Wireless System Overview 5
Terminal, Identification and Function 6
Wiring 6
Screw terminal arrangement and wiring 7
Typical Applications 7
Main outputs wiring 7
Remote sensor accessories 8
Configuring and Status Display Instructions 9
Status display 9
User interface 11
User configuring instructions menu 11
Local keypad interface 12
Installer Configuration Parameter Menu 16
Fresh Air Damper Control Sequences 27
Specifications 31
Drawing & Dimensions 32
1 | VZ7656E1000W Installation Guide
INSTALLATION
Remove the security screw on the bottom of
Terminal Equipment Controller cover.
Open unit by pulling on the bottom
side of Terminal Equipment
Controller (fig. 1).
Remove wiring terminals from sticker.
Please read the FCC ID and IC label
installed in the cover upon removal of
cover for the wireless products.
Location
1. Should not be installed on an outside
wall.
2. Must be installed away from any
direct heat source.
3. Should not be installed near an
air discharge grill.
4. Should not be affected by direct
sun radiation.
5. Nothing should restrict vertical
air circulation to the Terminal
Equipment Controller.
Installation
1. Swing open the Terminal
Equipment Controller PCB to
the left by pressing the PCB
locking tabs (fig. 2).
2. Pull out cables 6” out from the
wall.
3. Wall surface must be flat and
clean.
4. Insert cable in the central hole
of the base.
5. Align the base and mark the
location of the two mounting
holes on the wall. Install base in
the proper orientation. Arrow on
base should be facing up.
6. Install anchors in the wall.
7. Insert screws in mounting holes
on each side of the base (fig. 2).
8. Gently swing back the circuit
board on the base and push on
it until the tabs lock it.
9. Strip each wire 1/4 inch from
end.
2 | VZ7656E1000W Installation Guide
10. Insert each wire according to wiring diagram.
When replacing an existing Terminal Equipment Controller, label the
wires before removal of the Terminal Equipment Controller.
Electronic controls are static sensitive devices. Discharge yourself
properly before manipulating and installing the Terminal Equipment
Controller.
A short circuit or improper wiring may permanently damage the Terminal
Equipment Controller or the equipment.
All VT7000 series Terminal Equipment Controllers are designed for use
as operating controls only and are not safety devices. These instruments
have undergone rigorous tests and verification prior to shipping to ensure
proper and reliable operation in the field. Whenever a control failure
could lead to personal injury and or loss of property, it becomes the
responsibility of the user or installer or electrical system designer to
incorporate safety devices (such as relays, flow switch, thermal
protections, etc…) and or an alarm system to protect the entire system
against such catastrophic failures. Tampering with the devices or
unintended application of the devices will result in a void of warranty.
11. Gently push excess wiring back into hole (fig. 3).
12. Re-Install wiring terminals in their correct locations (fig. 3).
13. Re-install the cover (top side first) and gently push extra wire length back into
the hole in the wall.
14. Install security screw.
THEORY OF OPERATION
The VZ7656 series uses a Viconics proprietary adaptive logic algorithm to control the
space temperature. This algorithm controls the heating and or air conditioning system to
minimize overshoot while still providing comfort. It provides exceptional accuracy due to
its unique PI time proportioning control algorithm, which virtually eliminates temperature
offset associated with traditional, differential-based On-Off thermostats.
Fig.2 - On-Off mechanical control vs. PI electronic control.
Features overview
7 day schedule models, 2 or 4 events.
Supports up to 120 zones per system WITHOUT any network wires.
C02 control logic based on fresh air volume or fresh air damper position.
Fresh air damper output for building C02 level control.
Gas, oil or electric system compatibility.
3 | VZ7656E1000W Installation Guide
Remote outdoor sensing capability for added flexibility.
- System mode heating and cooling lockout.
- Zone perimeter reheat lockout.
Remote discharge air sensor input for monitoring and control purpose.
- System efficiency feedback.
- Discharge high limit heating lockout.
- Discharge low limit cooling lockout.
Remote return air sensor input for monitoring control.
- System efficiency feedback.
- Return high limit heating lockout.
