Viessmann B2HB 45, B2HB 57 Installation Instructions Manual

Installation Instructions
for use by heating contractor
Vitodens 200-W, Series B2HB Models 45, 57 Wall-mounted, gas-fired condensing boiler
For operation with natural gas and liquid propane gas Heating input: 32 to 199 MBH 9 to 58 kW
VITODENSr 200-W
H
5680 493 - 05 12/2015
Product may not be exactly as shown
IMPORTANT
Read and save these instructions for future reference.
Please file in Service Binder
Safety
Vitodens 200-W B2HB 45, 57 Installation
Safety, Installation and Warranty Requirements
Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the instructions listed below and details printed in this manual can cause product/property damage, severe personal injury, and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections).
Product documentation Read all applicable documentation before commencing installation. Store documentation near boiler in a readily accessible location for reference in the future by service personnel.
For a listing of applicable literature, please see section entitled “Important Regulatory and Safety Requirements”.
Warranty Information contained in this and related product documentation must be read and followed. Failure to do so renders the warranty null and void.
Licensed professional heating contractor The installation, adjustment, service and maintenance of this equipment must be performed by a licensed professional heating contractor.
Please see section entitled “Important Regulatory and Installation Requirements”.
Contaminated air Air contaminated by chemicals can cause by-products in the combustion process, which are poisonous to inhabitants and destructive to Viessmann equipment.
For a listing of chemicals which cannot be stored in or near the boiler room, please see subsection entitled “Mechanical room” in the “Installation Instructions”.
Advice to owner Once the installation work is complete, the heating contractor must familiarize the system operator/ ultimate owner with all equipment, as well as safety precautions/requirements, shutdown procedure, and the need for professional service annually before the heating season begins.
WARNING
Installers must follow local regulations with respect to installation of carbon monoxide detectors. Follow the Viessmann maintenance schedule of the boiler contained in this manual.
Operating and Service Documentation
It is recommended that all product documentation such as parts lists, operating and service instructions be handed over to the system user for storage. Documentation is to be stored near boiler in a readily accessible location for reference by service personnel.
22
Carbon monoxide Improper installation, adjustment, service and/or maintenance can cause flue products to flow into living space. Flue products contain poisonous carbon monoxide gas.
For information pertaining to the proper installation, adjustment, service and maintenance of this equipment to avoid formation of carbon monoxide, please see subsection entitled “Mechanical room” and “Venting requirements” in the “Installation Instructions”.
Fresh air This equipment requires fresh air for
safe operation and must be installed ensuring provisions for adequate combustion and ventilation air exist.
For information pertaining to the fresh air requirements of this product, please see subsection entitled “Mechanical room” in the “Installation Instructions”.
Equipment venting Never operate boiler without an installed venting
system. An improper venting system can cause carbon monoxide poisoning.
For information pertaining to venting and chimney requirements, please see section entitled “Venting Connection”. All products of combustion must be safely vented to the outdoors.
WARNING
This boiler requires fresh air for safe operation and must be installed with provisions for adequate combustion and ventilation air (in accordance with local codes and regulations of authorities having jurisdiction).
Do not operate this boiler in areas with contaminated combustion air. High levels of contaminants such as dust, lint or chemicals can be found at construction sites, home renovations, in garages, workshops, in dry cleaning/laundry facilities, near swimming pools and in manufacturing facilities.
Contaminated combustion air will damage the boiler and may lead to substantial property damage, severe personal injury and/or loss of life. Ensure boiler/burner is inspected and serviced by a qualified heating contractor at least once a year in accordance with the Service Instructions of the boiler.
5680 493 - 05
Vitodens 200-W B2HB 45, 57 Installation
Safety, Installation and Warranty Requirements
Safety
Fiberglass wool and ceramic fiber materials
WARNING
Inhaling of fiberglass wool and/or ceramic fiber materials is a possible cancer hazard. These materials can also cause respiratory, skin and eye irritation.
The state of California has listed the airborne fibers of these materials as a possible cancer hazard through inhalation. When handling these materials, special care must be applied.
Suppliers of ceramic fiber products recommend the following first aid measures:
- Respiratory tract (nose and throat) irritation: If respiratory tract irritation develops, move the person to a dust free location.
