Viconics VWG-50 Installation Guide

VWG-50-5000
Viconics Wireless Gateway
Hardware Installation Guide
January 10th, 2012 / 028-0369-R1
C
ONTENTS
Disclaimers 2 Trademarks 3 Overview 3 Parts Available 4 Preparation 4
Included in this Package 4 Material and Tools Required 5
Precautions 5
Safety Precautions 5 Static Discharge Precautions 6
Mounting 7
Environmental Requirements 7 Physical Mounting 7 Removing and Replacing the Cover 8 Installation Minimum Spacing Distance Requirements 9 Board Layout 10
Wiring Details 10
Grounding 10
VWG-PS-AC 120 VAC Wall mounted power supply 11
Power Wiring 11 Communications Wiring 11 Ethernet—BACnet™ over IP wiring 11 RS485-BACnet™ MS-TP wiring. 13
Antenna installation 14
Controller mounted antenna (VWG-WA) 14 Remote mounted antenna (VWG-RA) 14
Power Up and Initial Checkout 14
Procedure - Initial power up and checkout 14
About the Battery 15 Related Documentation 16 Status LEDs 16 Maintaining the VWG 17 Returning a Defective Unit 18 Certifications 19 Specifications 19
 
      
                       
1 | VWG-50-Installation Manual
DISCLAIMERS
NO WARRANTY. Viconics, Inc. (herein after referred to as “Viconics”) makes no warranty as to the accuracy of or use of this technical documentation. Any use of the technical documentation or the information contained therein is solely at the risk of the user.
Documentation may include technical or other inaccuracies or typographical errors. Viconics reserves the right to make changes to this document without prior notice, and the reader should in all cases consult Viconics to determine whether any such changes have been made. The information in this publication does not represent a commitment on the part of Viconics.
Viconics shall not be liable for incidental or consequential damages resulting from the furnishing, performance, or use of this material.
This guide contains links and references to third-party websites that are not under the control of Viconics, and Viconics is not responsible for the content of any reference material or linked websites. If you access a third party website mentioned in this guide, then you do so at your own risk. Viconics provides these links only as a convenience, and the inclusion of the link does not imply that Viconics endorses or accepts any responsibility for the content on those third-party sites.
Electronic controls are static sensitive devices. Discharge yourself properly before manipulation and installing the Viconics wireless gateway.
All Viconics wireless gateways and related wireless controllers are to be used only as operating controls. Whenever a control failure could lead to personal injury and or loss of property, it becomes the responsibility of the user to add safety devices and or alarm system to protect against such catastrophic failures.
All VT7000 series wireless controllers and associated VWG (Viconics Wireless Gateway) have been rigorously tested to ensure reliable operation in most building applications using the latest 2.4 Zigbee™ technologies. Viconics cannot guarantee against potential network interference should additional wireless systems be deployed sharing close proximity.
Best practices covered in this manual and all related Viconics VWG documents should be considered as a guide to apply Viconics Wireless Network devices only. The instructions included in this manual are based upon Viconics in house testing and should be referred to as a guide only.
Viconics Inc. may not be held liable for continued reliable, or robust operation of any and all wireless based devices. Although Viconics has taken many precautions in assuring the robustness of the VT7000 series wireless controller product line and associated network access point (VWG-50-XXXX-1000) Please note; future application of additional wireless devices utilizing the same or similar channels and / or frequencies may degrade performance of overall system and / or reliability.
Non-approved modifications or changes made to the VWG or wireless controllers may void the FCC compliance of the VWG and wireless controllers.
2 | VWG-50-Installation Manual
Ferrites supplied with the power supply and VWG MUST be installed according to instructions. Failure to do so may void the FCC compliance of the VWG and wireless controllers.
Only VWG-PS-DC and VWG-PS-AC power supply can be used with the VWG. The usage of another non-approved power supply may void the FCC compliance of the VWG and wireless controllers.
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
TRADEMARKS
Niagara, Niagara AX is a registered trademark of Tridium, Inc. LON, LonWorks™ and LonTalk™ are registered trademarks of Echelon™ ™ Corporation. BACnet™ is a registered trademark of ASHRAE.
OVERVIEW
This document covers the mounting and wiring of the Viconics VWG-50 series product. It assumes that you are an engineer, technician, or service person who is performing control system installation. Instructions in this document apply to the following products:
Note: Not covered in this document is the configuration appliance software required for fully setup the gateway. This includes setting host IP address, passwords, database, and other controller and network utilities. Refer to the document LIT-VWG-50-SETUP-Exx for more information.
3 | VWG-50-Installation Manual
PARTS AVAILABLE
V
V
V
Part number Description
Viconics BACnet™™ over MS-TP & IP wireless gateway.
VWG-50-5000
VWG-RA
WG-WA
WG-PS-AC
WG-BB
Includes:
Supports up to 50 wireless controllers
Factory mounted wireless adapter
24 VAC panel mounted power supply
Gateway mounted antenna
Remote antenna for gateway when the gateway is installed inside a metal cabinet or when remote antennal mounting is required by physical installation
Replacement antenna for gateway mounted antenna setup
120 VAC to 15 VDC power supply for VWG with cord
Replacement battery backup pack for the VWG
PREPARATION
Unpack the VWG and power module (either VWG-PS-DC or VWG-PS-AC) and inspect the contents of the packages for damaged or missing components. Be sure the factory-installed ferrite is on the cord of the power supply unit. If damaged, notify the appropriate carrier at once and return any damaged components for immediate repair or replacement.
Included in this Package
Included in this package you should find the following items:
VWG-50-XX-1000 base controller.  Local antenna for the VWG  This VWG-50-XX-1000 Hardware installation guide Configuration tool on a mini-CD
Power module required for operation, are ordered and sold separately. The power
module can be one of the following: – VWG-PS-DC: 24VAC in-line (DIN-mount capable), or VWG-PS-AC: External 120 VAC wall-mount power adapter
4 | VWG-50-Installation Manual
Material and Tools Required
f
r
The following tools and supplies may be required for installation: DIN rail, type NS35/7.5 (35mm x 7.5mm), recommended for panel mount installation.
Length of DIN rail should be minimum 6.5 “(165 mm).
If using a VWG-PS-DC power supply, use UL listed, Class 2, 24VAC transformer,
supplying a minimum of 5VA to the VWG. Note that the VWG-PS-DC power supply provides isolation — a dedicated transformer is not required.
Suitable screws and screwdriver for mounting DIN rail, or if DIN rail not used, for
mounting bases of VWG controller and VWG-PS-DC power supply (if used).
PRECAUTIONS
This document uses the following warning and caution conventions:
Cautions remind the reader to be careful. They alert readers to situations where there is a chance that the reader might perform an action that cannot be undone, might receive unexpected results, or might lose data. Cautions contain an explanation of why the action is potentially problematic.
Warnings alert the reader to proceed with extreme care. They alert readers to situations where there is a chance that the reader might do something that can result in personal injury or equipment damage. Warnings contain an explanation of why the action is potentially dangerous.
Safety Precautions
The following items are warnings of a general nature relating to the installation and start-up of the VWG controller. Be sure to heed these warnings to prevent
personal injury or equipment damage
.
Depending on power module used, the circuit powering the VWG is 24VAC at
50/60 Hz (if using the VWG-PS-DC power supply or 120 VAC at 50/60 Hz (i using the VWG-PS-AC power supply). Disconnect power before installation o servicing to prevent electrical shock or equipment damage.
Make all connections in accordance with national and local electrical
codes. Use copper conductors only.
To reduce the risk of fire or electrical shock, install in a controlled
environment relatively free of contaminants.
This device is only intended for use as a monitoring and control device. To
prevent data loss or equipment damage, do not use it for any other purpose.
All Viconics wireless gateways and related wireless controllers are to be used
only as operating controls. Whenever a control failure could lead to personal injury and or loss of property, it becomes the responsibility of the user to add safety devices and or alarm system to protect against such catastrophic
5 | VWG-50-Installation Manual
failures.
Static Discharge Precautions
Static charges produce voltages high enough to damage electronic components. The microprocessors and associated circuitry within a VWG controller are sensitive to static discharge. Follow these precautions when installing, servicing, or operating the system:
Work in a static-free area. Discharge any static electricity you may have accumulated.
Discharge static electricity by touching a known, securely grounded object.
Do not handle the printed circuit board (PCB) without proper protection
against static discharge. Use a wrist strap when handling PCBs. The wrist strap clamp must be secured to earth ground.