- Return low limit cooling lockout.
- Communication lost control function.
Password protected configuration menu and lockable keypads for security.
A configurable digital input for added flexibility. The input can be configured as the
following:
None: No function will be associated with the input.
Service: a backlit flashing Service alarm will be displayed on the Terminal
Equipment Controller LCD screen when the input is energized. It can be tied in
to the AC unit control card, which provides an alarm in case of malfunction.
Filter: a backlit flashing Filter alarm will be displayed on the Terminal
Equipment Controller LCD screen when the input is energized. It can be tied to a
differential pressure switch that monitors filters.
RemNSB: remote NSB timer clock input. Will disable the internal scheduling of
the Terminal Equipment Controller. The scheduling will now be set as per the
digital input. The menu part related to scheduling is disabled and no longer
accessible. It provides low cost setback operation via occupancy sensor or from
a dry contact.
RemOVR: temporary occupancy contact. Disables all override menu function of
the Terminal Equipment Controller. . The override function is now controlled by a
manual remote momentarily closed contact. When configured in this mode, the
input operates in a toggle mode.
With this function enabled it is now possible to toggle between unoccupied &
occupied setpoints for the amount of time set by parameter (TOccTime)
temporary occupancy time.
Automatic smart fan operation saves energy during unoccupied periods.
Non volatile EEPROM memory prevents loss of parameters during power shortage.
Configurable SPST output relay on scheduling models for lighting, exhaust fan or
fresh air control.
6 hour typical reserve time for clock in case of power loss.
Built in 0 to 10 VDC by-pass damper / VFD output logic for static pressure control.
- Built in static pressure loop control.
- 0 to 5 VDC static pressure input.
Easy configuration and self-binding operation
Easy configuration without using any special software or additional tools.
Can be used as stand-alone or with supervision controller for monitoring purposes.
Truly scalable in terms of supported number of zones and RTU units.
4 | VZ7656E1000W Installation Guide
WIRELESS SYSTEM OVERVIEW
Viconics VZ7260X5X00W Zone controllers are used in conjunction with the
VZ7656X1000W roof top controllers. Combined, they are designed for operating typical;
single or multistage RTU’s and their associated local zones. For example, a typical job
layout system may feature 3 RTU controllers and a total of 31 zones. This would bring to
total number of nodes (individual Com addresses) to 34. RTU 1 would have 10 zones
under its command, RTU 2 would have 10 zones under its command and RTU 3 would
have 11 zones under its command.
Typical Wireless Zoning System Installation
5 | VZ7656E1000W Installation Guide
TERMINAL,IDENTIFICATION AND FUNCTION
Terminal Use
Terminal
Identification
Description
1 – Cool 2
Y2
Output for cooling / compressor stage
number 2.
2 – Cool 1
Y1
Output for cooling / compressor stage
number 1.
3 - Fan G Output for the fan.
4 - 24 V ~ Hot
RC
Power supply of controller, hot side
(Delivered from the RTU).
5 - 0 V ~ Com
C
Power supply of controller, common side.
Also used as reference for the analog BPD
output when used (Delivered from the RTU).
6- Heat Switch Leg
RH
24 VAC switched leg for the heating stages.
If heating stages are part or RTU,
install a jumper across RC & RH.
If heating stages are part of separate
equipment with a different power
supply, feed external switched power
leg through RH without installing a
jumper across RC & RH.
7 – Heat 1
W1
Output for heating stage number 1.
8- Heat 2
W2
Output for heating stage number 2.
9 – By-pass damper
BPD
Local analog 0 - 10 VDC by-pass damper /
VFD output.
10 – Economizer Output
EC
0-10 VDC analog fresh air damper /
economizer output.
11 – Static pressure
SP
Local analog 0 – 5 VDC static pressure
input.
12 – AI
AI
0-10 VDC analog input for airflow transmitter
13 - RS
RS
Return air temperature sensor input. If
sensor fails, controller will use the on-board
thermistor sensor to control if the
communication is lost.
14 - Scom
Scom
Reference input for DI 1, RS, OS & DS.
