Viessmann WB2B 80, WB2B 105, B2HA 80, B2HA 88, B2HA 100 Installation Instructions Manual

...
Page 1
Installation Instructions
Heat Exchanger Assembly
for use by heating contractor for Vitodens 200-W WB2B / B2HA
Part Number: 7831454 WB2B 80, 105 Part Number: 7843753 B2HA 80, 88, 100, 285, 311, 352
Safety and Installation Requirements
Please ensure that these instructions are read and understood before starting any service work. Failure to comply with these instructions may cause product/property damage, severe personal injury and/or loss of life.
Working on the equipment
The installation, adjustment, service and maintenance of this product must be performed by a licensed professional heating contractor who is qualified and experienced in the installation, service, and maintenance of hot water boilers. There are no user serviceable parts on the boiler, burner or control.
Ensure that main power to the equipment being serviced is off.
Ensure that the main fuel supply valve to the boiler is closed.
Take precautions to avoid accidental activation of power or fuel during service work.
Do not perform service work on any component part without ensuring safe operation of the heating system. When replacing parts, use original Viessmann or Viessmann approved replacement parts.
Refer to the Installation and Service Instructions applicable to this boiler.
5698 072 - 02 08/2017
Page 2
Accessing the Heat Exchanger
Heat Exchanger Assembly Installation
For more details refer to the Installation and Service Instructions applicable to this boiler.
1. With the electrical power and fuel supply off, open the control cover and switch the ON/OFF control switch to OFF.
2. Remove the front enclosure panel.
3. Close the boiler isolation valve or drain the system.
4. Remove the burner assembly.
Replacing Supply Pipe/Sensors/Refractory
1. Remove the Torx screw G (T-25) with the washer and pull the refractory H straight out.
2. Disconnect electrical connectors from the heating supply pipe A.
3. To replace the following:
- Remove connecting clip for boiler temperature sensor B.
- Remove 2 Phillips screws for high limit sensor C.
4. Pull off the connecting clip E to disconnect the pressure gauge hose from the heating supply pipe A.
boiler
Legend
Tighten the following fasteners on assembly:
C 8.9 lb.in. (1 Nm) D 70.8 lb.in. (8 Nm) G 35 lb.in. (4 Nm)
5. Remove the two Torx screws (T-40) D at the top and loosen the compression fitting at the bottom on the heating supply pipe A and remove pipe with top O-ring F.
6. Replace parts as required and reassemble as per steps 5 through 1 respectively and torque fasteners per legend.
2
5698 072 - 02
Page 3
Heat Exchanger Assembly Installation
Replacing Heat Exchanger/Return Pipe
1. Drain water from the heat exchanger through the sediment faucet drain valve.
IMPORTANT
Residual water may leak out during disassembly.
2. Remove supply pipe (see Replacing Supply Pipe).
3. Remove the two Phillips screws A under the control console and slide out. Disconnect all wiring connectors, remove console and set aside.
IMPORTANT
The control console must be removed to protect it from accidental water spillage.
4. Loosen by hand and remove the condensate hose B.
5. Disconnect the flue gas temperature sensor plug inside the boiler from the vent pipe adaptor C.
Legend
Tighten the following fasteners on assembly:
A 8.9 lb.in. (1 Nm) D 8.9 lb.in. (1 Nm) J 74 lb.ft. (100 Nm) F 70.8 lb.in. (8 Nm) H 70.8 lb.in. (8 Nm)
6. Remove the four Allen screws (4 mm) D and disconnect the vent pipe adaptor C from the heat exchanger.
7. Loosen compression fittings on the bottom of both return pipes J above the shut off valves.
8. Remove the four 13 mm Hex nuts F and remove heat exchanger G from the boiler.
9. Remove the Torx screws (T-40) H at the top of the heating return pipes J and remove with O-rings I and K.
IMPORTANT
Use new gaskets and O-rings on all connections.
10. Replace parts as required and reassemble the heat exchanger as per steps 9 through 2 respectively and torque fasteners per legend.
5698 072 - 02
3
Page 4
Reconnecting the Boiler
Heat Exchanger Assembly Installation
1. Install the condensate drain pipe with a suitable gradient. Pull the condensate hose so far out of the boiler that no unnecessary bends are created inside the boiler. Check tightness of siphon connection.
IMPORTANT
Ensure the condensate drain pipe is pulled down and positioned to allow the condensate to properly drain.
2. Discharge condensate from the boiler into the drainage system, either directly or (if required) via a neutralization unit (accessory).
Installation Instructions of Neutralization Unit (if applicable)
IMPORTANT
Pipe ventilation must take place between the siphon trap and the neutralization unit (if applicable).
IMPORTANT
Do not connect the drain pipe from any other appliance, such as water softener backwash pipe, to Vitodens conĀ­densate drain pipe.
1. Fill the boiler, bleed air and check for leaks.
Refer to the Installation and Service Instructions to activate air bleed program.
2. Install burner assembly.
WARNING
Gas leaks can lead to explosions. Check the gas pipe seals to ensure that there are no leaks.
3. Close control unit.
4. Install front enclosure.
(recycled and recyclable) paper.
5. Place the boiler back in operation.
For more details refer to the Installation and Service Instructions applicable to this boiler.
Air gap
Technical information subject to change without notice. Printed on environmentally friendly