VICOR AC-DC, F-Series, A-Series Application Notes

FlatPAC Family
50 to 600 Watt AC-DC Switchers
Application Notes
Functional and Mechanical Layout
Installation and Operation Guidelines
Product Description
FlatPAC switchers that contain BatMod current source modules instead of VI-200 converters are indicated by the suffix -BM following the FlatPAC part number. BatMod converters provide a programmable output current, rather than a controlled output voltage. Consequently, the output supervisory terminal functions differ on FlatPACs with BatMod modules.
F-Series
(Strappable Input)
A-Series
(Autoranging Input)
12
Application Notes
2
MOD-DIS Input. Apply a current of 1–30 mA to disable output.
Forward voltage drop of internal opto diode is 1.65 V max. @ 30 mA max.
AC-OK and BUS-OK Status Outputs. Output transistors saturated if OK. Vce sat. = < 0.4 V @ 1.5 mA. Maximum voltage is 70 Vdc.
30 mA max.
Disable
MOD DIS +
MOD DIS –
V
+
AC OK –
AC OK +
BUS OK –
Status
1.5mA max.
V
+
r
r
AC Mains Connections
Supervisory Connections (2-up and 3-up models)
AC Mains
Earth Ground
MOD DIS – MOD DIS + AC OK – AC OK + BUS OK – BUS OK +
Internal Supervisory Circuits (Optocouplers)
Autoranging models:
Do not connect
Manual strap models:
Connect for 115 Vac Open for 230 Vac
ST2 ST1 L2/N L1 GND
3
+Sense and –Sense must be connected locally or remotely (shown).
+ V
OUT
To Load
– V
OUT
R1 10K
R2
+ OUT
+ SENSE
TRIM
– SENSE
– OUT
RESISTOR VALUES FOR TRIMMING STANDARD OUTPUT VOLTAGES
Nominal Output Voltage 5 V 12 V 15 V 24 V 28 V 48 V Trim Range
R1(kΩ) .953 15.8 22.1 41.2 48.7 90.9 R2(k)909090909090
+10%, -10%
V
LINE
> 90 (180) Vac
AC Line
Interrupted
AC
Line
AC OK
DC OK
T0
T1 T2
T3
T4
Conditions: Full Load 90 (180) Vac, AC Line
Timing Diagram—Status Signals (2-up and 3-up models)
Output Trimming (All models with VI-200s)
Battery
Charger
External Control Functions
+ OUT
V
TRIM
I
TRIM
I
MON
– OUT
Programmable
Current Source
12–48V
Battery
+
Load
+
OR
Typical Applications (FlatPACs with BatMods only)
Time Interval Min Typ Max Units Notes
T1-T0 0 0.1 1.0 ms T3-T2 0 ms T4-T2 5 ms Ride-through time T4-T3 5 ms AC fail warning time
Loading...
+ 5 hidden pages