15 - OS
OS
Outside air temperature sensor input.
16 - DS
DS
Discharge air temperature sensor input.
Wiring
6 | VZ7656E1000W Installation Guide
Screw terminal arrangement and wiring
BPD
EC
SP
AI
RS
SCom
OS
DSGY1
Y2
W2
W1
RHCRC
VZ7656E Controller Terminals
TYPICAL APPLICATIONS
Main outputs wiring
Wiring notes:
Note 1: If the same power source is used for the heating stages, install jumper across RC &
RH. Maximum current is 2.0 amps.
Note 2: If auxiliary output is used to toggle occupancy of the electronic control card inside
the equipment, configure the relay parameter (Aux cont) to the N.O. setting. A
second relay can be added for additional functionality of the occupancy output.
Note 3: Analog outputs and inputs use a half bridge rectifier. Reference of the control
signal is the common of the power supply of the Terminal Equipment Controller.
(Terminal C)
Note 4: Electromechanical contacts are to be used with the digital inputs. Electronic triacs
cannot be used as mean of switching for the input. The switched leg to the input for
the input to activate is terminal C (common)
Note 5: The transformer of the unit provides power to the t Terminal Equipment Controller
and the additional loads that will be wired to the Terminal Equipment Controller.
7 | VZ7656E1000W Installation Guide
Remote sensor accessories
Model no.
Description
S2020E1000
Outdoor temperature sensor
S2060A1000
Averaging temperature sensor
S2000D1000
Duct mounted temperature sensor
ºC
ºF
Kohm
ºC
ºF
Kohm
ºC
ºF
Kohm
ºC
ºF
Kohm
ºC
ºF
Kohm
-40
-40
324.3197
-20
-4
94.5149
0 32
32.1910
20
68
12.4601
40
104
5.3467
-39
-38
303.6427
-19
-2
89.2521
1 34
30.6120
21
70
11.9177
41
106
5.1373
-38
-36
284.4189
-18 0 84.3147
2 36
29.1197
22
72
11.4018
42
108
4.9373
-37
-35
266.5373
-17 1 79.6808
3 37
27.7088
23
73
10.9112
43
109
4.7460
-36
-33
249.8958
-16 3 75.3299
4 39
26.3744
24
75
10.4443
44
111
4.5631
-35
-31
234.4009
-15 5 71.2430
5 41
25.1119
25
77
10.0000
45
113
4.3881
-34
-29
219.9666
-14 7 67.4028
6 43
23.9172
26
79
9.5754
46
115
4.2208
-33
-27
206.5140
-13 9 63.7928
7 45
22.7861
27
81
9.1711
47
117
4.0607
-32
-26
193.9703
-12
10
60.3980
8 46
21.7151
28
82
8.7860
48
118
3.9074
-31
-24
182.2686
-11
12
57.2044
9 48
20.7004
29
84
8.4190
49
120
3.7607
-30
-22
171.3474
-10
14
54.1988
10
50
19.7390
30
86
8.0694
50
122
3.6202
-29
-20
161.1499
-9
16
51.3692
11
52
18.8277
31
88
7.7360
51
124
3.4857
-28
-18
151.6239
-8
18
48.7042
12
54
17.9636
32
90
7.4182
52
126
3.3568
-27
-17
142.7211
-7
19
46.1933
13
55
17.1440
33
91
7.1150
53
127
3.2333
-26
-15
134.3971
-6
21
43.8268
14
57
16.3665
34
93
6.8259
54
129
3.1150
-25
-13
126.6109
-5
23
41.5956
15
59
15.6286
35
95
6.5499
55
131
3.0016
-24
-11
119.3244
-4
25
39.4921
16
61
14.9280
36
97
6.2866
56
133
2.8928
-23
-9
112.5028
-3
27
37.5056
17
63
14.2629
37
99
6.0351
57
135
2.7886
-22
-8
106.1135
-2
28
35.6316
18
64
13.6310
38
100
5.7950
58
136
2.6886
-21
-6
100.1268
-1
30
33.8622
19
66
13.0307
39
102
5.5657
59
138
2.5926
Fig.10 – Remote Duct Mounted Temperature Sensor
Remote mount temperature sensors use 10K NTC thermistor.
