FlatPAC Family
50 to 600 Watt
AC-DC Switchers
Application Notes
Functional and Mechanical Layout
Installation and Operation Guidelines
Product Description
The FlatPAC family of user-definable offline power supplies provides a complete
power solution that incorporates one, two, or three standard Vicor DC-DC
converters and a front-end subassembly in a modular package. FlatPAC is available
with one, two, or three outputs and total output ratings of 50–600 W. These power
supplies feature an autoranging input, which automatically senses the input line
voltage and sets the power supply’s input range accordingly. FlatPAC’s unique
modular design accommodates over 10,000 different configurations.
FlatPAC power supplies that contain BatMod current source modules instead of
VI-200 converters are indicated by the suffix -BM following the FlatPAC part
number. BatMod converters provide a programmable output current, rather than a
regulated output voltage. Consequently, the output supervisory terminal functions
differ on FlatPACs with BatMod modules.
U-Series
Product is internally fused
Application Notes
MOD DIS Input. Apply a current of
1–30 mA to disable output. Forward
voltage drop of internal opto diode is
1.65 V max. at 30 mA max.
AC OK and BUS OK Status Outputs.
Outputs low when OK.
Vce sat. = < 0.4 V @ 1.5m A. Maximum
external pullup is 70 Vdc. AC OK and
BUS OK signals are isolated and can
have different reference levels.
V
+
r
AC OK
+
–
1.5mA
max.
V
+
r
BUS OK
+
–
30mA max.
Disable
MOD DIS
V
+
+
–
1.5mA
max.
FlatPAC
AC Mains and Supervisory Connections
External Supervisory Functions (2-up and 3-up models only)
MOD DIS –
MOD DIS +
AC OK –
AC OK +
BUS OK –
BUS OK +
Internal
Supervisory
Circuits
(Optocouplers)
AC Mains
Earth Ground
L1
L2/N
GND
2-Up
and
3-Up
1-Up
3
+Sense and –Sense must be connected locally or remotely (shown).
RESISTOR VALUES FOR TRIMMING STANDARD OUTPUT VOLTAGES
Nominal
5 V 12 V 15 V 24 V 28 V 48 V Trim Range
Output Voltage
R1(KΩ) .953 15.8 22.1 41.2 48.7 90.9 +10%, -10%
R2(KΩ) 90 90 90 90 90 90 +10%, -10%
V
LINE
> 90 (180)Vac
AC Line
Interrupted
AC
Line
AC OK
BUS OK
T0
T1 T2
T3
T4
Conditions: Full Load 90 (180)Vac, AC Line
Timing Diagram—Status Signals (2-up and 3-up models only)
Output Sense and Trim (All models with VI-200s)
Load
+
–
Battery
Charger
External
Control
Functions
Programmable Current
or Voltage Source
12–48V
Battery
+
–
+Out
V
TRIM
I
TRIM
I
MON
–Out
External
Control
Functions
+Out
V
TRIM
I
TRIM
I
MON
–Out
Typical Applications (Models with BatMods only)
Time Interval Min Typ Max Units Notes
T1-T0 0 0.1 1.0 ms
T3-T2 0 – – ms Ride-through time
T4-T2 5 – – ms Hold-up time
T4-T3 5 – – ms AC fail warning time
+Out
+Sense
Trim
–Sense
–Out
R2
R1
10K
+ V
V
OUT
OUT
RTN