mixer M2
1
M
3 4
5 6
7
8
2
wP
wQ
1
Vitodens 242-F
2
Outside temperature sensor
3
Heating circuit without mixer A1
4
Heating circuit with mixer M2
5
Temperature limiter to restrict the maximum temperature of underfloor heating systems
6
Flow temperature sensor M2
7
Heating circuit pump M2
8
Extension kit for one heating circuit with mixer M2
wP
Solar collectors
wQ
Collector temperature sensor
Note
The flow rate of the heating circuit with­out mixer must be at least 30 % greater than the flow rate of the heating circuit with mixer.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Service
Page 76
76
Function/system components Code
Adjust Group
Operation with LPG 82:1 "General" System with only one heating circuit with mixer, with extension kit for mixer with DHW heating
00:4 "General"
System with DHW circulation pump: DHW circulation pump connected at internal exten­sion H1 or H2
System version 4
One heating circuit without mixer A1, one heating circuit with mixer M2 and system separation
1
2
3
4
5
7
6
9
M
8
wP
wQ
1
Vitodens 242-F
2
Outside temperature sensor
3
Heating circuit without mixer A1
4
Heating circuit with mixer M2
5
Temperature limiter to restrict the maximum temperature of underfloor heating systems
6
Flow temperature sensor M2
7
Heating circuit pump M2
8
Extension kit for one heating circuit with mixer M2
9
Heat exchanger for system separa­tion
wP
Solar collectors
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Page 77
77
wQ
Collector temperature sensor
Function/system components Code
Adjust Group
Operation with LPG 82:1 "General" System with only one heating circuit with mixer, with extension kit for mixer with DHW heating
00:4 "General"
System with DHW circulation pump: DHW circulation pump connected at internal exten­sion H1 or H2
System version 5
One heating circuit without mixer A1, one heating circuit with mixer M2 (with extension kit), one heating circuit with mixer M3 (with extension kit) and low loss header (with/without DHW heating)
M M
1
qT
8
7
6
5
9
qP
qQ
qW
qE
qR
2
wP
wQ
4
3
1
Vitodens 242-F
2
Outside temperature sensor
3
Heating circuit without mixer A1 (heating circuit 1)
4
Heating circuit pump A1
5
Heating circuit with mixer M2 (heat­ing circuit 2)
6
Flow temperature sensor M2
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Service
Page 78
78
7
Heating circuit pump M2
8
Extension kit for one heating circuit with mixer M2
9
Heating circuit with mixer M3 (heat­ing circuit 3)
qP
Temperature limiter to restrict the maximum temperature of underfloor heating systems
qQ
Flow temperature sensor M3
qW
Heating circuit pump M3
qE
Extension kit for one heating circuit with mixer M3
qR
Low loss header
qT
Flow temperature sensor, low loss header
wP
Solar collectors
wQ
Collector temperature sensor
Function/system components Code
Adjust Group
Operation with LPG 82:1 "General" System with only two heating circuits with mixer, with extension kit for mixer (without unregulated heating circuit) with DHW heating
00:8 "General"
System without DHW circulation pump: Heating circuit pump A1 connected at internal exten­sion H1 or H2
53:2
System with DHW circulation pump: Heating circuit pump A1 connected at extension AM1, terminal A1
DHW circulation pump connected at extension AM1, terminal A2 or
DHW circulation pump connected at internal exten­sion H1 or H2
System with low loss header 04:0 "Boiler"
Adjusting the heating curves
The heating curves illustrate the relation­ship between the outside temperature and the boiler water or flow tempera­ture. To put it simply, the lower the outside temperature, the higher the boiler water or flow temperature. The boiler water or flow temperature in turn affects the room temperature.
Settings in the delivered condition:
■ Slope = 1.4
■ Level = 0
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Page 79
79
Note
If the heating system includes heating circuits with mixers, then the flow tem­perature of the heating circuit without mixer is higher by a selected differential (8 K in the delivered condition) than the flow temperature of the heating circuits with mixers.
The differential temperature is adjusta­ble via coding address "9F" in the "Gen- eral" group.