- Eye irritation: If eyes become irritated, flush immediately with large amounts of lukewarm water for at least 15 minutes. Eyelids should be held away from the eyeball to ensure thorough rinsing. Do not rub eyes.
- Skin irritation: If skin becomes irritated, remove soiled clothing. Do not rub or scratch exposed skin. Wash area of contact thoroughly with soap and water. Using a skin cream or lotion after washing may be helpful.
- Gastrointestinal irritation: If gastrointestinal tract irritation develops, move the person to a dust free environment.
Suppliers of fiberglass wool products recommend the following precautions be taken when handling these materials:
- Avoid breathing fiberglass dust and contact with skin and eyes.
- Use NIOSH approved dust/mist respirator.
- Wear long-sleeved, loose fitting clothing, gloves and eye protection.
- Wash work clothes separately from other clothing. Rinse washer thoroughly.
- Operations such as sawing, blowing, tear-out and spraying may generate airborne fiber concentration requiring additional protection.
First aid measures
- If eye contact occurs, flush eyes with water to remove dust. If symptoms persist, seek medical attention.
- If skin contact occurs, wash affected areas gently with soap and warm water after handling.
WARNING
Appliance materials of construction, products of combustion and the fuel contain alumina, silica, heavy metals, carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful substances which can cause serious injury or loss of life and which are known to the State of California to cause cancer, birth defects and other reproductive harm. Always use proper safety clothing, respirators and equipment when servicing or working nearby the appliance.
About these Installation Instructions
Take note of all symbols and notations intended to draw attention to potential hazards or important product information. These include “WARNING”, “CAUTION”, and “IMPORTANT”. See below.
Warnings draw your attention to the presence of
WARNING
Indicates an imminently hazardous situation which, if not avoided, could result in loss of life, serious injury or substantial product/property damage.
CAUTION
Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or product/ property damage.
IMPORTANT
potential hazards or important product information.
Cautions draw your attention to the presence of
potential hazards or important product information.
Helpful hints for installation, operation or maintenance
which pertain to the product.
This symbol indicates that additional, pertinent
information is to be found.
This symbol indicates that other instructions must
be referenced.
5680 493 - 05
3
Table of Contents
Vitodens 200-W B2HB 45, 57 Installation
Page
Safety
General Information
Set-up
Safety, Installation and Warranty Instructions................2
Product documentation.............................................2
Warranty................................................................2
Licensed professional heating contractor....................2
Contaminated air....................................................2
Advice to owner......................................................2
Carbon monoxide.....................................................2
Fresh air................................................................2
Equipment venting...................................................2
About these Installation Instructions..........................3
Important Regulatory and Installation Requirements........5
Codes.......................................................................5
Instructing the system user......................................5
Initial start-up..........................................................5
Working on the equipment.......................................5
Technical literature..................................................5
For installations on the Commonwealth of
Massachusetts........................................................6
CSD-1 field testing of high limit switches..................6
Applicability..............................................................8
Product Information....................................................8
Multi boiler system..................................................8
Mechanical Room.....................................................9
Before Set-up........................................................10
Minimum Clearances.................................................10
Recommended minimum service clearances..............10
Boiler Connections
Preparing the Connections.........................................11
Wall Mounting.........................................................13
Fitting the wall mounting bracket............................13
Installing the wall mounting bracket.........................13
Installation of mounting bracket on
brick/concrete wall................................................13
Boiler mounting bracket and frame...........................14
Installation on wood studs......................................14
Installation on metal studs....................................14
Frame Mounting....................................................16
Models B2HB 45, 57 Frame Mounting....................17
Connections............................................................18
Connecting power..................................................18
Boiler venting........................................................18
Proper piping practice.............................................18
Gas shut-off valve connection.................................18
Gas connection and piping......................................19
Gas piping pressure test.........................................20
Heating water connections......................................20
DHW storage tank information.................................21
Making the DHW connections...............................21
Accessing the control unit connections.....................22
Routing the connecting cables.................................24
Connecting DHW sensor.........................................25
Setting altitude parameters.....................................25
Control base.........................................................26
External accessory connection box..........................27