Temperature vs. Resistance Chart for 10 Kohm NTC Thermistor
(R
= 10K±3% - B
25°C
= 3975K±1.5%)
25/85°C
S2000D1000; remote duct mounted temperature sensor c/w junction box.
This sensor can be used for:
Remote return air temperature
sensing with the sensor
mounted on the return air duct.
Outside air temperature sensing
with the sensor installed in the
fresh air plenum.
Supply air temperature sensing.
S2060A1000; remote averaging duct mounted temperature sensor c/w junction
box.
This sensor can be used for:
Remote averaging return air temperature sensing with the sensor mounted on
the return air duct.
Outside air temperature averaging sensing with the sensor installed in the
fresh air plenum.
Supply air temperature averaging sensor for economizer models with the
sensor in the mixing plenum.
8 | VZ7656E1000W Installation Guide
S2020E1000; outdoor air temperature sensor
WIRING S2000D1000, S2060A1000 and S2020E1000
Remote wiring 1 sensor Remote wiring 4 sensors
10 K
10 K
10 K
10 K
10 K
Scom
DS
Scom
OS
Scom
RS
or
or
Scom
DS
Scom
OS
Scom
RS
or
or
This sensor can be used for:
Outside air temperature sensing with the sensor installed directly exposed to
the elements.
Sensor uses a water resistant NEMA 4 ABS enclosure for outdoor
applications.
CONFIGURING AND STATUS DISPLAY INSTRUCTIONS
Status display
The Terminal Equipment Controller features a two-line, eightcharacter display. There is a low backlight level that is always
active and can only be seen at night.
When left unattended, the Terminal Equipment Controller has
an auto scrolling display that shows the current status of the
system.
Each item is scrolled sequentially with the back lighting in low level mode. Pressing any
key will cause the back light to come on to high level.
Manual scroll of each menu item is achieved by pressing the Yes (scroll) key repetitively.
The last item viewed will be shown on the display for 30 seconds before returning to
automatic scrolling. Temperature is automatically updated when scrolling is held.
9 | VZ7656E1000W Installation Guide
Sequence of auto-scroll status display:
CLOCK
STATUS
SYSTEM
MODE
SCHEDULE
STATUS
OUTDOOR
TEMPERATURE
ALARMS
Monday
12:00
AM
Sys mode
auto
Occupied
Outdoor
x.x °C or°F
DAS Alarm
Sys mode
off
Occupied
hold
FA Alarm
Sys mode
heat
Unoccup
SetClock
Sys mode
cool
High CO2
Com Lost
Clock
Status
System
Mode
Schedule
Status
Outdoor
Temperature
Alarms
(if detected)
Monday
Sys Mode
Occupied
Outdoor
Service
12:00
AM
Off xx.x °C or °F
DAS Alrm
Sys Mode
Unoccupied
SetClock
Auto Filter
Sys Mode
Override
Comm Lost
Cool
Sys Mode
Heat
Outdoor air temperature
Outdoor air temperature display is only enabled when outdoor air temperature sensor is
connected.
A maximum range status display of 50 °C (122 °F) indicates a shorted sensor.
Associated functions, such as mode lockouts and economizer function are
automatically disabled.
A minimum range status -40 °C (-40 °F) is not displayed and indicates a opened
sensor or a sensor not connected. Associated functions, such as mode lockouts and
economizer function are automatically disabled.
Alarms
If alarms are detected, they will automatically be displayed at the end of the status
display scroll.
During an alarm message display, the back lit screen will light up at the same time as
the message and shut off during the rest of the status display.
Two alarms maximum can appear at any given time.
The priority for the alarms is as follows:
Sequence of manual-scroll status display:
Manual scroll of each menu item is achieved by pressing the Yes (scroll) key repetitively. The
last item viewed will be shown on the display for 30 seconds before returning to automatic
scrolling. Temperature is automatically updated when scrolling is held.
10 | VZ7656E1000W Installation Guide
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.