0.2
Outside temperature in °C
Boiler water or
Flow temperature in °C
Slope
2.4
2.6
2.8
3.0
3.2
3.4
90
80
70
60
50
40
30
0 -5 -10 -15 -20510
2.0
2.2
Set room temperature in °C
35
30
25
20
15
10
5
0.4
0.6
0.8
1.0
1.2
1.4
-30-25
1.8
1.6
Slope setting ranges:
■ Underfloor heating systems: 0.2 to 0.8
■ Low temperature heating systems: 0.8 to 1.6
Selecting the set room temperature
Individually adjustable for each heating circuit.
The heating curve is offset along the axis of the set room temperature. With the heating circuit pump logic function ena­bled, the curve modifies the starting and stopping characteristics of the heating circuit pump.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Service
Page 80
80
Standard set room temperature
90
-20
26 + 20
A
C
D
E
B
Example 1: Adjustment of the standard set room temperature from 20 to 26 °C
A
Boiler water temperature or flow temperature in °C
B
Outside temperature in °C
C
Set room temperature in °C
D
Heating circuit pump "OFF"
E
Heating circuit pump "ON"
Changing the standard set room temper­ature
Operating instructions
Reduced set room temperature
+20 14 5
90
-20
D E
A
C
B
Example 2: Adjustment of the reduced set room temperature from 5 °C to 14 °C
A
Boiler water temperature or flow temperature in °C
B
Outside temperature in °C
C
Set room temperature in °C
D
Heating circuit pump "OFF"
E
Heating circuit pump "ON"
Changing the reduced set room temper­ature
Operating instructions
Changing the slope and level
Individually adjustable for each heating circuit.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Page 81
81
A
B
Boiler water or
flow temperature in °C
90
+20 -20
Outside temperature in °C
3.5
1.4
0.2
A
Changing the slope
B
Changing the level (vertical parallel offset of the heating curve)
Extended menu:
1. å
2. "Heating"
3. Select heating circuit.
4. "Heating curve"
5. "Slope" or "Level"
6. Select heating curve according to the system requirements.
Connecting the control unit to the LON
The LON communication module (accessories) must be plugged in.
Installation instructions LON communication module
Note
The data transfer via LON can take sev­eral minutes.
Single boiler system with Vitotronic 200-H and Vitocom 200 (example)
Set the LON subscriber numbers and further functions via code 2 (see the fol­lowing table).
Note
In the same LON system, the same sub­scriber number must not be allocated twice. Only one Vitotronic may be program­med as fault manager.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Service
Page 82
82
All coding addresses in the table are listed in the "General" group. Boiler control unit Vitotronic 200-H Vitotronic 200-H Vitocom
LON LON LON
Subscriber no. 1, Code "77:1".
Subscriber no. 10, Code "77:10".
Subscriber no. 11, Set code "77:11".
Subscriber
no. 99. Control unit is fault manager, Code "79:1".
Control unit is not fault manager, Code "79:0".
Control unit is not fault manager, Code "79:0".
Device is fault
manager.
Control unit transmits the time, Code "7b:1".
Control unit receives the time, Set code "81:3".
Control unit receives the time, Set code "81:3".
Device re-
ceives the
time. Control unit transmits outside temperature, Set code "97:2".
Control unit receives outside tempera­ture, Set code "97:1".
Control unit receives outside tempera­ture, Set code "97:1".
Viessmann system number, Code "98:1".
Viessmann system number, Code "98:1".
Viessmann system number, Code "98:1".
LON subscriber fault monitoring, Code "9C:20".
LON subscriber fault monitoring, Code "9C:20".
LON subscriber fault monitoring, Code "9C:20".
Carrying out a LON subscriber check
The subscriber check is used to test communication with the system devices connected to the fault manager.
Preconditions:
■ The control unit must be programmed
as fault manager (code "79:1" in the "General" group).
■ The LON subscriber number must be
programmed in all control units.
■ The LON subscriber list in the fault
manager must be up to date.
Service menu:
1. Press OK and simultaneously for approx. 4 s.
2. "Service functions"
3. "Subscriber check"
4. Select subscriber (e.g. subscriber 10).
5. Start the subscriber check with "OK".
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Page 83
83
■ Successfully tested subscribers are designated with "OK".