Condensate connection........................................28
4
5680 493 - 05
Vitodens 200-W B2HB 45, 57 Installation
Table of Contents
Page
Boiler Connections (continued)
Control Connections
Safety Connections and Pressure Testing.....................29
Installing boiler safety devices.................................29
Low water cut-off..................................................30
Performing a boiler pressure test.............................30
Waterside Flow........................................................30
Waterside flow (primary circuit)...............................30
Installation Examples.................................................32
General.................................................................32
Clearances............................................................32
System Layout 1-9...................................................33
Alternative DHW Connection....................................42
Boiler in Heating/Cooling............................................43
Boiler in heating/cooling application..........................43
Boiler with Low Water Cut-off..................................44
Boiler with low water cut-off (remote-mounted
field supplied)........................................................44
Venting Connection.................................................42
Electrical Connections..............................................43
Power supply connection of accessories...................43
Connection of accessories.......................................43
Overview of Electrical Connections,
Models B2HB 45 and 57...........................................44
Additional Information
Accessing the X3 Plug..............................................48
Connecting the Low-loss Header Sensor......................48
Connecting the Outdoor Temperature Sensor..............49
External 0-10 Volt Signal Connection.........................50
24 VAC Thermostat Connection...............................51
LON Module..........................................................52
Installing the LON module to the boiler
control board.........................................................52
Connecting the LON module cable...........................52
Accessory Kit..........................................................53
Accessory kit connections for heating circuit
with mixing valve..................................................53
Closing the Control Unit............................................53
Closing the control cover .......................................52
Closing the External Accessory Connection Box............53
Reinstalling the Front Enclosure Panel..........................55
Instructing the system user.....................................55
Technical Data.........................................................57
Installation Fittings....................................................59
Lighting and Operating Instructions.............................60
5680 493 - 05
5
General Information
Important Regulatory and Installation Requirements
Codes
The installation of this unit shall be in accordance with local codes or, in the absence of local codes, use CAN/ CSA-B149.1 or .2 Installation Codes for Gas Burning Appliances for Canada. For U.S. installations use the National Fuel Gas Code ANSI Z223.1. Always use latest editions of codes.
In Canada all electrical wiring is to be done in accordance with the latest edition of CSA C22.1 Part 1 and/or local codes. In the U.S. use the National Electrical Code ANSI/ NFPA 70. The heating contractor must also comply with both the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1, and the Installation Code for Hydronic Heating Systems, CSA B214-01, where required by the authority having jurisdiction.
Instructing the system user
The installer of the system is responsible to ensure the system operator/ultimate owner is made familiar with the system functioning, its activation, and its shut-down.
Initial start-up
Initial start-up must be performed by a qualified heating contractor. Proper completion of the Maintenance Record by the heating contractor is also required.
Working on the equipment
The installation, adjustment, service, and maintenance of this boiler must be done by a licensed professional heating contractor who is qualified and experienced in the installation, service, and maintenance of hot water boilers. There are no user serviceable parts on the boiler, burners, or control. Ensure main power supply to equipment, the heating system, and all external controls has been deactivated. Close main gas supply valve. Take precautions in all instances to avoid accidental activation of power during service work.
The following topics must be covered: Proper system operation sequence. Explain the equipment. Demonstrate an emergency shut-down, what to do and what not. Explain that there is no substitute for proper maintenance to help ensure safe operation.
The Maintenance Record is located in the Service Instructions
Please carefully read this manual prior to attempting start­up, maintenance or service. Any warranty is null and void if these instructions are not followed.
For information regarding other Viessmann System Technology componentry, please reference documentation of the respective product.
We offer frequent installation and service seminars to familiarize our partners with our products. Please inquire.
Technical literature
Literature for the Vitodens boiler:
- Technical Data Manual
- Installation Instructions
- Service Instructions
- Operating Instructions and User’s Information Manual
- Instructions of other Viessmann products utilized and installed
- Installation codes mentioned in this manual
The completeness and functionality of field supplied electrical controls and components must be verified by the heating contractor. These include low water cut­offs, flow switches (if used), staging controls, pumps, motorized valves, air vents, thermostats, etc.
Leave all literature at the installation site and advise the system operator/ultimate owner where the literature can be found. Contact Viessmann for additional copies.
This product comes with several safety instruction labels attached. Do not remove! Contact Viessmann immediately if replacement labels are required.
