Viconics VWG-50 Wireless Gateway Guide Specification
Part 1 – General
1.01 System Description – The VWG-50 when utilized in conjunction with the Viconics VT7000xxxxxW
series and VZ7000xxxxxW wireless communicating controllers shall offer the integrator simple BACnet IP
or BACnet MS/TP objects to integrate over standard building automation systems using familiar
integration toolsets. The Viconics communicating controllers and gateway with wireless field bus allows
the centralization of stand-alone equipment without the need to pass communication wiring.
1.02 Quality Assurance – The wireless gateway must have the following industry approvals and
specifications:
Specifications
Platform
• PowerPC 405EP 250 MHz processor
• 64MB SDRAM & 64 MB Serial Flash
• 128 KB Static RAM
• Battery Backup - 5 minutes typical - shutdown
begins within 10 seconds
• Real-time clock - 3 months backup max via
battery
Operating System
• QNX RTOS
• IBM J9 JVM Java Virtual Machine
• NiagaraAX
Wired Communications
• 2 Ethernet Ports – 10/100 Mbps (RJ-45
Connectors)
• 1 RS 232 Port (9 pin D-shell connector)
• 1 RS 485 non-isolated port (3 Screw
Connector on base board)
Wireless Communications
• Direct spread spectrum 2.4 GHz ISM bands
• Transmission power is under 1 mW at –0.4
dBm for channels 11 to 25 and –4.0 dBm for
channel 26
Power Supply
• VWG-PS-AC 120 VAC to 15 VDC power
supply for VWG with cord
Chassis
• Construction: Plastic, din rail or screw mount
chassis, plastic cover
• Cooling: Internal air convection
• Dimensions: 6.313” (16.04 cm) W x
4.820”(12.24 cm) H (including connectors) x
2.438” (6.19 cm) D
Environment
• Operating temperature range: 0° to 50°C (32°F
to 122°F)
• Storage Temperature range: 0° to 60°C (32°F
to 140°F)
• Relative humidity range: 5% to 95%, noncondensing
Agency Listings
• UL 916, C-UL listed to Canadian Standards
Association
• (CSA) C22.2 No. 205-M1983 “Signal
Equipment”
• FCC Part 15 Subpart C
• C-tick (Australia)
Part 2 – Equipment
2.01 General – The VWG-50 Wireless Gateway shall provide a simple way in which to integrate Viconics
wireless communicating controllers into today’s building automation systems using either BACnet MS/TP
or BACnet IP open protocols.
The Viconics Wireless Gateway and related VT7000xxxx Wireless Communicating Controllers
shall be supplied with a factory mounted wireless adapter and operate using ZigBee/IEEE
802.15.4 physical layer for communication.
The VWG-50 shall act as a wireless access point between the Viconics Wireless Communi cating
Controllers and the BACnet IP or BACnet MS/TP wired supervisory system (supplied by others).
The VWG-50 shall provide familiar BACnet objects for easy integration.
The VWG-50 shall have a built-in configuration tool accessible by a network used to configure
and commission the VWG-50 as well as discover the wireless communicating controllers.
A maximum of 50 (fifty) Viconics wireless communicating controllers shall be added wirelessly to
a single VWG-50 database.
A maximum distance between each node (controller) for non-line-of-sight must be less than
50feet. The maximum distance between two nodes for clear line of sight must be less than
100feet. Ensure that at least one controller is within 50 feet of the VWG-50 for every cluster of 10
controllers installed.
The VWG-50 shall be supplied with an integrated antenna for wireless communication. An
optional remote antenna (Part # VWG-RA-1000 shall be available depending on the physical
installation of the gateway (example: VWG-50 installed in a metal cabinet),.
The VWG-50 shall be supplied with a custom 10-cell NiMH battery pack mounted to the unit
(under the cover). This battery shall allow the VWG to continue operation through very short power
bumps (a few seconds in duration). If a longer power outage occurs, the fully charged battery shall
provide enough run time for the VWG to backup data and then shutdown. Shutdown shall occur
automatically, after data is backed up to on-board flash memory.
Model required: VWG-50-MSTP-1000 for BACnet MS/TP
Model required: VWG-50-IP-1000 for BACnet IP