■ Unsuccessfully tested subscribers are designated with "Not OK".
Note
To carry out a new subscriber check, create a new subscriber list with "Delete list?" (subscriber list is upda­ted).
Note
During the subscriber check, the display for the relevant subscriber shows the subscriber no. and "Wink" for approx. 1 min.
Scanning and resetting the "Service" display
After the limits specified in coding addresses "21" and "23" in the "Boiler" group have been reached, the red fault indicator flashes and "Service" and "¸" appear on the programming unit display.
Acknowledging and resetting service
Press OK to acknowledge a service message.
Note
An acknowledged service message that was not reset reappears the following Monday.
After a service has been carried out (resetting service)
1. Press OK and å simultaneously
for approx. 4 s.
2. "Service functions"
3. "Service reset"
Note
The selected service parameters for hours run and interval restart at 0.
Fitting the cover panel and front panels
Fit the cover panel; see position A in diagram on page 48.
■ Fit the front panels; see page 41.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Service
Page 84
84
Instructing the system user
The system installer should hand the operating instructions to the system user and instruct the user in operating the system. This includes all components installed as accessories, e.g. remote control units. In addition, the system installer must make the user aware of the required mainte­nance work.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Page 85
85
■ On control units for weather-compen­sated operation codes are displayed as plain text.
■ Codes that have not been assigned a function due to the heating system equipment level or the setting of other codes are not displayed.
■ Heating systems with one heating cir­cuit without mixer and one or two heat­ing circuits with mixer: The heating circuit without mixer is labelled "Heating circuit 1" and the heating circuits with mixer are labelled
"Heating circuit 2" or "Heating cir­cuit 3".
If the heating circuits were individually named, the selected name and "HC1", "HC2" or "HC3" appears instead.
1. Press OK and å simultaneously
for approx. 4 s.
2. "Coding level 1"
3. Select the required coding address
group:
"General"
"Boiler"
"DHW"
"Solar"
"Heating circuit 1/2/3"
"All codes std device" In this group, all coding addresses from coding level 1 (except coding addresses from the "Solar" group) are displayed in ascending order.
4. Select coding address.
5. Select value according to the follow- ing tables and confirm with OK.
6. If you want to reset all codes to their delivered condition: Select "Standard setting" in "Cod­ing level 1".
Note
This also resets codes at coding level
2.
"General"
Select group "General" (see page 85).
Code 1
Calling up coding level 1
5773 238 GB
Service
Page 86
86
Coding
Coding in the delivered condition Possible change System design
00:2 One heating circuit with-
out mixer A1 (heating cir­cuit 1)
00:4 to 00:10
For system schemes, see the following table:
Value ad­dress 00: ...
Description
2 One heating circuit without mixer A1 (heating circuit 1) (code is set au-
tomatically) 4 One heating circuit with mixer M2 (heating circuit 2) 6 One heating circuit without mixer A1 (heating circuit 1)
One heating circuit with mixer M2 (heating circuit 2)
(code is set automatically) 8 One heating circuit with mixer M2 (heating circuit 2)
One heating circuit with mixer M3 (heating circuit 3) 10 One heating circuit without mixer A1 (heating circuit 1)
Two heating circuits with mixer M2 (heating circuit 2) and M3 (heating
circuit 3)
(code is set automatically)
Code 1
"General"
(cont.)
5773 238 GB
Page 87
87
Coding in the delivered condition Possible change Internal circulation pump function
51:0 Internal circulation pump
always starts when there is a heat demand
51:1 System with low loss head-
er: When there is a heat de­mand, the internal circula­tion pump is only started if the burner is operational. Circulation pump is switch­ed off on expiry of run-on time.
51:2 System with heating water
buffer cylinder: When there is a heat de­mand, the internal circula­tion pump is only started if the burner is operational. Circulation pump is switch­ed off on expiry of run-on time.
Subscriber no.
77:1 LON subscriber number 77:2
to 77:99
LON subscriber number, adjustable from 1 to 99: 1 - 4 = Boiler 5 = Cascade 10 - 97 = Vitotronic 200-H 98 = Vitogate 99 = Vitocom
Detached house/apartment building
7F:1 Detached house 7F:0 Apartment building
Holiday program and time program for DHW heating can be set separately
Code 1
"General"
(cont.)