Vitodens 200-W B2HB 45, 57 Installation
6
5680 493 - 05
Vitodens 200-W B2HB 45, 57 Installation
General Information
Important Regulatory and Installation Requirements (continued)
For installations on the Commonwealth of Massachusetts, the following modifications to NFPA-54 chapter 10 apply: Excerpt from 248 CMR 5-08: 2(a) For all side-wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the sidewall exhaust vent termination is less than (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side-wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side-wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professional for the installation of hard-wired carbon monoxide detectors. a. In the event that the side-wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard-wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level. b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side-wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side-wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
CSD-1 Field Testing of High Limit Switches for Vitodens boilers – where required by law. As per ASME Boiler and Pressure Vessel Code, section IV, subsection HG-613 TEMPERATURE CONTROL requirements, Vitodens 200-W hot water boilers are protected from over-temperature by two temperature-operated controls. These temperature control devices conform to Standards for Limit Controls, and are accepted by CSA, a nationally recognized testing agency. Each boiler is equipped with a manual reset high temperature limit control and a temperature control that will cut off fuel supply when the system water temperature reaches a preset operating temperature. VIESSMANN IS NOT RESPONSIBLE FOR ANY DAMAGES THAT THE FOLLOWING TEST PROCEDURE MAY RESULT IN BY OVERHEATING THE SYSTEM.
The Vitodens 200 boilers are equipped with flow switches or sensors that when activated enable the burner to operate. The fixed high limit, when tripped, produces a fault that will require manual reset of the boiler control.
Fixed High Limit fault simulation #1:
- Ensure that the boiler and boiler pump are in normal operating condition (pump output is the boiler pump).
- Remove the cover from the back of the boiler control allowing access to the boiler control plugs.
- Under the extended menu (in the Operating manual), select ‘Test mode’ then ‘flue gas test ON’ and press ‘OK’.
- The boiler/burner will start a firing cycle and will gradually go into high fire mode.
- Once the burner ignites, disconnect the boiler pump plug from the boiler control board (gently with pliers). Note: For boiler models equipped with flow switches (only boiler sizes 19 to 100), it may be required that flow switches be jumpered during testing.
- Observe the boiler temperature on the control display.
- The temperature will gradually rise as more heat is put into the boiler heat exchanger. The burner will then shut off.
- The boiler temperature should continue to rise and once it reaches 210ºF (99ºC) the manual reset high limit safety switch will trip electronically generating an F2 fault.
- Should the limit temperature not be reached during the test, repeat the test with the following additional step;
- two minutes after the burner shuts off, energize the boiler pump for a maximum of 1 second (by plugging in boiler pump plug ).
Fixed High Limit fault simulation #2:
- Close the boiler valve and jumper across the flow switch.
- Run the boiler at high fire and it will shut down by the coding card (in B2TB models, set coding address 06 to maximum) but should continue to steady increase the boiler temperature until the fixed high limit is tripped.
- Once the fixed high limit is tripped, slowly open the boiler valve to safely cool the boiler down.
5680 493 - 05
7
General Information
Applicability
CAUTION
The boiler serial number must be provided when ordering replacement parts. Some replacement parts are not reverse compatible with previous versions of the Vitodens 200-W B2HB boiler.
IMPORTANT
When ordering replacement parts, provide either the 16-digit boiler serial number (on the bar code label) or the 12-digit ASME/NB serial number, located as shown underneath boiler front enclosure panel. Refer to page 15 for instructions on how to remove front enclosure panel.
NG and LPG Model No. B2HB 45 Serial No. 7454703 jjjjjjjjj
Model No. B2HB 57 Serial No. 7454704 jjjjjjjjj
Vitodens 200-W B2HB 45, 57 Installation
Product Information
Natural gas-fired wall-mounted condensing heating boiler for weather-responsive operation in closed loop, forced circulation hot water heating systems for space heating and domestic hot water (DHW) production.
Models B2HB 45 and 57 are for operation with natural gas. For a fuel conversion to liquid propane gas refer to the service instructions for details.
Boiler model must be selected based on an accurate heat loss calculation of the building. Ensure boiler model is compatible with connected radiation.