5773 238 GB
Service
Page 88
88
Coding in the delivered condition Possible change Lock out controls
8F:0 Operation enabled in
standard menu and ex­tended menu.
Note
The respective code is only activated when you exit the service menu.
8F:1 Operation blocked in
standard menu and exten­ded menu. Emissions test mode can be enabled.
8F:2 Operation enabled in
standard menu and blocked in extended menu. Emissions test mode can be enabled.
Set flow temperature for external demand
9b:70 Set flow temperature for
external demand 70 °C
9b:0 to 9b:127
Set value adjustable from 0 to 127 °C (limited by boiler­specific parameters)
"Boiler"
Select group "Boiler" (see page 85).
Coding
Coding in the delivered condition Possible change Burner service in 100 hours
21:0 No service interval (hours
run) selected
21:1 to 21:100
The number of hours run before the burner should be serviced is adjustable from 100 to 10 000 h. One adjusting step
100 h
Service interval in months
23:0 No interval for burner
service
23:1 to 23:24
Interval adjustable from 1 to 24 months
Code 1
"General"
(cont.)
5773 238 GB
Page 89
89
Coding in the delivered condition Possible change Service status
24:0 "Service" not shown on
display
24:1 "Service" is shown on dis-
play (the address is auto­matically set and must be manually reset after the service)
Filling/Venting
2F:0 Venting program/fill pro-
gram disabled
2F:1 Venting program enabled 2F:2 Fill program enabled
"DHW"
Select group "DHW" (see page 85).
Coding
Coding in the delivered condition Possible change Set DHW temperature reheating suppression
67:40 For solar DHW heating:
Set DHW temperature 40 °C. DHW reheating is suppressed above the selected set temperature. (DHW heating by the boil­er only if solar energy is not sufficient).
67:0 to 67:95
Set DHW temperature ad­justable from 0 to 95 °C (limited by boiler-specific parameters). Observe the setting of cod­ing address "56".
Enable DHW circulation pump
73:0 DHW circulation pump:
"ON" according to time program
73:1 to 73:6
During the time program "ON" from once per hour for 5 min to "ON" 6 times per hour for 5 min
73:7 Constantly "ON"
"Solar"
Select group "Solar" (see page 85).
Code 1
"Boiler"
(cont.)
5773 238 GB
Service
Page 90
90
Coding
Coding in the delivered condition Possible change Speed control solar circuit pump
02:1 Solar circuit pump (multi
stage) is speed-control­led with wave packet con­trol.
02:0 Solar circuit pump (multi
stage) is not speed-control­led.
02:2 Do not adjust
Cylinder maximum temperature
08:60 Set DHW temperature
(maximum cylinder tem­perature) 60 °C.
08:10 to 08:90
Set DHW temperature ad­justable from 10 to 90 °C.
Stagnation time reduction
0A:5 Temperature differential
for stagnation time reduc­tion (reduction in the speed of the solar circuit pump to protect system components and heat transfer medium) 5 K.
0A:0 Stagnation time reduction
is disabled. 0A:1 to 0A:40
Temperature differential
adjustable from 1 to 40 K.
Flow rate solar circuit
0F:70 The flow rate of the solar
circuit at the maximum pump speed is set to 7 l/min.
0F:1 to 0F:255
Flow rate adjustable from
0.1 to 25.5 l/min.
1 step ≙ 0.1 l/min.
"Heating circuit ..."
Select group "Heating circuit ..." (see page 85).
Code 1
"Solar"
(cont.)
5773 238 GB
Page 91
91
Coding
Coding in the delivered condition Possible change Economy function outside temperature
A5:5 With heating circuit pump
logic function (economy control): Heating circuit pump "OFF" when the outside temperature (AT) is 1 K higher than the set room temperature (RT
set
)
AT > RT
set
+ 1 K
A5:0 Without heating circuit
pump logic function A5:1 to A5:15
With heating circuit pump
logic function: Heating cir-
cuit pump "OFF"; see fol-
lowing table
Parameter address A5:...
With heating circuit pump logic function: Heating cir­cuit pump "OFF"
1 AT > RT
set
+ 5 K
2 AT > RT
set
+ 4 K
3 AT > RT
set
+ 3 K
4 AT > RT
set
+ 2 K
5 AT > RT
set
+ 1 K
6 AT > RT
set
7 to
AT > RT
set
– 1 K
15 AT > RT
set
– 9 K
Coding in the delivered condition Possible change Extended economy function adjusted outside temperature
A6:36 Extended economy mode
disabled
A6:5 to A6:35
Extended economy control
enabled, i.e. the burner and
heating circuit pump stop
and the mixer is closed at a
variable value, adjustable
between 5 and 35 °C plus
1 °C. The base value is the
adjusted outside tempera-
ture. This value is based on
the actual outside temper-
ature and a time constant
which takes into account
the cooling down of an
average building.
Code 1
"Heating circuit ..."
(cont.)
5773 238 GB
Service
Page 92
92
Coding in the delivered condition Possible change Extended economy function mixer
A7:0 Only for heating circuit
with mixer: Without mixer economy function
A7:1 With mixer economy func-
tion (extended heating cir­cuit pump logic): Heating circuit pump also "OFF":
■ If the mixer has been closed for longer than 20 min.
Heating circuit pump "ON":
■ If the mixer changes to control function
■ If there is a risk of frost
Pump idle time, transition reduced mode
A9:7 With pump idle time:
Heating circuit pump "OFF" if set value is modi­fied by changing the op­erating mode or changing the set room tempera­ture
A9:0 Without pump idle time A9:1 to A9:15
With pump idle time, ad­justable from 1 to 15. 1 = short idle time 15 = long idle time
Weather-compensated/room temperature hook-up
b0:0 Only for heating circuit
with mixer and remote control: Heating mode/reduced mode: Weather-compen­sated
b0:1 Heating mode: Weather-
compensated Reduced mode: With room temperature hook-up
b0:2 Heating mode: With room
temperature hook-up Reduced mode: Weather­compensated
b0:3 Heating mode/reduced
mode: With room tempera­ture hook-up
Code 1
"Heating circuit ..."
(cont.)
5773 238 GB
Page 93
93
Coding in the delivered condition Possible change Economy function room temperature
b5:0 Only for heating circuit
with mixer and remote control: Without room tempera­ture-dependent heating circuit pump logic func­tion
b5:1 to b5:8
Heating circuit pump logic function, see the following table.
Parameter ad­dress b5:...
With heating circuit pump logic function: Heating circuit pump "OFF" Heating circuit pump "ON"
1 RT
actual
> RT
set
+ 5 K RT
actual
< RT
set
+ 4 K
2 RT
actual
> RT
set
+ 4 K RT
actual
< RT
set
+ 3 K
3 RT
actual
> RT
set
+ 3 K RT
actual
< RT
set
+ 2 K
4 RT
actual
> RT
set
+ 2 K RT
actual
< RT
set
+ 1 K
5 RT
actual
> RT
set
+ 1 K RT
actual
< RT
set
6 RT
actual
> RT
set
RT
actual
< RT
set
– 1 K
7 RT
actual
> RT
set
– 1 K RT
actual
< RT
set
– 2 K
8 RT
actual
> RT
set
– 2 K RT
actual
< RT
set
– 3 K
Coding in the delivered condition Possible change Min. flow temperature heating circuit
C5:20 Electronic minimum flow
temperature limit 20 °C (only in operation with standard room tempera­ture)
C5:1 to C5:127
Minimum limit adjustable from 1 to 127 °C (limited by boiler-specific parameters)
Max. flow temperature heating circuit
C6:74 Electronic maximum flow
temperature limit set to 74 °C
C6:10 to C6:127
Maximum limit adjustable from 10 to 127 °C (limited by boiler-specific parame­ters)
Code 1
"Heating circuit ..."
(cont.)
5773 238 GB
Service
Page 94
94
Coding in the delivered condition Possible change Heating program - changeover
d5:0 With external operating
program changeover (ob­serve setting for coding addresses "3A", "3b" and "3C" in the "General" group). Operating program switches to "Constant central heating with re­duced room tempera­ture" or "Standby mode" (subject to the setting of the set reduced room temperature).
d5:1 The operating program
switches to "Constant op­eration with standard room temperature".