Vitodens 200-W, B2HB series boilers are factory-tested and calibrated. Further gas valve adjustments are not typically required during field start-up.
Product may not be exactly as shown
A Inox-Radial heat exchanger made from stainless steel – for high operational reliability and a long service life. Large heating output in the smallest of spaces
B Modulating MatriX cylinder burner for extremely clean combustion and quiet operation
C Variable speed combustion fan for quiet and economical operation
D Gas and water connections
E Digital boiler control unit
Multi boiler system
In connection with the installation of a multi boiler system observe the installation instructions of the multi boiler system accessories.
8
5680 493 - 05
Vitodens 200-W B2HB 45, 57 Installation
General Information
Mechanical Room
During the early stages of designing a new home, we recommend that proper consideration be given to constructing a separate mechanical room dedicated to the gas- or oil-fired heating equipment and domestic hot water storage tank(s).
The boiler must be located in a heated indoor area, near a floor drain, and as close as possible to a wall. Whenever possible, install the boiler near an outside wall so that it is easy to duct the venting system to the boiler.
Locate the boiler on a wall capable of supporting 210 lb. (95 kg) [the weight of the boiler filled with water]. Ensure that the boiler location does not interfere with the proper circulation of combustion and ventilation air of other fuel burning equipment within the mechanical room (if applicable).
The maximum room temperature of the mechanical room where the boiler is located must not exceed 104ºF (40ºC).
Installation area conditions
WARNING
Incorrect ambient conditions can lead to damage to the heating system and put safe operation at risk.
H Ensure ambient temperatures are higher than 32°F
(0°C) and lower than 104°F (40°C).
H Prevent the air from becoming contaminated by
halogenated hydrocarbons (e.g. as contained in paint solvents or cleaning fluids) and excessive dust (e.g. through grinding or polishing work). Combustion air for the heating process, and ventilation of the boiler room must be free of corrosive contaminants. To that end, any boiler must be installed in an area that has no chemical exposure. The list to the right indicates the main, currently known sources.
H Avoid continuously high levels of humidity (e.g. through
frequent drying of laundry).
H Never close existing ventilation openings.
WARNING
If you notice fire coming from the appliance, call the fire department immediately! Do not attempt to extinguish the fire unless qualified to do so.
IMPORTANT
The service life of the boiler’s exposed metallic surfaces, such as the casing and fan housing, is directly influenced by proximity to damp and salty marine environments. In such areas, higher concentration levels of chlorides from sea spray, coupled with relative humidity, can lead to degradation of the exposed metallic surfaces mentioned above. Therefore, it is imperative that boilers installed in such environments not be installed using direct vent systems which draw outdoor air for combustion. Such boilers must be installed using room air dependent vent systems; i.e. using room air for combustion. The indoor air will have a much lower relative humidity and, hence, potential corrosion will be minimized.
Sources of combustion and ventilation air contaminants Areas likely to contain contaminants:
H New building construction
H Swimming pools
H Remodelling areas, hobby rooms
H Garages with workshops
H Furniture refinishing areas
H Dry cleaning/laundry areas and establishments
H Auto body shops
H Refrigeration repair shops
H Metal fabrication plants
H Plastic manufacturing plants
H Photo processing plants
H Beauty salons
Products containing contaminants:
H Chlorine-type bleaches, detergents and cleaning
solvents found in household laundry rooms
H Paint and varnish removers
H Hydrochloric acid, muriatic acid
H Chlorine-based swimming pool chemicals
H Spray cans containing chlorofluorocarbons
H Chlorinated waxes and cleaners
H Cements and glues
H Refrigerant leaks
H Calcium chloride used for thawing
H Sodium chloride used for water softening salt
H Permanent wave solutions
H Adhesives used to fasten building products and other
similar items
H
Antistatic fabric softeners used in clothes dryers
Boiler operation in marine environments (damp, salty coastal areas)
WARNING
Fire causes a risk of burns and explosion!
H Shut down the boiler H Close fuel shut-off valves H Use a tested fire extinguisher, class ABC.
5680 493 - 05
9
Set-up
Before Set-up
Before placing boiler in its installation location, ensure all necessary accessories are installed.
Minimum Clearances
Vitodens 200-W B2HB 45, 57 Installation
CAUTION
The boiler must be installed in such a way that gas ignition system components are protected from water (spraying, splashing, etc.) during boiler operation and service.
Recommended minimum service clearances
For typical Vitodens installations, Viessmann recommends installing the boiler with the clearances shown in the illustration on the left.
Note: The 12 in. (305 mm) side clearance specified is
only recommended to be able to view the boiler certified rating plate, decal and also accommodate the PRV installation kit.
Note: The Vitodens 200-W, B2HB boiler has passed the
zero inches vent clearance to combustibles testing requirements dictated by the boiler Harmonized Standard ANSI Z21.13. CSA 4.9 (latest edition) and therefore is listed for zero clearance to combustibles when vented with a single-wall special venting system (AL-29-4C material) or UL/ULC-listed CPVC/PPs gas vent material. The zero inches vent clearance to combustibles for the Vitodens 200-W, B2HB boiler supercedes the clearance to combustibles listing that appears on the special venting system label.
If the pressure relief valve is rotated 90º facing forward by using an extension between the tee and the boiler connection, then this clearance can be reduced to b in. This b in. clearance is only required to be able to remove the boiler’s front cover and view the rating plate attached to it, if needed. This reduced clearance is also used in Vitodens multiple boiler installation system as described in the multiple boiler installation instructions.
The Vitodens 200-W, B2HB boiler is approved for closet and alcove installation with the following clearances to combustibles.
Table 1 Clearances
Top Front Rear Left Right Vent pipe
00 AL CL0000
AL = Alcove CL = Closet
See the Vitodens 200-W B2HB Venting System Installation Instructions for details.
10
5680 493 - 05
Vitodens 200-W B2HB 45, 57 Installation
Preparing the Connections
*1 DHW
Connections
(Field Supplied)
Boiler Connections
Use an approved pipe sealant or teflon tape when connecting the following installation fittings.
This section constitutes an overview only! Refer to subsequent sections for detailed information on individual piping connections.
Legend
DR Boiler heating return for domestic hot water production DS Boiler heating supply for domestic hot water production BD Boiler Drain BF Boiler Fill BR Boiler Return BS Boiler Supply GC Gas Connection PRV Pressure Relief Valve *1 See page 40 for alternate DHW connection. *2 Discard when using the multi-boiler distribution manifold
5680 493 - 05
11
Boiler Connections
Preparing the Connections (continued)
Vitodens 200-W B2HB 45, 57 Installation
This section constitutes an overview only! Refer to subsequent sections for detailed information on individual piping connections.
Use an approved pipe sealant or teflon tape when connecting the following installation fittings.
IMPORTANT
The maximum ambient temperature must not exceed 104ºF (40ºC).
Note: When preparing gas, water and electrical
connections in the field, see section entitled “Wall Mounting” on page 13, 14 and 15 of this manual for information regarding the installation of the wall mounting bracket.
1. Heating water connections and gas connection to be made in the field. See illustration and connection­specific section for details.
2. See subsection entitled “Electrical Connections”
for details regarding power supply to the Vitodens 200-W B2HB boiler.
Legend
A Boiler Supply B Gas Connection, 1” NPTF C Boiler Return D Recommended height (single boiler system) E Condensate drain
12
5680 493 - 05
Vitodens 200-W B2HB 45, 57 Installation
Wall Mounting
Boiler Connections
Fitting the wall mounting bracket
Following are the installation instructions for the mounting bracket on each material. See the instructions applicable to your installation requirements.
Installing the wall mounting bracket
The Vitodens 200-W B2HB can be wall-mounted on a concrete wall.
Note: The enclosed screws and rawl plugs are only
suitable for concrete. For other construction materials, use bolts and anchors that are suitable for 210 lb (95 kg) loads.
Installation of mounting bracket on brick/concrete wall
1. Drill holes 7 31/64 in. (12 mm).
2. Install rawl plugs and screw mounting bracket
to wall.
3. Ensure the mounting bracket is level.
CAUTION
Whichever mounting method is used, ensure that the bracket is tightly and securely fastened to wall. Failure to secure boiler properly could cause boiler to loosen, posing a severe safety hazard.