Ext. heating program changeover to heating circuit
d8:0 With extension EA1:
No operating program changeover.
d8:1 Operating program
changeover via input DE1.
d8:2 Operating program
changeover via input DE2.
d8:3 Operating program
changeover via input DE3.
Max. pump speed in standard mode
E6:... Only for heating systems
without a heating circuit with mixer: Maximum speed of the in­ternal variable speed heating circuit pump in % of the max. speed in standard mode. Value is specified by boiler-specif­ic parameters (only for weather-compensated control units).
E6:0 to E6:100
Maximum speed adjusta­ble from 0 to 100 %
Code 1
"Heating circuit ..."
(cont.)
5773 238 GB
Page 95
95
Coding in the delivered condition Possible change Min. pump speed
E7:30 Only for heating systems
without a heating circuit with mixer: Minimum speed of the in­ternal variable speed heating circuit pump: 30 % of the max. speed (only for weather-com­pensated control units)
E7:0 to E7:100
Minimum speed adjustable from 0 to 100 % of the max­imum speed
Screed function
F1:0 Screed drying disabled. F1:1
to F1:6
Only for heating circuit with mixer: 6 different temperature/ time profiles can be selec­ted for screed drying (see page 163)
F1:15 Constant flow temperature
20 °C
Party mode time limit
F2:8 Time limit for party mode
or external operating pro­gram changeover via but­ton: 8 h
*1
Note
Observe settings of cod­ing addresses "3A", "3b" and "3C" in group "Gen- eral", as well as "d5" and "d8" in group "Heating circuit...".
F2:0
No time limit.
*1
F2:1 to F2:12
Time limit adjustable from 1 to 12 h
*1
*1
In the "Heating and DHW" program, party mode ends automatically when the system changes over to operation with standard room temperature.
Code 1
"Heating circuit ..."
(cont.)
5773 238 GB
Service
Page 96
96
Coding in the delivered condition Possible change Start temperature raising
F8:–5 Temperature limit for ter-
minating reduced mode –5 °C, see example on page 165. Observe the setting of coding address "A3".
F8:+10 to F8:–60
Temperature limit adjusta­ble from +10 to –60 °C
F8:–61 Function disabled
End temperature raising
F9:–14 Temperature limit for rais-
ing the set reduced room temperature –14 °C, see example on page 165.
F9:+10 to F9:–60
Temperature limit for rais­ing the set room tempera­ture to the value selected for standard mode adjusta­ble from +10 to –60 °C
Set flow temperature increase
FA:20 Raising the set boiler wa-
ter or flow temperature by 20 % when changing from operation with re­duced room temperature to operation with stand­ard room temperature. See example on page 166.
FA:0 to FA:50
Temperature rise adjusta­ble from 0 to 50 %
Duration set flow temperature increase
Fb:60 Duration of the set boiler
water or flow temperature rise (see coding address "FA") 60 min. See exam­ple on page 166.
Fb:0 to Fb:300
Duration adjustable from 0 to 300 min.
Code 1
"Heating circuit ..."
(cont.)
5773 238 GB
Page 97
97
All codes are accessible in coding level 2.
■ Codes that have not been assigned a function due to the heating system equipment level or the setting of other codes are not displayed.
■ The heating circuit without mixer is labelled "Heating circuit 1" and the heating circuits with mixer are labelled
"Heating circuit 2" or "Heating cir­cuit 3".
If the heating circuits were individually named, the selected name and "HC1", "HC2" or "HC3" appears instead.
1. Press OK and å simultaneously
for approx. 4 s.
2. Press OK and simultaneously for
approx. 4 s.
3. "Coding level 2"
4. Select the required coding address
group:
"General"
"Boiler"
"DHW"
"Solar"
"Heating circuit 1/2/3"
"All codes std device" In this group, all coding addresses from coding level 1 (except coding addresses from the "Solar" group) are displayed in ascending order.
5. Select coding address.
6. Select value according to the follow- ing tables and confirm with OK.
7. If you want to reset all codes to their delivered condition: Select "Standard setting" in "Cod­ing level 2".
Note
This also resets codes at coding level
1.