5680 493 - 05
13
Boiler Connections
Wall Mounting (continued)
Vitodens 200-W B2HB 45, 57 Installation
Boiler mounting bracket
Install the boiler mounting bracket to the wall studs. Ensure the mounting bracket is level.
To mount on wood or metal studs a cross bar or frame may be required as reinforcement. The wall and studs must be capable of supporting a minimum of 210 lb. (95 kg).
For construction materials, use fixings that are suitable for 210 lb (95 kg) loads.
Installation on wood studs
Install mounting bracket on wood studs as per illustration. Drill 3/16” pilot holes to insert mounting bolts. Ensure that holes are located in the center of each wood stud. Secure with bolts to wooden studs as shown.
Installation on metal studs
install mounting bracket on metal studs as per illustration. Drill f” pilot holes to insert anchors. Ensure that holes are located in the center of each metal stud. Use appropriate fasteners to mount to metal studs (not supplied). Secure with bolts to metal studs as shown. Ensure the mounting bracket is level.
14
5680 493 - 05
Vitodens 200-W B2HB 45, 57 Installation
Wall Mounting (continued)
Boiler Connections
1. Remove the external accessories connection box cover.
2. Loosen the screws at the bottom of the boiler (do not remove completely).
3. Remove the front encloser panel (lift up and pull away from the boiler).
4. Mount boiler onto the mounting bracket.
5. Adjust the levelling screws to ensure the boiler is level. Place the round bubble level on top of the boiler to verify. Note: For draining of the condensate (see page 26).
6. Install supplied installation fittings as per layout on page 11.
CAUTION
The boiler must be level both vertically and horizontally to ensure proper draining of the condensate.
5680 493 - 05
15
Boiler Connections
Frame Mounting
Vitodens 200-W B2HB 45, 57 Installation
The boiler stand is used for free-standing installation of a single boiler within the mechanical room.
When using the boiler stand, ensure that the stand is securely fastened to the floor (recommended concrete expansion anchors are Hilti model KB-TZ e x 4 or equivalent.
The Vitodens 200-W, model B2HB does not come with a mounting template. The wall location for the frame, mounting bracket and all vents must be field calculated.
Boiler mounting bracket and frame
1. Attach the wall mounting bracket (supplied with the boiler) to the boiler mounting frame using the supplied hardware. Ensure that the wall mounting bracket is level.
2. Move the rack into position and secure to the floor (and to the wall if needed).
16
5680 493 - 05
Vitodens 200-W B2HB 45, 57 Installation
Models B2HB 45, 57 Frame Mounting
Boiler Connections
1. Remove the external accessories connection box cover.
2. Loosen the screws at the bottom of the boiler (do not remove completely).
3. Remove the front encloser panel (lift up and pull away from the boiler).
4. Mount boiler onto the mounting bracket and ensure the boiler is securely mounted. Then install the holding bracket to the frame on top of the boiler.
5. Adjust the levelling screws to ensure the boiler is level.
6. Connect the boiler to the installation fittings.
CAUTION
The boiler must be level both vertically and horizontally to ensure proper draining of the condensate.
5680 493 - 05
17
Boiler Connections
Connections
Vitodens 200-W B2HB 45, 57 Installation
Connecting power
The Vitodens 200-W boiler has a external accessories connection box installed, which requires a 120VAC/12A power supply. Refer to the wiring diagram (see page 44).
Boiler venting
The Vitodens 200-W B2HB boiler comes with a pre-installed vent pipe adaptor. Run venting system, single-wall or coaxial, through the side wall or the roof, taking the shortest possible route and at a rising angle (min. 3º).
WARNING
Remove outer gasket if single wall (boiler room air dependant) venting system is used.
2 imperfect threads
Leave 2 threads bare
Manual gas shutoff
Closed
Open
Proper piping practice
Support piping by proper suspension method. Piping must not rest on or be supported by boiler. Use moderate amount of dope.
Gas shut-off valve connection
1. Make gas connections in accordance with codes CAN/CSA B149.1 and .2 or National Fuel Gas Code ANSI Z223.1/NFPA 54, as well as local codes.
2. Connect gas shutoff valve to the boiler gas connection.
3. Once connected close gas shutoff valve on boiler.
See following page for details on gas connection and piping.
18
5680 493 - 05
Loading...
+ 42 hidden pages