"General"
Select group "General" (see page 97).
Code 2
Calling up coding level 2
5773 238 GB
Service
Page 98
98
Coding
Coding in the delivered condition Possible change
00:2 One heating circuit with-
out mixer A1 (heating cir­cuit 1)
00:4 to 00:10
For system schemes, see the following table:
Value ad­dress 00: ...
Description
2 One heating circuit without mixer A1 (heating circuit 1) (code is set au-
tomatically) 4 One heating circuit with mixer M2 (heating circuit 2) 6 One heating circuit without mixer A1 (heating circuit 1)
One heating circuit with mixer M2 (heating circuit 2)
(code is set automatically) 8 One heating circuit with mixer M2 (heating circuit 2)
One heating circuit with mixer M3 (heating circuit 3) 10 One heating circuit without mixer A1 (heating circuit 1)
Two heating circuits with mixer M2 (heating circuit 2) and M3 (heating
circuit 3)
(code is set automatically)
Coding in the delivered condition Possible change
11:≠9 No access to the coding
addresses for the com­bustion controller param­eters
11:9 Access open to the coding
addresses for the combus­tion controller parameters
2A:0 Without wireless outside
temperature sensor
2A:1 With wireless outside tem-
perature sensor (automatic recognition)
2A:2 Wireless outside tempera-
ture sensor not used 2d:0 Do not adjust 32:0 Without extension AM1 32:1 With extension AM1 (auto-
matic recognition) 33:1 Function output A1 at ex-
tension AM1: Heating circuit pump
33:0 DHW circulation pump 33:2 Circulation pump for cylin-
der heating 34:0 Function output A2 at ex-
tension AM1: DHW circulation pump
34:1 Heating circuit pump 34:2 Circulation pump for cylin-
der heating
Code 2
"General"
(cont.)
5773 238 GB
Page 99
99
Coding in the delivered condition Possible change
35:0 Without extension EA1 35:1 With extension EA1 (auto-
matic recognition)
36:0
Function output aBJ at extension EA1: Fault message
36:1 Feed pump 36:2 DHW circulation pump
3A:0 Function input DE1 at ex-
tension EA1: No function
3A:1 Operating program
changeover
3A:2 External demand with set
flow temperature. Set value setting: Coding address "9b" in this group. Internal circulation pump function: Coding address "3F" in this group.
3A:3 External blocking.
Internal circulation pump function: Coding address "3E" in this group.
3A:4 External blocking with fault
message input. Internal circulation pump function: Coding address
"3E" in this group. 3A:5 Fault message input 3A:6 Brief operation, DHW cir-
culation pump (pushbutton
function).
DHW circulation pump run-
time adjustment: Coding
address "3d" in this group
3b:0 Function input DE2 at ex-
tension EA1: No function
3b:1 Operating program
changeover 3b:2 External demand with set
flow temperature.
Set value setting: Coding
address "9b" in this group.
Internal circulation pump
function: Coding address
"3F" in this group. 3b:3 Function input DE2: Exter-
nal blocking.
Code 2
"General"
(cont.)
5773 238 GB
Service
Page 100
100
Coding in the delivered condition Possible change
Internal circulation pump function: Coding address "3E" in this group.
3b:4 Function input DE2: Exter-
nal blocking with fault mes­sage input Internal circulation pump function: Coding address 3E
3b:5 Function input DE2: Fault
message input
3b:6 Function input DE2: Brief
operation, DHW circulation pump (pushbutton func­tion). DHW circulation pump run­time adjustment: Coding address 3d
3C:0 Function input DE3 at ex-
tension EA1: No function
3C:1 Operating program
changeover
3C:2 External demand with set
flow temperature. Set value setting: Coding address "9b" in this group. Internal circulation pump function: Coding address "3F" in this group.
3C:3 External blocking.
Internal circulation pump function: Coding address "3E" in this group.
3C:4 External blocking with fault
message input Internal circulation pump function: Coding address
"3E" in this group. 3C:5 Fault message input 3C:6 Brief operation, DHW cir-
culation pump (pushbutton
function).
Code 2
"General"
(cont.)
5773 238 GB
Loading...